Professional Documents
Culture Documents
Agenda
Who am I and why am I talking?
Typical fire sprinkler approval, design, and installation
What is Acceptance Testing
Why perform Acceptance Testing
Activities performed during Acceptance Testing
Documentation of Acceptance Testing
Perils of not performing Acceptance Testing
Open discussion and questions
Closing
Kevin Geidel, CFPS, CET
Fire Protection Engineer
C&S Engineers, Inc.
Who Am I? Objectives
Kevin Geidel, CFPS, CET
Fire Protection Engineer – C&S Companies Explain code requirements for acceptance testing
Adjunct Professor – SUNY OCC FPT Explain hydrostatic pressure testing
Firefighter/EMT – Liverpool FD Explain system operational tests
Past President – SFPE NY Empire Chapter Identify information on Contractor’s Material and Test
NYS Certified Code Enforcement Official Certificate for Underground Piping and Aboveground
Fire Investigator – NAFI‐CFEI, CVFI, CFII, and IAAI‐ECT Piping
M.S. – Safety, Security & Emergency Management Explain the requirements for flow testing a backflow
B.S. – Fire & Safety Engineering Technology prevention assembly
Describe components inspected in field inspection
Explain required end user information
Fire Code of NYS
Chapter 9 – Fire Protection Systems
Section 901 – General
Explain code requirements for acceptance testing
901.1 Scope. The provisions of this chapter shall specify where fire protection systems are
Explain hydrostatic pressure testing required and shall apply to the design, installation, inspection, operation, testing and
Explain system operational tests maintenance of all fire protection systems.
1
10/2/2015
Fire Code of NYS Fire Code of NYS
Fire Code of NYS Fire Code of NYS
Title 19 (NYCRR) Title 19 (NYCRR)
Chapter XXXII – Division of Code Enforcement and Administration Chapter XXXII – Division of Code Enforcement and Administration
Part 1203 – Uniform Code: Minimum Standards for Administration and Enforcement Part 1203 – Uniform Code: Minimum Standards for Administration and Enforcement
(a) Building permits. (a) Building permits.
(1) Building permits shall be required for work which must conform to the Uniform Code. A (2) An application for a building permit shall request sufficient information to permit a
government or agency charged with or accountable for administration and enforcement determination that the intended work accords with the requirements of the Uniform
of the Uniform Code may exempt from the requirement for a permit the categories of Code and shall require submissions of the following information and documentation:
work listed in subparagraphs (i) through (xii) of this paragraph. An exemption from the …
requirement to obtain a permit shall not be deemed an authorization for work to be (v) at least 2 sets of construction documents (drawings and/or specifications) that
performed in violation of the Uniform Code. The following categories of work may be define the scope of the proposed work.
excluded from the requirements for a building permit:
… (3) Construction documents shall not be accepted as part of an application for a building
(xii) repairs, provided that such repairs do not involve: permit unless such documents:
…
(d) the removal from service of all or part of a fire protection system for any (i) are prepared by a New York State registered architect or licensed professional
period of time engineer where required by the Education Law;
…
Fire Code of NYS Fire Code of NYS
2
10/2/2015
Fire Code of NYS Building Code of NYS
901.3 Modifications. No person shall remove or modify any fire protection system installed or
maintained under the provisions of this code or the Fire Code of New York State without
approval by the code enforcement official.
24.2.5 Backflow Prevention Assemblies
24.2.6 Exposure Systems
NFPA 13 – Standard for the Installation of Sprinkler Systems
Chapter 24 – Systems Acceptance
Explain code requirements for acceptance testing 24.2 Acceptance Requirements
24.2.1 Hydrostatic Tests
Explain hydrostatic pressure testing
Explain system operational tests 24.2.1.1 Unless permitted… all piping and attached appurtenances subjected to
system working pressure shall be hydrostatically tested at 200 psi and shall
Explain acceptance testing of the main system drain maintain that pressure without loss for 2 hours.
