You are on page 1of 3

21/5/2021 UROX.

S5198 - Smoke Detectors for Fire Alarm Systems | UL Product iQ

UROX.S5198 - Smoke Detectors for Fire Alarm Systems

Smoke Detectors for Fire Alarm Systems


XTRALIS PTY LTD S5198
4 North Dr, Virginia Park
236-262 East Boundary Rd
Bentleigh, East Victoria, 3165 Australia

Investigated To UL 268 (7th ed.)


Products Suitable for Ducts, D(I) and D(ST) are investigated to UL 268A

Velocity
Range Date Time of Firmware
Detector Compatibility (fpm) of Manufacture Version
Firmware
Model Application Type Restrictions Min Max Manufacture Version Update

VEP-A00-P-UL, VEP- OAP, AS Laser *1 0 4000 2020-06-22 8.13.01 -


A10-P-UL, VEP-A00-1P-
UL (a)(b)(c)

VES-A00-P-UL, VES-A10- OAP, AS Laser *1 - - 08-31-2020 8.13.01 -


P-UL (a)(b)(c)

VEU-A00-UL, VEU-A10- OAP, D, AS Laser *1 - - 08-31-2020 8.13.01 -


UL (a)(b)(c)

VLF-500-UL OAP, D, Laser D4 0 4000 2021/05/01 3.34.00 -


AS, AS-D

Investigated To UL 268 (previous editions)


Products Suitable for Ducts, D(I) and D(ST) are investigated to UL 268A

Velocity
Range Date Time of Firmware
Detector Compatibility (fpm) of Manufacture Version
Firmware
Model Application Type Restrictions Min Max Manufacture Version Update

OSE-HPW, OSE-SPW, OAP PB None - - - - -


OSE-HP, OSE-HP-01

OSI-10, OSI-45, OSI-90, OAP PB None - - - - -


OSE-SP(+), OSE-SP-
01(+)

VFD-100 OAP P D1 0 300 - - -

https://iq.ulprospector.com/en/profile?e=153209 1/3
21/5/2021 UROX.S5198 - Smoke Detectors for Fire Alarm Systems | UL Product iQ

VFD-200 OAP I *1 0 300 - - -

VFD-400 (hc) OAP P(IHD) *1 0 300 - - -

Control Unit
Compatibility
Base Model Related Detector Restrictions

VFD-000, VFD-300, VFD-200, VFD-100, VFD-400 B2


VFD-002

VFD-003, VFD-300, VFD-200, VFD-100, VFD-400 B2


VFD-005

VFD-400 55000-550, 55000-650, 55000-886, 55000-450, 58000-450, 58000-550, B2


58000-650, 58000-750

B2 - For connection to Listed control units with which compatibility was determined by test or a review of circuit parameters. Interconnection and
compatible models indicated on installation wiring diagram for detector (base) and/or control unit.

D1 - Listing limited to specific system control unit. Information on compatible control unit indicated on installation drawing of control unit and/or
detector.

D4 - For connection to any manufacturer's Listed compatible control unit.

*1 - For connection to Listed control units, Refer to the installation documents for compatible control panels.

OAP - Open Area Protection

AS - Air Sampling

D - Duct Detector

AS-D - Air Sampling Duct

PB - Projected Beam

P - Photoelectric

I - Ionization

IHD - Includes Integral Heat Detector

Date of Manufacture identifies the manufacturing start date of all product models that will use the specific Time of Manufacture Firmware
Version. The date of manufacture is noncoded and in the format YEAR (in 4 digits), MONTH (in letters), DAY (in 2 digits).

Time of Manufacture Firmware Version identifies a numerical and/or alphabetic series designation that is product and date-code specific and
will only identify the Firmware Version at the time the product was manufactured. The numeric and/or alphabetic sequence is defined by the
manufacturer.

Firmware Version Update is a numerical and/or alphabetic sequential identification that is product and date-code specific and sequentially
identifies the Firmware Version Update from the previous version of firmware. The numerical and/or alphabetic sequence is defined by the
manufacturer.

(+) - Provisionally Listed.

(a) - Suitable for Open Area Protection with limits as described in the installation manual and ASPIRE2 (TM) for the samplie pipe network
calculations for the pipe network per NFPA 72 requiements.

(b) - Suitable for Air Duct Installation with limits as described in the installation manual

(c) - 3/4" CPVC Piping, Listed to UL 1887 (which includes plenum rated areas) for use with all VESDA series air sampling smoke detectors.
https://iq.ulprospector.com/en/profile?e=153209 2/3
21/5/2021 UROX.S5198 - Smoke Detectors for Fire Alarm Systems | UL Product iQ

(hc) - Employs integral 135 F rated heat sensor and is Complementary Listed under Heat-Automatic Fire Detectors (UQGS).

Note - Fittings (VIWT). Listed for use in air plenums, complying with the requirements of the Standard for Fire Test of Plastic Sprinkler Pipe for
Visible Flame and Smoke Characteristics, UL 1887, for use with all VESDA series air sampling smoke detectors.

Last Updated on 2021-05-14

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following
format: "© 2021 UL LLC"

https://iq.ulprospector.com/en/profile?e=153209 3/3

You might also like