Hydronic Boiler

MAGNATHERM FT ®

CFH  Firetube Boiler


 Indoor / Outdoor, Sizes 1000 - 3000
Date:

Submittal Data
Project #:

Engineer: Project Name:

MagnaTherm FT Submittal Data


Prepared By: Location:
MagnaTherm FT Submittal Data

Standard • ASME "H" stamp • Electronic PID modulating


Bid Date: • Sensor for indirect DHW tank
Contractor:
MagnaTherm
Features
Standard FT
• Submittal
160 psi maximum
ASME "H" stamp Data
working pressure • control withPID
Electronic large touchscreen
modulating • Outdoor
Sensor for reset with DHW
indirect air sensor
tank
Features • 160
Certified for Category
psi maximum II andpressure
working and color
control display
with large touchscreen • Outdoor
Horizontal or vertical
reset with airdirect
sensor vent
• Category IV Category
Certified for vent systems
II and • Multiple
and colorindependent
display heat demands • Horizontal
Vent and air orpipe lengths
vertical directofvent
up to
Standard •• ASME "H" stamp
Indoor/outdoor
Category IV vent systems • •Electronic PID modulating
VARI-PRIME
Multiple boiler pump
independent demands •
heat control Sensor
• 100Vent for indirect DHW
equivalent
and air pipe feet tank
(each)
lengths of up to
Standard
Features •• 160 psi maximum working pressure control with large touchscreen • Outdoor reset with air sensor
Features Low NOx system exceeds the
Indoor/outdoor • via user-selectable
VARI-PRIME boiler fixed
pumpboiler
control • 100Highequivalent
& low gas feet pressure
(each)switches
• Certified for Category II and and color display • Horizontal or vertical direct vent
• most stringent
Low NOx regulations
system exceeds for
theair temperature rise fixed boiler
via user-selectable • High
Vent & temperature
low gas pressure cutoff switches
Category IV vent systems • Multiple independent heat demands • Vent and air pipe lengths of up to
qualitystringent regulations for air
most • temperature
Wired and programmed
rise to control • Vent
Normally open alarm
temperature contact
cutoff
• Indoor/outdoor • VARI-PRIME boiler pump control 100 equivalent feet (each)
• High condensing efficiency
quality • boiler
Wired isolation valves to control
and programmed • Normally
Air filter open alarm contact
• Low NOx system exceeds the via user-selectable fixed boiler • High & low gas pressure switches
• Up tocondensing
High 20:1 turndown modulation
efficiency
most stringent regulations for air
•temperature
Controller
boiler cascades
isolation
rise
valveswith up to
• • Built-in
Air filtercondensate trap
Vent temperature cutoff
• Sophisticated
Up gas/airmodulation
to 20:1 turndown
quality
valve
• •Wired
eight MagnaTherm
Controller cascadesFT boilers
with
and programmed to control
up to • • Temperature
Built-in & pressure
condensate
Normally open alarm contact
trap gauge

•• allows
High for constant
Sophisticated gas/air
condensing control
valve
efficiency •boiler
Accepts
eight 4-20ma
MagnaTherm
isolation valves or 0-10VDC
FT boilers • Air• filter
Low water cutoff
Temperature & pressure gauge

