Study of Different Components and Their Functions

of an Air Circuit Braker (ACB)


Md. Abdullah Nabil Sadman Sakib Rafat Raisa Tabassum Tasin
Electrical Electronics Engineering Electrical Electronics Engineering Electrical Electronics Engineering
American International University- American International University- American International University-
Bangladesh Bangladesh Bangladesh
Dhaka,Bangladesh Dhaka,Bangladesh Dhaka,Bangladesh
nabilabdullah12@gmail.com sakib75@gmail.com raisatasin715@gmail.com

Lia Moni Tahmina Akter Urmi


Electrical Electronics Engineering Electrical Electronics Engineering
American International University- American International University-
Bangladesh Bangladesh
Dhaka,Bangladesh Dhaka,Bangladesh
liamoni982@gmail.com tahminaurmi99@gmail.com

Abstract—The overall purpose of power system protection resistance is increased to such an extent that the voltage drop
is to detect any faults or abnormal conditions that could cause across the arc becomes more than the system voltage, and
the system to malfunction or create a full power outage and the arc gets extinguished at the current zero of AC wave.Air
isolate them from the healthy portion. Protecting the critical break circuit breakers are employed in DC circuits and Ac
power system equipment will require analysis. A circuit
breaker is used to break circuits during faulty conditions such
circuits up to 12,000 voltages. Such breakers are usually of
as short circuits or over current manually or remotely. These indoor type and installed on vertical panels or indoor draw
devices are mainly used to protect the system. Few devices out switch gear. AC circuit breakers are widely employed
namely relays, switches, fuses and many more can be connected indoor medium voltage and low voltage switchgear. [2]
to protect the electrical systems along with circuit breakers. Based on the arc quenching medium circuit breakers are
ACB play an important part in ensuring that electrical safety classified into several types. Air circuit breaker is one of the
devices are properly protected. This lab study highlights the types. In ACB air is used to clear arc from the arcing zone.
manual and automatic contact closing operations, as well as the In this experiment construction of ACB is examined
tripping mechanism and the under voltage shunt tripping
properly and following things are observed:
mechanism.
1. Observe the contact closing operation manually
Keywords— Power system protection, ACB, Faulty 2. Observe the contact closing operation automatically
conditions. 3. Observe the tripping mechanism
4. Observe the under voltage shunt tripping mechanism [7]
II. THEORY
I. INTRODUCTION
ACB is the short form for Air Circuit Breaker. Air circuit A. Defination and Types of ACB
breakers (ACB) are used for the protection of circuits which Air Circuit breaker /ACB is an electrical switching device
have current of about 800 Amperes to 10-kilo Amperes used to protect electrical circuits from overcurrent, under
flowing through them. The ACB provides the circuit voltage and short circuits. These devices are generally used
protection against the short circuit and the overcurrent in low voltage applications and operate in the air as an arc
condition in an electrical circuit. The air circuit breakers extinguishing medium considering the atmospheric pressure.
(ACB’s) are used in the circuits where the voltage range of ACBs have a large capacity and a steel frame with parts
installed inside.[3]
the circuit is below 450 Volts. The ACB trip is described as
when the current or voltage in a circuit in which the current
between 800A to 10kA is flowing gets greater than the
predefined values the ACB gets opened and the flow of
current and voltage in the circuit is stopped. Similarly, ACB
is opened in case of a short circuit and it prevents the circuit
from more damage. The main function of the ACB is to
quench the arching during overloading. [1]
In the air break, circuit breaker the contact separation and
arc extinction take place in air at atmospheric pressure. In
air break circuit breaker high resistance principle is
employed. In this circuit breaker arc is expanded by the
mean of arc runners, arc chutes, and arc resistance is
increased by splitting, cooling and lengthening.The arc

