SINAMICS DCP
DC/DC Power Converter
Operating Instructions
Edition 11/2014
___________________
Introduction 1
___________________
Safety notes 2
SINAMICS ___________________
Description 3
___________________
Preparations for use 4
SINAMICS DCP ___________________
Mounting 5
___________________
Electrical connection 6
Operating Instructions ___________________
Commissioning 7
___________________
Operation 8
___________________
Servicing 9
___________________
Spare parts 10
___________________
Disposal 11
___________________
Service and Support A
___________________
Technical data B
___________________
Quality documents C
___________________
Additional documents D
___________________
Checklists and forms E
___________________
Assembly documents F
___________________
Index G
11/2014
A5E34382853K
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 5
Preface
SINAMICS DCP
6 Operating Instructions, 06/2014, A5E34382853K
Table of contents
Preface ................................................................................................................................................... 5
1 Introduction ........................................................................................................................................... 11
2 Safety notes .......................................................................................................................................... 13
2.1 Safety concept ........................................................................................................................14
2.2 Notes on operator protection ..................................................................................................15
2.2.1 Information about electromagnetic fields ................................................................................17
2.3 Notes on plant safety ..............................................................................................................18
2.4 ESD-sensitive components .....................................................................................................19
3 Description ............................................................................................................................................ 21
4 Preparations for use .............................................................................................................................. 25
4.1 Device order numbers.............................................................................................................25
4.2 Rating plate .............................................................................................................................25
4.3 Ordering information for options and accessories ..................................................................27
5 Mounting ............................................................................................................................................... 29
6 Electrical connection ............................................................................................................................. 31
6.1 EMC-compliant installation .....................................................................................................32
6.1.1 Basic information about EMC .................................................................................................32
6.1.2 EMC-compliant installation of SINAMICS DCP (installation instructions) ..............................34
6.2 Block diagram with connection suggestion .............................................................................36
6.3 Components ............................................................................................................................37
6.4 Terminals and connectors ......................................................................................................38
6.5 Additional system components ...............................................................................................46
6.5.1 Option Board: Communication Board Ethernet CBE20 ..........................................................46
6.5.1.1 Description ..............................................................................................................................46
6.5.1.2 Safety instructions ...................................................................................................................46
6.5.1.3 Interface description................................................................................................................47
6.5.1.4 Meaning of the LEDs ..............................................................................................................48
6.5.1.5 Assembly ................................................................................................................................51
6.5.1.6 Technical data .........................................................................................................................52
7 Commissioning ..................................................................................................................................... 53
7.1 Switching on ............................................................................................................................55
7.1.1 BOP20 status display during ramp-up ....................................................................................56
7.2 Commissioning using the BOP20 operator panel ...................................................................57
7.2.1 Requirements ..........................................................................................................................57
7.2.2 Commissioning steps ..............................................................................................................58
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 7
Table of contents
SINAMICS DCP
8 Operating Instructions, 06/2014, A5E34382853K
Table of contents
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 9
Table of contents
SINAMICS DCP
10 Operating Instructions, 06/2014, A5E34382853K
Introduction 1
The objective of these Operating Instructions is to convey know-how necessary to enable
instructed persons to operate the system professionally and safely.
Knowledge of the Operating Instructions and descriptions of the associated components is
required for all work on the various components. In case of doubt, request support from the
Siemens Customer Support.
Only appropriately trained and instructed personnel is permitted to operate the system.
These Operating Instructions are intended to inform and instruct defined target groups,
safeguard the manufacturer against liability, observe the product, provide traceability and
reproducibility, as well as the long-term or legally required archiving of the relevant
information content.
The individual sections of the Operating Instructions provide information about the product
itself, the handling of the product, and the actions of users.
This document includes safety information and the most important technical details of the
SINAMICS DCP.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 11
Introduction
SINAMICS DCP
12 Operating Instructions, 06/2014, A5E34382853K
Safety notes 2
Note
For reasons of clarity, this documentation does not contain all of the detailed information on
all of the product types. This documentation cannot take into consideration every
conceivable type of installation, operation and maintenance.
If you require further information or technical details on the documentation, please request
this from the manufacturer (CEE RC-AT SIMEA DT-LD / Siemensstraße 90 / A-1210 Wien).
We would also like to point out that the contents of this documentation are neither part of nor
modify any prior or existing agreement, commitment or contractual relationship.
WARNING
Note the safety instructions
Operating, servicing, maintaining or installing the SINAMICS DCP may result in property
damage, serious injury, and even death if the safety instructions are not observed.
You must strictly comply with all notes regarding intended use. Different operating modes,
overloads, load cycles, and differing ambient conditions are permitted only after special
arrangement with the manufacturer.
WARNING
Qualified personnel
The system is at a hazardous voltage. Failure to comply with these Operating Instructions
can lead to death, serious injury and material damage.
Only qualified personnel are permitted to work on this system. Such personnel must be
thoroughly acquainted with all the warnings and maintenance procedures referred to in
these Operating Instructions.
Perfect, safe and reliable operation of the system assumes that it has been professionally
transported, stored, mounted and installed as well as correct operation and servicing.
Note
In addition to the safety instructions stated here, make sure that the safety instructions in the
manuals for the individual devices are also observed and followed at all times when working
with different components.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 13
Safety notes
2.1 Safety concept
DANGER
Grounding the SINAMICS DCP
High voltages that could cause death or serious injury may be still present in the SINAMICS
DCP even after the system has been shut down.
Work on the power units is only permitted when steps have been taken to ensure proper
grounding.
SINAMICS DCP
14 Operating Instructions, 06/2014, A5E34382853K
Safety notes
2.2 Notes on operator protection
Note
Qualified personnel
All work associated with the transport, installation, commissioning, operation or maintenance
must be performed by qualified specialist personnel (skilled electricians according to EN
50110-1 "Operation of electrical installations").
For the purpose of these basic safety instructions, "skilled technical personnel" means
people who are familiar with the installation, mounting, commissioning and operation of the
product. They must be properly qualified for the tasks with which they are charged.
The personnel must also be thoroughly familiar with all safety-related instructions and
measures in this documentation.
WARNING
Dangerous parts
The SINAMICS DCP may have live parts during operation.
Unauthorized removal of required covers, improper use, or incorrect installation or
operation may lead to death and serious injury or property damage.
Always take the appropriate precautions before touching any components.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 15
Safety notes
2.2 Notes on operator protection
WARNING
Dangerous voltages
High voltages can cause death or serious injury if the safety rules are not observed or if the
equipment is handled improperly.
As soon as the DC link or the battery is connected, dangerous DC voltages are present.
When the SINAMICS DCP is in operation, high voltages occur, and can remain present for
a longer period after the equipment is switched off.
Make sure that work is only carried out by qualified personnel under strict observance of
the five safety rules, the warning notices in this documentation, and the safety-relevant
instructions.
DANGER
Capacitor discharge / dangerous voltages
After disconnection of the supply voltage, voltages are still present in the SINAMICS DCP
devices that could result in death or serious injury.
After you have switched off the power supply, observe the discharge time of the DC-link
capacitors of 1 minute before you perform any maintenance work or repair work and do not
touch the device during this period.
Measure the voltage once the discharge time has elapsed.
CAUTION
Hot surfaces
Certain components (e.g. heat sink, reactors, IGBT modules, etc.) can become very hot
during operation.
These components can remain very hot for some time after operation. Serious injury
(scalding) may occur if you come into contact with these components.
Do not touch hot components even after you have switched off the SINAMICS DCP.
SINAMICS DCP
16 Operating Instructions, 06/2014, A5E34382853K
Safety notes
2.2 Notes on operator protection
WARNING
Electromagnetic radiation during operation of the plant
Electromagnetic fields are generated during operation of electrical power engineering
equipment, such as transformers, converters, and motors.
Electromagnetic fields can interfere with electronic devices, which could cause them to
malfunction.
For example, the operation of heart pacemakers can be impaired, potentially leading to
damage to a person's health or even death. Steps must be taken, therefore, to ensure that
persons with heart pacemakers cannot enter these areas.
The plant operator is responsible for taking appropriate measures (labels and hazard
warnings) to adequately protect operating personnel and others against any possible risk.
● Observe the relevant nationally applicable health and safety regulations or the applicable
national regulations in the country of installation.
● Display adequate hazard warning notices on the installation.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 17
Safety notes
2.3 Notes on plant safety
Requirements
The operating company is responsible for the plant safety.
Ensure that:
● Basic planning activities and all work associated with transport, assembly, installation,
commissioning, maintenance and repair are performed exclusively by qualified personnel
or by experts assigned responsibility.
● The entire product documentation must always be available for all of the work that is
performed.
● The technical data and specifications regarding the permissible installation, connection,
environmental and operating conditions are always consequentially observed.
● The setup and safety regulations specific to this machine are observed and personal
safety precautions taken.
● It is prohibited for unqualified persons to work on these devices or in their vicinity.
SINAMICS DCP
18 Operating Instructions, 06/2014, A5E34382853K
Safety notes
2.4 ESD-sensitive components
NOTICE
Electrostatic discharge
Electronic modules contain components that can be destroyed by electrostatic discharge.
These modules can be easily destroyed if they are not handled properly.
To protect your equipment against damage, follow the instructions given below.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 19
Safety notes
2.4 ESD-sensitive components
SINAMICS DCP
20 Operating Instructions, 06/2014, A5E34382853K
Description 3
Area of application
A SINAMICS DCP is used to control the electrical power flow between two direct current
systems. The device operates as a controlled current source.
The main application of the SINAMICS DCP is to control the electrical power flow:
● From a DC link (the input side, terminals P1 and N1) to a stationary battery (the output
side, terminals P2 and N2).
This is also called motorized operation and means positive current.
● From a battery (the output side, terminals P2 and N2) back to the DC link (the input side,
terminals P1 and N1).
This is also called generator operation and means negative current.
The power flow in both directions (from the DC link to the battery and from the battery to the
DC link) is called bidirectional.
The voltages in the two DC circuits are independent of one another.
The electrical power flow, controlled by a signed current setpoint specification, is possible
irrespective of the voltages in the two DC circuits (in the nominal range).
The integration of a SINAMICS DCP in a complete technical system is illustrated in Chapter
Block diagram with connection suggestion (Page 36).
Design
The SINAMICS DCP are compact devices and contain power units and open-loop/closed-
loop control electronics.
The open-loop/closed-loop control electronics comprise several modules.
The module visible when the front plate is removed is called CUD (Control Unit DC).
LEDs are fitted on the CUD and other modules. They are not visible externally. They are not
relevant for the user, they are only used for diagnostics by SIEMENS experts.
The power units are equipped with IGBT technology, the heat sink is grounded.
The devices are forced-ventilated, the air flow is from the bottom to the top.
The minus cable is led from the input to the output, the current is controlled in the plus
branch.
The devices are only approved for cabinet mounting, vertical installation.
The SINAMICS DCP devices have IP20 degree of protection.
The connecting terminals are accessible from the front.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 21
Description
Communication with the devices is via fieldbus (PROFIBUS or PROFINET) during normal
operation and STARTER for the parameter assignment and diagnostics.
Additional components
● CBE20 additional module
– The CBE20 additional module is inserted in the option module slot of the CUD. It
enables the SINAMICS DCP to participate in a PROFINET network as a slave.
● Memory card
– The memory card enables the functions described in Chapter Memory card functions
(Page 95).
SINAMICS DCP
22 Operating Instructions, 06/2014, A5E34382853K
Description
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 23
Preparations for use 4
4.1 Device order numbers
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 25
Preparations for use
4.2 Rating plate
Explanation:
(1P) ... Article number
(S) ... Serial number
A5E ... SIEMENS-internal article number
FS ... Functional State (version of the supplied product)
SCCR ... Short-Circuit Current Rating (short-circuit strength)
WARNING
Hazardous Voltage
There is a warning notice below the rating plate on the front cover about the hazardous
voltage present for up to 1 minute on the device after disconnection from the power supply.
SINAMICS DCP
26 Operating Instructions, 06/2014, A5E34382853K
Preparations for use
4.3 Ordering information for options and accessories
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 27
Preparations for use
4.3 Ordering information for options and accessories
SINAMICS DCP
28 Operating Instructions, 06/2014, A5E34382853K
Mounting 5
The SINAMICS DCP is only designed for cabinet mounting.
It must be mounted vertically.
The arrangement of the fixing positions is shown in the following:
Figure 5-1 Dimensions and fixing positions for product version (Functional State) 01
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 29
Mounting
Figure 5-2 Dimensions and fixing positions as of product version (Functional State) 02
The area below the device must be unobstructed and allow sufficient supply air.
The area above the device must allow the air outlet and the air outlet openings of the device
must be unobstructed.
The lateral clearance to other components (also for the attachment of further SINAMICS
DCPs) must be at least 20 mm.
The customer must make provisions for clamping the power cables.
