Professional Documents
Culture Documents
INSTALLATION MANUAL
English
MODELS Français
(Ceiling Suspended type)
FHQ35CAVEB FHQ100CAVEB
Español
FHQ50CAVEB FHQ125CAVEB
FHQ60CAVEB FHQ140CAVEB
FHQ71CAVEB FHQ140CAVEA
Italiano
FHQ35CAVEB FHQ100CAVEB
FHQ50CAVEB FHQ125CAVEB SPLIT SYSTEM Air Conditioners Installation manual
FHQ60CAVEB FHQ140CAVEB
FHQ71CAVEB FHQ140CAVEA
1 English
01_EN_3P368557-1.fm Page 2 Wednesday, December 10, 2014 10:31 AM
(12) Screw
(11) Wiring
Name for wiring
fixture
fixture (Miscellaneous)
2. BEFORE INSTALLATION
Quantity 2 pcs. 2 pcs.
When unpacking and moving the indoor unit after • Operation manual
M4 × 12
unpacked, do not apply force to the piping (refrigerant and • Installation manual
drain) and resin parts. Shape • Declaration of conformity
• Make sure to check in advance that the refrigerant to be used
for installation work is R410A.
(The air conditioner will not properly operate if a wrong refrig-
erant is used.)
• For installation of the outdoor unit, refer to the installation 2-2 OPTIONAL ACCESSORIES
manual attached to the outdoor unit. • For this indoor unit, the remote controller is separately
• Do not throw away the accessories until the installation work required.
is completed. • There are 2 kinds of remote controller; wired type and wire-
• After the indoor unit is carried into the room, to avoid the less type.
indoor unit from getting damaged, take measures to protect Install the remote controller to the place where the customer
the indoor unit with packing materials. has given consent.
(1) Determine the route to carry the unit into the room. Refer to the catalog for the applicable model.
(2) Do not unpack the unit until it is carried to the installation (Refer to the installation manual attached to the remote con-
location. troller for how to install.)
Where unpacking is unavoidable, use a sling of soft
material or protective plates together with a rope when
lifting, to avoid damage or scratches to the indoor units.
English 2
01_EN_3P368557-1.fm Page 3 Wednesday, December 10, 2014 10:31 AM
CARRY OUT THE WORK GIVING CAUTION TO THE Points of the operation explanation
FOLLOWING ITEMS AND AFTER THE WORK IS
In addition to the general usage, since the items in the
COMPLETED CHECK THESE AGAIN. operation manual with the WARNING and CAU-
TION marks are likely to result in human bodily injuries
1. Items to be checked after the installation work is com-
and property damages, it is necessary not only to
pleted
explain these items to the customer but also to have the
Check customer read them.
Items to be checked In case of defective
column It is also necessary to explain the items of “NOT MAL-
Are the indoor and outdoor Drop · vibration · FUNCTION OF THE AIR CONDITIONER” to the customer
units rigidly fixed? noise and have the customer read them carefully.
Are the installation work of the out- Does not operate ·
door and indoor units complete? burnout
Have you carried out a leakage
test with the test pressure Does not cool / 3. SELECTION OF INSTALLATION LOCA-
specified in the outdoor unit Does not heat
installation manual?
TION
Is the insulation of refrigerant When unpacking and moving the indoor unit after
piping and drain piping com- Water leakage unpacked, do not apply force to the piping (refrigerant and
pletely carried out? drain) and resin parts.
Does the drain flow out (1) Select the installation location that meets the following
Water leakage conditions and get approval of the customer.
smoothly?
Is the power supply voltage • Where the cool and warm air spreads evenly in the room.
identical to that stated in the Does not operate · • Where there is no obstacles in the air passage.
manufacturer’s label on the air burnout • Where drainage can be ensured.
conditioner? • Where the ceiling lower surface is not inclined.
Are you sure that there is no • Where there is sufficient strength to withstand the mass
Does not operate · of the indoor unit (if the strength is insufficient, the indoor
wrong wiring or piping or no
burnout
loose wiring? unit may vibrate and get in contact with the ceiling and
Danger in case of generate unpleasant chattering noise).
Is earthing completed? • Where a space sufficient for installation and service can
leakage
Are the sizes of electric wiring Does not operate · be ensured. (Refer to Fig. 1 and Fig. 2)
according to the specification? burnout • Where the piping length between the indoor and the out-
Is any of air outlets or inlets of
door units is ensured within the allowable length. (Refer
the indoor and outdoor units to the installation manual attached to the outdoor unit.)
blocked with obstacles? Does not cool / • Where there is no risk of flammable gas leak.
(It may lead to capacity drop Does not heat
due to fan speed drop or mal- [ Required installation space (mm) ]
function of equipment.)
