HIGHLIGHTED POINTS FOR IS 1180 (Part 1) : 2014

Want create site? Find Free WordPress Themes and plugins.

To improve the efficiency of our electrical system recently Bureau of Indian Standards has

taken some major steps to improve the electrical network of our country and now from 1st Feb

2016 distribution transformer is added in mandatory equipment list of BIS and to

manufacturing the transformer manufacturer must be obtained the license from BIS for this

BIS issued the Fourth revision of IS 1180 (Part1): Outdoor Type Oil Immersed Distribution

Transformers upto 2500kVA, 33KV Specification. In which BIS have been mentioned some

major changes in the specification of transformers, some of the major highlighted points are

as below:

In revised IS, transformers have been divided in three categories, which are as below:

a) Three phase distribution transformers upto and including 200KVA

b) Three phase distribution transformers higher than 200KVA upto and including 2500KVA

c) Single phase distribution transformers upto and including 25KVA

In revised IS specification, losses for each rating for each category have been defined in

three levels which are denoted by as follows;

a) Energy Efficiency Level 1,

b) Energy Efficiency Level 2

3) Energy Efficiency Level 3

In each level maximum losses (No Load Loss + Load Loss) at 50% load & 100% load have

been specified for each rating in all categories. Losses in Energy Efficiency Level 1 is almost

equal to ECBC 2009 guidelines.

In revised IS 1180 there are three energy efficiency levels and for each categories, maximum

values of total losses have been defined on 50% load and 100% load. Losses & percentage

value of impedance for different categories are as below:


a) Three phase distribution transformers upto and including 200KVA, 11KV Class
Sl. Rating (KVA) % Z Energy Efficiency Energy Efficiency Energy Efficiency
No. Level 1 Level 2 Level 3

@ 50% @ @ 50% @ @ 50% @


100% 100% 100%

1 16KVA 4.5% 150W 480W 135W 440W 120W 400W

2 25KVA 4.5% 210W 695W 190W 635W 175W 595W

3 63KVA 4.5% 380W 1250W 340W 1140W 300W 1050W

4 100KVA 4.5% 520W 1800W 475W 1650W 435W 1500W

5 160KVA 4.5% 770W 2200W 670W 1950W 570W 1700W

6 200KVA 4.5% 890W 2700W 780W 2300W 670W 2100W

b) Three phase distribution transformers Higher than 200KVA upto and including 2500KVA, 11KV

Class
Sl. Rating (KVA) %Z Energy Efficiency Energy Efficiency Energy Efficiency
No. Level 1 Level 2 Level 3

@ 50% @ 100% @ 50% @ 100% @ 50% @ 100%

1 250KVA 4.5% 1050W 3150W 980W 2930W 920W 2700W

2 315KVA 4.5% 1100W 3275W 1025W 3100W 955W 2750W

3 400KVA 4.5% 1300W 3875W 1225W 3450W 1150W 3330W

4 500KVA 4.5% 1600W 4750W 1510W 4300W 1430W 4100W

5 630KVA 4.5% 2000W 5855W 1860W 5300W 1745W 4850W

6 1000KVA 5.0% 3000W 9000W 2790W 7700W 2620W 7000W

7 1250KVA 5.0% 3600W 10750W 3300W 9200W 3220W 8400W

8 1600KVA 6.25% 4500W 13500W 4200W 11800W 3970W 11300W

9 2000KVA 6.25% 5400W 17000W 5050W 15000W 4790W 14100W

10 2500KVA 6.25% 6500W 20000W 6150W 18500W 5900W 17500W


c) Single Phase distribution transformers upto and including 25KVA, 11KV Class
Sl. Rating (KVA) % Z Energy Efficiency Energy Efficiency Energy Efficiency
No. Level 1 Level 2 Level 3

@ 50% @ @ 50% @ @ 50% @


100% 100% 100%

1 5KVA 4.0% 40W 115W 35W 95W 30W 75W

2 10KVA 4.0% 70W 190W 60W 170W 55W 150W

3 16KVA 4.0% 95W 265W 82W 224W 63W 190W

4 25KVA 4.0% 125W 340W 110W 300W 95W 260W

Further to above it is also observed that IS 1180 are now also applicable for 22KV & 33KV

class transformers, losses values for 22KV & 33KV class transformers shall be applicable as

per below clause:

a) For transformers having voltage class above 11KV and upto and including 22KV, the

permissible total loss value shall not exceed by 5% of the maximum total losses values

mentioned in table a) & b) for three phase.

b) For transformers having voltage class above 22KV and upto and including 33KV, the

permissible total loss value shall not exceed by 7.5% of the maximum total losses values

mentioned in table a) & b) for three phase.

c) For transformers having voltage class above 11KV and upto and including 22KV, the

permissible total loss value shall not exceed by 7.5% of the maximum total losses values

mentioned in table c) for single phase.

d) For transformers having voltage class above 22KV and upto and including 33KV, the

permissible total loss value shall not exceed by 10% of the maximum total losses values

mentioned in table c) for single phase.