SUPPLEMENT 09/2018

Table of Corrections

Description
Page
As Printed Correction
2.90.6 Protection for Structure Containing 2.90.6 Protection for Structure Containing
xii Flammable Liquids and Gases – Page 159 Flammable Liquids and Gases – Page 149
1.1.1 General 1.1.1 General
Accessible, Readily (Readily Accessible). Accessible, Readily (Readily Accessible).
Capable of being reached quickly for operation, Capable of being reached quickly for operation,
3 renewal, or inspections without … renewal, or inspections without …
FPN: Use of keys is a common practice under controlled or FPN: Use of keys is a common practice under controlled or
supervised conditions and a common alternative to the ready supervised conditions and a common alternative to the ready
access requirements under such supervised conditions as access requirements under such supervised conditions as
provided elsewhere in the NEC. provided elsewhere in the PEC1.
Section 1.10.1.15(C)(1) 1.10.1.15(C)(1)
Equipment Provisions. The determination of Equipment Provisions. The determination of
22 termination provisions of equipment shall be termination provisions of equipment shall be
based on 1.10.1.14(C)(1)a or (C)(1)b. Unless based on 1.10.1.15(C)(1)a or (C)(1)b. Unless
the equipment is listed and marked otherwise, the equipment is listed and marked otherwise,
1.10.2.1 Spaces About Electrical Equipment. 1.10.2.1 Spaces About Electrical Equipment.
(A) Working Space. (A) Working Space.
25 (4) Limited Access. (4) Limited Access.
(c) sAll enclosure doors or hinged panels shall (c) All enclosure doors or hinged panels shall be
be capable of opening a minimum of 90 degrees. capable of opening a minimum of 90 degrees.
2.0.1.7 Use of Insulation of a White or … 2.0.1.7 Use of Insulation of a White or …
(C)(2) (C)(2)
(See upper left corner of page 37) (See upper left corner of page 37)
37
… permitted by 4.0.2.3, that is used for … permitted by 4.0.2.3, that is used for
connecting an appliance or equipment permitted connecting an appliance or equipment permitted
by 400.7. This shall … by 4.0.1.7. This shall …
2.10.1.6 Branch-Circuit Voltage Limitations 2.10.1.6 Branch-Circuit Voltage Limitations
39 (C)(5) (C)(5)
Informational Note: See 410.137 for auxiliary equipment FPN: See 4.10.12.8 for auxiliary equipment limitations
limitations
Section 2.15.1.2(A)(1)(a) Section 2.15.1.2(A)(1)(a)
Exception No. 2: Where a portion of a feeder is Exception No. 2: Where a portion of a feeder is
connected at both its supply and load ends to connected at both its supply and load ends to
separately installed pressure connections as separately installed pressure connections as
covered in 1.10.1.14(C)(2), it shall be permitted covered in 1.10.1.15(C)(2), it shall be permitted
to have an allowable ampacity not less than the to have an allowable ampacity not less than the
50
sum of the continuous load plus the sum of the continuous load plus the
noncontinuous load. No portion of a feeder noncontinuous load. No portion of a feeder
installed under the provisions of this exception installed under the provisions of this exception
shall extend into an enclosure containing either shall extend into an enclosure containing either
the feeder supply or the feeder load the feeder supply or the feeder load
terminations, as covered in 1.10.1.14(C)(1). terminations, as covered in 1.10.1.15(C)(1).
2.20.4.7 Schools. The calculation of a feeder … 2.20.4.7 Schools. The calculation of a feeder …
61 demand factors of Table 220.86 apply … demand factors of Table 2.20.4.7 apply …