*30 or more *30 or more
Have you recorded the refrig-
Refrigerant charge
erant piping length and the
amount is not clear
refrigerant charge added?
Check
300 or more
Items to be checked
column
Have you carried out field setting? (if necessary)
Are the control box lid, the air filter and the suction grille
attached?
Discharge
Does the cool air discharge during the cooling operation and
the warm air discharge during heating operation?
Suction 2500 or more
Have you explained how to operate the air conditioner from floor level
showing the operation manual to the customer? For high
Have you explained the description of cooling, heating, Obstacles installation
program dry and automatic (cooling/heating) given in
the operation manual to the customer?
Fig. 2
If you set the fan speed at thermostat OFF, did you Floor level
explain the set fan speed to the customer?
Have you handed the operation manual and the instal-
lation manual to the customer? NOTE
• If there is extra space required for * part, servicing can be
conducted more easily if 200mm or more is secured.
3 English
01_EN_3P368557-1.fm Page 4 Wednesday, December 10, 2014 10:31 AM
(2) Make holes for hanging bolts, piping outlet, drain pip-
CAUTION ing outlet, and electric wiring inlet.
• Install the indoor and outdoor units, power supply wiring, • Use the installation pattern paper (5).
remote controller wiring and transmission wiring at least 1 • Determine the locations of hanging bolts, piping outlet,
meter away from televisions or radios to prevent image inter- drain piping outlet and electric wiring inlet. And make the
ference or noise. hole.
(Depending on the radio waves, a distance of 1 meter may
not be sufficient to eliminate the noise.) (3) Remove the parts of the indoor unit.
• Install the indoor unit as far as possible from fluorescent 1) Remove the suction grille.
lamps. • Slide the suction grille fixing knobs (35, 50 type: 2
If a wireless remote controller kit is installed, the transmission places for each, 60~140 type: 3 places for each) toward
distance may be shorter in a room where an electronic lighting backward direction (as shown by an arrow) to open the
type (inverter or rapid start type) fluorescent lamp is installed. suction grille widely. (Refer to Fig. 4)
• Keeping the suction grille opened, hold the knob at the
(2) Use hanging bolts for installation. back of the suction grille and at the same time, pull the
Investigate if the installation place can withstand the mass suction grille forward to remove. (Refer to Fig. 5)
of the indoor unit and, if necessary, hang the indoor unit
Fixing knob Suction grille
with bolts after it is reinforced by beams etc. (Refer to the
installation pattern paper (5) for the mounting pitch.).
(3) Ceiling height
This indoor unit can be installed up to 4.3m (for 35-71
model, 3.5m) of the ceiling.
Fig. 4
G H
200
175
J
5
Fig. 5
View from the front
2) Remove the decoration side panel (right, left).
Left back drain Wall hole for back side
piping outlet hole
• Remove the fixture screw of the decoration side panel
piping outlet
(one for each), pull forward (arrow direction) to remove.
(φ100 hole)
(Refer to Fig. 6)
Back side wiring • Take out accessories. (Refer to Fig. 6)
outlet location
• Open the knock hole at the wiring inlet side at the rear
surface or top surface, and install the attached resin
A Unit dimension Top panel drain piping bushing (10).
connection position
B Hanging bolt pitch
C Resin bushing (10)
D
163
189
(accessory)
30
87
E
690 Unit dimension
Removable part
Hanging bolt pitch
210
English 4
01_EN_3P368557-1.fm Page 5 Wednesday, December 10, 2014 10:31 AM
Hanger fixing
screw (M5) Double nuts
Hanger Fig. 10
Hanger installing bolt (M8) (2) Lift up the indoor unit, slide from the front and put the
hanger installing bolt (M8) into the securely for temporary
Loosen
Hanger hanging. (Refer to Fig. 11)
Fig. 8
(3) Tighten the hanger fixing screws (M5) at 2 places, which
were removed, as they were before.
(Refer to Fig. 11)
CAUTION It is necessary to prevent misalignment of the indoor unit.
Do not remove the tape (milky white) applied to the outside
of the indoor unit. It may cause electric shocks or a fire. (4) Tighten the hanger installing bolts (M8) at 4 places
securely. (Refer to Fig. 11)
(4) Install the hanging bolts. Attachment part
• Use M8 or M10 bolts for hanging the indoor unit. Hanger
• Adjust the length of the hanging bolt from the ceiling in
advance. (Refer to Fig. 9)
• Use hole-in-anchors for the existing bolts and embedded
inserts or foundation bolts for new bolts, and fix the unit
firmly to the building so that it may withstand the mass of
the unit. Hanger installing
In addition, adjust the distance from the ceiling in bolt (M8)
Hanger
advance.
fixing screw
(M5)
CAUTION Reinforcing plate (left/right)
If the hanging bolt is too long, it may damage or break the Fig. 11
When carrying the indoor unit,
indoor unit or options. do not hold the reinforcing plates.
