SIEMENS INDUSTRY INC EX4724


8 Fernwood Rd
Florham Park, NJ 07932-1906 USA
Agent Qty, m3
3
Nom Size, m Mounting Rupture
Container Part No. Position Valve Type Valve Part No. Disc No.

N/A N/A 25 mm(1 inch) 740-697900-03 500-649926BG


713-697900-01 Vertical

N/A N/A 25 mm(1 inch) 740-697900-03 500-649926BG


713-697901-01 Vertical

N/A N/A 38 mm(1-1/2 inch) 740-697902-03 500-649926BG


713-697902-01 Vertical

N/A N/A 38 mm(1-1/2 inch) 740-697902-03 500-649926BG


713-697903-01 Vertical

N/A N/A 64 mm(2-1/2 inch) 740-697904-03 500-649926BG


713-697904-01 Vertical

N/A N/A 64 mm(2-1/2 inch) 740-697904-03 500-649926BG


713-697905-01 Vertical

N/A N/A 102 mm(4 inch) 740-649670-04 718-649670-21


713-649660-02 Vertical

N/A N/A 102 mm(4 inch) 740-649670-04 718-649670-21


713-649670-01 Vertical

(Container
Nom (Container) Indicator) Mounting Valve Type (Valve)
Size, kg Part No. Fill Range, kg Position (Size NPS) Part No.

16 713-697900-01 7.3-15.9 Vertical Only 25 mm(1 inch) 740-697900-03

32 713-697901-01 14.0-32.2 Vertical Only 25 mm(1 inch) 740-697900-03

68 713-697902-01 29.9-68.9 Vertical Only 38 mm(1-1/2 inch) 740-697902-03

113 713-697903-01 49.4-114.8 Vertical Only 38 mm (1-1/2 inch) 740-697902-03

https://iq.ulprospector.com/en/profile?e=226438 1/7
20/5/2021 GAQFC.EX4724 - Clean Agent Extinguishing System Units | UL Product iQ

170 713-697904-01 73.9-171.9 Vertical Only 64 mm(2-1/2 inch) 740-697904-03

254 713-697905-01 109.3-254.5 Vertical Only 64 mm(2-1/2 inch) 740-697904-03

408 713-649660-01 175.5-408.2 Vertical Only 102 mm(4 inch) 740-649670-04

544 713-649670-01 235.4-544.3 Vertical Only 102 mm(4 inch) 740-649670-04

Size mm/NPS 180° Nozzle Part No. 360° Nozzle Part No.

CPYEN-REF Nozzle Reference Drawing (HFC-227ea Only) Nozzle Reference Drawing (HFC-227ea Only)

CPYEN2-REF Nozzle Reference Drawing (Novec 1230 Only) Nozzle Reference Drawing (Novec 1230 Only)

Component Part No.

DISCHARGE HOSE

Flexible Cylinder Hose 500-697942BG

500-697943BG

500-697944BG

ADAPTERS

25.4 mm (1 in.) Top Plug Adapter Assembly 500-697922BG

25.4 mm (1 in.) Top Plug Adapter 747-697922-01

Fitting 747-697922-03

Core 747-697922-02

Core - Alternate ( Novec 1230 Only) 747-697922-01

Sealant 450-697959-01

38.1 mm (1-1/2 in.) Top Plug Adapter Assembly 500-697923BG

38.1 mm (1-1/2 in.) Top Plug Adapter 747-697923-01

Fitting 747-697922-03

Sealant 450-697959-01

63.5 mm (2-1/2 in.) Top Plug Adapter Assembly 500-697924BG

63.5 mm (2-1/2 in.) Top Plug Adapter 747-697924-01

PNEUMATIC ACTUATORS

Piston Actuator Assembly 500-679926BG

Upper Cap 712-697926-07

Body 712-697926-05

https://iq.ulprospector.com/en/profile?e=226438 2/7
20/5/2021 GAQFC.EX4724 - Clean Agent Extinguishing System Units | UL Product iQ

