Professional Documents
Culture Documents
, Governor
Erik Jacobson
Director, Regulatory Relations
Pacific Gas and Electric Company
77 Beale Street, Mail Code B10C
P.O. Box 770000
San Francisco, CA 94177
SUBJECT: Integration Capacity Analysis Methodology for the Online Map and
Interconnection Use Case
Sincerely,
Edward Randolph
Director, Energy Division
Erik Jacobson Pacific Gas and Electric Company
Director 77 Beale St., Mail Code B13U
Regulatory Relations P.O. Box 770000
San Francisco, CA 94177
Fax: 415-973-3582
November 6, 2017
Advice 5178-E
(Pacific Gas and Electric Company ID U 39 E)
Subject: Integration Capacity Analysis Methodology for the Online Map and
Interconnection Use Case
Purpose
Pursuant to Ordering Paragraph (OP) 7 of Decision (D.) 17-09-026, Pacific Gas and
Electric Company (PG&E) submits this advice letter to detail the Integration Capacity
Analysis methodology for the online map and interconnection use case.
Background
This Decision addresses Track 1 methodological issues for the Integration Capacity
Analysis (ICA), as well as the Locational Net Benefits Analysis (LNBA). It requires an
Advice Letter to be filed to document the ICA methodology, as it is a culmination of
several reports and rulings over the past year, including two Assigned Commissioner’s
Rulings (May 2, 2016 and August 23), the Demonstration Projects A and B reports
(PG&E’s report was filed December 27, 2016), and a final working group Report (filed
March 15, 2017). This Track 1 Decision defines the Integration Capacity Analysis
methodology to be the methodologies prescribed by the May 2, 2016 and August 23,
2016 Rulings and modified as discussed in the Decision. These modifications are listed
Advice 5178-E -2- November 6, 2017
in the enclosed document. The enclosed document captures the Track 1 Decision’s
ICA methodology to be used for the online map and interconnection use cases.
Protests
Anyone wishing to protest this filing may do so by letter sent via U.S. mail, facsimile or
E-mail, no later than November 27, 2017, which is 21 days1 after the date of this filing.
Protests must be submitted to:
Copies of protests also should be mailed to the attention of the Director, Energy
Division, Room 4004, at the address shown above.
The protest shall also be sent to PG&E either via E-mail or U.S. mail (and by facsimile,
if possible) at the address shown below on the same date it is mailed or delivered to the
Commission:
Erik Jacobson
Director, Regulatory Relations
c/o Megan Lawson
Pacific Gas and Electric Company
77 Beale Street, Mail Code B13U
P.O. Box 770000
San Francisco, California 94177
1
The 20-day protest period concludes on a weekend. PG&E is hereby moving this date to the
following business day.
Advice 5178-E -3- November 6, 2017
Effective Date
PG&E requests that this Tier 1 advice filing become effective upon date of filing, which
is November 6, 2017.
Notice
In accordance with General Order 96-B, Section IV, a copy of this advice letter is being
sent electronically and via U.S. mail to parties shown on the attached list and the parties
on the service lists for R.14-08-013 and A.15-07-006. Address changes to the General
Order 96-B service list should be directed to PG&E at email address
PGETariffs@pge.com. For changes to any other service list, please contact the
Commission’s Process Office at (415) 703-2021 or at Process_Office@cpuc.ca.gov.
Send all electronic approvals to PGETariffs@pge.com. Advice letter filings can also be
accessed electronically at: http://www.pge.com/tariffs/.
/S/
Erik Jacobson
Director, Regulatory Relations
Attachments
Protests, dispositions, and all other correspondence regarding this AL are due no later than 21 days1 after the date of this filing, unless
otherwise authorized by the Commission, and shall be sent to:
California Public Utilities Commission Pacific Gas and Electric Company
Energy Division Attn: Erik Jacobson
EDTariffUnit Director, Regulatory Relations
505 Van Ness Ave., 4th Flr. c/o Megan Lawson
77 Beale Street, Mail Code B13U
San Francisco, CA 94102 P.O. Box 770000
E-mail: EDTariffUnit@cpuc.ca.gov San Francisco, CA 94177
E-mail: PGETariffs@pge.com
1
The 20-day protest period concludes on a weekend. PG&E is hereby moving this date to the following business day.