Page 1 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
2.25.3.2 Isolating Switches. Where oil 2.25.3.2 Isolating Switches. Where oil
69 switches … meeting the requirements of switches … meeting the requirements of
230.204(B), … 2.30.8.5(B), …
70 2.30.1 Generals 2.30.1 General
2.30.1.1 Scope 2.30.1.1 Scope
Figure 2.30.1.1 Services Figure 2.30.1.1 Services
General Part 2.30.1 General Part 2.30.1
Overhead Service-Drop Conductors Part 2.30.2 Overhead Service Conductors Part 2.30.2
71 Underground Service-Lateral Conductors Part 2.30.3 Underground Service Conductors Part 2.30.3
Service-Entrance Conductors Part 2.30.4 Service-Entrance Conductors Part 2.30.4
Service-Equipment - General Part 2.30.5 Service-Equipment - General Part 2.30.5
Service-Equipment - Disconnecting Means Part 2.30.6 Service-Equipment - Disconnecting Means Part 2.30.6
Service-Equipment - Overcurrent Protection Part 2.30.7 Service-Equipment - Overcurrent Protection Part 2.30.7
Services Exceeding 600 Volts, Nominal Part 2.30.8 Services Exceeding 600 Volts, Nominal Part 2.30.8
2.30.1.1 Scope 2.30.1.1 Scope
Figure 2.30.1.1 Services Figure 2.30.1.1 Services

71

2.30.2.3 Clearances. 2.30.2.3 Clearances.


2.30.2.3(B)(1) 2.30.2.3(B)(1)
73 … surface only for overhead service conductors … surface only for overhead service conductors
supported on and cabled together with a supported on and cabled together with a
grounded bare messenger where the voltage does grounded bare messenger where the voltage does
not exceed 150 volts to ground not exceed 300 volts to ground
2.30.3.2 Size and Rating. 2.30.3.2 Size and Rating.
(C) Grounded Conductors. The grounded (C) Grounded Conductors. The grounded
74
conductor shall not be less than the minimum conductor shall not be less than the minimum
size required by 2.50.2.3(C). size required by 2.50.2.5(C).
Section 2.30.3.4 Spliced Conductors. Section 2.30.3.4 Spliced Conductors.
Service conductors shall be permitted to be Service conductors shall be permitted to be
74
spliced or tapped in accordance with 1.10.1.14, spliced or tapped in accordance with 1.10.1.15,
3.0.1.5(E), 3.0.1.13, and 3.0.1.15. 3.0.1.5(E), 3.0.1.13, and 3.0.1.15.
2.30.4.1 Number of Service-Entrance … 2.30.4.1 Number of Service-Entrance …
Exception No. 5: One set of service-entrance Exception No. 5: One set of service-entrance
74
conductors connected to … covered by conductors connected to … covered by
2.30.3.13(5) or 2.30.6.13(6). 2.30.6.13(5) or 2.30.6.13(6).
Section 2.30.4.7 Spliced Conductors. Section 2.30.4.7 Spliced Conductors.
Service-entrance conductors shall be permitted Service-entrance conductors shall be permitted
76
to be spliced or tapped in accordance with to be spliced or tapped in accordance with
1.10.1.14, 3.0.1.5(E), 3.0.1.13, and 3.0.1.15. 1.10.1.15, 3.0.1.5(E), 3.0.1.13, and 3.0.1.15.