XXX-X-XXXX-XXXX-X/XX/$XX.00 ©20XX IEEE


Fig. 1: Air Circuit Breaker [4] for low and medium voltage circuits is shown in the figure
below. There are two sets of contacts called the main
There are different types of ACB. These are- contacts and arcing or auxiliary contacts. Main contacts are
1)Plain Break type ACB. usually of copper and conduct the current in the closed
2)Magnetic Blowout Type ACB. position of the breakers. They have low contact resistance
3)Air Chute ACB. and are silver plated.
4)Air Blast Circuit Breaker [4] The arcing contacts are hard, heat resistant and usually of
Plain Break Type Air Break Circuit Breaker: It is the copper alloy. Arcing contacts are used to relieve the main
simplest one in which contacts are made in the shape of two contacts from damage due to arcing. The arcing contacts are
horns. The air initially strikes across the shortest distance easily renewable when required. The auxiliary and arcing
between the horns and is driven steadily upwards by the contacts close before and open after the main contacts
convection currents caused by heating of air during arcing during the operation.
and the interaction of the magnetic and the electric fields. Here the blowouts consist of a steel insert in the arcing
The arc extends from one tip to the other when the horns are chutes. These are so arranged that the magnetic field
fully separated resulting in lengthening and cooling arc. induced in them by the current in the arc moves it upwards
The relative slowness of the process and the possibility of still faster. The steel plates divide the arc into a number of
arc spreading of adjacent metal works limits the application arcs in the series.
of about 500V and too low power circuits. The distribution of voltage along the arc length is not linear,
Magnetic Blow-Out Type Air Break Circuit Breaker: Some but it is accompanied by a rather large anode and cathode
air circuit breakers are used in the circuits having voltage up drops. In case the total sum of anode and drops of all the
to 11 KV, the arc extinction is accomplished using magnetic short arcs in series exceeds the system voltage, conditions
field provided by the current in blowout coils connected in for the quick extinction of the arc are automatically
series with the circuit being interrupted. Such coils are established.
called blow out the coil. The magnetic field itself does not When the contact has come in contact with the relatively
extinguish the arc. It simply moves the arc into chutes where cool surfaces of the steel plants gets rapidly and effectively
the arc is lengthened, cooled and extinguished. The arc cooled. The movement of the arc may be naturally or aided
shields prevent arc spreading to an adjacent network. by a magnetic blowout. Thus, the arc is extinguished by
lightening and increasing the power loss of the arc. [2]

B. Ratings of ACB
Air circuit breakers come in with different ratings as
different circuits utilize different current and voltage ratings.
However the standard ratings of the ACB’s lie in the range
of 400A to 1600A. Similarly, another class of ACB lies in
2000A to 5000A rating. The standard current ratings of the
ACB are these however, the voltage, the physical ratings of
the ACB vary from manufacturer to manufacturer. [4]