• of modulation
allows
Up for turndown
to 20:1 constant control
modulation • •Controller
external modulation
Acceptscascades
4-20ma or orup
external
0-10VDC
with to • • Water
Low flow
water
Built-in condensate trap switch
cutoff
•• • Water
TM
Trumodulation
of Trac real-time
Sophisticated O2 sensing
gas/air valve setMagnaTherm
point modulation
external
eight control FT boilers
or external • 75 psi flow
Temperature (517kPa)
switchASME
& pressure gaugerated
• maintains
Tru Trac
allows
TM
efficiency
real-time
for constant throughout
O2 sensing
control • •Accepts
Modbus
set point RTU
control
4-20ma & BACnet
or 0-10VDCMSTP • • 75
Low pressure
psi cutoff
water relief valve
(517kPa) ASME rated
the
of modulation
maintains rangethroughout
efficiency
modulation •external
on board
Modbus RTU & BACnet
modulation MSTP
or external • • Flange
Water pressure water
flow switch relieffittings
valve
•• Tru
the Trac
TM
Stainless steel vertical
real-time
modulation range firetube heat
O2 sensing •seton
Multiple
point pump control for boiler
control
board • 75• psiBurner
(517kPa)
Flange site
water glass
ASME rated
fittings
• maintains
Stainless efficiency
exchanger throughout
withvertical
steel welded construction
firetube heat • •Modbus
pump, RTU
Multiplesystem& BACnet
pump pump, MSTP
control &forindirect
boiler DHW • Burner
pressure relief
Heat exchanger valve
site glasswarranty:
• the modulation
Sealed withrange
combustion
exchanger chamber
welded construction onpump,
boardpump,
water systemeach indirect DHW •
with& delay
pump, • 10-Year
Flange Heat water fittings non-prorated
limited
exchanger warranty:
•• Stainless
Sealed steel vertical
Pre-mixcombustion
stainless steelfiretube
burnerheat
chamber • •Multiple pump
Indirect
water water
pump, control
heater
each forpriority
with boiler
delay • Burner site glass
25-year
10-Year limited
limited thermal shock
non-prorated
• exchanger with welded construction
Pre-mix stainless steel burner
pump, system pump, & indirect DHW
• Indirect water heater priority • Heat exchanger warranty:
• 1-Year limited
25-year limitedparts warranty
thermal shock
• Sealed combustion chamber water pump, each with delay 10-Year limited non-prorated
• 1-Year limited parts warranty
• Pre-mix stainless steel burner • Indirect water heater priority 25-year limited thermal shock
• 1-Year limited parts warranty

Boiler Number of Units Voltage


Data
Boiler Number of Units 120V, single ph (1000-2000)
Voltage 208V, three ph (2000-3000)
Boiler Data
Data
Boiler Number of Units Voltage
208V, single ph (1000-2000)
120V, single ph (1000-2000) 480V, three ph (2000-3000)
208V,

Data Fuel 220/240V,


208V,
120V, single single
single
ph ph ph (1000-2000)
(1000-2000)
(1000-2000) 600V,
threethree
480V,
208V, ph (2000-3000)
ph (2000-3000)
FuelNatural 220/240V,
208V, single
single ph ph (1000-2000)
(1000-2000) 600V,
480V, threethree ph (2000-3000)
ph (2000-3000)
FuelNatural 220/240V, single ph (1000-2000) 600V, three ph (2000-3000)
Natural

Factory ASME CSD-1 Additional auto & manual 75 psi pressure relief valve (std)
Factory
Mounted
Factory BACnetCSD-1
ASME IP gateway reset high auto
Additional limit switches
& manual 30 psi pressure relief valve (std)
75
Mounted
Factory ASME CSD-1 Additional auto & manual 75 psi
Options
Mounted LonWorks
BACnet IP gateway
gateway Alarmhigh
reset bell with
limit silence switch
switches 30pressure
50 relief relief
psi pressure valvevalve
(std)
Options
Mounted BACnet IP gateway reset high limit switches 30 psi
Options LonWorks gateway Alarm bell with silence switch 60pressure relief relief
psi pressure valve valve
50 psi pressure relief valve
Options LonWorks gateway Alarm bell with silence switch 50 psi pressure relief valve
125psi
psipressure
pressurerelief
reliefvalve
valve
60
60 psi pressure relief valve
150 psi pressure relief valve
125
125 psi pressure relief valve
150 psi pressure relief valve
150 psi pressure relief valve

Accessories Gateway for BACnet IP Screen for vertical stainless Screen/adapter for vertical or
for Field
Accessories
Accessories Gateway for LonWorks
BACnet IP
Gateway for BACnet IP
H steel vent
Screen for vertical stainless
Screen for vertical stainless
horizontal PCV ducted
Screen/adapter air or
for vertical
Screen/adapter for vertical or
Mounting
for Field Motorizedfor
Gateway isolation valve(s)
LonWorks Screen for horizontal CPVC vent
steel vent Screen forPCV
horizontal horizontal
ductedgalvanized
air
125 psi pressure relief valve
150 psi pressure relief valve

Accessories Gateway for BACnet IP Screen for vertical stainless Screen/adapter for vertical or
Accessories
for Field Gateway for LonWorks steel vent horizontal PCV ducted air
for Field
Mounting Motorized isolation valve(s) Screen for horizontal CPVC vent Screen for horizontal galvanized
Mounting Condensate neutralizer Screen for vertical CPVC vent or vertical ducted air
Condensate neutralizer with pump Screen for horizontal Screen for horizontal
Vent terminal for outdoor unit polypropylene vent polypropylene ducted air
Screen for outdoor unit air Screen for vertical Screen for vertical
Vent terminal for horizontal polypropylene vent polypropylene ducted air
stainless steel vent