(5) When hanging the indoor unit, make sure to use the level to
Ceiling slab
have better drainage and install it horizontally. Also, if it is
Foundation bolt possible at the installation site, install so that the drain pip-
25 - 55 mm
5 English
01_EN_3P368557-1.fm Page 6 Wednesday, December 10, 2014 10:31 AM
Spanner
45°±2°
15.7 ± 1.5 8.9 ± 0.2
English 6
01_EN_3P368557-1.fm Page 7 Wednesday, December 10, 2014 10:31 AM
CAUTION
Insulation of field piping must be carried out up to the con- Gas side piping insulating method
nection inside the casing. If the piping is exposed to the
atmosphere, it may cause sweating or burn due to touching Do not leave
Piping insulating material (unit side) clearance
the piping, electric shocks or a fire due to the wiring touch-
ing the piping. Joint insulating material (6) (accessory)
Gas piping
Liquid piping
Indoor unit
Clamp (4)
(accessory)
Piping insulating
material (field supply)
Tighten the piping
For prevention of sweating, insulating material
do not expose the piping
Fig. 15
7 English
01_EN_3P368557-1.fm Page 8 Wednesday, December 10, 2014 10:31 AM
(1) For rear side piping • After piping is finished, cut the removed penetration cover
• Remove the rear piping penetration cover, and connect along the shape of piping, and install.
the piping. (Refer to Fig. 16 and Fig. 18) Also, for top panel penetration cover, as it was before
removed, put the horizontal blade motor and thermistor
(2) For upward piping
lead through the clamp of the top panel penetration cover
• For upward piping, L-shaped connection piping kit
and fix. (Refer to Fig. 16 and Fig. 19)
(optional accessory) will be required.
When doing this, block any gaps between the piping pen-
• Remove the top panel penetration cover, and use the L-
etration cover and the piping using putty to prevent dust
shaped connection piping kit (optional accessory) to con-
from entering the indoor unit.
duct piping. (Refer to Fig. 16 and Fig. 17)
(3) For right side piping Horizontal blade motor lead
• Remove the stay for packing and delivering (reinforcing Top panel penetration
Thermistor lead
plate) at the right side, and put back the screw to the orig- cover clamp part
inal position of the indoor unit. (Refer to Fig. 18)
• Open the knockout hole at the decoration side panel
(right), and connect piping. (Refer to Fig. 18)
View from air inlet side
Rear piping penetration cover
Top panel Cutoff
Fig. 19
View from * Before brazing refrigerant piping, have nitrogen flow through
air inlet side the refrigerant piping and substitute air with nitrogen. Then,
carry out brazing (NOTE 2). (Refer to Fig. 20) After all the
Cut at the position avoiding
the knob part of the brazing works are finished, carry out flare connection with the
penetration cover indoor unit.
Cutoff
Pressure reducing valve
Nitrogen
Stop valve Nitrogen
Refrigerant piping
Fig. 20
English 8
01_EN_3P368557-1.fm Page 9 Wednesday, December 10, 2014 10:31 AM
CAUTION
If an old drain hose or an elbow or a clamp is used, it may
cause water leakage.
• Bend the tip of the metal clamp (2) so that the sealing
material does not bulge. (Refer to Fig. 26)
• When performing insulation, wind the large sealing mate-
rial (Large) (8) attached starting from the base of the
metal clamp (2) and drain hose (1) in the direction of the
Fixing
arrow. (Refer to Fig. 25 and Fig. 26)
screw for
protection net Protection net Sealing material (Large) (8)
Metal clamp (2)
(accessory) (accessory)
Fig. 22
9 English
01_EN_3P368557-1.fm Page 10 Wednesday, December 10, 2014 10:31 AM
or more
100mm
(accessory) Sealing material (accessory)
(Large) (8)
Applying direction Centralized drain piping
Drain hose (1)
Install with downward inclination If water stagnates in the
(accessory)
approx. 45° of 1/100 or more so that no air drain piping, the piping
approx. 45° Drain hose (1) will be stagnated. may be clogged.
(accessory)
Sealing Fig. 28
material Sealing material
(Large) (8) (Large) (8) • Connecting drain piping.