Fig. 2: Magnetic Blow-Out Type Air Break Circuit Breaker

It is important to connect the coils at correct polarity so that


the arc is directed upwards. As the breaking action becomes
more effective with large currents, this principle has resulted
in increasing the rupturing capacities of such breakers to
higher values.
Arc chute is an efficient device for arc extinction in air and
performs the following three interrelated functions Fig. 3: ACB Rating [4]
1. It confines the arc within a restricted space.
2. It provides magnetic control over the arc movement so as
to make arc extinction within the devices. III. WORKING PRINCIPLE
3. It provides for the rapid cooling of arc gasses to ensures Air circuit breakers operate with their contacts in free air.
arc extinction by deionization. Their method of arc quenching control is entirely different
Air Chute Air Break Circuit Breaker: The normal from that of oil circuit-breakers. They are always used for a
arrangement of air-chute air break circuit breaker employed low-voltage interruption and now tends to replace high-
voltage oil breakers. The below-shown figure illustrates the frame to avoid rust and enhance reliability. The coordination
principle of air breaker circuit operation. of components within the frame allows ACBs to perform
Air Circuit breakers generally have two pairs of contacts. different functions and also consists of an electrical switch
The main pair of contacts (1) carries the current at normal to obtain stable performance.
load and these contacts are made of copper metal. The 4.The rated current and shell rating of ACB is higher
second pair is the arcing contact (2) and is made of carbon. compared to other circuit breakers. This also means that the
When the circuit breaker is being opened, the main contacts allowable current value of ACB is also higher and can be
open first. When the main contacts opened the arcing used to protect the motor. [3]
contacts are still in touch with each other. As the current
gets a parallel low resistive path through the arcing contact.
During the opening of main contacts, there will not be any V. CONSTRACTION & MAINTAINANCE OF ACB
arcing in the main contact. The arcing is only initiated when The construction of an air circuit breaker can be done by
finally the arcing contacts are separated. The each of the arc using different internal and external parts like the following.
contacts is fitted with an arc runner which helps. The arc The external parts of ACB mainly include the ON & OFF
discharge to move upward due to both thermal and button, an indicator for the position of the main contact, an
electromagnetic effects as shown in the figure. As the arc is indicator for the mechanism of energy storage, LED
driven upward it enters in the arc chute, consisting of indicators, RST button, controller, rated nameplate, handle
splatters. for energy storage, displays, shake, fault trip rest button,
The arc in the chute will become colder, lengthen and split rocker repository, etc. [6]
hence arc voltage becomes much larger than the system
voltage at the time of operation of air circuit breaker, and
therefore the arc is extinguished finally during the current
zero.
The air brake circuit box is made of insulating and fireproof
material and it is divided into different sections by the
barriers of the same material, as shown above,. At the
bottom of each barrier is a small metal conducting element
between one side of the barrier and the other. When the arc,
driven upwards by the electromagnetic forces, enters the
bottom of the chute, it is split into many sections by the
barriers, but the each metal piece ensures electrical
continuity between the arcs in each section, the several arcs
are consequently in the series.
When the oscillation starts between C and L as described
for the idealised circuit breaker shown in Figure below, this
resistance damps the oscillation heavily. Certainly, it is
Fig. 4: Construction of ACB [6]
usually so heavy that the damping is critical, the oscillation
cannot then take place at all, and the restriking voltage,
The internal parts of ACB mainly include supporting
instead of appearing as a high-frequency oscillation, rises
structure with steel sheet, the current transformer used to
dead-beat to its eventual value of peak generator voltage. [5]
protect the trip unit, pole group insulating box, horizontal
terminals, arcing chamber, trip unit for protection, terminal
IV. CHARECTARISTICS & FUNCTIONS OF ACB box, closing springs, CB opening & closing control, plates
to move arcing and main contacts, plates for fixed main &
ACBs are used in power systems including transformers, arcing contacts. [5]
power distribution stations, industrial and mining enterprises
due to its multiple advantages such as high sectional ACBs work like circuit protection devices for an extensive
capability, perfect function, compact structure and excellent range of low voltage applications up to 600V AC like UPS,
performance. generators, mini power stations, MCCB distribution boards,
1.When the incident of current overload or failure happens, etc and their sizes range from 400A to 6300A otherwise
ACB will instantly cut off the circuit acting as a larger.In this circuit breaker, nearly 20% of failures in the
combination of a fuse switch and an overheating relay. power distribution system occur due to less maintenance,
Under-voltage protection, and short-circuit protection are tough grease, dust, corrosion & frozen parts. So
effective in solving the problems of power equipment and maintenance of circuit breaker is the ideal choice to ensure
lines. consistent operation as well as expand the lifetime. The air
2.ACBs control the electrical circuits to operate electrical circuit breaker maintenance is very important. For that, it
equipment normally by cutting off and connecting the load should be turned off first, and then separated from both
circuit. These devices are compact due to their small size faces by opening the required electrical isolator. The circuit
and lightweight. Industrial, mining, power transformers, breaker should be worked at this no isolated condition for
distribution stations, and in many more places ACBs are restricted and distant areas in every year. The circuit breaker
used as they match the requirements of the industry and are must be worked electrically from restricted and isolated after
easy to install. that mechanically from restricted. This kind of process will
3.Insulation plates are used in ACBs as a protective measure make the breaker more consistent by detaching any outside
on both sides to separate the conductors while ensuring layer developed among sliding faces. [6]
safety in daily operation. The parts are placed within the
For testing a circuit breaker, different kinds of test
equipment are used to verify the condition of the circuit
VI. APPARATUS breaker in any power system. This testing can be performed
To do this lab we must need some equipment that are through different test methods as well as kinds of testing
required for conduct lab. The required apparatus are- equipment. The testing devices are analyzer, micro
1. ACB ohmmeter, primary injection tester with high current, etc.
2. DC source There are some benefits of circuit breaker testing like the
3. Clamp Meter [7] following.
1.The performance of the circuit breaker can be enhanced.
2.The circuit can be checked on load or offload.
VII. EXPERIMENTAL PRESIDURE 3.Recognizes requirement of maintenance
For energizing the charging motor, closing the contacts, 4.Issues can be avoided
opening the contacts and under voltage tripping, the 5.Early indications of faults can be identified [6]
terminals of control circuits for the motor are connected as
shown in the diagram. One incandescent lamp is connected
across one of the three phases of the contacts and the IX. ADVANTAGE & DISADVANTAGE OF ACB
neutral. [7] The advantages of an air circuit breaker include the
following.