Sizing Data
Modulation
Minimum Maximum Minimum Maximum Thermal Combustion
Sizing Data Model
Input Rate Input Rate Output Rate Output Rate Efficiency Efficiency
Turndown
Ratio
MBH kw MBH kw MBH kw MBH kw % %
1000 67 19.6 999.9 293 63 18.5 950 278 95.8 96.1 15:1
1500 75 22.0 1500 440 71 20.8 1425 418 95.9 96.3 20:1
2000 100 29.3 1999.9 586 95 27.8 1900 557 95.4 95.5 20:1
3000 150 44.0 3000 879 143 41.9 2850 835 95.9 95.9 20:1

Product Operating Shipping


Model Water Content
Weight Weight Weight

lbs kg lbs kg lbs kg gal l


1000 1300 590 1934 878 1450 658 76 288
1500 1450 658 2292 1041 1600 726 101 382
2000 1750 795 2717 1234 1950 885 116 439
3000 2050 931 3292 1495 2250 1022 149 564

Clearances
Suggested
Clearance to
Clearances Combustibles
Service
Clearance
inches cm inches cm
Front 18 46 24 61
Back 18 46 24 61
Left 3 8 12 30
Right 3 8 12 30
Top 3* 8 24* 61

Note: A 4" high equipment pad is required.


This pad must NOT extend more than 3" beyond the boiler base structure at the rear of the boiler.
*24" top clearance is suggested to service the unit.

Electrical
Electrical
Data
Data 1000 1500 2000 3000
Current Current Current Current
Voltage FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP
120V, 1 phase 5.0 6.2 15.0 6.2 7.8 15.0 7.8 9.7 20.0 N/A N/A N/A
208V, 1 phase 2.9 3.6 15.0 3.6 4.5 15.0 4.5 5.6 15.0 N/A N/A N/A
220/240V, 1 phase 2.7 3.4 15.0 3.4 4.2 15.0 4.3 5.3 15.0 N/A N/A N/A
208V, 3 phase N/A N/A N/A N/A N/A N/A 3.3 4.1 15.0 4.5 5.6 15.0
480V, 3 phase N/A N/A N/A N/A N/A N/A 1.5 1.9 15.0 2.1 2.6 15.0
600V, 3 phase N/A N/A N/A N/A N/A N/A 1.1 1.4 15.0 1.4 1.8 15.0
FLA - FullAmperage
Full Load Load Amperage
Minimum
MCA Circuit Ampacity
- Minimum Circuit Ampacity
Max Over-current Protection
MOP - Maximum Over-current Protection
Venting
Information
Venting
Information Maximum
Maximum Typical
Vent Model
Vent / Air
Air Pipe Size Ducted Air Pipe
Category IV Category IV
Maximum Category II Vent
Information Connector Size
Vent / Air
Maximum
Length
Vent Pipe Size
Category IV
Vent Pipe
Category IV
Typical
Pipe Size***
Model Air Pipe Size Ducted Air Pipe Length Category II Vent
Connector Size Vent Pipe Size Vent Pipe
Length Pipe Size***
inches cm inches cm ft* m inches cm ft*Lengthm inches cm
1000 6
inches 15
cm 6
inches 15
cm 100
ft* 30.5
m 6
inches 15
cm 100
ft* 30.5
m 12
inches 30
cm
1500
1000 8
6 20
15 8
6 20
15 100
100 30.5
30.5 8
6 20
15 100
100 30.5
30.5 14
12 36
30
2000
1500 8
8 20
20 8
8 20
20 100
100 30.5
30.5 8
8 20
20 100
100 30.5
30.5 18
14 46
36
3000
2000 10
8 25
20 10
8 25
20 100
100 30.5
30.5 10
8 25
20 100
100 30.5
30.5 22
18 56
46
3000 10 25 10 25 100 30.5 10 25 100 30.5 22 56

*Equivalent Feet: Equivalent Feet: To calculate maximum equivalent length, measure the linear feet of the pipe