Piston 712-697926-03

O-Ring 325-697960-AB

LOCAL MANUAL CONTROL

Local Manual Control Assembly 500-697925BG

Local Manual Control Assembly - Alternate (Novec 1230 Only) 500-697974BG

Body 718-697925-01

Body - Alternate (Novec 1230 Only) 718-697925-02-10

Lever 360-697925-02

Knob, Round 360-697925-03

Bushing, Locking Pin 345-697925-04

Locking Pin 370-697925-05

Locking Pin Button 370-697925-06

Spring 385-697925-07

Spring - Alternate (Novec 1230 Only) 385-697925-08-10

Set Screw 899-697925-08

Roll Pin 370-697925-09

Pull Tite Seal 360-697925-10

Pull Pin 360-697925-11

Label 575-697925-12

Plunger (Novec 1230 Only) 360-697925-04-10

Fastener (Novec 1230 Only) 195-697925-01-10

SHUTTLE VALVES

25.4 mm (1 in.) Shuttle Valve Assembly 500-697948GB

25.4 mm (1 in.) Shuttle Valve Body 712-697948-01

25.4 mm (1 in.) Shuttle Valve End Cap 712-697948-02

25.4 mm (1 in.) Shuttle 712-697948-03

38.1 mm (1-1/2 in.) Shuttle Valve Assembly 500-697949BG

38.1 mm (1-1/2 in.) Shuttle Valve Body 712-697949-01

38.1 mm (1-1/2 in.) Piston 712-697949-03

38.1 mm (1-1/2 in.) End Cap 712-697949-02

38.1 mm (1-1/2 in.) Shuttle Outlet 712-697949-04

https://iq.ulprospector.com/en/profile?e=226438 3/7
20/5/2021 GAQFC.EX4724 - Clean Agent Extinguishing System Units | UL Product iQ

38.1 mm (1-1/2 in.) Locating Pin 370-697949-05

CHECK VALVES

50.8 mm (2 in.) Flapper Check Valve 712-050476-0, rev. AB

76.2 mm (3 in.) Flapper Check Valve 712-050477-0, rev. AB

50.8 mm (2 in.) Flapper Check Valve 712-050476-0

76.2 mm (3 in.) Flapper Check Valve 712-050477-0

50.8 mm (2 in.) NPT to 38.1 mm (1-1/2 in.) grooved adapter 731-050480-0

76.2 mm (3 in.) NPT to 2-1/2 in. grooved adapter 731-050481-0

101.6 mm (4 in.) NPT 712-050478-0, rev. AA

101.6 mm (4 in.) NPT - Alternate 712-050478, rev. AB

MISCELLANEOUS COMPONENTS

Flexible Actuation Hose 500-697942BG

500-697943BG

500-697944BG

Flexible Cylinder Hose 500-697950BG

500-697951BG

500-697952BG

Siphon Tubes 380-697900-02

Mounting Brackets 500-697907BG

500-697908BG

500-697909BG

500-697910BG

500-649667-00

500-649677BG

Supervisory Pressure Switch (NC) 500-697939BG

Supervisory Pressure Switch (NO) 500-697940BG

Vent 714-697912-03

Nipple 714-697912-02

Pressure Gauge Face Artwork (HFC-227ea Only) 500-697963BG

Pressure Gauge Face Artwork (Novec 1230 Only) 500-697972BG

CPY-POS, Pressure Operated Switch 500-697941BG

https://iq.ulprospector.com/en/profile?e=226438 4/7
20/5/2021 GAQFC.EX4724 - Clean Agent Extinguishing System Units | UL Product iQ

CPY-TD, Test Dowel for Solenoid 500-697965BG

CPY-MRS, main Reserve Switch 500-697964BG

LIQUID LEVEL INDICATORS

CPY-LLI, Liquid Level Indicator 68.0/113.4 kg (150/250 lb) Cylinder 500-697969BG

CPY-LL2, Liquid Level Indicator 170.1/254.0 kg (375/560 lb) Cylinder 500-697970BG

Liquid Level Indicator, 408.2/544.3 kg (900/1200 lb) Cylinder 500-649674BG

SLAVE COMPONENTS

CPY-PE, Elbow Slave 500-697945BG

CPY-PT, Tee-Slave 500-697946BG

PILOT COMPONENTS

CPY-PLT, Pilot Cylinder 713-697900-01

CPY-PLT Valve Assembly 740-697900-03

544 kg CYLINDER UNIT

Mounting Bracket 500-649677BG

Floor Strap 500-649846BG

Burst Disc 718-649671-21

Piston Actuator Assembly 500-697926BG

Piston Actuator Body 712-697926-01

Piston 712-697926-03

Piston Rod 712-697926-04

Piston Actuator Adapter 712-697926-02

Vent Ball 899-697900-12

1/4" Pipe Nipple 714-697912-02

Vent 714-697912-03

Core 747-697922-02

RTV Sealant 450-697904-18

Epoxy Sealant 450-697959-01

Removable Fitting 747-697922-03

Shipping Cap 899-697947-03

101.6 mm (4in.) Flex Hose 500-649848BG

https://iq.ulprospector.com/en/profile?e=226438 5/7
20/5/2021 GAQFC.EX4724 - Clean Agent Extinguishing System Units | UL Product iQ

