POWER-RELATED DATA (power ratings are net brake power to ISO 3046)
3D Fuel Stop 3D Fuel Stop
3A Continuous 3B Prime Power 3A Continuous 3B Prime Power
Power ISO 3046 Power ISO 3046
Power ISO 3046 ISO 3046 Power ISO 3046 ISO 3046
Engine Mechanical Power kWm 1310 1575 1750 1420 1736 1910
Fan Losses kWe 49 49 49 64 64 64
Marathon Electric Generator Efficiency % 0.964 0.959 0.954 0.963 0.964 0.962
Genset Net Output Power @ .8pf kWe 1216 1463 1623 1306 1612 1776
Engine rated speed rpm 1500 (50Hz) 1800 (60Hz)
Mean piston speed m/s 10.5 12.6
Mean effective pressure bar 18.3 22 24.5 16.5 20.2 22.3
GENERAL CONDITIONS (for maximum power)
Intake air depression (new filter) mbar 15 15
Intake air depression, max. mbar 50 50
Exhaust back pressure, max. mbar 85 85
Fuel supply temperature °C 25 25
Max supply fuel temperature °C 55 55
FUEL CONSUMPTION (+ 5 %; EN 590; 42.8 MJ/kg;+ 5%; fuel density 0.86 g/ml )
100 % Load g/kWh 192 193 196 200 201 206
75 % Load g/kWh 197 194 190 204 199 198
50 % Load g/kWh 207 201 198 218 212 208
25 % Load g/kWh 240 228 220 260 245 236
No-load fuel consumption kg/h 21 21 21 29 29 29
Constant engine power available at intake air temperatures of up to 40°C and site altitudes of up to 3000 m above sea level.