*Equivalent Feet: and add 5 feet


Equivalent (1.5m)
Feet: for eachmaximum
To calculate elbow used.
equivalent length, measure the linear feet of the pipe
***Category II: Category II pipe size may vary. Draft must
and add 5 feet (1.5m) for each elbow used.remain between -0.1 and -0.001" w.c..
Notes:
***Category II: Category II pipe size may vary. Draft must remain between -0.1 and -0.001" w.c..
1. Installations in the U.S. require exhaust vent pipe that is CPVC complying with ANSI/ASTM D1785 F441,
Notes:
1.stainless steelincomplying
Installations with UL1738,
the U.S. require exhaustorvent
polypropylene
pipe that is complying with ULC
CPVC complying S636.
with ANSI/ASTM D1785 F441,
2.stainless
Installations in Canada require exhaust vent pipe that is certified to ULC
steel complying with UL1738, or polypropylene complying with ULC S636.S636.
3.
2. Intake (air) pipe
Installations must berequire
in Canada PVC orexhaust
CPVC vent
that complies
pipe that with ANSI/ASTM
is certified to ULCD1785
S636. F441, ABS that complies with
ANSI/ASTM D1527, stainless steel, or galvanized material.
3. Intake (air) pipe must be PVC or CPVC that complies with ANSI/ASTM D1785 F441, ABS that complies with
ANSI/ASTM D1527, stainless steel, or galvanized material.

Water Flow
Requirements
Temperature Rise
Water Flow Model 20°F 30°F 40°F 50°F 60°F 70°F
Requirements Flow HL* Flow HL* Flow HL* Flow HL* Flow HL* Flow HL*
gpm ft gpm ft gpm ft gpm ft gpm ft gpm ft
1000 95 1.9 63 1.1 48 0.7 38 0.5 32 0.4 27 0.3
1500 142 3.4 95 1.6 71 1.0 57 0.6 48 0.5 41 0.3
2000 190 4.5 127 2.1 95 1.2 76 0.8 63 0.6 54 0.4
3000 285 7.0 190 3.5 142 2.1 114 1.4 95 1.0 81 0.8
*Headloss is for boiler only (no piping).

Temperature Rise
Model 11°C 17°C 22°C 28°C 33°C 39°C
Flow HL* Flow HL* Flow HL* Flow HL* Flow HL* Flow HL*
l/m (m) l/m (m) l/m (m) l/m (m) l/m (m) l/m (m)
1000 360 0.6 239 0.3 182 0.2 144 0.2 121 0.1 102 0.1
1500 538 1.0 360 0.5 269 0.3 216 0.2 182 0.2 155 0.1
2000 719 1.4 481 0.6 360 0.4 288 0.2 239 0.2 204 0.1
3000 1079 2.1 719 1.1 538 0.6 432 0.4 360 0.3 307 0.2
*Headloss is for boiler only (no piping).
Dimensions

Dimensional Model "A" "B" "C" "D" "E" "F" "G" "H"
Data in (cm) in (cm) in (cm) in (cm) in (cm) in (cm) in (cm) in (cm)
1000 30.2 (76.7) 80.0 (203) 52.4 (133) 70.5 (179) 60.0 (152) 8.2 (20.9) 60.0 (152) 74.2 (188)
1500 30.2 (76.7) 80.0 (203) 52.4 (133) 70.5 (179) 60.0 (152) 7.8 (19.7) 60.3 (153) 74.2 (188)
2000 34.6 (87.9) 80.0 (203) 56.3 (143) 73.3 (189) 60.0 (152) 9.1 (23.0) 63.1 (160) 73.6 (187)
3000 34.6 (87.9) 80.0 (203) 56.3 (143) 75.5 (192) 60.0 (152) 8.4 (21.4) 65.4 (166) 73.6 (187)