(accessory) (accessory) Do not connect the drain piping directly to the sewage
(For right (For left rear/ that gives off ammonia odor. The ammonia in the sewage
back / right side) left side) may go through the drain piping and corrode the heat
Inserting direction exchanger of the indoor unit.
for the screw driver • When installing the drain pump kit (optional accessory),
also refer to the installation manual included to the drain
Tightening part pump kit.
approx. 45° Metal clamp (2) (accessory) (2) After piping is finished, check if the drain flows
smoothly.
• Gradually put about 0.6 liter of water for drain confirma-
Drain hose (1) (accessory) tion into the drain pan from the air outlet.
(Refer to Fig. 29)
Bend the tip without
Air outlet
tearing the sealing
material (Large) (8)
Fig. 26
100mm
• Be sure to insulate all drain piping running indoors. or more
• Do not deflect the drain hose (1) inside of the indoor unit.
(Refer to Fig. 27)
(It may cause abnormal noise such as bubbling noise.)
(If the drain hose (1) is deflected, it may damage the suc-
Plastic container for pouring water
tion grille.)
Fig. 29 (Tube length of 100mm is necessary)
Do not deflect
• After the drain piping work, install the stay for packing and
delivering (reinforcing plate), which was removed in the
section of ‘‘6. REFRIGERANT PIPING WORK’’.
However, it is not necessary to install the stay for packing
and delivering at the right side (reinforcing plate).
Fig. 27 (Refer to Fig. 30)
CAUTION
To prevent dust from entering the indoor unit, cover the gap
with the drain piping by putty or insulation (field supply) so
that no clearance is made.
However, when putting piping and remote controller wiring
through the same hole, cover the gap between the through Stay for packing and delivering
Screw
cover and the piping after ‘‘8. ELECTRIC WIRING WORK’’ (reinforcing plate)
is completed. Fig. 30
English 10
01_EN_3P368557-1.fm Page 11 Wednesday, December 10, 2014 10:31 AM
• Make sure to earth the air conditioner. • If the above is not available, make sure to observe the follow-
Earthing resistance should be according to applicable legis- ing items.
lation. • 2 wirings of different sizes to the terminal block for power
• Do not connect the earth wiring to gas or water piping, light- supply is prohibited.
ning conductor or telephone earth wiring.
• Gas piping ............Ignition or explosion may occur if the Connection of 2 Connection of 2 Connection of
gas leaks. wirings of same size wirings on one side wirings of different
must be carried out is prohibited. sizes is prohibited.
• Water piping .........Hard vinyl tubes are not effective on both sides.
earths.
• Lightning conductor or telephone earth wiring..................
Electric potential may rise abnormally if struck by a light-
ning bolt.
• For electric wiring work, refer to also the “WIRING DIA-
GRAM” attached to the control box lid. (Abnormal heating may occur if the wirings are not tightened
• Never connect the power supply wiring to the terminal block securely.)
for remote controller wiring, or otherwise the entire system
may be damaged. • Use the required wirings, connect them securely and fix
• Carry out installation and wiring of the remote controller these wirings so that external force may not apply to the ter-
according to the “installation manual” attached to the remote minals.
controller. • Use a proper screw driver for tightening the terminal screws.
• Do not touch the Printed Circuit Board assy during the wiring If an improper screw driver is used, it may damage the screw
work. Otherwise, it may cause damage. head and a proper tightening cannot be carried out.
• If a terminal is over tightened, it may be damaged. Refer to
8-2 SPECIFICATIONS FOR FIELD WIRING the table shown below for tightening torque of terminals.
For the wiring of outdoor units, refer to the installation manual Tightening torque (N·m)
attached to the outdoor units.
• Remote controller and transmission wiring are field supply. Terminal block for remote controller
0.88 ± 0.08
(Refer to Table 3) and transmission wiring
Terminal block for power supply 1.47 ± 0.14
Table 3
Earth terminal 1.69 ± 0.25
2
Wire Size (mm ) Length
H05VV-U4G • Conduct wiring so that the earth lead comes out from the
Transmission wiring 2.5 – notched part of the cup washer. (Otherwise, earth lead con-
(NOTE 1)
Vinyl cord with tact will be insufficient and grounding effect may be lost.)
Remote controller Max. • Do not carry out soldering finish when stranded wirings are
sheath or cable 0.75 - 1.25
wiring 500m* used.
(2 wire) (NOTE 2)
* This will be the total extended length in the system when Ring type crimp style terminals
doing group control.
Wiring specifications are shown on the condition that the wiring
Cup washer
has a voltage drop of 2%.
1.It shows the case when conduit piping are used. When the
conduit piping are not used, use H07RN-F.