Page 2 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
2.30.6.2 Maximum Number of Disconnects. 2.30.6.2 Maximum Number of Disconnects.
2.30.6.2(A) General. 2.30.6.2(A) General.
… than six sets of disconnects per service … than six sets of disconnects per service
grouped in any one location. grouped in any one location.
78 FPN No. 1: There may be more than one location of service FPN: There may be more than one location of service
disconnecting means grouping in multiple-occupancy disconnecting means grouping in multiple-occupancy
buildings or a site development with group of single detached buildings or a site development with group of single detached
buildings. buildings.
FPN No. 2: See Section 2.40.2.1(B)(1) and (B)(2) on
requirements for feeder taps.
2.30.6.2 Maximum Number of Disconnects. 2.30.6.2 Maximum Number of Disconnects.
2.30.6.2(A) General. 2.30.6.2(A) General.
… wiring shall be limited to a maximum of six. … wiring shall be limited to a maximum of six.
78 All service disconnecting means shall be clearly All service disconnecting means shall be clearly
labeled “SERVICE DISCONNECT FOR labeled “SERVICE DISCONNECT FOR
POWER SUPPLY CUTOFF". POWER SUPPLY CUTOFF".
FPN: See Section 2.40.2.1(B)(1) and (B)(2) on requirements for
feeder taps.
2.30.6.10 Rating of Service Disconnecting 2.30.6.10 Rating of Service Disconnecting
Means. The service disconnecting means … in Means. The service disconnecting means … in
79
accordance with Part III, IV, or V of Article accordance with Part 2.20.3, 2.20.4, or 2.20.5 of
2.20, as applicable. In no case … Article 2.20, as applicable. In no case …
2.30.6.10 Rating of Service Disconnecting 2.30.6.10 Rating of Service Disconnecting
Means. Means.
79
(D) One-Family Dwellings. For a one-family (D) One-Family Dwellings. For a one-family
dwelling, the … than 60 amperes, 3-wire. dwelling, the … than 60 amperes.
2.40.1.6 Standard Ampere Ratings. 2.40.1.6 Standard Ampere Ratings.
(A) Fuses and Fixed-Trip Circuit Breakers. (A) Fuses and Fixed-Trip Circuit Breakers.
The standard ampere ratings for fuses and The standard ampere ratings for fuses and
85
inverse time circuit breakers shall be considered inverse time circuit breakers shall be considered
as shown in Table 2.40.1.6. Additional standard as shown in Table 2.40.1.6(A). Additional
… standard …
2.40.1.6 Standard Ampere Ratings. 2.40.1.6 Standard Ampere Ratings.
(A) Fuses and Fixed-Trip Circuit Breakers. (A) Fuses and Fixed-Trip Circuit Breakers.
85
… Additional standard ampere ratings for fuses … Additional standard ampere ratings for fuses
shall be 1, 3, 6, 10, and 601. The use … shall be 1, 3, 6, 10, and 60. The use …
2.40.2.1 Location in Circuit. 2.40.2.1 Location in Circuit.
(B)(5)(4) near the upper right corner of page 88 (B)(5)(4) near the upper right corner of page 88
88 a. Outside … a. Outside …
a. Inside, nearest … b. Inside, nearest …
b. Where installed … c. Where installed …
2.40.2.1 Location in Circuit. 2.40.2.1 Location in Circuit.
89 (C)(2)(1) at upper left corner of page 89 (C)(2)(1) at upper left corner of page 89
a. Not less than the rating … b. Not less than the rating …