SINAMICS DCP
30 Operating Instructions, 06/2014, A5E34382853K
Electrical connection 6
WARNING
DANGER
This product can cause a direct current in the protective ground conductor. When a residual
current device (RCD) or a residual current monitor (RCM) is used for protection in the event
of direct or indirect contact, only an RCD or RCM of type B is permissible on the power
supply side of this product.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 31
Electrical connection
6.1 EMC-compliant installation
What is EMC?
EMC stands for "electromagnetic compatibility" and describes "the capability of a device to
function satisfactorily in an electromagnetic environment without itself causing interference
unacceptable for other devices in the environment". Therefore, the various units used should
not cause interference to one another.
Within the context of the EMC Directive, the SINAMICS DCP units described in this
document are not "units" at all, but are instead "components" that are intended to be
installed in an overall system or overall plant. For reasons of clarity, however, the generic
term "units" is used in many cases.
SINAMICS DCP
32 Operating Instructions, 06/2014, A5E34382853K
Electrical connection
6.1 EMC-compliant installation
Four different categories are defined in EN 61800-3 depending on the location and the
power:
Category C1: Systems for rated voltages < 1000 V for unlimited use in the first environ-
ment
Category C2: Stationary systems for rated voltages < 1000 V for use in the second envi-
ronment. Use in the first environment is possible if the system is operated
and installed by qualified personnel. The warning information and installa-
tion instructions supplied by the manufacturer must be observed.
Category C3: Systems for rated voltages < 1000 V for exclusive use in the second envi-
ronment
Category C4: Systems for rated voltages ≥ 1000 V or for rated currents ≥ 400 A for use in
complex systems in the second environment
The figure below shows how the four categories are assigned to the first and second
environments:
SINAMICS DCP devices are always used in the second environment (Category C3).
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 33
Electrical connection
6.1 EMC-compliant installation
The SINAMICS DCP devices satisfy the requirements for interference emissions and
interference immunity defined in EN 61800-3 for the second environment (Category C3) and
those in the generic standards EN 61000-6-2 and EN 61000-6-4.
WARNING
General information
In order to ensure electromagnetic compatibility (EMC) in rugged electrical environments and
adhere to the standards required by the relevant legislating body, the EMC rules listed below
should be followed during the construction and installation stages.
1 Connect all metallic parts of the control cabinet to one another over a flat area with
good conductivity (not paint against paint!). Use contact or scratch washers if neces-
sary. The cabinet door must be connected to the cabinet using the shortest possible
ground strips (at the top, center, and bottom).
2 Contactors, relays, solenoid valves, electromechanical operating hours counters, etc.,
in the cabinet and - where applicable - in neighboring cabinets - must be provided with
quenching combinations such as RC elements, varistors, and diodes. These must be
connected directly at the appropriate coil.
3 Whenever possible, lead signal cables 1) into the cabinet at one level only.
4 Unshielded cables in the same circuit (outgoing/incoming conductors) must be twisted
where possible, or the area between them minimized, to prevent unnecessary frame
antennae.
SINAMICS DCP
34 Operating Instructions, 06/2014, A5E34382853K
Electrical connection
6.1 EMC-compliant installation
5 Connect spare wires to the cabinet ground 2) at both ends. This achieves an additional
shielding effect.
6 Avoid unnecessary cable lengths in order to keep coupling capacities and inductances
low.
7 Crosstalk is generally reduced if the cables are laid close to the control cabinet ground.
Therefore, do not route cables freely around the cabinet, but lay them as close as pos-
sible to the cabinet enclosure / mounting plates. This also applies to spare cables.
8 Signal and power cables must be physically separated (to prevent coupling paths).
Minimum clearance: 20 cm should be aimed at. If it is not possible to physically sepa-
rate the encoder and motor cables, the encoder cable must be decoupled either using
a partition or by routing it in a metal conduit. The partition or metal conduit must be
grounded at several points.
9 Ground the shields of digital signal cables at both ends (source and destination), ensur-
ing maximum contact area and good conductivity. In the event of poor equipotential
bonding between the shield connections, run an additional equalizing conductor with a
cross-section of at least 10 mm² parallel to the shield for the purpose of reducing the
shield current. Generally speaking, the shields may also be connected to the cabinet
enclosure (ground) 2) at several points. The shields can be connected several times
even outside the control cabinet. Foil shields should be avoided, as they are are at
least 5 times less effective than braided shields.
10 Shields for analog signal cables may be connected to ground at both ends if equipoten-
tial bonding is good (this must be done over a large area with good conductivity). It can
be assumed that equipotential bonding is good if all metal parts are well interconnected
and the electronics components are supplied from a single source.
Footnotes
1) Signal cables are defined as:
Digital signal cables, e.g. cables for incremental encoders
Analog signal cables, e.g. ±10 V setpoint cable
Serial interfaces, e.g. PROFIBUS and PROFINET
2) Generally speaking, "ground" refers to all metallic conductive parts that can be con-
nected to a protective conductor, such as the cabinet enclosure, motor enclosure, or
foundation ground.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 35
Electrical connection
6.2 Block diagram with connection suggestion
SINAMICS DCP
36 Operating Instructions, 06/2014, A5E34382853K
Electrical connection
6.3 Components
6.3 Components
Fuses
The device must be protected by a DC fuse on the input side and output side.
Specified type
Siemens PV fuse 63 A with designation 3NE1218-4
Fuse holder: Siemens 3NH3230
Line contactors
The DC power contactors must control 1000 V and 50 A.
Recommended type
Siemens 3TC4817-0LB4
Precharging resistors
Recommended type
CAV 150 C 100R 800, manufacturer: Danotherm
Precharging contactors
Recommended type
High-voltage relay H-507
Type code H00-04507/11-001128-002/005.00
Coil voltage 24 V
Manufacturer: Hengstler
Note
The contacts must be connected in parallel.
Note
With the recommended series resistor, the max. contact load of 10 A is not exceeded.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 37
Electrical connection
6.4 Terminals and connectors
Power connections
● The power connection DC input (DC link) is on the bottom left of the device
● The power connection DC output (battery side) is on the bottom right of the device
● The ground connection is on the bottom left of the device
SINAMICS DCP
38 Operating Instructions, 06/2014, A5E34382853K
Electrical connection
6.4 Terminals and connectors
Terminal arrangement
The connection cable must be stranded with a minimum cross-section of 10 mm2. The cable
used must satisfy the requirements of the recommended connection cable.
Note
The sheaf diameter of the cable must not be greater than 10 mm.
Ground connection
The device must be grounded. The device has a ground connection on the bottom, identified
by a grounding symbol.
Tightening torque of the screw terminals for the protective conductor: 25 Nm.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 39
Electrical connection
6.4 Terminals and connectors
Terminal block for the 24 VDC power supply and switching contacts
On the top of the device (see following figure), there is a terminal block with 10 terminals.
SINAMICS DCP
40 Operating Instructions, 06/2014, A5E34382853K
Electrical connection
6.4 Terminals and connectors
Terminal arrangement
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 41
Electrical connection
6.4 Terminals and connectors
Communication connections
The cables for PROFIBUS or PROFINET must be connected inside the device. The front
cover must be removed for this.
● The PROFIBUS connector X126 is on the CUD module. The cable can be led out at the
bottom through the intended aperture.
● The PROFINET connector X1400 is on the CBE20 module. The cable can be led out at
the top through the intended aperture.
① PROFIBUS cable
SINAMICS DCP
42 Operating Instructions, 06/2014, A5E34382853K
Electrical connection
6.4 Terminals and connectors
① PROFINET cable
-X178, -X179:
Type FMC 1.5 plug-in terminal
Conductor size Rigid/flexible/conductor sizes (mm2/mm2/AWG): 0.2 - 1.5 / 0.2 - 1.5 / 24 - 16
Flexible with end sleeve with/without plastic sleeve: 0.25 - 1.5 / 0.25 - 0.75 mm2
Stripping length 10 mm
-XR1,- XS1, -XT1:
Type MSTB 2.5 / CIF plug-in terminal
Conductor size Rigid/flexible/conductor sizes (mm2/mm2/AWG): 0.2 - 2.5 / 0.2 - 2.5 / 24 - 12 flexible with
end sleeve with/without plastic sleeve: 0.25 - 2.5 / 0.25 - 2.5 mm2
Stripping length 7 mm
Tightening torque 0.5 - 0.6 Nm
-X126:
Type Submin D, 9-pin
-X100, -X101:
Type Modular jack 8/4 (RJ45)
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 43
Electrical connection
6.4 Terminals and connectors
SINAMICS DCP
44 Operating Instructions, 06/2014, A5E34382853K
Electrical connection
6.4 Terminals and connectors
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 45
Electrical connection
6.5 Additional system components
6.5.1.1 Description
The SINAMICS DCP can be connected to PROFINET using the Communication Board
CBE20 interface module. The module supports PROFINET IO with Isochronous Realtime
Ethernet (IRT) and PROFINET IO with RT. Mixed operation is not permissible. PROFINET
CBA is not supported.
The option board has an X1400 interface with four ports for communication.
The Communication Board CBE20 allows SINAMICS Link connections and the connection to
EtherNet/IP to be established.
Note
By inserting the CBE20, the IF1 communication channel switches over from PROFIBUS to
PROFINET. Communication is therefor no longer possible via PROFIBUS.
NOTICE
Damage or malfunctions of the Option Board by inserting and withdrawing during operation
Withdrawing and inserting the Option Board during operation can damage it or cause it to
malfunction.
• Only withdraw or insert the Option Board when the Control Unit is de-energized.
NOTICE
The CBE20 must only be operated by qualified personnel. The ESD information must be
observed.
SINAMICS DCP
46 Operating Instructions, 06/2014, A5E34382853K
Electrical connection
6.5 Additional system components
Overview
MAC address
The MAC address of the Ethernet interface is located on the upper side of the board.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 47
Electrical connection
6.5 Additional system components
For diagnostic purposes, the ports have one green and one yellow LED (for a description,
see Chapter Meaning of the LEDs (Page 48)).
SINAMICS DCP
48 Operating Instructions, 06/2014, A5E34382853K
Electrical connection
6.5 Additional system components
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 49
Electrical connection
6.5 Additional system components
SINAMICS DCP
50 Operating Instructions, 06/2014, A5E34382853K
Electrical connection
6.5 Additional system components
6.5.1.5 Assembly
Before assembly of the CBE20, the front plate must be removed and the electronics pulled
out slightly.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 51
Electrical connection
6.5 Additional system components
Push the CBE20 into the option module interface ① on the CUD from above, and tighten the
screws ②.
Tool: Torx T10 screwdriver tightening torque 1 Nm.
Figure 6-10 Assembling the CBE20
SINAMICS DCP
52 Operating Instructions, 06/2014, A5E34382853K
Commissioning 7
WARNING
This unit is subject to hazardous voltage levels and contains dangerous rotating machine
parts (fans). Failure to comply with these Operating Instructions can lead to death, serious
injury and material damage.
Only qualified personnel who are familiar with all the safety instructions in this description,
as well as the installation, operating, and maintenance instructions, should carry out work
on this unit.
Perfect, safe and reliable operation of the equipment assumes that it has been
professionally transported, stored, mounted and installed as well as correct operation and
servicing.
Even when all contactors are open, the device is still subject to dangerous electrical voltage
levels. The internal DC-link capacitors may still be charged. Before starting any service or
maintenance work, disconnect the device on both power unit sides (P1/N1 and P2/N2).
To operate the SINAMICS DCP, the front cover fixing screw must be tight.
These instructions are not exhaustive and, as such, cannot outline all the measures
required in order to operate the device safely. Where necessary, additional information or
instructions may be required for special applications. If you encounter specific problems
that have not been handled in enough detail for the purposes of the buyer, then please
contact your local Siemens office.
The use of non-approved parts for carrying out repair work on the device or handling of the
device by inadequately qualified personnel will result in dangerous conditions with the risk
of death, serious injury, or extensive damage to equipment. All safety measures listed in
these Operating Instructions, as well as all warning signs attached to the device, must be
followed.
Observe all the warning notices in Chapter Safety notes (Page 13) of these Operating
Instructions.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 53
Commissioning
6.5 Additional system components
NOTICE
Before coming into contact with modules (and in particular the CUDs), the operator must be
electrostatically discharged in order to protect electronic components against high voltages
that are produced by electrostatic charging. The easiest way to do this is to touch a
conductive, grounded object immediately beforehand (for example, bare metal parts of
control cabinet).
Modules must not come into contact with highly insulating materials (such as plastic sheets,
insulated desktops, or articles of clothing manufactured from synthetic fibers).
Modules may be placed only on conductive surfaces.
Note
During a data save operation initiated by the user, the electronics power supply for the
SINAMICS DCP must not be interrupted.
An active data save operation is indicated by the following actions:
• The RDY LED flashes (see Chapter Description of the LEDs on the CUD (Page 189))
• The BOP20 flashes
Interrupting the power supply while saving can lead to the loss of the current device
parameter assignments. See also Chapter Memory card functions (Page 95), Section
"Memory card functions".
SINAMICS DCP
54 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.1 Switching on
7.1 Switching on
After the device is switched on (POWER ON), the SINAMICS DCP ramps up. Ramp-up to
operating state 7.0 in the SINAMICS DCP with the saved parameters (RAM to ROM was
carried out) takes approx. 45 s. Ramp-up without the saved parameters (first commissioning)
takes approx. 60 s.