Identify information on Contractor’s Material and Test
24.2.1.2 Portions of systems normally subjected to system working pressures in
Certificate for Underground Piping and Aboveground excess of 150 psi shall be tested as described in 24.2.1.1, at a pressure of 50
Piping psi in excess of system working pressure.
Explain the requirements for flow testing a backflow 24.2.1.3 Where cold weather will not permit testing with water, an interim air test
prevention assembly shall be permitted to be conducted as described in 24.2.2. This provision shall
not remove the or replace the requirement for conducting the hydrostatic
Describe components inspected in field inspection test as described in 24.2.1.1.
Explain required end user information
3
10/2/2015
Question: Question:
Is it acceptable to utilize compressed gas to provide the required Is it acceptable to utilize compressed gas to provide the required
test pressure when completing a hydrostatic test? test pressure when completing a hydrostatic test?
Answer:
The use of nitrogen or other inert gases to increase the water
pressure to the required test pressure is an acceptable test
method; however, for reasons of safety, these gases can only
be used in conjunction with water‐filled piping. Dry piping
should never be pressurized with gases beyond 40 psi.
24.2.1.5 Where addition or modification is made to an existing system affecting
more than 20 sprinklers, the new portion shall be isolated and tested at not
less that 200 psi for 2 hours.
24.2.1.6 Modifications that cannot be isolated, such as relocated drops, shall not
require testing in excess of system working pressure.
24.2.1.7 Loss shall be determined by a drop in gauge pressure or visual leakage.
24.2.1.8 The test pressure shall be read from a gauge located at the low elevation
point of the system or portion being tested.
24.2 Acceptance Requirements
24.2.1 Hydrostatic Tests
Where is the hydrostatic test pressure measured during the test?
24.2.1.9 Additives, corrosive chemicals such as sodium silicate, or derivatives of
sodium silicate, brine, or similar acting chemicals shall not be used while
Answer: hydrostatically testing systems or for stopping leaks.
24.2.1.10 Piping between the exterior fire department connection and the check
The hydrostatic test pressure is measured at the lowest elevation valve in the fire department inlet pipe shall be hydrostatically tested in the
same manner as the balance of the system. After repair or replacement work
within the system or portion of the system being tested. affecting the fire department connection, the piping between the exterior
Testing at a high point of the system, which due to static head, and the check valve in the fire department inlet pipe shall be isolated and
hydrostatically tested at 150 psi.
would increase the test pressure significantly, is not
24.2.1.11 When deluge system are being hydrostatically tested, plugs shall be
considered necessary. The procedure is carried out in this way installed in fittings and replaced with open sprinklers after the test is
due to the fact that application of pressure typically occurs at completed, or the operating elements of automatic sprinklers shall be
removed after the test is completed.
the lower elevation, and these high pressures would not be
24.2.1.12 Provisions shall be made for the proper disposal of water used for
anticipated at the higher elevations within the system. flushing or testing.
4
10/2/2015
Question: Question:
Is it required that the fire department connection (FDC) piping be Is it required that the fire department connection (FDC) piping be
hydrostatically tested? hydrostatically tested?
Answer:
The FDC piping, including the portion between the exterior FDC
and the check valve in the connection’s inlet pipe, must be
tested. Because the piping from the check valve to the hose
connection is not normally subjected to water pressure, this
could lead the contractor to mistakenly believe that testing of
that portion is not required.
Question: Question:
Is the testing process different for a new installation of piping Is the testing process different for a new installation of piping
than it is for piping that is being repaired or replaced? than it is for piping that is being repaired or replaced?
Answer:
For repair or replacement work on FDC piping, a 2‐hour
hydrostatic test is required at not less than 150 psi. Other
portions of pipe, such as the inspector’s test connection and
drain and auxiliary drains, are not typically subject to high
pressure and do not have to be tested to ensure integrity of
the entire system.
Question: Question:
What is the process for hydrostatically testing a remote FDC? What is the process for hydrostatically testing a remote FDC?
Answer:
Any buried piping connecting the FDC to the system can be
tested in accordance with the requirements of 10.10.2.2 and
10.10.2.4 (hydrostatic test for underground piping).