2.Sheathed vinyl cord or cable (insulation thickness: 1mm or
more)
Notched part
11 English
01_EN_3P368557-1.fm Page 12 Wednesday, December 10, 2014 10:31 AM
(4) Connect the remote controller wiring led from the routing
hole to the terminals (P1 and P2) of the terminal block WARNING
(X1M: 4P). (There is no polarity.) When wiring, form the wirings orderly so that the control
After this is done, use the wiring fixture (11) and clamp (4) box lid can be securely fastened. If the control box lid is not
attached to bind the wiring without applying tension to the in place, the wirings may float up or be sandwiched by the
connecting section of the wirings. box and the panel and cause electric shocks or a fire.
English 12
01_EN_3P368557-1.fm Page 13 Wednesday, December 10, 2014 10:31 AM
P1 P2
Group control remote controller
Indoor unit (Optional accessory) Fig. 33
13 English
01_EN_3P368557-1.fm Page 14 Wednesday, December 10, 2014 10:31 AM
(2) Connect crossover wiring between the terminals (P1, P2) 10. MOUNTING SUCTION GRILLE · DECO-
inside the control box for the remote controller. (There is no
RATION SIDE PANEL
polarity.) (Refer to Fig. 34 and Table 3)
Install securely in the reverse order when decoration side panel
Terminal for remote
controller wiring (P1, P2) and suction grille were removed.
Indoor unit 2
Indoor unit 1 (Master) • When installing the suction grille, hang the string of the suc-
P1 P2 F1 F2 P1 P2 F1 F2 tion grille to the hanging part of the indoor unit shown Fig. 38.
Terminal block
(X1M)
CAUTION
Crossover wiring
to next unit When closing the suction grille, the strap may get caught.
Confirm that the strap does not stick out of the side of the
Terminal block
(X1M) suction grille before closing.
Fig. 35
Round hole Hook
Control with 2 remote controllers control Round hole
Remote Remote
NOTE) controller 1 controller 2 11. FIELD SETTING
(Optional (Optional
accessory) accessory) <<Refer to also the installation manual attached to the out-
1 2 3 door unit.>>
P1 P2
* For simultaneous operation system, be sure to [4-2] For ON/OFF OPERATION, set the SECOND CODE No.
connect the remote controller to the master unit. Fig. 37 to “02”.
(It is set to FORCED OFF when shipped from the factory.)
NOTE
• Ask your customer to keep the manual attached to the
• Terminal numbers of outdoor and indoor units must be remote controller together with the operation manual.
matched. • Do not carry out setting other than those shown in the table.
English 14
01_EN_3P368557-1.fm Page 15 Wednesday, December 10, 2014 10:31 AM
11-1 SETTING WHEN AN OPTIONAL ACCESSORY 11-5 SETTING FAN SPEED DURING THERMOSTAT
IS ATTACHED OFF
• For setting when attaching an optional accessory, refer to the • Set the fan speed according to the using environment after
installation manual attached to the optional accessory. consultation with your customer.
Table 6
11-2 WHEN USING WIRELESS REMOTE CONTROL-
LER Setting Mode No.
FIRST SECOND
• When using a wireless remote controller, it is necessary to CODE No. CORD No.
set the wireless remote controller address. Fan operates / stops Operates 01
Refer to the installation manual attached to the wireless during thermo OFF 11 (21) 2
remote controller. (Cooling · heating) Stops 02
11-3 SETTING CEILING HEIGHT (TYPE 100 OR Fan speed during (Extra low) 01
cooling 12 (22) 6
LESS) Setting 02
thermostat OFF
• When installing indoor unit type 35 - 100, specify the SEC-
Fan speed during (Extra low) 01
OND CODE No. in accordance with the ceiling height.
heating 12 (22) 3
thermostat OFF Setting 02
Table 4
Ceiling height (m)
11-6 SETTING NUMBER OF THE CONNECTED
FIRST SECOND INDOOR UNITS AS SIMULTANEOUS OPERA-
Mode
Type Type Type CODE CODE
No.
No. No.
TION SYSTEM
35,50 60,71 100
• When using in simultaneous operation system mode, change
the SECOND CODE No. as shown in Table 7.
2.7 2.7 3.8 • When using in simultaneous operation system mode, refer to
Standard 01
or less or less or less “SIMULTANEOUS OPERATION SYSTEM INDIVIDUAL
13 (23) 0
2.7 - 2.7 - 3.8 - SETTING” section to set master and slave units separately.
High ceiling 02
3.5 3.5 4.3
Table 7
11-4 SETTING FILTER SIGN FIRST SECOND
Setting Mode No.