The status of the LEDs on the CUD (see also Chapter Description of the LEDs on the CUD
(Page 189)) can only be seen when the device cover is open.
Note
If options are being used and in the case of certain device configurations, the duration of the
ramp-up increases.
Note
If an external memory card with previously saved data is plugged into the SINAMICS DCP
during ramp-up, the device ramps up based on the parameter assignments saved on the
card (see also Chapter Memory card functions (Page 95)).
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 55
Commissioning
7.1 Switching on
The states listed above are automatically run through during the commissioning and are normally not
visible.
In the following exceptional cases, ramp-up is interrupted with display value 33. In this state,
the device can be parameterized via BOP20 and via STARTER:
● Differences have been identified between the reference and actual topology.
– Correct the topology (e.g. re-insert the TM component).
– Accept the actual topology into the reference topology by setting p9905=1 or p9905=2.
Ramp-up is continued.
● A memory card with a parameter data set which comes from a SINAMICS DCP with a
different MLFB, is inserted in the device.
– Accept the parameter data set by setting p9906=3. Ramp-up is continued.
SINAMICS DCP
56 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.2 Commissioning using the BOP20 operator panel
7.2.1 Requirements
SINAMICS basics
If you are not yet familiar with SINAMICS basics (parameters, drive objects, BICO
technology, etc.), please read Chapter Basics (Page 89) before starting commissioning.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 57
Commissioning
7.2 Commissioning using the BOP20 operator panel
SINAMICS DCP
58 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.2 Commissioning using the BOP20 operator panel
Note
The functionality of the undervoltage/overvoltage protection is used to protect the battery and
the DC link. For further details, see Chapter Closed-loop control (Page 180) at Voltage
limitation.
10 Reactor current
11 Current at the input (= side 1)
12 Current at the output (= side 2)
20 Power
〈6〉Setting the source for the control word and the setpoint
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 59
Commissioning
7.3 Commissioning with the STARTER commissioning tool
7.3.1.1 Description
Description
You can use the STARTER commissioning tool to configure and commission the SINAMICS
drives or drive systems as well as the SINAMICS DCP. The drive configuration can be
performed with the aid of the STARTER wizard for drive configuration.
Note
In this chapter, "drive", "drive unit" or "drive system" always refers to the SINAMICS DCP.
Note
This chapter describes how to commission with STARTER. STARTER has a comprehensive
online help that explains in detail all of the sequences and setting options in the system. This
is the reason why this chapter is restricted to the individual commissioning steps.
Note
The SIMOTION SCOUT engineering tool includes the STARTER functionality to commission
drives.
As of version V4.2, SCOUT has also been released for commissioning the SINAMICS DCP.
SINAMICS DCP
60 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.3 Commissioning with the STARTER commissioning tool
② Project navigator The elements and objects contained in the project are displayed in this area.
③ Working area Changes to the drive units are made in this area.
④ Detail view This area displays detailed information, for instance about faults and alarms.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 61
Commissioning
7.3 Commissioning with the STARTER commissioning tool
Note
The interactive screens are pre-assigned defaults that you need to adapt to your application
and configuration under certain circumstances.
This is intentional:
Objective: By taking time to consider what configuration data you enter, you can prevent
inconsistencies between the project data and drive unit data (identifiable in online mode).
SINAMICS DCP
62 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.3 Commissioning with the STARTER commissioning tool
Figure 7-2 Main screen of the STARTER parameterization and commissioning tool
⇒ Close the "STARTER Getting Started Drive Commissioning" screen by selecting HTML
Help > Close.
Note
When you deactivate the Display wizard during start checkbox, the project wizard is no
longer displayed the next time you start STARTER.
You can bring up the project wizard by selecting Project > New with wizard.
To deactivate the online help for Getting Started, follow the instructions provided in the help.
You can call up the online help at any time by selecting Help > Getting Started.
STARTER features a detailed online help system.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 63
Commissioning
7.3 Commissioning with the STARTER commissioning tool
⇒ Enter a project name and, if necessary, the author, storage location and a comment.
⇒ Click Next > to set up the PG/PC interface.
SINAMICS DCP
64 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.3 Commissioning with the STARTER commissioning tool
⇒ Click PG/PC… and set up the interface according to your device configuration.
The Properties..., Copy... and Select... buttons are available.
Set S7ONLINE as access point.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 65
Commissioning
7.3 Commissioning with the STARTER commissioning tool
Note
To parameterize the interface, you must install the appropriate interface card (e.g. PC
Adapter (PROFIBUS)).
We recommend the use of the Siemens USB PROFIBUS Adapter CP5711. Order number
6GK1571-1AA00.
Note
PG/PC is the only master on bus must be activated if no other masters (PC, S7, etc.) are
available on the bus.
Note
Even if no PROFIBUS interface is installed in the PC, projects can be generated and
PROFIBUS addresses for the drive objects can be assigned.
Only the bus addresses available in the project will be offered. That prevents double bus
address assignments.
SINAMICS DCP
66 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.3 Commissioning with the STARTER commissioning tool
⇒ After completion, click OK to confirm the setup and to return to the project wizard.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 67
Commissioning
7.3 Commissioning with the STARTER commissioning tool
Note
For a download, the bus address assigned here is transferred to the device, but is not
transferred to parameter p918.
To keep p918 consistent with the project, after a "Load to target device" a "Load to PG" must
still be performed – and must be repeated after every change to p918 using BOP20.
⇒ Click Insert
The selected drive unit is displayed in the project wizard preview window.
SINAMICS DCP
68 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.3 Commissioning with the STARTER commissioning tool
⇒ Click Finish to complete the creation of a new project for the drive unit.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 69
Commissioning
7.3 Commissioning with the STARTER commissioning tool
⇒ In the project navigator, click the plus sign next to the drive unit that you want to configure.
The plus sign changes into a minus sign and the options for configuring the drive unit appear
as a directory tree under the drive unit.
⇒ Double click Configure drive unit
SINAMICS DCP
70 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.3 Commissioning with the STARTER commissioning tool
⇒ If you have plugged in a PROFINET CBE20 module (option G33), the module needs to be
activated here
⇒ Click Next >
Under Drive properties, you can enter optional information about the drive/project.
⇒ Click Next >
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 71
Commissioning
7.3 Commissioning with the STARTER commissioning tool
⇒ If you want to use the free function blocks, you can activate them here.
⇒ Click Next >
SINAMICS DCP
72 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.3 Commissioning with the STARTER commissioning tool
You can filter the MLFB list with the supply voltage and range selection boxes.
⇒ Select the corresponding device according to the MLFB on the rating plate.
⇒ Click Next >
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 73
Commissioning
7.3 Commissioning with the STARTER commissioning tool
SINAMICS DCP
74 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.3 Commissioning with the STARTER commissioning tool
Telegram selection
⇒ Select a standard telegram type or, with free configuration, the process data lengths.
Note
If a standard telegram is selected, BICO interconnections are triggered which cannot be re-
parameterized. If, e.g. p0840 is to be changed again, a switchover to free telegram
configuration has to be made first.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 75
Commissioning
7.3 Commissioning with the STARTER commissioning tool
Summary
⇒ You can use the Copy to clipboard function to copy the summary of the drive unit data
displayed on the screen to a word processing program for subsequent use.
⇒ Click Finish.
⇒ Save your project on the hard disk via Project > Save.
SINAMICS DCP
76 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.3 Commissioning with the STARTER commissioning tool
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 77
Commissioning
7.3 Commissioning with the STARTER commissioning tool
● Step 2
Select DCM_ADVANCED_CUD as drive unit in the following screen and confirm with OK:
SINAMICS DCP
78 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.3 Commissioning with the STARTER commissioning tool
● Step 3
Select the menu command Download:
● Step 4
Activate the checkbox to select that Copy RAM to ROM is to be performed after the
download.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 79
Commissioning
7.3 Commissioning with the STARTER commissioning tool
Alternatively, the download to the target system can also be performed as follows:
● Step 1
Select the menu command Target system > Download > Project to target system
Selection in the toolbar
Note
Your project data has now been transferred to the drive unit. Presently, this data is only in
the volatile memory (RAM) of the drive unit, however, neither saved in the non-volatile
memory (ROM) nor on an optionally inserted memory card (see also Memory card
functions (Page 95)).
To save your project data in the ROM and on the optionally available memory card of
your drive unit so that it is protected against power failure, carry out the following steps.
● Step 2
Select the menu command Target system > Target system > Copy RAM to ROM
Selection in the toolbar
Note
The button for copying RAM to ROM can only be activated if the drive unit has been
marked in the project navigator.
SINAMICS DCP
80 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.3 Commissioning with the STARTER commissioning tool
Requirements
● A serial interface (COM) must be available on the PC from which the connection will be
made.
Connecting cables
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 81
Commissioning
7.3 Commissioning with the STARTER commissioning tool
Settings
1. In STARTER, from Project > Set PG/PC interface, select the Serial cable (PPI) interface.
If this is not available in the drop-down list, you first have to add it using Select.
Note
If the interface cannot be added to the selection menu, the drive for the serial interface
still needs to be installed.
This is located in the following path on the STARTER CD:
\installation\starter\starter\Disk1\SerialCable_PPI\
STARTER must not be active while the driver is being installed.
2. Enter the following settings. The "0" address and the transmission rate 19.2 kbit/s are
important here.
SINAMICS DCP
82 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.4 Activating function modules
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 83
Commissioning
7.4 Activating function modules
The function modules can be accessed in the "Function modules" tab in the opening dialog.
SINAMICS DCP
84 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.4 Activating function modules
Note
This process is not supported by STARTER because it uses its own mechanisms.
Activation is through p0108. r0108 and is available at each DO as a display parameter for
the activated function modules.
The setting is made on p0108[i] in the Control Unit. In this case, the index corresponds to the
DO.
Index 0 stands for the CU,
Index 1 for the first DO – the default is the closed loop control DO DC_CTRL,
Index 2 optionally the first TMxx, etc.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 85
Commissioning
7.4 Activating function modules
Note
If PROFINET is to be used only as a commissioning interface but process control is through
PROFIBUS, after commissioning the CBE20, the process data interface needs to be set
back to PROFIBUS (p8839 = 1).
SINAMICS DCP
86 Operating Instructions, 06/2014, A5E34382853K
Commissioning
7.4 Activating function modules
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 87
Commissioning
7.4 Activating function modules
SINAMICS DCP
88 Operating Instructions, 06/2014, A5E34382853K
Operation 8
8.1 Operation
8.1.1 Basics
8.1.1.1 Parameters
Parameter types
The following adjustable and display parameters are available:
● Adjustable parameters (can be written and read)
These parameters have a direct effect on how a function responds.
Example: Ramp-up and ramp-down time of the setpoint ramp
● Display parameters (can only be read)
These parameters are used to display internal variables.
Example: Current voltage on side 1 and side 2
All these parameters can be read via PROFIBUS and changed by means of p parameters
using the mechanisms defined in the PROFIdrive profile.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 89
Operation
8.1 Operation
Parameter categories
The parameters of the individual drive objects are categorized into data sets as follows:
● Data set independent parameters
These parameters exist only once per drive object.
● Data set dependent parameters
These parameters can exist several times for each drive object and can be addressed via
the parameter index for reading and writing. A distinction is made between different data
set types:
– CDS: Command Data Set
By parameterizing several command data sets and switching between them, the
SINAMICS DCP can be operated with different preconfigured signal sources.
– DDS: Drive Data Set
The drive data set contains the parameters for switching between different drive
control configurations.
The CDS and DDS can be switched over during normal operation.
Note
With the SINAMICS DCP, the parameters of the closed-loop control are not implemented as
DDS parameters.
Note
The power supply to the Control Unit may first be switched off only after saving has finished
(i.e. after saving has started, wait until the parameter has the value 0 again).
Reset parameters
The parameters can be reset to the factory setting as follows:
SINAMICS DCP
90 Operating Instructions, 06/2014, A5E34382853K
Operation
8.1 Operation
After this has been done, p0976 is automatically set to 0 and p0009 is set to 1.
Note
DCC is not supported in software version V1.1.
This data is also saved in the non-volatile memory (ROM). All user data is deleted from the
ROM as follows:
Note
Data on the memory card is not deleted by setting p0976 = 200. In spite of this, when
deleting all user data, it is not permissible that a memory card is inserted. An inserted
memory card would mean that for an automatic ramp-up after p0976 = 200, as usual, the
data would be read from the memory card (see also Chapter Memory card functions
(Page 95)). The device would ramp-up with the parameter assignment from the memory
card.
Access level
The parameters are subdivided into access levels. The SINAMICS DCP List Manual
specifies the access level at which the parameter can be displayed and modified. The
required access levels 0 to 4 can be set in p0003.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 91
Operation
8.1 Operation
SINAMICS DCP
92 Operating Instructions, 06/2014, A5E34382853K
Operation
8.1 Operation
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 93
Operation
8.1 Operation
Note
Each installed drive object is allocated a number between 0 and 63 during first
commissioning so that it can be identified internally.