5
10/2/2015
24.2 Acceptance Requirements 24.2 Acceptance Requirements
24.2.1 Hydrostatic Tests 24.2.2 Dry Pipe and Double Interlock Preaction System(s) Air Test
24.2.1.13 Test Blanks 24.2.2.1 In addition to the standard hydrostatic test, an air pressure test at 40 psi
shall be conducted for 24 hours. Any leakage that results in a loss of pressure
24.2.1.13.1 Test blanks shall have painted lugs protruding is such a way as to in excess of 1.5 psi for the 24 hours shall be corrected.
clearly indicate their presence.
24.2.2.2 Where systems are installed in spaces that are capable of being operated
24.2.1.13.2 The test blanks shall be numbered, and the installing contractor shall in temperatures below 32⁰F, air pressure leakage tests required in 24.2.2 shall
have a record keeping method ensuring their removal after work is be conducted at the lowest nominal temperature of the space.
completed.
24.2.13.3 When subject to hydrostatic test pressures, the clapper of a differential‐
type valve shall be held off its seat to prevent damaging the valve.
Question: Question:
Are NFPA 13R sprinkler systems required to be hydrostatically Are NFPA 13R sprinkler systems required to be hydrostatically
tested to a pressure of a least 200 psi? tested to a pressure of a least 200 psi?
Answer:
All NFPA 13R sprinkler systems must be hydrostatically tested to
a pressure of at least 200 psi in accordance with NFPA 13,
unless the system has 20 or fewer sprinklers with no FDC.
NFPA 13 – Standard for the Installation of Sprinkler Systems
Chapter 24 – Systems Acceptance
24.2 Acceptance Requirements
Explain code requirements for acceptance testing
Explain hydrostatic pressure testing 24.2.3 System Operational Tests
Explain system operational tests 24.2.3.1 Waterflow Devices.
Identify information on Contractor’s Material and Test
24.2.3.2 Dry Pipe Systems
Certificate for Underground Piping and Aboveground
Piping 24.2.3.3 Deluge and Preaction Systems
Explain the requirements for flow testing a backflow
24.2.3.4 Main Drain Valves
prevention assembly
24.2.3.5 Operating Test for Control Valves
Describe components inspected in field inspection
Explain required end user information 24.2.4 Pressure Reducing Valves
24.2.6 Exposure Systems
6
10/2/2015
24.2 Acceptance Requirements 5.11 Sprinkler Waterflow Alarm‐Initiating Devices
24.2.3 System Operational Tests
5.11.1 The provisions of Section 5.11 shall apply to devices that initiate an alarm
24.2.3.1 Waterflow Devices. Waterflow detecting devices including the indicating a flow of water in a sprinkler system
associated alarm circuits shall be flow tested through the inspector’s test
connection and shall result in an audible alarm on the premises within 5 5.11.2 Activation of the initiating device shall occur within 90 seconds of waterflow at
minutes after such flow begins and until such flow stops. the alarm‐initiating device when flow occurs that is equal to or greater than that
from a single sprinkler of the smallest orifice size installed in the system.
5.11.3 Movement of water due to waste, surges, or variable pressure shall not initiate
an alarm signal.
24.2.3.2.1 A working test of the dry pipe valve alone and with a quick‐
opening device, if installed, shall be made by opening the inspector’s
test connection.
24.2.3.2.2 The test shall measure the time to trip the valve and the time for
water to be discharged from the inspector’s test connection. All times
shall be measured from the time the inspector’s test connection is
completely opened.
24.2.3.2.2.1 Dry system calculated for water delivery in accordance
with 7.2.3.6 shall be exempt from any specific delivery time
requirement.
24.2.3.2.3 The results shall be recorded using the contractor’s material and
test certificate for aboveground piping.
24.2 Acceptance Requirements
What is meant by “first evidence of waterflow?” 24.2.3 System Operational Tests
24.2.3.3 Deluge and Preaction Systems
Answer: 24.2.3.3.1 The automatic operation of a deluge or preaction valve shall be
tested in accordance with the manufacturer’s instructions.