Page 3 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
2.40.7.6 Applications. A circuit breaker with a 2.40.7.6 Applications. A circuit breaker with a
straight voltage rating, such as 230V … circuit straight voltage rating, such as 230V … circuit
93 breaker is marked 1ö–3ö to indicate such breaker is marked 1Φ-3Φ to indicate such
suitability. suitability.
2.50.2.1 Alternating-Current Systems to Be 2.50.2.1 Alternating-Current Systems to Be
Grounded. Grounded.
2.50.2.1(B) 2.50.2.1(B)
100 (1) Where the system can be grounded so that (1) Where the system can be grounded so that
the maximum voltage to ground on the the maximum voltage to ground on the
ungrounded conductors does not exceed 150 ungrounded conductors does not exceed 250
volts volts
2.50.2.3 Circuits Not to Be Grounded. 2.50.2.3 Circuits Not to Be Grounded.
101 (5) Secondary circuits of lighting systems as (5) Secondary circuits of lighting systems as
provided in 6.80.2.7(A)(2). provided in 6.80.2.4(A)(2).
2.50.2.5 Grounding Service-Supplied 2.50.2.5 Grounding Service-Supplied
Alternating- Current Systems. Alternating- Current Systems.
101 (A) (A)
(1) … (2) … (1) … (2) … (3) … (1) … (2) … (3) … (4) … (5) …
2.50.2.5 Grounding Service-Supplied … 2.50.2.5 Grounding Service-Supplied …
(A) System Grounding Connections. (A) System Grounding Connections.
101
(3) Load-Side Grounding Connections. (3) Load-Side Grounding Connections.
FPN: See 250.30 for separately derived … FPN: See 2.50.2.11 for separately derived …
2.50.2.7 Conductor to Be Grounded — 2.50.2.7 Conductor to Be Grounded —
102 Alternating- Current Systems. Alternating- Current Systems.
(1) … (2) … (3) … (1) … (2) … (1) … (2) … (3) … (4) … (5) …
2.50.2.11 Grounding Separately Derived … 2.50.2.11 Grounding Separately Derived …
(A) Grounded Systems. (A) Grounded Systems.
103 (1) System Bonding Jumper. (1) System Bonding Jumper.
Exception No. 1: For systems installed in Exception No. 1: For systems installed in
accordance with 45.0.1.6, a single … accordance with 4.50.1.6, a single …
2.50.3.15 Grounding Electrode … 2.50.3.15 Grounding Electrode …
(B) Securing and Protection Against … (B) Securing and Protection Against …
111 (4) In Contact with the Earth. Grounding (4) In Contact with the Earth. Grounding
electrode conductors and grounding … comply electrode conductors and grounding … comply
with 300.5, but … with 3.0.1.5, but …
2.50.3.15 Grounding Electrode … 2.50.3.15 Grounding Electrode …
(D)(3) (D)(3)
112 (Near upper left corner of page 112) (See upper left corner of page 112)
(3) Supply-side bonding jumper (3) Supply-side bonding jumper
The connection shall … in accordance with The connection shall … in accordance with
250.66 based on … 2.50.3.17 based on …
2.50.3.15 Grounding Electrode … 2.50.3.15 Grounding Electrode …
112 (E) Raceways and Enclosures … (E) Raceways and Enclosures …
(1) … (2) … (3) … (3) … (1) … (2) … (3) … (4) …
Page 4 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
2.50.5.5 Bonding for Communication … 2.50.5.5 Bonding for Communication …
(Near upper left corner of page 116) (Near upper left corner of page 116)
Exception following (A)(6) Exception following (A)(6)
116 Exception: In existing buildings or structures Exception: In existing buildings or structures
where any of the intersystem bonding and where any of the intersystem bonding and
grounding electrode conductors required by grounding electrode conductors required by
770.100(B)(2), … 7.70.4.1(B)(2), …
2.50.5.15 Bonding of Piping Systems … 2.50.5.15 Bonding of Piping Systems …
119 (C) Structural Metal. (C) Structural Metal.
(1) … (2) … (3) … (0) … (4) … (1) … (2) … (3) … (4) … (5) …
2.50.6.5 Equipment Connected by Cord and 2.50.6.5 Equipment Connected by Cord and
120 Plug. Under any of the conditions described in Plug. Under any of the conditions described in
2.50.6.15(1) through (4), exposed, normally … 2.50.6.5(1) through (4), exposed, normally …
2.50.6.5 Equipment Connected by Cord … 2.50.6.5 Equipment Connected by Cord …
Exception: Listed tools, listed appliances, and Exception: Listed tools, listed appliances, and
120
listed equipment covered in 2.50.6.15(2) listed equipment covered in 2.50.6.5(2) through
through (4) shall not be … (4) shall not be …
2.50.6.13 Size of Equipment Grounding 2.50.6.13 Size of Equipment Grounding
Conductors. Conductors.
(F) Conductors in Parallel. For circuits of (F) Conductors in Parallel. For circuits of
124
parallel conductors as permitted in 310.10(H), parallel conductors as permitted in 3.10.2.1(H),
the equipment grounding conductor shall be the equipment grounding conductor shall be
installed in accordance with (1) or (2). installed in accordance with (1) or (2).
Section 2.50.7.19(A) Connections. Section 2.50.7.19(A) Connections.
Connections and splices shall be made in Connections and splices shall be made in
128
accordance with 1.10.1.14(B) except that accordance with 1.10.1.15(B) except that
insulation shall not be required. insulation shall not be required.
2.80.3.4 Interconnections. 2.80.3.4 Interconnections.
(B) Through Spark Gap or Device. Where the (B) Through Spark Gap or Device. Where the
135
surge … otherwise grounded as in 250.52, an surge … otherwise grounded as in 2.50.3.3, an
interconnection … interconnection …
2.85.3.3 Type 1 SPDs. Type 1 SPDs shall be 2.85.3.3 Type 1 SPDs. Type 1 SPDs shall be
136 installed in accordance with 285.23(A) and (B). installed in accordance with 2.85.3.3(A) and (B).
2.85.3.4 Type 2 SPDs. 2.85.3.4 Type 2 SPDs.
(A) Service-Supplied Building or Structure. (A) Service-Supplied Building or Structure.
136
Type 2 SPDs shall … device required in 230.91, Type 2 SPDs shall … device required in 2.30.7.2,
unless … unless …
3.0.1.3 Conductors. 3.0.1.3 Conductors.
(B) Conductors of the … (B) Conductors of the …
153 (1) Paralleled Installations. (1) Paralleled Installations.
Exception: Conductors installed … isolated Exception: Conductors installed … isolated
phase, neutrals and … phase, neutral and …