SINAMICS DCP
94 Operating Instructions, 06/2014, A5E34382853K
Operation
8.1 Operation
Basics
The CUD (Control Unit for the SINAMICS DCP) manages three memory areas:
● A volatile memory, the RAM, also called work memory
● A non-volatile memory, the ROM, also called flash memory
● An optionally available portable memory card
Note
Memory cards can be ordered as an option (S03) or as accessories, see Chapter
Ordering information for options and accessories (Page 27).
SINAMICS DCP does not accept other memory cards.
The work memory receives all project information and application programs while the device
is being operated. To save the current data from the work memory, you must copy it to non-
volatile memory before shutting down, see Chapter Commissioning (Page 53), "Copy RAM
to ROM" function.
An optional memory card is used:
● For saving various parameter data sets
● For transferring the parameter data sets to additional SINAMICS DCPs
● For series commissioning
The memory card is needed:
● For installing software updates
● For loading the DCC block library to the SINAMICS DCP
Note
DCC is not supported in software version V1.1.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 95
Operation
8.1 Operation
Note
The memory card supplied from Siemens as option S03 includes, when supplied, a copy of
the internal device software. These files are required for software updates. These files can
be deleted for other applications.
Before you use the card for the functions described in this chapter, copy these files to a local
folder of your PG/PC and delete the files on the memory card.
Note
The DCC library itself is not saved as a part of the parameter data set.
SINAMICS DCP
96 Operating Instructions, 06/2014, A5E34382853K
Operation
8.1 Operation
Copying parameter data sets from non-volatile memory to the memory card
There are three ways of copying parameter data sets from non-volatile memory (ROM) to the
memory card:
● The system is switched off
– Insert a memory card into the CUD
– Switch on the system
– The system is put into operation by the software in the "ROM"
– Then the complete updated parameter data set with the index 0 is automatically
copied from the "ROM" to the memory card without a prompt appearing.
● The system is switched on
– Insert a memory card into the CUD
– Execute the command "RAM to ROM" (p0977 = 1). The updated parameter data set is
copied automatically, first to the "ROM" and then as a data set to the memory card
with index 0. If the memory card already contains a parameter data set with the index
0, this will be overwritten without a prompt appearing.
● The system is switched on
– By the user, utilizing the parameter data transfer from ROM to the memory card:
p0804 = 2, p0802 = (0..100) as target on the memory card and p0803 = (0/10/11/12)
as source from the ROM.
Note
While saving (BOP20 flashes, RDY LED flashes), the device must NOT be switched off.
Switching off the device while saving leads to the loss of the most recently performed and
not yet saved device parameterization.
Note
When options are being used and with certain device configurations, the saving operation
can take several minutes.
Note
When a memory card is inserted, the RAM to ROM command (p0977 = 1) will copy the
parameter data set with the index 0 from the ROM to the memory card. A parameter data set
that might have been previously saved on the memory card is overwritten.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 97
Operation
8.1 Operation
Copying parameter data sets from the memory card to non-volatile memory
There are two ways of copying parameter data sets from the memory card to non-volatile
memory:
● The system is switched off
– Insert a memory card containing a parameter data set with the index 0 into the CUD.
– Switch on the system. The new parameter data set will be copied to the ROM
automatically. The parameter data set with the index 0 which was previously in the
ROM will be overwritten.
– The system will then boot with the new parameter data set.
● The system is switched on
The user starts data transmission from the memory card to the ROM with parameters
p0802, p0803 and p0804:
– p0804 = 1
– p0802 = (0 ... 100) as source from the memory card and p0803 = (0/10/11/12) as
target to the ROM.
Note
The parameter data set in the ROM is overwritten during system start-up. If a memory card
with a parameter data set is inserted when the system is switched on, the parameter data set
with the index 0 in the ROM will be overwritten by the new one with the index 0 on the
memory card.
SINAMICS DCP
98 Operating Instructions, 06/2014, A5E34382853K
Operation
8.1 Operation
Procedure:
● Completely commission a "sample" SINAMICS DCP. As soon as all of the parameters
have been correctly set, carry out "RAM to ROM".
● Switch off the system and insert a memory card into the CUD. Switch on the system.
● The parameter assignment is saved on the memory card. If DCC charts are activated in
the system, then these as well as the DCC library are also saved on the memory card.
● Remove the card.
● Insert the card into a CUD that is switched-off and has still not been parameterized.
Switch on the system (POWER ON).
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 99
Operation
8.1 Operation
● During ramp-up, the parameter assignment is transferred to the CUD and copied to the
ROM as well as to the RAM. If DCC charts and the DCC library were saved on the
memory card, then these are also copied.
● The card can be removed once the system has powered-up. The CUD that was not
parameterized yet now has the same parameter assignment as the original "sample"
drive.
Note
The MLFB of the unit from which the parameter data set originated is also saved in a
parameter data set. If the parameter data set is loaded to a device with another MLFB
(POWER ON with the memory card inserted), then the device signals an inconsistent
topology (ramp-up stops with display "33" on the BOP, fault A1420 is output). This occurs, if
e.g. a parameter set that was generated from a 50 A unit is loaded to a 200 A device. In this
state, the user can accept the parameter set by setting p9906 = 3. The system continues to
ramp up.
Important parameters
p0977: Save all parameters (for details, see the SINAMICS DCP List Manual).
p0802: Data transfer of parameters [0, 10, 11, 12], memory card as source or target
p0803: Data transfer of parameters [0...100], non-volatile device memory as source or
target
p0804: Start of parameter data transfer and specification of transfer direction:
p0804 = 1: Transfer from the memory card to non-volatile device memory
p0804 = 2: Transfer from non-volatile device memory to memory card
Procedure:
SINAMICS DCP
100 Operating Instructions, 06/2014, A5E34382853K
Operation
8.1 Operation
Note
If the memory card is removed without a request being made, this can destroy the file
system on the memory card.
Note
The STARTER commissioning tool is recommended when using BICO technology.
Table 8- 2 Binectors
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 101
Operation
8.1 Operation
Table 8- 3 Connectors
SINAMICS DCP
102 Operating Instructions, 06/2014, A5E34382853K
Operation
8.1 Operation
Note
A connector input (CI) cannot be interconnected to any connector output (CO, signal
source). The same applies for a binector input (BI) and binector output (BO).
"Data type" in the parameter list provides information about the data type of the parameter
and the data type of the BICO parameter for each CI and BI parameter.
For CO and BO parameters, only the data type of the BICO parameter is given.
Notation:
BICO input data type: Parameter data type / BICO parameter data type
Example: Unsigned32 / Integer16
BICO output data types: BICO parameter data type
Example: FloatingPoint32
The possible interconnections between the BICO input (signal sink) and BICO output (signal
source) are listed in the table titled "Possible combinations for BICO interconnections", which
can be found in the "Explanations on the parameter list" chapter of the SINAMICS DCP List
Manual.
The BICO parameter interconnection can be implemented in different command data sets
(CDS). The different interconnections are activated by switching data sets. Interconnections
across drive objects are also possible.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 103
Operation
8.1 Operation
Binector-connector converters
● Several digital signals are converted to a 32-bit integer double word or to a 16-bit integer
word.
● p2080[0...15] BI: PROFIdrive PZD send bit-by-bit
Connector-binector converters
● A 32-bit integer double word or a 16-bit integer word is converted to individual digital
signals.
● p2099[0...1] CI: PROFIdrive PZD selection receive bit-by-bit
SINAMICS DCP
104 Operating Instructions, 06/2014, A5E34382853K
Operation
8.1 Operation
8.1.2 Parameter assignment via the BOP20 (Basic Operator Panel 20)
Table 8- 4 Displays
Display Meaning
Top left The active drive object of the BOP is displayed here.
2 digits The displays and key operations always refer to this drive object.
RUN Lights up when the SINAMICS DCP is in the RUN state (operation).
RUN is also displayed via bit r0899.2.
Top right The following is displayed in this field:
2 digits
• More than 6 digits: Characters that are still present but are invisible (e.g. "r2" ––> 2 charac-
ters to the right are invisible, "L1" ––> 1 character to the left is invisible)
• Designation of BICO inputs (bi, ci)
• Designation of BICO outputs (bo, co)
• Source object of a BICO interconnection to a drive object different than the active one.
S Lights up if at least one parameter was changed and the value was not transferred to the non-
volatile memory.
P Lights up if the parameter value does not become effective until the P key is pressed.
C Lights up if at least one parameter was changed and the calculation for consistent data man-
agement has still not been initiated.
Bottom 6 digits Displays parameters, indices, faults and alarms.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 105
Operation
8.1 Operation
For certain user actions (e.g. restore factory setting) a two-digit number is displayed on the
BOP20. This number provides information about the SINAMICS DCP state. The meaning of
these numbers is provided in the BOP20 status display during ramp-up (Page 56).
Table 8- 5 Keys
Lower
SINAMICS DCP
106 Operating Instructions, 06/2014, A5E34382853K
Operation
8.1 Operation
BOP20 functions
Table 8- 6 Functions
Name Description
Backlight The backlight can be set using p0007 in such a way that it switches itself off automatically
after the set time if no actions are carried out.
Switch active drive From the BOP perspective, the active drive is defined using p0008 or using the keys "FN" and
"Arrow up".
Units The units are not displayed on the BOP.
Access level The access level for the BOP is defined using p0003.
The higher the access level, the more parameters can be selected via the BOP.
Parameter filter The parameter filter in p0004 can be used to filter the available parameters in accordance with
their particular function.
Select status display Actual values and setpoints are displayed on the status display.
The status display can be set via p0006.
User parameter list Using the user parameter list in p0013, parameters can be selected for access.
Hot swapping The BOP can be unplugged and plugged while energized.
• The ON and OFF keys have a function.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 107
Operation
8.1 Operation
Note
During a data save operation initiated by the user, the electronics power supply for the
SINAMICS DCP must not be interrupted.
An active data save operation is indicated by the following actions:
• The RDY LED flashes (see Chapter Description of the LEDs on the CUD (Page 189))
• The BOP20 flashes
Interrupting the electronics power supply while saving can lead to the loss of the current
device parameter assignment. See also Chapter Memory card functions (Page 95).
SINAMICS DCP
108 Operating Instructions, 06/2014, A5E34382853K
Operation
8.1 Operation
Characteristics
● Status display
● Changing the active drive object
● Displaying/changing parameters
● Displaying/acknowledging faults and alarms
● Controlling the drive using the BOP20
Status display
The status display for each drive object can be set using p0005 and p0006.
Using the status display, you can switch to the parameter display or to a different drive
object. The following functions are supported:
● Changing the active drive object
– Press the "FN" and "Arrow up" keys -> the drive object number at the top left flashes
– Select the required drive object using the arrow keys
– Confirm with the "P" key
● Parameter display
– Press the "P" key
– The required parameter can be selected using the arrow keys
– Press the "FN" key -> parameter r0000 is displayed
– Press the "P" key -> returns to the status display
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 109
Operation
8.1 Operation
Parameter display
The parameters are selected in the BOP20 using the number. To call up the parameter
display from the status display, press the "P" key. You can search for the parameters you
require using the arrow keys. To display the parameter value, press the "P" key again. You
can toggle between the drive objects by pressing the "FN" keys and the arrow keys
simultaneously. You can toggle between r0000 and the parameter that was last displayed by
pressing the "FN" key in the parameter display.
SINAMICS DCP
110 Operating Instructions, 06/2014, A5E34382853K
Operation
8.1 Operation
Value display
To switch from the parameter display to the value display, press the "P" key. In the value
display, the values of the adjustable parameters can be increased and decreased using the
arrow. The cursor can be selected using the "FN" key.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 111
Operation
8.1 Operation
SINAMICS DCP
112 Operating Instructions, 06/2014, A5E34382853K
Operation
8.1 Operation
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 113
Operation
8.1 Operation
Displaying faults
Displaying alarms
SINAMICS DCP
114 Operating Instructions, 06/2014, A5E34382853K
Operation
8.2 Inputs/outputs
Note
For simple commissioning, only bit 0 should be interconnected. When interconnecting bits 0
... 2, then the system is powered-down according to the following priority: OFF2, OFF3,
OFF1.
8.2 Inputs/outputs
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 115
Operation
8.2 Inputs/outputs
Properties
Inputs Properties
AI 0, AI 1 • Differential inputs
• Voltage inputs -10 to +10 V or
• Current inputs -20 to +20 mA or 4 to 20 mA
• Hardware input filter: T = 1 ms
• Integrating measuring procedure. Averaging time = 1 ms. The average value determined during
this time is provided in BICO format.
AI 2 • Differential input
• Voltage input -10 to +10 V
• Hardware input filter: T = 1 ms
• Integrating measuring procedure. Averaging time = 1 ms. The average value determined during
this time is provided in BICO format.