The measurement of time for water to be discharged from the 24.2.3.3.2 The manual and remote control operation, where present, shall
inspector’s test connection is based on the first evidence of also be tested.
waterflow, because it would be subject to interpretation if a
wait was required to determine when a steady flow rate was
achieved. During testing, the water discharging from the
inspector’s test connection will initially be erratic, with
spurting and momentary stoppages, due to mixing with air
that is still in the system.
7
10/2/2015
24.2.3.4.1 The main drain valve shall be opened and remain open until the
system pressure stabilizes
24.2.3.3.2 That static and residual pressures shall be recorded on the
contractor’s material and test certificate.
Question: Question:
What is the purpose of the main drain test? How do you determine the flow from a main drain during the
main drain test?
Answer:
The main drain test is an important part of the acceptance for a
sprinkler system because it establishes baseline data regarding
the water supply against which future tests can be compared.
24.2 Acceptance Requirements
How do you determine the flow from a main drain during the 24.2.3 System Operational Tests
Answer:
The results of the main drain test are used to track the relative
condition of the water supply and to determine if the
waterflow to the system has a major obstruction, but it is not
used as a measure of the actual capacity of the water supply.
Even though water is discharged during the test, the main
drain is not considered to be a waterflow test and the actual
flow rate is not measured.
8
10/2/2015
24.2 Acceptance Requirements 24.2 Acceptance Requirements
24.2.4 Pressure Reducing Valves 24.2.6 Exposure Systems
24.2.4.1 Each pressure‐reducing valve shall be tested upon completion of Operating tests shall be made of exposure protection systems upon completion
installation to ensure proper operation under flow and no‐flow conditions. of installation, where such tests do not risk water damage to the building on
which they are installed or to adjacent buildings.
24.2.4.2 Testing shall verify that the device properly regulates outlet pressure at
both maximum and normal inlet pressure conditions.
24.2.4.3 The results of the flow test of each pressure‐reducing valve shall be
recorded on the contractor’s material and test certificate.
24.2.4.4 The results shall include the static and residual inlet pressures, static and
residual outlet pressures, and the flow rate.
Location &Floor Make & Model Setting STATIC PRESSURE RESIDUAL PRESSURE (flowing) FLOW RATE
Contractor's Material and Test Certificate for A boveground Piping PRESSURE
REDUCING
Inlet (psi) Outlet (psi) Inlet (psi) Outlet (psi) Flow (GPM)
Explain code requirements for acceptance testing
understood the owner’s representative’s signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with
approving authorities requirements or local ordinances.
DESCRIPTION piping leakage shall be stopped.
Property Name PNEUMATIC: Establish 40 psi (2.7 bars) air pressure and measure drop, which shall not exceed 1-1/2 psi (0.1 bars) in 24 hours. Test pressure
1. Date tanks at normal water level and air pressure and measure air pressure drop, which shall not exceed 1-1/2 psi (0.1 bars) in 24 hours.
Property Address City State Zip
Explain hydrostatic pressure testing
All pipe hydraulically tested at: psi (_______ bar) for hrs If no, state reason
Accepted by approving authorities(names) Dry Pipe pneumatically tested Yes No
Equipment operates properly Yes No
Address Do you certify as the sprinkler contractor that additives and corrosive chemicals, sodium silicate or derivatives of sodium silicate, brine, or other
PLANS
corrosive chemicals were not used for testing systems or stopping leaks? Yes No
Explain system operational tests
Installation conforms to accepted plans Yes No
DRAIN Reading of gage located near Residual pressure with valve
Equipment used is approved? Yes No TESTS
If no, explain deviations TEST water supply test connection: psi (________ bar) in test connection open wide. psi (________ bar)
Underground mains and lead in connections to system risers flushed before connection made to sprinkler piping
Has person in charge of fire equipment been instructed as to location of Verified by copy of the Contractor’s Material & Test Yes No Other, explain
control valves and care and maintenance of this new equipment? Yes No Certificate for Underground Piping.