1. High-speed re-closures facility


2. Used for frequent operation
3. Need less maintenance
4. High-speed operation
5. Fire risk can be eliminated not like in oil circuit breakers
6. Consistent and short arcing time, so burning of contacts is
less.
The disadvantages of air circuit breaker include the
following.
1.A drawback of the arc chute principle is its inefficiency at
low currents where the electromagnetic fields are weak.
2.The chute itself is not necessarily less efficient in its
lengthening and de-ionizing action than at high currents, but
the arc movement into the chute tends to become slower,
and high-speed interruption is not necessarily obtained. [6]
Fig. 4: Implementation of experimental circuit [7]

When the ON switch is pushed the contacts will be closed X. APPLICATIONS


and the lamp will glow and when the “OFF” switch is Air Circuit Breakers are used for controlling the power
pushed the contacts will be opened and the lamp will stop station auxiliaries and industrial plants. They offer
glowing. It is important to keep in mind that the voltage protection to industrial plants, electrical machines like
across the under voltage coil (i.e D1 and D2) should be transformers, capacitors, and generators.
maintained at about 220 V (ac) otherwise contacts cannot be 1.They are mainly used for the protection of plants, where
closed by pushing the ON switch. If the voltage across the there are possibilities of fire or explosion hazards.
under voltage coil is reduced below 200 V (approax.) the 2.The air brake principle of the air breaker circuit arc is used
breaker will automatically be tripped. [7] in DC circuits and AC circuits up to 12KV.
3.The air circuit breakers have high resistance power that
VIII. TESTING PROCEDURE helps in increasing the resistance of the arc by splitting,
cooling, and lengthening.
Circuit Breaker Testing is mainly used to check each 4.An air circuit breaker is also used in the Electricity sharing
switching system operation as well as the programming of system and NGD about 15kV [6]
the complete tripping construction. So, testing is very
essential for any kind of circuit breaker to ensure secure and
consistent performance. As compared to other devices, XI. REPORT QUESTION AND ANSWER
performing testing is more challenging. Suggest a protection scheme for a 10HP motor.
When a malfunction occurs in a circuit breaker then it can Answer: The amount of protection and its type, used for a
lead to a short circuit within the coils, incorrect behavior, motor is a compromise between factors such as the
damage the mechanical connections, etc. Thus, circuit importance of the motor, the potential dangers, the type of
breakers need to test regularly to overcome all these faults. duty and the requirements of protection coordination against
Different types of tests performed in circuit breaker mainly the cost of the protection scheme.The protection schemes
include mechanical, thermal, dielectric, short circuit, etc. that are illustrated represent common practise and
The routine tests of a circuit breaker are a trip test, insulation international recommendations for the protection of motors
resistance, connection, contact resistance, overload tripping, of different powers, and are divided into 4 categories:
instantaneous magnetic tripping, etc. 1.Protection of low power motors (less than 100 HP);
2.Protection of motors up to 1 000 HP; XII. DISCUSSION
3.Protection of motors greater than 1 000 HP; The air circulates the circuit breaker's magnetic coil, where
4.Additional protection for synchronous motors. it acts as an ARC quenching medium. It is very simplistic in
Protection of low power motors: Low power motors are construction. Circuit breakers smaller than normal are
normally protected by fuses associated with thermal associated with air circuit breakers. The length of the
overload relays incorporating bimetallic elements (Figure 5) distance between the contacts should be wide because if we
– the fuses protecting against short circuits. use it in high voltage the ARC needs to be extinguished with
no particular arrangement. The air circuit breaker doesn't
need an arc control system because it is set to run at 1KV.
The only perfect alternatives in the case of severe fault
current and low voltage are those that use ABCs with an
appropriate arc control system (low voltage level above 1
KV).

XIII. CONCLUSION
Due to the present pandemic situation as our university is
closed we can not observe the above equipment in hand. But
our honorable faculty did his at best to understood us about
all the functions, characteristics and specifications of those
equipment. To make our understanding more convenience
Fig.5: Schematic of fuse protection for low power motors [8] our faculty shows us a video which helps us more to
understand all the features. The main objective of this
Or low voltage breakers plus thermal overload relays experiment was to get familiar with different kinds of
(Figure 6) when the breaker should have a magnetic element insulators, fuses and Miniature circuit breaker and we have
to trip instantaneously under short circuit conditions. [8] understood all the specifications very well which is required
to fulfill this lab objective. So we can say, the lab was
successfully achieved.

REFERENCES
[1] https://www.electgo.com/acb-trip/
[2] https://circuitglobe.com/air-break-circuit-breaker.html
[3] https://www.micronovaimpex.com/how-acb-works/
[4] https://www.electgo.com/what-is-acb/
[5] https://electricalswitchboards.com.au/air-circuit-breaker-works/
[6] https://www.elprocus.com/air-circuit-breaker-acb-working-principle-
application/
Fig. 6: Schematic of low voltage breaker protection for low power motor [7] aiub lab menual
[8]
[8] https://electrical-engineering-portal.com/protection-schemes-of-
generators-and-motors

You might also like