AI 3, AI 4, AI 5, AI • Differential inputs
6
• Voltage inputs -10 to +10 V
• Hardware input filter: T = 100 µs
• Sampling measuring procedure. Sampling time = 250 µs. The mean value taken from four sam-
pling values is provided in BICO format.
Function diagrams
SINAMICS DCP
116 Operating Instructions, 06/2014, A5E34382853K
Operation
8.2 Inputs/outputs
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 117
Operation
8.3 Communication, IT security
Note
IT security (industrial security)
In order to ensure the safe operation of your systems, you must take suitable measures, e.g.
industrial security or network segmentation. You can find more information on Industrial
Security on the Internet at:
- (www.siemens.de/industrialsecurity)
SINAMICS DCP
118 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
WARNING
Working on the opened device
Only perform all work when the device is current-free.
Please observe the warning notices in Chapter 1.
PROFIBUS connection
Standard/advanced CUD
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 119
Operation
8.4 Communication via PROFIBUS DP
Bus connector
The cables must be connected using PROFIBUS bus connectors as these contain the
necessary bus terminating resistors.
Matching PROFIBUS bus connector, order no. 6GK1500-0FC10:
SINAMICS DCP
120 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
Note
PROFIBUS for drive technology is standardized and described in the following document:
References: /P5/ PROFIdrive Profile Drive Technology
NOTICE
Destruction of the CAN bus nodes
No CAN cables must be connected to interface X126. If CAN cables are connected, the
CUD and other CAN bus nodes may be destroyed.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 121
Operation
8.4 Communication via PROFIBUS DP
● Master
Masters are categorized into the following classes:
– Master class 1 (DPMC1):
Central automation stations that exchange data with the slaves in cyclic and acyclic
mode. Communication between the masters is also possible.
Examples: SIMATIC S7, SIMOTION
– Master class 2 (DPMC2):
Devices for configuration, commissioning, operator control and monitoring during bus
operation. Devices that only exchange data with the slaves in acyclic mode.
Examples: Programming devices, human machine interfaces
● Slaves
With respect to PROFIBUS, the SINAMICS drive unit is a slave.
SINAMICS DCP
122 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
Note
The sequence of drive objects in HW Config must be the same as that in the drive (p0978).
The telegram structure depends on the drive objects taken into account during configuration.
Configurations are permitted that do not take into account all of the drive objects that are
present in the drive system.
Example:
The following configurations, for example, are possible:
● Configuration with CU_DC, DC_CTRL
● Configuration with DC_CTRL
● And others
Task
The drive system comprises the following drive objects:
SINAMICS DCP with the objects
● CU_DC
● DC_CTRL
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 123
Operation
8.4 Communication via PROFIBUS DP
When you click "Details", the properties of the configured telegram structure are displayed
(e.g. I/O addresses, axis separator).
SINAMICS DCP
124 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 125
Operation
8.4 Communication via PROFIBUS DP
Note
A teleservice adapter can be connected to the PROFIBUS interface (X126) for remote
diagnostics purposes.
SINAMICS DCP
126 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
Figure 8-18 Hardware catalog of the GSD file with direct data exchange functionality
The SINAMICS S DXB GSD file contains among other things standard telegrams, free
telegrams and slave-to-slave telegrams for configuring direct data exchange. With the aid of
these telegram parts and an axis separator, a telegram for the drive unit must be composed
for each drive object.
Processing a GSD file in HW Config is covered in the SIMATIC documentation. Suppliers of
PROFIBUS components can provide their own bus configuration tool. The description of the
respective bus configuration tool is described in the relevant documentation.
Device identification
Identification for individual slaves facilitates diagnostics and provides an overview of the
nodes on the PROFIBUS.
The information for each slave is stored in the following CU-specific parameter:
r0964[0...6] device identification
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 127
Operation
8.4 Communication via PROFIBUS DP
SINAMICS DCP
128 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
Field Value
Network parameter profile DP
Network parameter baud rate Any
Communication partner address PROFIBUS address of the drive unit
Communication partner don’t care, 0
slot/rack
Field Value
Name Any
Controller Any
Type Depending on the addressed parameter value,
e.g.:
INT: for integer 16
DINT: for integer 32
WORD: for unsigned 16
REAL: for float
Range DB
DB Parameter number
(data block number) 1 ... 65535
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 129
Operation
8.4 Communication via PROFIBUS DP
Field Value
DBB, DBW, DBD Drive object no. and subindex
(data block offset) bit 15 ... 10:
Drive object no. 0 ... 63
bit 9 ... 0: Subindex 0 ... 1023
or expressed differently
DBW = 1024 * drive object no. + subindex
Length Not activated
Acquisition cycle Any
Number of elements 1
Decimal places Any
Note
• You can operate a SIMATIC HMI together with a drive unit independently of an existing
controller.
A basic "point-to-point" connection can only be established between two nodes (devices).
• The "variable" HMI functions can be used for drive units. Other functions cannot be used
(e.g. "messages" or "recipes").
• Individual parameter values can be accessed. Entire arrays, descriptions, or texts cannot
be accessed.
SINAMICS DCP
130 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
Note
The additional monitoring time (p2047) is only useful for cyclic communication.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 131
Operation
8.4 Communication via PROFIBUS DP
Figure 8-21 Direct data exchange communication with the publisher-subscriber model
Publisher
With the "direct data exchange" function, at least one slave must act as the publisher.
The publisher is addressed by the master when the output data is transferred with a modified
layer-2 function code (DXB.req). The publisher then sends its input data for the master with a
broadcast telegram to all bus nodes.
SINAMICS DCP
132 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
Subscriber
The subscribers evaluate the broadcast telegrams sent from the publishers, and use the
data which has been received as setpoints. These setpoints of the publisher are used in
addition to the setpoints received from the master, corresponding to the configured telegram
structure (p0922).
Requirements
The following requirements should be observed for the "direct data exchange" function:
● STARTER as of Version 4.2
● Configuration:
– Drive ES Basic, Drive ES SIMATIC or Drive ES PCS7 as of Version 5.3 SP3
– Alternatively using a GSD file
● The maximum number of process data per drive can be identified from the value in r2050
– minus the resources that have already been used
● A maximum of 16 links to publishers
Applications
For example, the following applications can be implemented using the "direct data
exchange" function:
● Specifying binector connections from another slave
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 133
Operation
8.4 Communication via PROFIBUS DP
SINAMICS DCP
134 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
Parameterizing telegram
The filter table is transferred as a dedicated block from the master to the slave with the
parameterizing telegram when a bus communication is established.
Configuration telegram
Using the configuration telegram, a slave knows how many setpoints are to be received from
the master and how many actual values are to be sent to the master.
For direct data exchange, a special space ID is required for each tap. The PROFIBUS
configuration tool (e.g. HW Config) generates this ID. The ID is then transferred with the
ChkCfg to the drive devices that operate as subscribers.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 135
Operation
8.4 Communication via PROFIBUS DP
Settings in HW Config
The project below is used to describe the settings in HW Config.
SINAMICS DCP
136 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
Procedure
1. Select a slave (e.g. SINAMICS DCP) and use its properties to configure the telegram for
the connected drive object.
2. In the "Configuration" tab of the drive unit, select, for example, standard telegram 1 for
the associated drive in the telegram selection.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 137
Operation
8.4 Communication via PROFIBUS DP
SINAMICS DCP
138 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
4. The "Insert slot" button can be used to create a new setpoint slot for the SINAMICS DCP
drive object.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 139
Operation
8.4 Communication via PROFIBUS DP
7. The "I/O address" column displays the start address for every DO. Select the start
address of the DO data to be read. This is 200 in the example. If the complete data of the
publisher is not read, set this via the "Length" column. You may also offset the start
address for the request so that data can be read out in the middle of the DO telegram.
SINAMICS DCP
140 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
8. The "Direct data exchange - Overview" tab shows you the configured direct data
exchange relationships which correspond to the current status of the configuration in HW
Config.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 141
Operation
8.4 Communication via PROFIBUS DP
9. When the direct data exchange link has been created, the standard telegram for the drive
object is replaced with the "User-defined" telegram in the configuration overview.
SINAMICS DCP
142 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
10.The details after the creation of the direct data exchange link for the drive object of the
SINAMICS DCP are as follows:
Figure 8-30 Details after the creation of the direct data exchange link
11.You must adjust the standard telegrams accordingly for every DO (drive object) of the
selected CU that shall actively participate in direct data exchange.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 143
Operation
8.4 Communication via PROFIBUS DP
Commissioning in STARTER
Direct data exchange is configured in HW Config and is simply an extension of an existing
telegram. Telegrams can be extended in STARTER (e.g. p0922 = 999).
In order to terminate the configuration of direct data exchange for the DOs, the telegram data
of the DOs in STARTER must be matched to those in the HW Config and must be extended.
The configuration is made centrally via the configuration of the respective CU.
SINAMICS DCP
144 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
Procedure
1. In the overview for the PROFIBUS telegram, you can access the telegram components of
the drive objects, here DC_CTRL. Select the telegram type "Free telegram configuration"
for the configuration.
2. Enter the telegram lengths for the input data and output data according to the settings in
HW Config. For direct data exchange links, the input data consists of the telegram
component of the master and the direct data exchange data.
3. Then set the telegram component in the telegram selection to the standard telegram for
drive objects (in the example: Standard telegram 1), which results in a split display of the
telegram types (standard telegram + telegram extension). The telegram extension
represents the telegram component of the direct data exchange.
By selecting the item "Communication → PROFIBUS" for the drive object "DC_CTRL" in the
project navigator, you obtain the structure of the PROFIBUS telegram in the receive and
send directions.
The telegram extension from PZD3 onwards is the component for direct data exchange.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 145
Operation
8.4 Communication via PROFIBUS DP
To connect the drive objects to the process data which is received via direct data exchange,
you also need to connect the appropriate connectors to the corresponding signal sinks. A list
for the connector shows all signals that are available for interconnection.
SINAMICS DCP
146 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
Figure 8-34 Linking the PZDs for direct data exchange with external signals
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 147
Operation
8.4 Communication via PROFIBUS DP
Figure 8-35 Hardware catalog of the GSD file with direct data exchange functionality
The SINAMICS S DXB GSD file contains among other things standard telegrams, free
telegrams and slave-to-slave telegrams for configuring direct data exchange. The user must
take these telegram parts and an axis separator after each drive object to compose a
telegram for the drive unit.
Processing a GSD file in HW Config is covered in the SIMATIC documentation. Suppliers of
PROFIBUS components can provide their own bus configuration tool. The description of the
respective bus configuration tool is described in the relevant documentation.
Device identification
Identification for individual slaves facilitates diagnostics and provides an overview of the
nodes on the PROFIBUS.
The information for each slave is stored in the Control Unit parameter r0964[0...6] device
identification.
SINAMICS DCP
148 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
Note
The subscribers do not monitor the existence of an isochronous publisher sign of life.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 149
Operation
8.4 Communication via PROFIBUS DP
SINAMICS DCP
150 Operating Instructions, 06/2014, A5E34382853K
Operation
8.4 Communication via PROFIBUS DP
Messages
The following PROFIBUS error texts can be displayed:
Power electronics faulted
An impermissible operating state of the power electronics was detected (overcurrent,
overtemperature, etc.). Check compliance with the permissible load cycles. Check the
ambient temperatures (fan).
Overtemperature of an electronic component
The temperature in the component has exceeded the highest permissible limit. Check the
ambient temperature / control cabinet ventilation.
Communication to the controller faulted
The communication to the higher-level controller (internal coupling, PROFIBUS, PROFINET,
etc.) is faulted or interrupted. Check the state of the higher-level controller. Check the
communication connection/wiring. Check the bus configuration/cycles.
Internal communication faulted
The internal communication between the SINAMICS components is faulted or interrupted.
Check the DRIVE-CLiQ wiring. Ensure an EMC-compliant installation. Observe the
maximum permissible quantity structures / cycles.
External signal state error
A measured value / signal state read-in via the input area (digital/analog/temperature) has
assumed an impermissible value/state. Identify and check the relevant signal. Check the set
thresholds.
Error in the parameterization / commissioning
An error was identified in the parameterization or in a commissioning procedure, or the
parameterization does not match the actual device configuration. Determine the exact cause
of the error with the commissioning tool, adapt the parameterization or device configuration.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 151
Operation
8.5 Communication via PROFINET IO
Description
The following options are available for online operation via PROFINET IO:
● Online operation via IP
Requirements
● STARTER with Version ≥ 4.1.5 (SINAMICS DCP is only supported as of STARTER
Version 4.1.5)
● CBE20
SINAMICS DCP
152 Operating Instructions, 06/2014, A5E34382853K
Operation
8.5 Communication via PROFINET IO
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 153
Operation
8.5 Communication via PROFINET IO
Settings in STARTER
The following settings are required in STARTER for communication via PROFINET:
● Options → Set PG/PC interface...
Assigning the IP address and name for the PROFINET interface of the drive unit
Use STARTER to assign an IP address and a name to the PROFINET interface (e.g.
CBE20).
Requirement:
● Connect a direct Ethernet cable from the PG/PC to the PROFINET interface of the
Control Unit (CUD).