Page 5 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
3.0.1.3 Conductors. 3.0.1.3 Conductors.
(C)(2) (C)(2)
154 b) Excitation, control, relay, and ammeter b) Excitation, control, relay, and ammeter
conductors used in connection … as the motor- conductors used in connection … as the motor-
circuit switchgear, switchboards, conductors. circuit conductors.
3.0.1.3 Conductors. 3.0.1.3 Conductors.
(C)(2) (C)(2)
154 c) In motors, transformers, control assemblies, c) In motors, transformers, switchgear,
and similar equipment, conductors of different switchboards, control assemblies, and similar
voltage ratings shall be permitted. equipment, conductors of different voltage
ratings shall be permitted.
3.0.1.5 Underground Installations. 3.0.1.5 Underground Installations.
(D) Protection from Damage. (D) Protection from Damage.
156 (4) Enclosure or Raceway Damage. (4) Enclosure or Raceway Damage.
… installed in rigid metal conduit, intermediate … installed in electrical metallic tubing, rigid
metal conduit, … metal conduit, intermediate metal conduit, …
Section 3.0.1.5(E) Section 3.0.1.5(E)
Splices and Taps. Direct-buried conductors or Splices and Taps. Direct-buried conductors or
cables shall be permitted to be spliced or tapped cables shall be permitted to be spliced or tapped
156
without the use of splice boxes. The splices or without the use of splice boxes. The splices or
taps shall be made in accordance with taps shall be made in accordance with
1.10.1.14(B). 1.10.1.15(B).
3.0.1.15 Boxes, Conduit Bodies, or … 3.0.1.15 Boxes, Conduit Bodies, or …
160 (H) Insulated Devices. As permitted in (H) Insulated Devices. As permitted in
334.40(B), a box … 3.34.2.31(B), a box …
3.0.1.9 Braid-Covered Insulated Conductors 3.0.2.9 Braid-Covered Insulated Conductors
— Exposed Installation. Exposed runs of — Exposed Installation. Exposed runs of
164 braid-covered insulated conductors shall have a braid-covered insulated conductors shall have a
flame-retardant braid. If the conductors … flame-retardant braid. If the conductors …
Section 3.10.2.6(A)(2) Section 3.10.2.6(A)(2)
168 FPN: See 1.10.1.14(C) for conductor temperature limitations FPN: See 1.10.1.15(C) for conductor temperature limitations
due to termination provisions. due to termination provisions.
Section 3.10.2.6(A)(3)(4) Section 3.10.2.6(A)(3)(4)
168 FPN No. 2: Refer to 1.10.1.14(C) for the temperature limitation FPN No. 2: Refer to 1.10.1.15(C) for the temperature
of terminations. limitation of terminations.
Section 3.10.2.6(B) Tables. Section 3.10.2.6(B) Tables.
2nd Paragraph 2nd Paragraph
169 … for the temperature rating of the termination … for the temperature rating of the termination
in accordance with the provisions of in accordance with the provisions of
1.10.1.14(C). 1.10.1.15(C).