Implementing Items from D.17-09-026
As directed in the October 10, 2017 decision, PG&E will utilize an iterative methodology
as demonstrated in Demonstration Project A. In addition to the methodological
requirements outlined in the May 2, and August 23, 2016 rulings, the following
methodological directives will be included:
• Update ICA results on a monthly basis for circuits which have experienced
relevant changes. These updates will be based on circuits which have
experienced a permanent change as a result of permanent distribution feeder
reconfiguration, significant upgrade to relevant electrical component such as
wires, protection devices or automation devices, or which have experiences
relevant increase in new DER interconnection requests.
• Employ 576 hourly profiles in the calculation and presentation of ICA results. This
includes the utilization of the 576 hourly load profile at the feeder level to
calculate the associated 576 ICA hourly profile at each electrical node or line
section within each distribution feeder.
• Calculate ICA values with and without the “No Reverse Flow” restriction at
Supervisory Control and Data Acquisition (SCADA) enabled Devices for initial
system-wide rollout in the same way modeled in Demo A.
o No Reverse Flow Restriction: The reverse flow of power at SCADA
enabled Devices will not restrain ICA values
o Reverse Flow Restriction: The operational flexibility (Op-Flex) ICA values
will be restrained to the not allow reverse power flow at the feeder’s
SCADA enabled devices.
o It should be noted that Op-Flex restriction was not applied for uniform load
and therefore, the ICA values for Uniform load (reverse) and Uniform load
(Op-Flex) will be the same and for these reason, PG&E may choose to
publish only one value for Uniform load to account for both Reverse flow
and Op-Flex flow ICA values.
• Present the following results and attributes in ICA maps, subject to appropriate
protections for customer-specific, proprietary and/or physical- or cyber-security
sensitive data:
Line section level
Attributes
• Circuit ID
• Section ID
• Voltage (kV)
• Substation ID
• System ID
ICA results
• Uniform generation(Reverse Flow)
• Uniform load(Reverse Flow)
• Fixed solar photovoltaic(Reverse Flow)
• Uniform generation(Op-Flex)
• Uniform load(Op-Flex)
• Fixed solar photovoltaic(Op-Flex)
Substation/Circuit level
Attributes from RAM Layer will be shown
Circuit ID
Voltage (kV)
Substation ID
Existing Generation (MW)
Queued Generation (MW)
Total Generation (MW)
• Display the following via links in the online ICA maps subject to appropriate
protections for customer-specific, proprietary and/or physical- or cyber-security
sensitive data:
• Circuit Load Profile;
• Substation Load Profile;
• Customer class proportions on circuit;
• Publish downloadable datasets the specific criteria violations such as thermal limits,
steady state ICA limits, Voltage fluctuation limits, Protection Limits, Operational
Flexibility associated with the limiting ICA value. The tools associated with
publishing of this data are still being developed. However, at minimum PG&E will
publish the data in an equivalent format as that of Demonstration Project A. PG&E
will report on progress on the development of the tools within the Intern Reports
• Model voltage regulating devices in initial system-wide rollout as it did for
Demonstration Project A and will continue to work with software vendors on the
ability to enable voltage regulating devices to be “unlocked”(float) within the iterative
power flow methodology.
• Calculate the ICA values such that:
1. ICA shall be limited by pre-existing conditions when adding DERs degrades
pre-existing condition. In this cases, SCE will publish an ICA value of zero;
and
2. ICA shall not be limited by pre-existing condition when adding DERs improves
pre-existing condition
Datasets
• Electric Distribution Geographic Information System (EDGIS): The circuit
model is built from detailed data, as described in level of granularity. It
contains the thermal ratings for conductors and devices, device and
equipment characteristics, and load and generation customer details.
• Load Shapes and Forecasts (LoadSEER): Load profiles and forecast
information that can be applied to the feeder loads and generation.