● Switch on the Control Unit (CUD).
The accessible nodes must be sought in STARTER:
● Project → Accessible nodes
SINAMICS DCP
154 Operating Instructions, 06/2014, A5E34382853K
Operation
8.5 Communication via PROFINET IO
The selected node is edited by right-clicking the field for the node and selecting the option
"Edit Ethernet node...".
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 155
Operation
8.5 Communication via PROFINET IO
In the dialog screen that appears next, enter a freely selectable device name, the IP address
and the subnet mask.
The subnet masks must match before STARTER can be operated.
SINAMICS DCP
156 Operating Instructions, 06/2014, A5E34382853K
Operation
8.5 Communication via PROFINET IO
After selecting the "Assign name" button, the following confirmation will appear if the
assignment was successful: In certain cases, a RAM to ROM is executed in the drive and
you must wait until it has been completed.
After selecting the "Assign IP configuration" button, the following confirmation will appear if
the assignment was successful: In certain cases, a RAM to ROM is executed in the drive
and you must wait until it has been completed.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 157
Operation
8.5 Communication via PROFINET IO
Once the "Edit Ethernet Node" dialog screen has closed and the node overview has been
updated (F5), a display indicates that the node properties have been successfully assigned.
Note
The IP addresses allocated for the PC and the PROFINET interface in the drive must be
different; otherwise communication between the PC and drive is not possible.
SINAMICS DCP
158 Operating Instructions, 06/2014, A5E34382853K
Operation
8.5 Communication via PROFINET IO
General information
PROFINET IO is an open Industrial Ethernet standard for a wide range of production and
process automation applications. PROFINET IO is based on Industrial Ethernet and
observes TCP/IP and IT standards.
Signal processing in real time and determinism is important in industrial networks.
PROFINET IO satisfies these requirements.
The following standards ensure open, multi-vendor systems:
● International standard IEC 61158
PROFINET IO is optimized for high-speed, time-critical data communication at field level.
PROFINET IO
Within the context of Totally Integrated Automation (TIA), PROFINET is the systematic
development of the following systems:
● PROFIBUS DP, the established fieldbus,
and
● Industrial Ethernet, the communication bus for the cell level
Experiences from both systems have been and are being integrated in PROFINET. As an
Ethernet-based automation standard defined by PROFIBUS International (PROFIBUS user
organization), PROFINET IO is a non-proprietary communication and engineering model.
PROFINET IO defines every aspect of the data exchange between IO controllers (devices
with so-called "master functionality") and the IO devices (those with so-called "slave
functionality") as well as parameter assignment and diagnostic processes. An IO system is
configured by virtually the same method used for PROFIBUS.
A PROFINET IO system is made up of the following devices:
● The IO controller controls automation tasks.
● An IO device is controlled and monitored by an IO controller. An IO device consists of
several modules and submodules.
● IO supervisor is an engineering tool typically based on a PC that is used to parameterize
and diagnose individual IO devices (drive units).
When a CBE20 Communication Board is inserted, SINAMICS DCP becomes an IO device in
terms of PROFINET. SINAMICS DCP and CBE20 can be used for communication via
PROFINET IO with RT.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 159
Operation
8.5 Communication via PROFINET IO
Cycle communication using PROFINET IO with IRT or using RT is possible on all drive units
equipped with a PROFINET interface. This means that problem-free communication using
other standard protocols is guaranteed within the same network.
Note
PROFINET for drive technology is standardized and described in the following document:
PROFIBUS Profile PROFIdrive – Profile Drive Technology
Version V4.1, May 2006,
PROFIBUS User Organization e. V.
Haid-und-Neu-Strasse 7
D-76131 Karlsruhe
- (www.profibus.com)
Order no. 3.172, spec. Chapter 6
• IEC 61800-7
NOTICE
Inserting the CBE20 Communication Board deactivates the cyclic PZD channel for
PROFIBUS DP.
Real-time communication
When communication takes place via TCP/IP, the resulting transmission times may be too
long and non-deterministic to meet production automation requirements. When
communicating time-critical IO user data, PROFINET IO therefore uses its own real-time
channel, rather than TCP/IP.
Determinism
Determinism means that a system will react in a predictable ("deterministic") manner.
With PROFINET IO, it is possible to precisely determine (predict) transmission times.
SINAMICS DCP
160 Operating Instructions, 06/2014, A5E34382853K
Operation
8.5 Communication via PROFINET IO
8.5.2.2 Addresses
MAC address
Every Ethernet and PROFINET interface is assigned a worldwide unique device identifier in
the factory. This 6-byte long device identifier is the MAC address. The MAC address is
divided up as follows:
● Three bytes for the manufacturer's ID
● Three bytes for the device identifier (consecutive number)
The MAC address is on a label (CBE20), e.g. 08-00-06-6B-80-C0
IP address
The TCP/IP protocol is a prerequisite for establishing a connection and for parameter
assignment. To allow a PROFINET device to be addressed as a node on Industrial Ethernet,
this device requires a unique IP address in the network. The IP address is made up of four
decimal numbers with a range of values from 0 through 255. The decimal numbers are
separated by a period. The IP address comprises:
● The address of the node (also called host or network node)
● The address of the (sub) network
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 161
Operation
8.5 Communication via PROFINET IO
IP address assignment
The IP addresses of IO devices can be assigned by the IO controller and always have the
same subnet screen as the IO controller. In this case, the IP address is not stored
permanently. The IP address entry is lost after POWER ON/OFF. The IP address can be
assigned retentively via the STARTER function "Accessible nodes".
This function can also be performed with HW Config of STEP 7. The function is called "Edit
Ethernet node" here.
Note
If the network is part of an existing Ethernet company network, obtain the information (IP
address) from your network administrator.
Note
The device name must be stored retentively using either STARTER, the Primary Setup Tool
(PST) or with HW Config of STEP 7.
Note
You can enter the address data for the ports of the optional CBE20 module in STARTER in
the expert list using parameters p8940, p8941, p8942 and p8943.
SINAMICS DCP
162 Operating Instructions, 06/2014, A5E34382853K
Operation
8.5 Communication via PROFINET IO
Properties
The PROFINET interface on a drive unit supports the simultaneous operation of:
● IRT – isochronous real-time Ethernet
● RT – real-time Ethernet
● Standard Ethernet services (TCP/IP, LLDP, UDP and DCP)
Note
The sequence of drive objects in HW Config must be the same as that in the drive (p0978).
The telegram structure depends on the drive objects taken into account during configuration.
Configurations are permitted that do not take into account all of the drive objects that are
present in the drive system.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 163
Operation
8.5 Communication via PROFINET IO
Example:
The following configurations, for example, are possible:
● Configuration with CU_DC, DC_CTRL
● Configuration with DC_CTRL, and others
SINAMICS DCP
164 Operating Instructions, 06/2014, A5E34382853K
Operation
8.5 Communication via PROFINET IO
PROFINET interfaces
The CBE20 option module can be inserted in the option slot of a CUD. The CBE20 is a
PROFINET switch with four ports.
Note
Ring topology
When connecting the ports, it must be ensured that for standard applications a ring topology
is not created. Additional information on ring topologies can be found in Chapter Media
redundancy (Page 167).
References
● The integration of a SINAMICS Control Unit in a PROFINET IO system is described in
detail in "SIMOTION SCOUT Communication" System Manual.
● For an example of how to link a Control Unit to a SIMATIC S7 via PROFINET IO, please
refer to the "PROFINET IO communication between an S7-CPU and SINAMICS S120"
FAQ on the Internet.
● For a description of the CBE20 and how you can use it in the drive, see Chapter Option
Board: Communication Board Ethernet CBE20 (Page 46).
Telegrams
PROFIdrive telegrams are available for implementing cyclic communication via PROFINET
IO (see Chapter Media redundancy (Page 167)).
DCP flashing
This function is used to check the correct assignment to a module and its interfaces.
1. In HW Config or the STEP 7 Manager, select the menu item "Target system" > Ethernet >
Edit Ethernet node".
The "Edit Ethernet Node" dialog box opens.
2. Click the "Browse" button.
The "Browse Network" dialog box opens and displays the connected nodes.
3. Select the CUD with inserted CBE20 as node.
The "DCP flashing" function is then activated via the "Flash" button.
The "DCP flashing" function is activated on the RDY LED (READY LED 2 Hz, green/orange
or red/orange) on the CUD.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 165
Operation
8.5 Communication via PROFINET IO
The LED will continue to flash as long as the dialog is open. When the dialog is closed, the
LED will go out automatically. The function is available as of STEP 7 V5.3 SP1 via Ethernet.
Note
SINAMICS does not support routing from PROFIBUS to PROFINET and vice versa.
Note
If a CBE20 module fails (e.g. due to a power failure), then communication with the
subsequent nodes is interrupted at this point.
SINAMICS DCP
166 Operating Instructions, 06/2014, A5E34382853K
Operation
8.5 Communication via PROFINET IO
RT
RT communication is based on standard Ethernet. The data is transferred via prioritized
Ethernet telegrams. Because standard Ethernet does not support any synchronization
mechanisms, isochronous operation is not possible with PROFINET IO with RT!
The real update cycle in which cyclic data is exchanged depends on the bus load, the
devices used and the quantity framework of the I/O data. The update cycle is a multiple of
the send cycle.
IRT
Two options are available with this RT class:
● IRT "high flexibility"
● IRT "high performance"
Is not supported by SINAMICS DCP.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 167
Operation
8.5 Communication via PROFINET IO
Note
For further information about configuring the PROFINET interface for the I/O controller and
I/O device, please refer to the following document: SIMOTION SCOUT Communication
System Manual.
Note
IRT "high performance" is not supported by SINAMICS DCP
The IRT "high performance" real-time class is supported by the drives of the SINAMICS
S110 and S120 series and is described here for reasons of completeness.
In addition to the bandwidth reservation, the telegram traffic can be further optimized by
configuring the topology. This enhances the performance during data exchange and the
deterministic behavior. The IRT time interval can thus be further optimized or minimized with
respect to IRT "high flexibility".
In addition to the isochronous data transfer provided by IRT, even the application itself
(position control cycle, IPO cycle) can be isochronous in the devices. This is an essential
requirement for closed-loop axis control and synchronization via the bus. Isochronous data
transfer with cycle times well below one millisecond and with a deviation in the cycle start
(jitter) of less than a microsecond provide sufficient performance reserves for demanding
motion control applications.
The RT classes IRT "high flexibility" and IRT "high performance" can be selected as options
in the synchronization settings configuration area of HW Config. In the description below,
both these classes are simply referred to as "IRT".
In contrast to standard Ethernet and PROFINET IO with RT, the telegrams for PROFINET IO
with IRT are transferred according to a schedule.
SINAMICS DCP
168 Operating Instructions, 06/2014, A5E34382853K
Operation
8.5 Communication via PROFINET IO
Modules
The following S110/S120 modules support the IRT "high performance":
● S120 CU320 together with the CBE20
● S120 CU320-2 DP together with the CBE20
● S120 CU320-2 PN
● S120 CU310 PN
● S120 CU310-2 PN
● S110 CU305 PN
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 169
Operation
8.5 Communication via PROFINET IO
Note
The "high performance" option must not be selected for SINAMICS DCP (an error
message is issued).
Synchronization domain
The sum of all devices to be synchronized form a synchronization domain. The whole
domain must be set to a single, specific RT class (real-time class) for synchronization.
Different synchronization domains can communicate with one another via RT.
For IRT, all IO devices and IO controllers must be synchronized with a common
synchronization master.
RT allows an IO controller to communicate with a drive unit outside a synchronization
domain or "through" another synchronization domain. As of Version 5.4 SP1, STEP 7
supports multiple synchronization domains on a single Ethernet subnet.
Example:
● Synchronization domain IRT: SIMOTION2 with SINAMICS
● SINAMICS, which is assigned to the IO system of SIMOTION1, is arranged in the
topology in such a way that its RT communication must be established through the IRT
synchronization domain.
SINAMICS DCP
170 Operating Instructions, 06/2014, A5E34382853K
Operation
8.5 Communication via PROFINET IO
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 171
Operation
8.5 Communication via PROFINET IO
Furthermore, the send cycles which can actually be set are determined by the intersection of
the send cycles supported by all the devices in the synchronization domain.
The reduction ratio between the update cycle of an IO device and the send cycle is set in the
"Properties" of the PROFINET interface for the relevant device.
Note
There is no intersection between the send cycles for the "even" and "odd" ranges!
Topology rules
SINAMICS DCP
172 Operating Instructions, 06/2014, A5E34382853K
Operation
8.5 Communication via PROFINET IO
Hardware catalog:
The drive unit from the appropriate device family entry in the hardware catalog must be
configured.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 173
Operation
8.5 Communication via PROFINET IO
See Chapter Ordering information for options and accessories (Page 27) for ordering data of
the memory card.
Alternatively, the GSDML file can be requested from the Customer Support.
The telegrams in subslots 2, 3 and 4 can be freely configured, i.e. they can also remain empty.