Page 6 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
Table 3.10.3.1(E) Thickness of Insulation for Table 3.10.3.1(E) Thickness of Insulation for
Shielded Solid Dielectric Insulated Shielded Solid Dielectric Insulated Conductors
Conductors Rated 2001 to 35000 Volts Rated 2001 to 35000 Volts

191

As Printed
Table 3.10.3.1(E) Thickness of Insulation for Shielded Solid Dielectric Insulated Conductors
Rated 2001 to 35000 Volts

192
Correction
Table 3.10.3.1(E) Thickness of Insulation for Shielded Solid Dielectric Insulated Conductors
Rated 2001 to 35000 Volts

Page 7 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
3.14.2.2 Number of Conductors in … 3.14.2.2 Number of Conductors in …
196 (B) Box Fill Calculations. The volumes in … (B) Box Fill Calculations. The volumes in …
installed wit a barrier shall … installed with a barrier shall …
3.14.2.2 Number of Conductors in Outlet, … 3.14.2.2 Number of Conductors in Outlet, …
(B) Box Fill Calculations. (B) Box Fill Calculations.
196 (1) Conductor Fill. Each conductor that (1) Conductor Fill. Each conductor that
originates outside … for free conductors in originates outside … for free conductors in
300.14 shall be … 3.0.1.14 shall be …
3.14.2.9 Supports. 3.14.2.9 Supports.
(E) Raceway-Supported Enclosure, without (E) Raceway-Supported Enclosure, without
200 … …
Exception: The following wiring methods … Exception: The following wiring methods …
(1) … (2) … (0) … (1) … (2) … (1) … (2) … (3) … (4) … (5) …
3.14.2.14 Pull and Junction Boxes … 3.14.2.14 Pull and Junction Boxes …
[Exception following (A)(2)] [Exception following (A)(2)]
202
Exception: Where a raceway … for one wire per Exception: Where a raceway … for one wire per
terminal in Table 312.6(A). terminal in Table 3.12.1.6(A).
3.30.2.1 Uses Permitted. 3.30.2.1 Uses Permitted.
(B) Specific Uses. (B) Specific Uses.
213 (1) Cable Tray. Type MC cable installed in (1) Cable Tray. Type MC cable installed in
cable tray shall comply with 3.92.2.1, 3.92.2.3, cable tray shall comply with 3.92.2.1, 3.92.2.3,
392.18, 3.92.22.11, … 3.92.2.9, 3.92.22.11, …
3.34.2.6 Exposed Work. 3.34.2.6 Exposed Work.
(C) In Unfinished Basements … (C) In Unfinished Basements …
217
Where cable is run at angles … protected in Where cable is run at angles … protected in
accordance with 300.4. Conduit … accordance with 3.0.1.4. Conduit …
3.42.2. Reaming and Threading. All cut ends 3.42.2.19 Reaming and Threading. All cut
shall be reamed or otherwise finished to remove ends shall be reamed or otherwise finished to
224
rough edges. Where conduit is threaded in the remove rough edges. Where conduit is
field, a standard … threaded in the field, a standard …
3.48.2.11 Size. 3.48.2.11 Size.
(B) Maximum. FMC larger than metric (B) Maximum. FMC larger than metric
227
designator 103 mm (trade size 3/8) shall not be designator 103 mm (trade size 4) shall not be
used. used.
3.50.2.1 Uses Not Permitted. LFMC shall not be 3.50.2.3 Uses Not Permitted. LFMC shall not be
used as follows: used as follows:
229 (1) Where subject to physical damage (1) Where subject to physical damage
(2) Where any … (2) Where any …

