Powercommand Modlon Ii Gateway Modbus - Lon Converter: Description Features
Powercommand Modlon Ii Gateway Modbus - Lon Converter: Description Features
PowerCommand
ModLon II Gateway
®
ModBus - LON Converter
Description Features
The PowerCommand® ModLon II Gateway is used to • Converts Echelon LonWorks data streams to register
interface PowerCommand Networks to devices and maps that can be read by equipment communicating
systems that communicate in Modbus® communication in Modbus RTU and Modbus ASCII format.
protocol. • FTT-10 transceiver.
The ModLon II Gateway provides an Echelon® • Modbus port EIA-232 configuration.
LonWorks® to Modbus RTU or Modbus ASCII • Capable of displaying data from PowerCommand
conversion via an RS232 serial connection. The Generator set controls, transfer controls, CCM and
gateway supplies predefined registers for DIM modules.
PowerCommand Network components. Selection of the • Service button, reset button and LED indicators.
gateway configuration is done by setting the dipswitches • Configured to PowerCommand networks using
on the device. Echelon LonMaker™ for Windows®.
• Operates on 9 - 32 VDC.
• CE and UL Listed and labeled.
• Warranty: PowerCommand Controls are supported by
a worldwide network of independent distributors who
provide parts, service and warranty support.
©2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation
and Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins
Power Generation. Other company, product, or service names may be trademarks or service marks of others.
S-1471c (6/08)
Specifications
Signal requirements Baud: Configurable through LonWorks
Network connections: Echelon LonWorks, twisted-pair Parity: Configurable through LonWorks
78 kbps, FTT-10.
Control power: 9 - 32 VDC. Word length: Configurable through LonWorks
Wiring materials for network signals are UL Listed twisted Stop bits: Configurable through LonWorks
pair wiring. Terminations for control power accept wire
up to 16 ga. Network length: Connects to LonWorks network of
maximum 1400 m (4600 ft) using UL/NEMA Level 4
Modbus connections: EIA-232 with DB-9 (female)
cable.
physical connection.
Environment
Physical
Weight: 0.11 kg (0.245 lbs) The gateway module is designed for proper operation
in ambient temperatures from 0 °C to +50 °C (32 °F to
Power +122 °F) and for storage from -20 °C to +60 °C (-4 °F
Current draw: 9 VDC = 0.15 A, 24 VDC = 0.06 A to +140 °F).
Dimensions
Notes:
1
For the data points engine runtime, the total kWh and total
fuel for the two registers designated as high and low are put
together as an unsigned double integer. This is accomplished
by multiplying the value in the high register by 65536 and
adding it to the value in the low register. Most software
packages automatically perform this calculation if the value is
simply identified as an unsigned double integer.
2
Value not supported in the 3200 controller.
3
Value not supported in the 3100 controller.
4
Value not supported.
5
With 3100 and 2100 controllers, the units are hours. With the
3200 controller, the units are seconds. The multiplier is
always 0.1
For all 3100 controllers, the values given are based on using
EEPROM firmware, version 2.0 or greater. The values for engine
runtime and total kwh are not available on QST–30 gensets.
Ordering information
Part number Description
0541-1149 ModLon II Gateway, CD, instructions, cable