UFW file and folder on the memory card Functionality (p8835) Pointer file content
/SIEMENS/SINAMICS/CODE/CB/CBE20_1.UFW PROFINET device 1
/SIEMENS/SINAMICS/CODE/CB/CBE20_3.UFW SINAMICS Link 3
/OEM/SINAMICS/CODE/CB/CBE20.UFW Customized 99
SINAMICS DCP
174 Operating Instructions, 06/2014, A5E34382853K
Operation
8.5 Communication via PROFINET IO
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 175
Operation
8.5 Communication via PROFINET IO
SINAMICS DCP
176 Operating Instructions, 06/2014, A5E34382853K
Operation
8.5 Communication via PROFINET IO
Messages
The following PROFIdrive error texts are displayed during forwarding via the PROFINET
diagnostics channel:
Hardware/software fault
A hardware or software malfunction was detected. Carry out a POWER ON for the relevant
component. If it occurs again, contact the hotline.
Supply voltage fault
An electronic power supply fault (48 V, 24 V, 5 V, etc.) was detected. Check the wiring.
Check the voltage level.
Power electronics faulted
An impermissible operating state of the power electronics was detected (overcurrent,
overtemperature, etc.). Check compliance with the permissible load cycles. Check the
ambient temperatures (fan).
Overtemperature of an electronic component
The temperature in the component has exceeded the highest permissible limit. Check the
ambient temperature / control cabinet ventilation.
Communication to the higher-level controller faulted
The communication to the higher-level controller (internal coupling, PROFIBUS, PROFINET,
etc.) is faulted or interrupted. Check the state of the higher-level controller. Check the
communication connection/wiring. Check the bus configuration/cycles.
Internal (DRIVE-CLiQ) communication faulted
The internal communication between the SINAMICS components is faulted or interrupted.
Check the DRIVE-CLiQ wiring. Ensure an EMC-compliant installation. Observe the
maximum permissible quantity structures / cycles.
External measured value / signal state outside of the permissible range
A measured value / signal state read-in via the input area (digital/analog/temperature) has
assumed an impermissible value/state. Identify and check the relevant signal. Check the set
thresholds.
Fault in the parameterization/configuration/commissioning procedure
An error was identified in the parameterization or in a commissioning procedure, or the
parameterization does not match the actual device configuration. Determine the exact cause
of the error with the commissioning tool, adapt the parameterization or device configuration.
General drive fault
Group fault, determine the exact cause of the fault with the commissioning tool.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 177
Operation
8.6 Switch on, switch off, enable
SINAMICS DCP
178 Operating Instructions, 06/2014, A5E34382853K
Operation
8.6 Switch on, switch off, enable
Note
The "Quick stop" command only needs to be present as a short pulse (> 10 ms). It is then
saved internally. It is only possible to reset the memory by applying the "Switch off"
command.
Procedure for specifying the operation enable (if a switch-on command is present):
1. The controllers are enabled.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 179
Operation
8.7 Closed-loop control
Setpoint specification
See function diagram 6805 in the SINAMICS DCP List Manual.
The SINAMICS DCP requires a setpoint that can be specified via fieldbus.
This setpoint can be the:
● Current setpoint
● Power setpoint
The setpoint must be specified as a signed relative value (percentage of the rated current or
rated power):
● Positive setpoint means current flow from side 1 (DC link) to side 2 (battery)
● Negative setpoint means current flow from side 2 (battery) to side 1 (DC link)
The setpoint is used to limit the steepness via a settable ramp.
(p55055, factory setting: 0 ... 100% in 50 ms).
Setpoints below a parameterizable threshold (p55056) are considered to be zero.
The specified setpoint is always converted to a choke current setpoint which is used for
control.
SINAMICS DCP
180 Operating Instructions, 06/2014, A5E34382853K
Operation
8.7 Closed-loop control
All limits depend on the installation altitude and the measured supply air temperature. See
Chapter Derating (Page 187).
Note
The overvoltage range is required for SINAMICS DCP applications in photovoltaic
installations, for the so-called "flying restart" of a PV array. This means, if the PV array under
no-load (and therefore has a higher voltage) is to be loaded. The load immediately reduces
the voltage of the PV array and thus the departure from the overvoltage range.
Note that after every operation in the overvoltage range, a waiting time of 5 minutes must be
observed before the SINAMICS DCP can be operated in the overvoltage range again. This
means that if the "flying restart" attempt fails, you must wait 5 minutes before another
attempt can be made.
Voltage limitation
See function diagram 6812 in the SINAMICS DCP List Manual.
The SINAMICS DCP provides limitation functions for the protection of the battery and DC
link.
The limitation cases are:
● Protection of the battery against overcharging
● Protection of the battery against overdischarging
● DC-link overvoltage
● DC-link undervoltage
A voltage limitation pair can be parameterized for each of these four limitation cases.
● Voltage value for the start of the limitation (current reduction) and
● Final voltage (at which current = 0 is reached)
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 181
Operation
8.7 Closed-loop control
Pulse-width modulation
See function diagram 6830 in the SINAMICS DCP List Manual.
The pulse-width modulation generates the control signals for the IGBT of the power unit. It
also controls the switchover of the current direction.
The switchover from loading (100% power) to regeneration (100% power) and vice versa, is
possible within a parameterizable time window (see p55065).
SINAMICS DCP
182 Operating Instructions, 06/2014, A5E34382853K
Operation
8.8 Precharging of the DC links
NOTICE
Current peaks
Direct connection (without precharging) to the DC link or the battery causes high current
peaks and can destroy the device.
The precharging is controlled by the device. It is assumed that the appropriate switchgear
and precharging resistances are present in the system (not part of the scope of delivery),
and connected according to Figure 6-3 Block diagram (Page 36).
The parameters to be set can be seen in function diagram 6835 and are described in the
parameter list in the List Manual.
There are two types of precharging:
● Resistance precharging
● Precharging through "step-up"
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 183
Operation
8.8 Precharging of the DC links
2. Resistance precharging on the output side (= side 2, = battery side), step-up on the input
side
– The precharging contactor on the output side is closed.
– When the waiting time p55355[1] expires, the line contactor on the output side is
closed. The output capacitance of the SINAMICS DCP should have been charged up
to the battery voltage before this time expires.
– There is a waiting period until the line contactor is closed (waiting time: p55356[1]).
– The precharging contactor on the output side is opened.
– The SINAMICS DCP steps up the input to the DC-link voltage (which is specified via
fieldbus).
– When the waiting time p55355[0] expires, the line contactor on the input side is
closed. The input capacitance of the SINAMICS DCP should have been charged up to
the DC-link voltage before this time expires.
Note
The step-up of the input capacitance takes significantly longer than the resistance
precharging. Therefore, the setting p55355[0] >= 2000 ms is recommended in this
case.
3. Resistance precharging on the input side (= side 1, = DC-link side), step-up on the output
side
– The precharging contactor on the input side is closed.
– When the waiting time p55355[0] expires, the line contactor on the input side is
closed. The input capacitance of the SINAMICS DCP should have been charged up to
the DC-link voltage before this time expires.
– There is a waiting period until the line contactor is closed (waiting time: p55356[0]).
SINAMICS DCP
184 Operating Instructions, 06/2014, A5E34382853K
Operation
8.8 Precharging of the DC links
Note
The step-up of the output capacitance takes significantly longer than the resistance
precharging. Therefore, the setting p55355[1] >= 2000 ms is recommended in this
case.
– There is a waiting period until the line contactor is closed (waiting time: p55356[1]).
To ensure successful connection, the received DC-link voltage or the battery voltage must
have an accuracy of 25 V or a tolerance of 2.5%.
Note
To reduce the current peaks and to ensure the connection, resistance precharging on both
sides is recommended.
Note
If "Precharging through step-up" is used in one of the two precharging circuits, then the
precharging relay and the precharging resistors can be omitted on this side.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 185
Operation
8.9 Operating hours counter, device fan
SINAMICS DCP
186 Operating Instructions, 06/2014, A5E34382853K
Operation
8.10 Derating
8.10 Derating
Depending on the ambient temperature and the installation altitude, the rated current, rated
power and overvoltage range must be reduced.
This reduction is called "derating".
The derating effects the current limitation and the power limitation (see function diagram
6810).
Rated current
At installation altitudes above 2000 m, the rated current is reduced by 7.5% / 1000 m.
At air supply temperatures of 40° C to 55° C, the rated current is reduced linearly to 60%.
At air supply temperatures above 55° C, the device is shut down with an alarm message.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 187
Operation
8.11 Runtime (operating hours counter)
Note
Faults and alarms are stamped with this system runtime.
SINAMICS DCP
188 Operating Instructions, 06/2014, A5E34382853K
Operation
8.12 Diagnostics
8.12 Diagnostics
The individual states during ramp-up are indicated by means of the LEDs on the CUD.
● The duration of the individual states varies.
● If an error occurs, the ramp-up procedure is aborted and the cause of the error is
indicated via the LEDs.
Remedy: Insert the appropriate memory card with the correct software and parameters.
● Once the device has successfully ramped up, all the LEDs are switched off briefly.
● Once the device has ramped up, the LEDs are controlled via the loaded software.
The description of the LEDs after ramp-up applies.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 189
Operation
8.12 Diagnostics
Note
The LEDs can only be seen when the front cover of the SINAMICS DCP is opened.
LED Meaning
RDY DP1 OPT MOD
Red Off Off Off Software being updated.
Red Red Off Off Software on the memory card is incomplete or defective.
2 Hz The software was not successfully updated. The CRC of the pro-
grammed firmware is incorrect.
Red Red Off Off Software was successfully updated. The electronic power supply
0.5 Hz 0.5 Hz must be switched off and back on again.
Red Red Off Off The software on the memory card does not belong to SINAMICS
2 Hz 2 Hz DCP.
Software version and hardware version of the CUD are not com-
patible. For information on the hardware/software compatibility,
see Chapter Upgrading the device software (Page 211).
Orange x x Off DRIVE-CLiQ component is being updated.
0.5 Hz
Orange x x Off DRIVE-CLiQ component has been updated.
2 Hz
Table 8- 18 Ramp-up
SINAMICS DCP
190 Operating Instructions, 06/2014, A5E34382853K
Operation
8.12 Diagnostics
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 191
Operation
8.12 Diagnostics
SINAMICS DCP
192 Operating Instructions, 06/2014, A5E34382853K
Operation
8.12 Diagnostics
Description
The faults and states detected by the individual components of the drive unit are indicated by
messages.
The messages are categorized into faults and alarms.
Note
The individual faults and alarms are described in Chapter "Faults and alarms" in the
SINAMICS DCP List Manual. Here you can also find a section titled "Function diagrams" →
"Faults and alarms", which contains function diagrams for the fault buffer, alarm buffer, fault
trigger, and fault configuration.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 193
Operation
8.12 Diagnostics
SINAMICS DCP
194 Operating Instructions, 06/2014, A5E34382853K
Operation
8.12 Diagnostics
Acknowledging faults
The list of faults and alarms specifies how each fault is acknowledged after the cause has
been remedied.
1. Acknowledgment of faults with "POWER ON"
– Switch the drive unit on/off (POWER ON).
2. Acknowledgment of faults with "IMMEDIATE"
– Via PROFIBUS control signal
STW1.7 (reset fault memory): 0/1 edge
Set STW1.0 (ON/OFF1) = "0" and "1"
– Via external input signal
Binector input and interconnection with digital input
p2103 = "Requested signal source"
p2104 = "Requested signal source"
p2105 = "Requested signal source"
Across all of the drive objects (DO) of a Control Unit
p2102 = "Requested signal source"
3. Acknowledgment of faults with "PULSE INHIBIT"
– The fault can only be acknowledged with a pulse inhibit (r0899.11 = 0).
– The same options are available for acknowledging as described under
acknowledgment with IMMEDIATE.
Note
The SINAMICS DCP cannot resume operation until all active faults have been
acknowledged.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 195
Operation
8.12 Diagnostics
Note
A fault buffer and an alarm buffer are provided for each drive object. The specific messages
are entered in these buffers for this object.
The contents of the fault buffer are saved to the non-volatile memory when the Control Unit
is powered down, i.e. the fault buffer history is still available when the device is powered up
again.
Note
The entry in the fault/alarm buffer is made after a delay. For this reason, the fault/alarm
buffer should not be read until a change in the buffer is also recognized (r0944, r2121) after
"Fault active"/"Alarm active" is output.
SINAMICS DCP
196 Operating Instructions, 06/2014, A5E34382853K
Operation
8.12 Diagnostics
Fault buffer
Faults which occur are entered in the fault buffer as follows:
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 197
Operation
8.12 Diagnostics
SINAMICS DCP
198 Operating Instructions, 06/2014, A5E34382853K
Operation
8.12 Diagnostics
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 199
Operation
8.12 Diagnostics
Note
Only those messages which are listed in the indexed parameters can be changed as
desired. All other messages retain their factory settings or are reset to the factory settings.
Examples:
• In the case of messages listed via p2128[0...19], the message type can be changed. The
factory setting is set for all other messages.
• The fault response of fault F12345 has been changed via p2100[n]. The factory settings
are to be restored.
