Professional Documents
Culture Documents
IPX Ratings
Not an entirely valid IP rating, but still occasionally seen on websites offering enclosures (but more
commonly lighting). The "x" simply denotes that the value for that number is missing. You can replace
it with a zero, assuming that it has not ingress protection rating. This may not be the case, but better
safe than sorry. The first number denotes foreign body ingress protection, the second moisture. So
"x"5 for example, means that there is no defined protection from solid objects, but protection against
low pressure water jets, while 5"x" would denote partial protection from dust, but no particular
protection from moisture.
Distribution Boards
• More number of DB shall be planned to reduce wiring
• Double door construction DB shall be used to avoid physical damage.
• Class-2 SPD shall be provided in each floor DB. More SPD can be provided in
sub-distribution boards as required.
• Central location of load shall be peferrable chosed for DB installation.
• All DBs shall be provided with ELCB. ELCB has two ratings. Current rating and
sensitivity rating (mentioned in milliamperes). Sensitivity rating are generally
30mA, 100mA and 300mA. ELCB sensitivity 30mA shall be used wherever there
are chances of electrical shock higher (wet areas like kitchen and toilets). Higher
sensitivity ELCB can be used with incomer of DB.