• Supervisory Control and Data Acquisition (SCADA): SCADA data is
leveraged by LoadSEER to develop the demand profile for each circuit, which
is then aggregated up to the substation bus.
• Advanced Metering Infrastructure (AMI): Interval metered data is extracted
for the customers on every circuit and load is allocated to the circuit model
and utilized in LoadSEER for profile evaluation.
Tools
• CYME Gateway: used to model and update distribution systems including but
not limited to conductors/cables, line devices, loads and generation
components
• CYMDIST: the Power Flow Analysis Tool used to perform load flow analyses
in order to determine electrical operating conditions of the distribution system.
o CYME’s new ICA module was also utilized specifically for iterative ICA
• Python: the dynamic object-oriented programming tool used to automate
both the streamlined method and the iterative method as well as perform data
analysis within the CYMDIST software
• LoadSEER: the load forecasting analysis tool used to develop electric
distribution forecasts and locational demand profiles throughout the system
• ESRI ArcDesktop: the maps and geographic information tool used for
creation of the geospatial ICA results visualization on the PG&E RAM map
Various data points are used to help inform the power flow analysis. While some
parameters are static and do not have any significant variance (i.e. conductor
impedance), there are some parameters that could have some variation and need to be
set for the analysis (i.e. starting voltage at substation). The sections are a listing of
some of the assumptions and starting points PG&E used in the analysis.
Geospatial Network
PG&E models each of its distribution feeders using its Power Flow Analysis Tool. This
tool analyzes power flow on distribution feeders by modeling conductors, line devices,
loads, and generation to determine impacts on distribution circuit level power quality
and reliability. These electrical models are updated weekly using the CYME Gateway to
reflect changes that occur on PG&E’s distribution system.
Secondary Service
At this time secondary services are not modeled in CYMDIST. This will be additional
work to the gateway as well as work to compile and translate into the GIS system. The
power flow models stop at the primary side of the service transformer. Because of this
the ICA is limited to evaluated primary distribution side issues and can’t determine any
secondary service issues.
Substation Model
Historically, PG&E’s distribution circuits in CYME are modeled from the circuit breaker
at the substation down to the primary side of customer service transformers. PG&E is
in development of upgrading the CYME Gateway to translate the GIS data from the new
GIS system being implemented. While the substation model is not critical to all
components of ICA, it may help in providing some more detail in the Power Quality and
Protection criteria to understand adjacent feeder impacts. Figure 8 shows how
CYMDIST utilizes a one-line model layer for subsation components versus the
geographic model for distribution lines.
Figure 3: Substation Models in CYMDIST
PG&E is continuing to enhance the models to include the substation models and will
incorporate to ICA as necessary and feasible. While the substation model may be
helpful, PG&E does not believe the direct modeling of it is necessary within the analysis
at this time. At a minimum, PG&E will implement what was performed in Demo A
regarding substation consideration.
Feeder Configuration
Feeder configurations in the model are set to the normal as planned switching states.
These configurations are used in the interconnection study process. The vast amount of
possible switching configurations and computational burden will be an interesting
hurdle. This is why PG&E proposed the method of evaluation called “Operational
Flexibility” to estimate when possible issues could occur without performing millions of
permutations on top of the already lengthy ICA analysis time. This topic is being
discussed further within the ICA Working Group.
4
Load
0% 7
4
12
Month11
5
2
1
90/ Load Hour
8
6
3
Percent
100%
80%
60%
40%
20% of
DER Placement
In its current stage the ICA is more focused on large centralized DER impacts and the
implementation into the interconnection process. Every new DER location is analyzed
independently of any other new DER being placed on the circuit. The iterative ICA
methods at this stage has explicitly only been utilized in a centralized DER approach.
Application of the iterative ICA will be limited to single interconnections alone and may
not be fully effective for aggregate groups of DER.