– p2100[n] = 0
Note
The value from CO: r2129 can be used as a group trigger.
CO: r2129 = 0 No selected message has been output.
CO: r2129 > 0 Group trigger.
At least one selected message has been output.
The individual binector outputs BO: r2129 should be investigated.
SINAMICS DCP
200 Operating Instructions, 06/2014, A5E34382853K
Operation
8.12 Diagnostics
Note
An external fault or alarm is triggered by a 1/0 signal.
An external fault and alarm do not usually mean that an internal message has been
generated. The cause of an external fault and alarm should therefore be corrected outside
the SINAMICS DCP.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 201
Operation
8.12 Diagnostics
SINAMICS DCP
202 Operating Instructions, 06/2014, A5E34382853K
Operation
8.13 Drive Control Chart (DCC) for SINAMICS DCP
General information
The DCC technology option (Drive Control Chart) is available for complex applications. With
DCC, a function diagram can be graphically created, which comprises elementary function
blocks (DCBs, Drive Control Blocks) that are connected with each other, and which can then
be loaded to the SINAMICS DCP.
The following steps are required to implement an executable DCC chart with the SINAMICS
DCP:
1. Installation of STARTER and a DCC license on the PC
– STARTER V4.4 is available on the product DVD of the SINAMICS DCP.
– The DCC license can be ordered as follows:
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 203
Operation
8.13 Drive Control Chart (DCC) for SINAMICS DCP
Note
Only version V4.60.07.00 enables DCC on the SINAMICS DCP, but not all other versions
(e.g. V4.60.06.00 or V4.70.07.00).
5. Compile the DCC chart on the PC and load it to the SINAMICS DCP
– Compile via the shortcut menu of the DCC chart:
Accept and compile
– Load the SINAMICS DCP via the STARTER menu:
Project > Download to target system
Note
If in the menu"Options > Settings…" the checkbox "Compile all programs before
loading" is activated under the "Download" heading, the manual "Accept and compile"
can be omitted.
Ramp-up time
If DCC is installed in the SINAMICS DCP, the ramp-up time increases by approx. 10 s.
SINAMICS DCP
204 Operating Instructions, 06/2014, A5E34382853K
Operation
8.13 Drive Control Chart (DCC) for SINAMICS DCP
● The actual CPU time load of the CUD can be read out on r9976.
● To make own calculations, the above-illustrated CPU time loads can be taken as "linear".
This means that:
– Half as many blocks in the same time slice generate half as much CPU time load, etc.
– The same number of blocks in a half as fast time slice generate half as much CPU
time load, etc.
The final limits are determined by the total memory available on the CUD. If the above-
mentioned maximum limits are exceeded, this can result in errors during upload or download
(e.g. fault F1105: CU memory insufficient) and the SINAMICS DCP can no longer be
switched on; a Power OFF/ON must be performed.
Note
In most cases, the CPU time load of the CUD is the limiting factor, not the memory load.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 205
Operation
8.13 Drive Control Chart (DCC) for SINAMICS DCP
If the checkbox is activated, the DCC library in the project is overwritten by that in the target
device.
SINAMICS DCP
206 Operating Instructions, 06/2014, A5E34382853K
Operation
8.13 Drive Control Chart (DCC) for SINAMICS DCP
Miscellaneous
● Free function blocks and a DCC chart can be used at the same time.
● If you load a DCC chart to the SINAMICS DCP, although the technology package
TPdcblib_SINAMICS_4_6.3.0 is not available in the SINAMICS DCP, then it signals an
error. To correct this error, proceed as follows:
– Install the technology package TPdcblib_SINAMICS_4_6.3.0 as described above.
– Then carry out a POWER OFF/ON.
– Load the STARTER project together with the DCC chart to the SINAMICS DCP.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 207
Operation
8.13 Drive Control Chart (DCC) for SINAMICS DCP
SINAMICS DCP
208 Operating Instructions, 06/2014, A5E34382853K
Servicing 9
SINAMICS DCP devices should only be serviced by personnel from the manufacturer or by
Siemens personnel trained by the manufacturer.
DANGER
Capacitor discharge / dangerous voltages
Once the line voltage has been disconnected, voltages that could result in death or serious
injury are still present in the SINAMICS DCP.
After you have switched off the power supply, observe the discharge time of the DC-link
capacitors of 1 minute before you perform any maintenance work or repair work and do not
touch the device during this period.
Measure the voltage at the DC-link capacitors once the discharge time has elapsed.
The SINAMICS DCP must be provided with extensive protection measures against
contamination in order to prevent voltage flashovers and damage. Dust and foreign bodies,
which are brought in by the cooling-air flow in particular, must be thoroughly removed at
certain intervals; this depends on the rate of accumulation of dirt, but should be carried out at
least every 12 months. The device must be blown out with dry compressed air at a maximum
of 1 bar, or cleaned using a vacuum cleaner.
The screw connections (also the protective conductor connections) must be retightened
each time that maintenance work is carried out on a SINAMICS DCP.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 209
Servicing
9.1 Upgrading software releases
Basics
The following steps are necessary:
Note
A memory card is required for the software update (see Chapter Ordering information for
options and accessories (Page 27)).
In this case, under certain circumstances, STARTER cannot assign the project to the correct
device version. If the STARTER project is not available, generate a new project with the old
device version (load to the PG before the software update) and then proceed as normal.
SINAMICS DCP
210 Operating Instructions, 06/2014, A5E34382853K
Servicing
9.1 Upgrading software releases
Note
Only memory cards which have been prepared for these systems by Siemens will be
accepted.
If the memory card is formatted, formatting must be performed with the FAT16 setting.
To download the latest software version, see Preface (Page 5).
Procedure
● Unzip the *.zip file to an empty memory card.
● Insert the card in the SINAMICS DCP, which has been switched-off, and switch the
device on again. The firmware is updated. The update has been completed if the RDY-
LED and the DP1-LED flash at 0.5 Hz (the update takes about 12 minutes).
● Carry out a POWER OFF. Remove the memory card from the SINAMICS DCP.
NOTICE
If the memory card is not removed from the SINAMICS DCP before the POWER ON, the
parameterization in the SINAMICS DCP is copied to the memory card during ramp-up, or a
parameterization already on the card copied to the SINAMICS DCP.
For a detailed description of this function, see Chapter Memory card functions (Page 95),
Section "Copying parameter data sets from non-volatile memory to the memory card".
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 211
Servicing
9.1 Upgrading software releases
Note
Electronic power supply must not be interrupted during the update, otherwise the update will
need to be restarted.
Note
To safely remove the memory card, see Chapter Memory card functions (Page 95)
Note
STARTER does not support a "downgrade" of the software version (e.g. V1.2 to V1.1).
SINAMICS DCP
212 Operating Instructions, 06/2014, A5E34382853K
Servicing
9.2 Replacing the fans
WARNING
Qualified personnel
Fans must only be replaced by qualified personnel.
The DC-link capacitors continue to carry dangerous voltage levels following disconnection.
For this reason, the device should not be opened until a reasonable period of time has
elapsed.
Failure to observe this warning information can result in death, serious injury, or extensive
material damage.
The recommendation to replace the fans is indicated by the alarm in Chapter Operating
hours counter, device fan (Page 186).
The individual fans cannot be replaced. The entire fan unit (contains four fans) must always
be replaced.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 213
Servicing
9.2 Replacing the fans
SINAMICS DCP
214 Operating Instructions, 06/2014, A5E34382853K
Spare parts 10
● The following spare part is available for the SINAMICS DCP:
– Fan unit 6RY1801-5AA00
● You can find information on spare parts
– Via the electronic spare parts catalog Spares On Web, after entering the serial
number and order number of your SINAMICS DCP in the Internet (registration
required).
Spares On Web (http://workplace.automation.siemens.de/sparesonweb)
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 215
Spare parts
SINAMICS DCP
216 Operating Instructions, 06/2014, A5E34382853K
Disposal 11
11.1 Environmental compatibility
Environmental aspects during development
The use of highly-integrated components has enabled the number of parts to be kept to a
minimum, with energy being used as efficiently as possible during production as a result.
Particular emphasis has been placed on ensuring that the metal and plastic parts have a low
volume and low weight, and that the number of different types is kept to a minimum.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 217
Disposal
11.1 Environmental compatibility
SINAMICS DCP
218 Operating Instructions, 06/2014, A5E34382853K
Service and Support A
Service
You can find information on our services and regional contact persons on the
Internet (www.siemens.de/automation/csi_de/service)
Service calls
Qualified personnel can perform repair work on your devices and offer services that ensure
their availability. This work can be carried out with charges that are scaled according to the
amount of time and work involved, or at a flat rate as part of a contract. Services whose
charges depend on the amount of time and work involved are performed within the normal
working hours for the region and with an appropriate response time.
You can get in touch with your regional contact if you wish to have any services carried out.
Note
We would be grateful if you could specify the following device data when you have any
queries:
• Device order number and serial number
• Software version
• Hardware version of the electronics module CUD (printed on the component side)
• Hardware version and software version of additional modules (if used)
Technical Support
Our technical support can provide you with technical assistance for products, systems, and
solutions:
German (www.siemens.de/automation/support-request)
English (www.siemens.com/automation/support-request)
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 219
Service and Support
European and African time Phone: +49 911 895 7222 8:00 to 17:00 CET
zone Fax: +49 911 895 7223
E-mail (mailto:support.automation@siemens.com)
America time zone 24-hour hotline: +1 800 333 7421
Phone: +1 423 262 2960 8:00 to 17:00
Fax: +1 423 262 2200 Eastern Standard Time
E-mail
(mailto:support.america.automation@siemens.com)
Asia/Australia time zone Phone: +86 1064 757575 7:30 to 17:30
Fax: +86 1064 747474 Beijing local time
E-mail (mailto:support.asia.automation@siemens.com)
Repairs
If you wish to have a part or device repaired, please get in touch with your regional contact
for repairs.
SINAMICS DCP
220 Operating Instructions, 06/2014, A5E34382853K
Technical data B
B.1 Ambient conditions
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 221
Technical data
B.1 Ambient conditions
Additional properties
The input side (side 1, terminals P1/N1) of the device is connected to a DC link in a normal
application.
● The following applies for product version (Functional State) 01:
The DC link must be grounded.
● The following applies as of product version (Functional State) 02:
The DC link does not need to be grounded.
● The device input side must be connected (precharging circuit, fuse) as described in
Chapter EMC-compliant installation of SINAMICS DCP (installation instructions)
(Page 34).
The output side (side 2, terminals P2/N2) of the device is connected to a battery in a normal
application.
● The device output side must be connected (precharging circuit, fuse) as described in
Chapter Electrical connection (Page 31).
● Parallel connection
Several devices can be connected in parallel on the input side, the output side or on both
sides simultaneously.
In parallel connection, each SINAMICS DCP is supplied with a setpoint from the higher-
level controller. The devices run independently. There is no direct communication of the
devices with each other.
SINAMICS DCP
222 Operating Instructions, 06/2014, A5E34382853K
Technical data
B.2 Device data
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 223
Technical data
B.3 Standards and certifications
Relevant standards
Certification
The product has a CE mark and an EC declaration of conformity as part of the low-voltage
directive (2006/95/EC) which defines the basic requirements for the safety of electrical
equipment.
SINAMICS DCP
224 Operating Instructions, 06/2014, A5E34382853K
Quality documents C
Empty chapter
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 225
Quality documents
SINAMICS DCP
226 Operating Instructions, 06/2014, A5E34382853K
Additional documents D
D.1 List of abbreviations
Note
The following list of abbreviations includes all abbreviations and their meanings used in the
entire SINAMICS user documentation.
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 227
Additional documents
D.1 List of abbreviations
SINAMICS DCP
228 Operating Instructions, 06/2014, A5E34382853K
Additional documents
D.1 List of abbreviations
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 229
Additional documents
D.1 List of abbreviations
SINAMICS DCP
230 Operating Instructions, 06/2014, A5E34382853K
Additional documents
D.1 List of abbreviations
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 231
Additional documents
D.1 List of abbreviations
SINAMICS DCP
232 Operating Instructions, 06/2014, A5E34382853K
Additional documents
D.1 List of abbreviations
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 233
Additional documents
D.1 List of abbreviations
SINAMICS DCP
234 Operating Instructions, 06/2014, A5E34382853K
Checklists and forms E
Empty chapter
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 235
Checklists and forms
SINAMICS DCP
236 Operating Instructions, 06/2014, A5E34382853K
Assembly documents F
Empty chapter
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 237
Assembly documents
SINAMICS DCP
238 Operating Instructions, 06/2014, A5E34382853K
Index G
Empty chapter
SINAMICS DCP
Operating Instructions, 06/2014, A5E34382853K 239
Index
SINAMICS DCP
240 Operating Instructions, 06/2014, A5E34382853K
Siemens AG Subject to change
Process Industries and Drives A5E34382853K
P.O. Box 48 48 © Siemens AG 2014
90026 NUREMBERG
GERMANY
DC Converters
SINAMICS DCM
www.siemens.com/automation