Identify information on Contractor’s Material and Test INSTRUCTIONS
If no, explain
Number removed
Certificate for Underground Piping and Aboveground
3. NFPA 25 Yes No
GASKETS
LOCATION
Supplies buildings Welded piping Yes No
OF SYSTEM
Make Model Year of Manufacture Orifice Size Quantity Temperature Rating If yes…
Do you certify as the sprinkler contractor that welding procedures comply with the requirements of
Piping
WELDING at least AWS B2.1? Yes No
Do you certify that the welding was performed by welders qualified in compliance with the requirements
SPRINKLERS of at least AWS B2.1? Yes No
Do you certify that the welding was carried out in compliance with a documented quality control procedure
to ensure that all discs are retrieved, that openings in piping are smooth, that slag and other welding
residue are removed, and that the internal diameters of piping are not penetrated? Yes No
Explain the requirements for flow testing a backflow
Type of pipe CUTOUTS Do you certify that you have a control feature to ensure that all cutouts (disks) are retrieved? Yes No
PIPE AND
(DISCS)
Type of fittings
FITTINGS HYDRAULIC Nameplate provided? If no, explain
DATA Yes No
ALARM DEVICES Maximum time to operate through test connection
prevention assembly
NAMEPLATE
ALARM VALVE Type Make Model Minutes Seconds
Describe components inspected in field inspection
Name of sprinkler contractor
Make Model Serial No. Make Model Serial No.
DRY PIPE
Contractor’s Address City State Zip
Time to trip through Water Pressure Air Pressure Trip Point Air Time water reached Alarm operated
OPERATING
Explain required end user information
test connection1,2 Pressure test outlet1,2 properly Signature
TEST
Minutes Seconds psi psi psi Minutes Seconds Yes No Tests witnessed by
For property owner (signed) Title Date
Without Q.O.D.
With Q.O.D.
For sprinkler contractor (signed) Title Date
If no, explain
Underground Piping
HYDROSTATIC All new underground piping hydrostatically tested at Joints covered
Contractor's Material and Test Certificate for TEST psi for hours Yes No
Explain code requirements for acceptance testing
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, contractor, and the State Fire Marshal. It is
understood the owner’s representative’s signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with
approving authority’s requirements or local ordinances.
Property Name
1. Date
HYDRANTS Number installed
gallons
Address
CONTROL
VALVES
Water control valves left wide open
If no, state reason
Hose threads of fire department connections and hydrants interchangeable with those of
Yes No
Explain hydrostatic pressure testing
the fire department answering alarm Yes No
Explain system operational tests
PLANS
Date left in service ________________________________________________________________________________________________________
Installation conforms to accepted plans Yes No
Equipment used is approved Yes No REMARKS _________________________________________________________________________________________________________________________
If no, state deviations _________________________________________________________________________________________________________________________
INSTRUCTIONS
Has person in charge of fire equipment been instructed as to location of
control valves and care and maintenance of this new equipment?
If no, explain
LOCATION
If no, explain
Supplies buildings
Signature
Pipe conforms to
Fittings conform to
_________________
_________________
Standard
Standard
Type joints
Yes
Yes
No
No
For Installing contractor (signed) Title Date
Piping
Explain the requirements for flow testing a backflow
If no, explain Additional explanation and notes:
FLUSHING: Flow the required rate until water is clear as indicated by no collection of foreign material in burlap bags at outlets such as hydrants and
blow-offs. Flush at flows not less than 390 GPM (1476 L/min) for 4-inch pipe, 880 GPM (3331 L/min) for 6-inch pipe, 1560 GPM (5905 L/min) for 8-inch
pipe, 2440 GPM (9235 L/min) for 10-inch pipe, and 3520 GPM (13323 L/min) for 12-inch pipe. When supply cannot produce stipulated flow rates,
obtain maximum available.
prevention assembly
TEST
DESCRIPTION
HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 psi (13.8 bars) for two hours or 50 psi (3.4 bars) above static pressure In excess
of 150 psi (10.3 bars) for two hours.