• A message to inform the air filter cleaning time will be indi- CODE No. CODE No.
cated on the remote controller. Pair system (1 unit) 01
• Set the SECOND CODE No. shown in the Table 5 according Simultaneous
to the amount of dust or pollution in the room. operation 02
• Though the indoor unit is equipped with the long life filter, it is system (2-unit)
necessary to periodically clean the filter to avoid clogging of Simultaneous 11 (21) 0
the filter. Please also explain the set time to the customer. operation 03
• The periodical filter cleaning time can be shortened depend- system (3-unit)
ing on the environment. Double twin multi
04
Table 5 (4-unit)
(2) Perform field setting (Refer to 11-1 to 11-5) for the master
unit.
(3) Turn off the main power supply switch after (2) is finished.
(4) Detach remote controller from the master unit and connect
it to the slave unit.
15 English
01_EN_3P368557-1.fm Page 16 Wednesday, December 10, 2014 10:31 AM
(5) Turn on the main power supply switch again, and as in (1), • If interior work is still unfinished when test operation fin-
change the SECOND CODE No. to “02”, individual setting. ishes, explain to the customer that the air conditioner
(6) Perform field setting (Refer to 11-1 to 11-4) for the slave must not be operated until interior work is completed in
unit. order to protect the indoor units.
(7) Turn off the main power supply switch after (6) is finished. (If the indoor unit is operated under this condition,
(8) If there is more than one slave unit, repeat steps (4) to (7). paint, glue, and other materials used during the interior
(9) Detach the remote controller from the slave unit after the finishing work will contaminate the indoor unit. This
setting, and reattach to the master unit. This is the end of may cause water splashes or leakage.)
the setting procedure. • If a malfunction occurs and the air conditioner cannot
* You do not need to rewire the remote controller from the operate, refer to “12-1 HOW TO DIAGNOSE FOR
master unit if the optional remote controller for slave unit PROBLEMS”.
is used. (However, remove the wiring attached to the • After completing the test operation, press the INSPEC-
remote controller terminal block of the master unit.) After TION/TEST OPERATION button once to put the indoor
the slave unit setting, remove the remote controller wir- unit in inspection mode, and make sure the malfunction
ing, and rewire the remote controller to the master unit. code is “00” (= normal).
(The indoor unit does not operate properly when two or If the code reads anything other than “00”, refer to “12-
more remote controllers are attached to the unit in the 1 HOW TO DIAGNOSE FOR PROBLEMS”.
simultaneous operation system mode.) • Press the INSPECTION/TEST OPERATION button
four times to return to normal operation mode.
(3)(7)
Earth Power supply Earth Power supply [Mode switching]
leakage 220 - 240V leakage 220 - 240V
breaker ~ breaker ~ BRC1C, BRC1D, Wireless remote controller
50Hz 50Hz
Outdoor Outdoor Normal Test
unit unit operating Once operation
1 2 3 1 2 3 mode mode
Once Once
NOTE) NOTE) (Press 4 Once
On
seconds *
ce
1 2 3 1 2 3 1 2 3 1 2 3 or more) Once * *
P1 P2 P1 P2 P1 P2 P1 P2
Field setting “Indoor “Outdoor
Indoor unit Indoor unit Indoor unit Indoor unit “Malfunction
unit type unit type
(Master) (Slave) (Master) (Slave) * After leaving 10 code” Once code” Once code”
seconds or display
P1 P2 Remote controller ( 4 ) P1 P2 display display
( 9 ) Remote controller more, the mode
(1) (5) returns to the
(2) (6) normal Inspection mode
Fig. 39 operating mode.
NOTE
• Terminal numbers of outdoor and indoor units must be 12-1 HOW TO DIAGNOSE FOR PROBLEMS
matched. With the power on. Troubles can be monitored on the
remote controller.
The fault diagnosis for the BRC1E model remote controller
should be performed while referring to the installation man-
12. TEST OPERATION ual supplied with the remote controller. For the other remote
controllers, perform the fault diagnosis using the following
Complete all the “1. Items to be checked after the installa-
procedure.
tion work is completed” on page 3. Please also refer to the
Trouble shooting with the remote controller display.
installation manual attached to with outdoor unit.
1 With the wired remote controller. (NOTE 1)
(1) The settings of the wired remote controller should be
When the operation stops due to trouble, the opera-
switched while referring to the manual attached to the
remote controller. tion lamp flashes, and the display indicates “ ”
(2) The settings of the other remote controller should be and the malfunction code. Diagnosis can be carried
switched in accordance with the following procedure. out using the malfunction code list according to the
• Make sure that the installation work for the indoor and indicated malfunction code.
outdoor units is all completed. In addition, when in group control it indicates the
• Make sure that the following items are all closed: the unit No., so the malfunction detected unit No. will be
control box lid of the indoor unit and the outer board clarified. For resetting the malfunction, see (NOTE
and piping cover of the outdoor unit. 2).