101.6 x 152.4 mm (6 x 4 in.) Flex Hose 240-649960-1

101.6 x 152.4 mm (6 x 4 in.) Flex Hose with Check Valve 500-649960BG

Check Valve Assembly 500-649849BG

Check Valve Body 240-649849-01

Check Valve Seat 240-649849-02

Check Valve Clapper 899-649849-03

Clapper Dowl Pin 899-649849-04

Clapper Hinge Pin 899-649849-05

899-649849-06

Spring 385-649849-07

Screw 240-649849-08

Fill Valve Assembly 500-697947BG

Parker O-ring Lube 500-697959BG

Manuals and Programs:

Part No. Date Description

500-697967 2016-08-09 Sinorex™ 227 Installation, Operation, and Maintenance Instruction Manual

CPY4.02 2014-04 Sinorex™ 227 Flow Calc. Software

500-697971 2016-12-14 Sinorex™ Novec 1230 Installation, Operation, and Maintenance Instruction Manual

CPY4.02 2014-04 Sinorex™ Novec 1230 Flow Calc. Software

ENGINEERED UNIT, Siemens Industry Inc.'s Sinorix™ 227 Clean Agent Engineered Extinguishing System Units, stored pressure type, 15.9, 31.8,
68.0, 113.4, 170.1, 254.0, 408.2, and 544.3 kg (35, 70, 150, 250, 375, 560, 900, and 1200 lbs) designed to discharge HFC-227ea extinguishing agent
for the control of fires in Class A, Class B, and Class C hazards in enclosed volumes. Suitable for use in occupied or unoccupied areas. The units are
super-pressurized with nitrogen to 24.82 bar (360 psig) at ambient temperature of 21.1°C (70°F), and having an operating temperature range of 0
to 54.4°C (32 to 130°F). Each system is to be designed and installed only in strict conformance with the requirements of the Standard for Clean
Agent Fire Extinguishing Systems, NFPA 2001, and the manufacturer's installation, operation, and maintenance manual p/n 500-697967, dated
2019-07-16 and flow calculation program p/n CPY4.02, dated April 2014. Copies are available from the above Listee.

AGENT STORAGE CONTAINER ASSEMBLY


Weight of Agent (kg) Part No.

16 CPY-35

32 CPY-70

68 CPY-150

113 CPY-250

170 CPY-375

254 CPY-560

https://iq.ulprospector.com/en/profile?e=226438 6/7
20/5/2021 GAQFC.EX4724 - Clean Agent Extinguishing System Units | UL Product iQ

408 CPY-900

544 CPY-1200

Siemens Industry Inc.'s Sinorix™ 1230 Clean Agent Engineered Extinguishing System Units, stored pressure type, 15.9, 31.8, 68.0, 113.4, 170.1,
254.0, 408.2, and 544.3 kg (35, 70, 150, 250, 375, 560, 900, and 1200 lbs) designed to discharge Novec 1230 extinguishing agent for the control of
fires in Class A, Class B, and Class C hazards in enclosed volumes. Suitable for use in occupied or unoccupied areas. The units are super-
pressurized with nitrogen to 24.82 bar (360 psig) at ambient temperature of 21.1°C (70°F), and having an operating temperature range of 0 to
54.4°C (32 to 130°F). Each system is to be designed and installed only in strict conformance with the requirements of the Standard for Clean Agent
Fire Extinguishing Systems, NFPA 2001, and the manufacturer's installation, operation, and maintenance manual p/n 500-697971, dated 2019-07-
16 and flow calculation program p/n CPY4.02, dated April 2014. Copies are available from the above Listee.

AGENT STORAGE CONTAINER ASSEMBLY


Weight of Agent (kg) Part No.

16 CPY-35

32 CPY-70

68 CPY-150

113 CPY-250

170 CPY-375

254 CPY-560

408 CPY-900

544 CPY-1200

Last Updated on 2019-10-17

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following
format: "© 2021 UL LLC"

https://iq.ulprospector.com/en/profile?e=226438 7/7

You might also like