LEAKAGE: New pipe laid with rubber gasketed joints shall, if the workmanship is satisfactory, have little or no leakage at the joints. The amount of
Describe components inspected in field inspection
leakage at the joints shall not exceed 2 quarts per hour (1.89 L/hr) per 100 joints irrespective of pipe diameter. The leakage shall be distributed over all
joints. If such leakage occurs at a few joints, the installation shall be considered unsatisfactory and necessary repairs made. The amount of allowable
leakage specified above can be increased by 1 fl oz per inch valve diameter per hour (30 mL/25 mm/hr) for each metal seated valve isolating the test
section. If dry barrel hydrants are tested with the main valve open so the hydrants are under pressure, an additional 5 oz per minute (150 mL/min)
leakage is permitted for hydrant.
Explain required end user information
New underground piping flushed according to_________________ standard by (company) Yes No
If no, explain
9
10/2/2015
Chapter 24 – Systems Acceptance
24.2 Acceptance Requirements
24.2.5 Backflow Prevention Assemblies
24.2.5.1 The backflow prevention assembly shall be forward flow tested to
ensure proper operation.
24.2.5.2 The minimum flow rate shall be the system demand, including hose
stream appliances where applicable.
NFPA 13 – Standard for the Installation of Sprinkler Systems
Fire Sprinkler Final Inspection Checklist
Explain code requirements for acceptance testing 1. Verify the installing contractor has a valid permit. Approved plans should be at site.
Explain hydrostatic pressure testing 2. Obtain Contractor’s Material and Test Certificate for Aboveground Piping for each system
Explain system operational tests installed. Signatures of installing contractor and building owner’s representative must be on
the form.
Identify information on Contractor’s Material and Test
Certificate for Underground Piping and Aboveground 3. Verify proper signage on riser components:
(a) Control valve
Piping (b) Main drain
Explain the requirements for flow testing a backflow (c) Inspector’s test
(d) Hydraulic design information plate
prevention assembly
Describe components inspected in field inspection 4. Verify spare sprinkler cabinet is installed and has the correct number of sprinklers, a sprinkler
wrench, and any special tools required for the system. (A copy of NFPA 25 should be provided
Explain required end user information to the owner, as well)
5. Verify proper sealing where piping penetrates floors and walls.
Fire Sprinkler Final Inspection Checklist Fire Sprinkler Final Inspection Checklist
6. Observe Main Drain Test and verify pressures at the base of the riser meet or exceed the 9. Walk thru the building and confirm:
required system demand pressure listed on the hydraulic calculation information plate (a) Sprinklers are free of obstructions by building elements (soffits, light fixtures, ceiling
attached to the riser. (Test should flow for at least two minutes) fans, exit signs, decorations, etc.)
(b) Sprinklers are not painted and all protective covers have been removed
7. Observe activation of the fire alarm notification devices on water flow, thru inspector’s test, (c) All sprinkler escutcheons have been installed properly
including: (d) Door and rooms signs are installed where required (example: “Sprinkler Riser Room” or
(a) Electric water flow bell on the exterior of the building. “Fire Sprinkler System Inside”)
(b) General alarm devices in the building (within 90 seconds of open inspector’s test) (e) Look at anything not completed at rough‐in inspection(s).
*Note: Confirm “Alarm” status at the control panel and observe description of activated device.
8. Confirm “Supervisory” signal and description of activated device at the control panel for:
(a) Tamper switches on valves (indicating a closed or partially [1/4 turn] closed valve)
(b) Low air pressure on dry pipe systems (if applicable)
(c) Fire pump requirement (if applicable)
*Note: All sprinkler systems are required to be monitored by a listed supervising station unless
otherwise approved. Confirm receipt of all signals at the supervising station.
10
10/2/2015
Question: Question:
Why are inspections, testing, and maintenance (ITM) so Why are inspections, testing, and maintenance (ITM) so
important to the effectiveness of a sprinkler system? important to the effectiveness of a sprinkler system?
Answer:
ITM are especially important because of the inactive nature of
sprinkler systems. Unlike other types of building systems that
are used on a routine basis, the sprinkler system is only used
during emergency situations. The system’s proper operating
condition is not verifiable through day‐to‐day operations, as
are HVAC, plumbing, and process systems.