• After completing the refrigerant piping, drain piping, 2 With the wireless remote controller.
and electrical wiring, clean the interior of the indoor unit (Also refer to the operation manual attached to the
and front panel. Next, perform test operation in accor- wireless remote controller.)
dance with the installation manual attached to with the When the operation stops due to trouble, the dis-
outdoor unit in order to protect the unit. (It is recom- play on the indoor unit flashes. In such a case, diag-
mended that the test operation is performed in the nose the fault contents with the table on the
presence of qualified electrical technician or engineer.) Malfunction code list looking for the Malfunction
• In test operation, make sure that airflow direction and code which can be found by following procedures.
fan speed can be obtained according to the settings. (NOTE 2)
English 16
01_EN_3P368557-1.fm Page 17 Wednesday, December 10, 2014 10:31 AM
(1) Press the INSPECTION /TEST OPERATION but- Indoor heat exchanger Abnormal stop is applied
ton, “ ” is displayed and “ 0 ” flashes. C4 liquid pipe temperature depending on the model or
(2) Press the PROGRAMMING TIME button and find sensor malfunction condition.
the unit No. which stopped due to trouble. Indoor heat exchanger
Abnormal stop is applied
Number of beeps 3 short beeps condenser / evaporator
C5 depending on the model or
................. Perform all the following operations temperature sensor mal-
condition.
1 short beep function
................. Perform (3) and (6) Abnormal stop is applied
Suction air thermistor
1 long beep C9 depending on the model or
malfunction
................. No trouble condition.
(3) Press the OPERATION MODE SELECTOR button CC Humidity sensor abnormal
and upper figure of the malfunction code flashes. Remote controller thermo
Remote controller air
(4) Continue pressing the PROGRAMMING TIME button CJ does not function, but body
thermistor malfunction
unit it makes 2 short beeps and find the upper code. thermo operation is enabled.
(5) Press the OPERATION MODE SELECTOR button Action of safety device
E0
and lower figure of the malfunction code flashes. (Outdoor unit)
(6) Continue pressing the PROGRAMMING TIME button Outdoor Printed Circuit
E1
unit it makes a long beep and find the lower code. Board failure (Outdoor unit)
• A long beep indicate the malfunction code. High pressure malfunc-
E3
tion (Outdoor unit)
NOTE Low pressure malfunc-
E4
1. When the INSPECTION/OPERATION button on the remote tion (Outdoor unit)
controller is pressed, the “ ” indication starts flashing. Compressor motor lock
E5
2. When the ON/OFF button is kept pressed for 5 seconds or malfunction (Outdoor unit)
longer during the inspection mode, the above trouble his- Compressor motor lock by
E6
tory indication disappears. In this case, after the malfunc- over current (Outdoor unit)
tion code indication flashes twice, the indication of code Outdoor fan motor lock
becomes “00” (normal) and unit NO. becomes “0”. Then, malfunction (Outdoor unit)
the display automatically changes from the inspection E7 Outdoor fan instant over-
mode to the normal mode. current malfunction
(Outdoor unit)
12-2 MALFUNCTION CODE E8
Input overcurrent (outdoor
• For places where the malfunction code is left blank, the unit)
Electric expansion valve
“ ” indication is not displayed. Though the system contin- E9
malfunction (Outdoor unit)
ues operating, be sure to inspect the system and make
Cooling/heating switch
repairs as necessary. EA
malfunction (Outdoor unit)
• Depending on the type of indoor or outdoor unit, the malfunc-
Discharge piping temper-
tion code may or may not be displayed.
F3 ature malfunction (Out-
Malfunc- Descriptions and mea- door unit)
Remarks
tion code sures High pressure control
F6
Indoor Printed Circuit (in cooling) (Outdoor unit)
A1
Board failure Sensor fault for inverter
H0
A3 Drain level abnormal (Outdoor unit) (NOTE 1)
Freeze-up protector or High pressure switch fail-
H3
A5 stopped by high pressure ure (Outdoor unit)
control (NOTE 1) Low pressure switch fail-
H4
Indoor fan motor over- ure (Outdoor unit)
load, over current, lock Faulty position detection
A6
Indoor Printed Circuit H6 sensor (Outdoor unit)
Board connection failure (NOTE 1)
Horizontal blade motor Outdoor fan motor posi-
locked H7 tion signal malfunction
A7 (Outdoor unit)
Only the airflow direction
cannot be controlled. CT abnormality
H8
Humidifier system mal- (Outdoor unit) (NOTE 1)
AF
function Outdoor air thermistor Abnormal stop is applied
Capacity setting adapter or H9 system malfunction (Out- depending on the model or
capacity data error, or discon- door unit) condition.
nection of the capacity setting Pressure sensor system
AJ Capacity setting failure
adapter, failure to connect the J1 malfunction (batch)
adapter, or the capacity is not (Outdoor unit)
set to the data-retention IC. Current sensor system Abnormal stop is applied
Transmission error J2 malfunction (Outdoor depending on the model or
between indoor unit) condition.