MAGNATHERM
MAGNATHERM
MAGNATHERM
FT -FTDimensional
- Dimensional
FT - Dimensional
Data
DataData
Model "J" "K" "L" "M" "N" "P" "R" "S"
T Dimensional
CFT Dimensional
CFT
DataDimensional
(inches/(cm)
Data (inches/(cm)
Data (inches/(cm) in (cm) in (cm) in (cm) in (cm) in (cm) in (cm) in (cm) in (cm)
ELAMODELA BA B C B C D C D P N R R P S S
1000 E 70.8 D E F
(180) E F
67.3 G (171) FG H
13.4 GH
(34.0) J
13.0HJ (33.1) K K
J
7.9 L
(20) LK 15.1 M
(38.4)ML N
6.4 N(16.3)
M P
2.9 (7.3)
1.0 8.2/(20.98).2/(2 60.90)/( 185.6220./4.(0 )2/0( 1.95)2.4) 60.0/( 152.4) 2.9/(7.3)2.9/
2/(76.7)
30.2/(76.7)
1.5
30.2/(76.7) 52.4/(13532
) .4/(1
70.5/(179)
33)52.4/70.5/(179)
(1 33)
1500 70.5/(179)
70.8 7.8(180)
/(19.77).8/67.3
(6109..37/)(157(171)
6
3.80 .3/.3
74.213.4
)()1/(91.5
/( 18784.4.2) /( 1
78
08
.8.4
/()1779
40
.72.8
)//( 1
(1878(33.1)
153.3) ) 13.0 67.3/(171.1)
73) .3) )60.3/((34.0)
9..47)) 70.8/7.9(179.7) (20)
67.3/(171.1)
13.4/(34) 67.3/(171.1)
13.4/(34) 15.1 13.0/(33.1)
13.0/(33.1) 13.4/(34) 6.413.0/(33.1)
(38.4) 15.1/(38.4)
(16.3) 2.76.4/(16.3)
15.1/(38.4) 6.4/(16.3)
(6.9) 15.1/(38.4) 6
2.7/(6.9)2.7/
80.0/(203.2)
80.0/(203.2)
80.0/(203.2) 60.0/(152.4)
60.0/(152.4)60.0/(152.4) 3.8/(9.6)3.8/(9.6) 3.8/(9.6)
2.0 73.3/(18783
.8.2000
3) /(188.87)3.3/72.0
(188.89).1(183)
/(23.09).1/67.3
(263.01)/( 196(171)
.6013./2.(1
)2/3( 1.06)013.4
.2) 63.1/(34.0)
( 160.2) 13.0 (33.1) 10.1 17.3 (44.0) 8.2 (20.9) 3.88.2/(20.9) 3.8/(9.5)3.8/
6/(87.9)
34.6/(87.9)
34.6/(87.9)56.3/(143.1)
56.3/(143.1)
56.3/(143.1) 73.6/(186.8)73.6/(186.8) 72.0/(182.8) 72.0/(182.8) (26)
72.0/(182.8)
73.6/(186.8) 17.3/(44.0)
17.3/(44.0) (9.5) 17.3/(44.0)
8.2/(20.9) 8
3.0 75.5/(197
15.8.5) /(191.87)5.5/(191.88).4/(21.48).4/(2 615.4)/( 186.645./2.(4 )2/1( 1.46)6.2) 65.4/( 166.2) 68.4/(176 38
.6.4) /(11743..46/)(3661
.684)..44/(137
64.360.)/6()351
.514)4.0.4
/(/3(53.65.)6) 14.0/(35.5) 3.6/(9.1)3.6/
3000 72.0 (183) 68.4 (174) 14.4 (36.6) 14.0 (35.5) 10.1 (26) 17.3 (44.0) 8.2 (20.9) 3.6 (9.1)

Inlet and outlet water connections are 3-inch 150# flanges, 4 hole, 6" bolt circle

MAGNATHERM FT ®

F F F

G G G
Pressure Pressure Pressure
Relief Relief Relief
Valve Valve Valve
D D D P P P
A A A C C C S S S R R
Gas Gas Gas
Inlet Inlet Inlet
2" NPT Pipe
2" NPT Pipe 2" NPT Pipe

Touchscreen
Touchscreen
Touchscreen
Display Display Display Air Air
Inlet Inlet

Water Water
Outlet Outlet
3” Flange3” Flange

ElectricalElectrical
Boxes Boxes
B B B
H H H
J J J
K K K
E E E

Vent Vent Vent Water Water


Inlet Inlet
3” Flange3” Flange

L M L M L M
4” Min 4” Min 4” Min
Condensate
Condensate Trap Trap Condensate Trap
1" Drain Hose
1" Drain Hose 1" Drain Hose
3” Max 3” Max 3” Max N N N

Laars Heating Systems Company reserves the right to change specifications, components, features, or to discontinue products without notice.

Customer Service and Product Support: 800.900.9276 • Fax 800.559.1583


Headquarters: 20 Industrial Way, Rochester, NH, USA 03867 • 603.335.6300 • Fax 603.335.3355
9 Brigden Gate, Halton Hills, Ontario, Canada L7G 0A3 (905) 203-0600 Fax: (905) 636-0666
www.Laars.com Litho in U.S.A. © Laars Heating Systems 20-07 Document 1460C