Question: Question:
How many spare sprinklers are required for an NFPA 13 How many spare sprinklers are required for an NFPA 13
installation? installation?
Answer:
A supply of at least six spare sprinklers (never fewer than six)
shall be maintained on the premises so that any sprinkler that
have operated or have been damaged in any way can be
promptly replaced. A minimum of two sprinklers of each type
and temperature rating should be provided. The larger the
facility, the more sprinklers required.
NFPA 13 – Standard for the Installation of Sprinkler Systems
Chapter 24 – Systems Acceptance
Explain code requirements for acceptance testing 24.4 Instructions
The installing contractor shall provided the property owner or the property owner’s
Explain hydrostatic pressure testing authorized representative with the following:
Explain system operational tests
(1) All literature and instructions provided by the manufacturer describing proper
Identify information on Contractor’s Material and Test operation and maintenance of any equipment and devices installed
Certificate for Underground Piping and Aboveground
(2) NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water‐Based Fire
Piping Protection Systems
Explain the requirements for flow testing a backflow
prevention assembly
Describe components inspected in field inspection
Explain required end user information
11
10/2/2015
Chapter 24 – Systems Acceptance
24.5 Hydraulic Design Information Sign
24.5.1 The installing contractor shall identify a hydraulically designed sprinkler system
with a permanently marked weatherproof metal or rigid plastic sign secured with
corrosion resistant wire, chain, or other approved means. Such signs shall be
placed at the alarm valve, dry pipe valve, preaction valve, or deluge valve supplying
the corresponding hydraulically designed area.
24.5.2 The sign shall include the following information:
(1) Location of the design area or areas
(2) Discharge densities over the design area or areas
(3) Required flow and residual pressure demand at the base of the riser
(4) Occupancy classification or commodity classification and maximum permitted
storage height and configuration
(5) Hose stream allowance included in addition to the sprinkler demand
(6) The name of the installing contractor
24.6 General Information Sign 24.6 General Information Sign
24.6.1 The installing contractor shall provide a general information sign used to 24.6.2 The sign shall include the following information:
determine system design basis and information relevant to the inspection, testing,
and maintenance requirements required by NFPA 25, Standard for the Inspection, (1) Name and location of the facility protected
Testing, and Maintenance of Water‐Based Fire Protection Systems. Such general (2) Presence of high‐piled and/or rack storage
information shall be provided with a permanently marked weatherproof metal or (3) Maximum height of storage planned
rigid plastic sign, secured with corrosion‐resistant wire, chain, or other acceptable (4) Aisle width planned
means. Such signs shall be placed at each system control riser, antifreeze loop, (5) Commodity classification
and auxiliary system control valve. (6) Encapsulation of pallet loads
(7) Presence of solid shelving
(8) Flow test data
(9) Presence of flammable/combustible liquids
(10) Presence of hazardous materials
(11) Presence of other special storage
(12) Location of auxiliary drains and low point drains
(13) Original results of main drain flow test
(14) Name of installing contractor or designer
(15) Indication of presence and location of antifreeze or other auxiliary systems
Chapter 24 – Systems Acceptance
24.6 General Information Sign
24.6.2 The sign shall include the following information:
(1) Name and location of the facility protected
(2) Presence of high‐piled and/or rack storage
(3) Maximum height of storage planned
(4) Aisle width planned
(5) Commodity classification
(6) Encapsulation of pallet loads
(7) Presence of solid shelving
(8) Flow test data
(9) Presence of flammable/combustible liquids
(10) Presence of hazardous materials
(11) Presence of other special storage
(12) Location of auxiliary drains and low point drains
(13) Original results of main drain flow test
(14) Name of installing contractor or designer
(15) Indication of presence and location of antifreeze or other auxiliary systems
12
10/2/2015
Company Company
And finally…..
Presentation Take Away:
All sprinkler systems require acceptance testing
CEO’s should witness acceptance testing
Understand what you are looking at
Ask questions throughout the process
Questions
Open Discussion
Kevin Geidel, CFPS, CET
kgeidel@cscos.com
315.703.4178
13