C1 Printed Circuit Board (Mas- Discharge piping thermis- Abnormal stop is applied
ter) and indoor Printed Cir- J3 tor system malfunction depending on the model or
cuit Board (Slave) (Outdoor unit) condition.
17 English
01_EN_3P368557-1.fm Page 18 Wednesday, December 10, 2014 10:31 AM
English 18
19
INDOOR UNIT H4P PILOT LAMP
A1P PRINTED CIRCUIT BOARD (DEFROST-ORANGE) WIRING DIAGRAM
C105 CAPACITOR (M1F) SS1 SELECTOR SWITCH 9
F1U FUSE (F, 5A, 250V) (MAIN/SUB)
HAP FLASHING LAMP SS2 SELECTOR SWITCH 10 11 11
(SERVICE MONITOR GREEN) (WIRELESS ADDRESS SET)
KPR MAGNETIC RELAY CONNECTOR FOR
(DRAIN PUMP) OPTIONAL PARTS
13
M1F MOTOR (INDOOR FAN) X15A CONNECTOR
M1S MOTOR (SWING BLADE) (FLOAT SWITCH)
14
R1T THERMISTOR (AIR) X24A CONNECTOR
R2T·R3T THERMISTOR (COIL) (WIRELESS REMOTE
SS1 SELECTOR SWITCH CONTROLLER)
12
(EMERGENCY) X25A CONNECTOR 6
V1R DIODE BRIDGE (DRAIN PUMP) 3
15
X1M TERMINAL BLOCK X33A CONNECTOR
01_EN_3P368557-1.fm Page 19 Wednesday, December 10, 2014 10:31 AM
15
X2M TERMINAL BLOCK (ADAPTOR FOR WIRING) 2
7
Z1F NOISE FILTER X35A CONNECTOR
Z1C FERRITE CORE (POWER SUPPLY FOR
(NOISE FILTER) ADAPTOR)
PS POWER SUPPLY CIRCUIT 1 4 8
RC SIGNAL RECEIVER CIRCUIT
TC SIGNAL TRANSMISSION
CIRCUIT
WIRELESS REMOTE CONTROLLER
(RECEIVER/DISPLAY UNIT)
5
A2P PRINTED CIRCUIT BOARD
A3P PRINTED CIRCUIT BOARD NOTES
BS1 PUSH BUTTON (ON/OFF) 1. : TERMINAL BLOCK : CONNECTOR : FIELD WIRING : SHORT CIRCUIT CONNECTOR
H1P PILOT LAMP (ON-RED) 2. IN CASE OF SIMULTANEOUS OPERATION INDOOR UNIT SYSTEM.
H2P PILOT LAMP SEE THE INDOOR UNIT WIRING ONLY.
3. FOR THE DETAIL, SEE WIRING DIAGRAM ATTACHED TO OUTDOOR UNIT.
(TIMER-GREEN)
4. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IN TO THE UNIT IN ACCORDANCE WITH THE ATTACHED
H3P PILOT LAMP INSTALLATION MANUAL.
(FILTER SIGN-RED) 5. X15A, X25A ARE CONNECTED WHEN THE DRAIN UP KIT IS BEING USED.
IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
6. IN CASE OF SIMULTANEOUS OPERATION SYSTEM, CONNECTION QUANTITY OF THE INDOOR UNITS VARIES ACCORDING
TO THE CONNECTION OUTDOOR UNIT, CONFIRM TECHNICAL GUIDE AND CATALOG, ETC. BEFORE CONNECTING.
7. IN CASE OF MAIN/SUB CHANGEOVER.
SEE THE INSTALLATION MANUAL ATTACHED TO REMOTE CONTROLLER.
8. SYMBOLS SHOW AS FOLLOWS: BLK: BLACK RED: RED BLU: BLUE WHT: WHITE YLW: YELLOW GRN: GREEN
ORG: ORANGE BRN: BROWN.
9. SHOWS ONLY IN CASE OF PROTECTED PIPING. USE H07RN-F IN CASE OF NO PROTECTION.
3D079559-1E FHQ35 • 50 • 60 • 71 • 100 • 125 • 140CAVEB, FHQ140CAVEA
Fig. 40
English
00_CV_3P368557-1.fm Page 2 Wednesday, November 26, 2014 5:21 PM