DER Parameters
In order to determine the impact of DER on the system, the analysis must consider a
few basic parameters of the DER. The following is the list of parameters that were
considered:
• Real Power Consumption (Load) and Real Power Injection (Generation)
o Results for ICA are to be agnostic to DER with final ICA as hourly results
o The analysis does not necessarily work in the manner of assuming a
specific reduction of output/input at a given hour. It evaluates what level
of output/input creates an expected violation at each hour.
o DER specific output is proposed to be considered in post analysis based
on the hourly results to get specific DER results
• Power Factor
o Base results will be run assuming a unity power factor
• Fault Contribution (for generators)
o Fault contribution will assume 120% of nameplate for inverter technologies
The iterative simulation is the direct modeling of new resources and performing iterative
simulations for determining integration capacity at each node. Each analysis uses
power flow calculation engines to compute the phase currents and voltages at every
node on the network given the load and generation levels under various scenarios in the
model.
Thermal Criteria
An hour-by-hour calculation is performed to compare the equipment thermal limits given
a certain amount of DERs. The Integration Capacity value is the highest value of DER
which can be connected at a node which does not exceed the thermal rating of any
piece of upstream equipment on the distribution circuit or substation.
The iterative technique evaluates the loading conditions of all the assets on the feeder
for each iteration of evaluation. When equipment thermal ratings are exceeded by their
respective power throughput then the tool flags this condition. This condition then
informs the ICA module that a thermal limit has been exceeded.
Voltage Variation
Voltage fluctuation is evaluated to ensure deviations from loads and resources on the
grid do not cause harm or affect power quality to nearby customers. The voltage
fluctuation limit used in Demo A is 3% 1, which is prescribed by engineering standard
practices. This criterion is used in order to minimize the impact of fluctuations caused by
DERs on other customers.
Iterative methods perform a power flow with the DER on and off and compare the node
voltages before and after. All voltage devices on the feeder are locked in order to
understand the true voltage variation before the voltage devices correct for such
changes. When any node voltage deviation surpasses the set threshold then the DER
size is recorded for that node.
Protection Criteria
The iterative method performs a fault flow analysis to the protection limitation. This
determines the specific fault contribution that would occur based on the impedance
between the fault and the generator and to ensure that the end of line fault current can
still be seen. The device fault current must exceed the minimum trip value by a specific
threshold as prescribed by protection engineering practices. A generator is placed at the
end of line fault location for each protective zone and then simulates a fault at that node.
1
The 3% limit can be found in IEEE Std 1453-2015 “IEEE Recommended Practice for the Analysis of
Fluctuating Installations on Power Systems” in Table 3 for medium voltage systems.
When protection device currents do not meet set thresholds then the DER value is
recorded.
The iterative method performs a power flow and determines if there is reverse flow
through the devices prescribed for assessment. The IOUs recognize that this is more of
a heuristic approach. While heuristic approaches were not encouraged, the IOUs have
established that non-heuristic approaches to analyzing this issue are quite process
intensive and will significantly hinder the ability to achieve efficient results.
Appendix: ICA Criteria Tables
‒ Substation Transformer --
‒ Circuit Breaker --
‒ Primary Conductor --
Voltage / Power Quality Creating power quality conditions outside acceptable ranges
‒ Transient Voltage Short time period relative voltage variation outside acceptable limits
‒ Voltage Regulator Impact Creating conditions for regulator to improperly manage voltage
‒ Substation Load Tap Changer Impact Creating conditions for LTC to improperly manage voltage
‒ Protective Relay Reduction of Reach Reducing bulk system fault contribution to protection devices
Creating conditions that diminish operating reliability and
Safety/Reliability
safety
‒ Transmission Penetration Limiting reverse flow into the transmission system
Thermal
‒ Substation Transformer 1
‒ Circuit Breaker
‒ Primary Conductor
‒ Main Line Devices
‒ Tap Line Devices
Voltage / Power Quality
‒ Transient Voltage
‒ Steady State Voltage
‒ Voltage Regulator Impact 2
‒ Substation Load Tap Changer Impact 3
Protection
‒ Protective Relay Reduction of Reach
Safety/Reliability
‒ Transmission Penetration
‒ Operational Flexibility