Page 8 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
Under Article 3.52 3.52.1.2 Definition.
Missing Sections 3.52.1.2 and 3.52.1.6 Rigid Polyvinyl Chloride Conduit (PVC). A
rigid nonmetallic raceway of circular cross
section, with integral or associated couplings,
230
connectors, and fittings for the installation of
electrical conductors and cables.
3.52.1.6 Listing Requirements. PVC conduit,
factory elbows, and associated fittings shall be
listed.
Section 3.52.2.1(H) Section 3.52.2.1(H)
Support of Conduit Bodies. … and shall not Support of Conduit Bodies. … and shall not
230
contain devices other than splicing devices as contain devices other than splicing devices as
permitted by 1.10.1.14(B) and 3.14.2.2(C)(2). permitted by 1.10.1.15(B) and 3.14.2.2(C)(2).
3.54.2.1 Uses Permitted. 3.54.2.1 Uses Permitted.
(4) In underground locations subject to (4) In underground locations subject to
234
severe corrosive influences as covered in 300.6 severe corrosive influences as covered in 3.0.1.6
and … and …
Section 3.55.2.1(H) Section 3.55.2.1(H)
Support of Conduit Bodies. … and shall not Support of Conduit Bodies. … and shall not
235
contain devices other than splicing devices as contain devices other than splicing devices as
permitted by 1.10.1.14(B) and 3.14.2.2(C)(2). permitted by 1.10.1.15(B) and 3.14.2.2(C)(2).
3.56.2.3 Uses Not Permitted. 3.56.2.3 Uses Not Permitted.
238
(1) … (2) … (3) … (0) … (1) … (2) … (3) … (4) …
3.56.3.21 Marking. LFNC shall be … 3.56.3.21 Marking. LFNC shall be …
239 accordance with 356.2 and … accordance with 3.56.1.2 and …
3.62.2.1 Uses Permitted. 3.62.2.1 Uses Permitted.
(3) In locations subject to severe corrosive (3) In locations subject to severe corrosive
242
influences as covered in 300.6 and where subject influences as covered in 3.0.1.6 and where
… subject …
362.22 Number of Conductors. The number of 3.62.2.13 Number of Conductors. The number
243 conductors shall not exceed that permitted by the of conductors shall not exceed that permitted by
percentage fill in Table 10.1.1.1. the percentage fill in Table 10.1.1.1.
3.66.2.1 Uses Permitted. 3.66.2.1 Uses Permitted.
(B) Nonmetallic Auxiliary Gutters. (B) Nonmetallic Auxiliary Gutters.
Nonmetallic auxiliary … insulation temperature Nonmetallic auxiliary … insulation temperature
rating. rating.
244
(1) Outdoors. Nonmetallic auxiliary gutters … FPN: Extreme cold may cause nonmetallic auxiliary gutters to
become brittle …
as suitable for the purpose.
(1) Outdoors. Nonmetallic auxiliary gutters …
FPN: Extreme cold may cause nonmetallic auxiliary gutters to
become brittle … as suitable for the purpose.
3.68.2.1 Uses Permitted. Busways shall … 3.68.2.1 Uses Permitted. Busways shall… with
with 3.68.2.1(A) through (C). 3.68.2.1(A) through (C).
246
FPN: See 3.0.1.21 for information concerning the spread of
fire or products of combustion.

Page 9 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
3.68.2.1 Uses Permitted. 3.68.2.1 Uses Permitted.
(C) Through Walls and Floors. (C) Through Walls and Floors.
(2) Floors. (2) Floors.
247 (b) In other than industrial … by liquids that are (b) In other than industrial … by liquids that are
retained by the curb. retained by the curb.
FPN: See 3.0.1.21 for information concerning the spread of
fire or products of combustion.
3.68.2.47 Branches from Busways. 3.68.2.47 Branches from Busways.
(B) Cord and Cable Assemblies. Suitable … (B) Cord and Cable Assemblies. Suitable …
and 4.0.1.12 and the following conditions: and 4.0.1.12 and the following conditions:
248 (1) … (2) … (3) … (1) … (2) … (3) …
Strain relief cable grips shall be provided for (4) Strain relief cable grips shall be provided
the cord or cable at the busway plug-in device for the cord or cable at the busway plug-in
and equipment terminations. device and equipment terminations.
3.70.2.21 Securing and Supporting. 3.70.2.21 Securing and Supporting.
(A) Cablebus Supports. Cablebus shall … for (A) Cablebus Supports. Cablebus shall … for
the required span length. the required span length.
250
Conductor Supports. The insulated conductors (B) Conductor Supports. The insulated
shall be supported on blocks or other identified conductors shall be supported on blocks or other
mounting means. identified mounting means.
3.76.2.61 Extensions from Metal Wireways. 3.76.2.61 Extensions from Metal Wireways.
Extensions from wireways shall be made with Extensions from wireways shall be made with
254 cord pendants installed in accordance with cord pendants installed in accordance with
400.10 or with … 4.0.1.10 or with …
3.82.1.6 Listing Requirements. Concealable 3.82.1.6 Listing Requirements. Concealable
256 nonmetallic … extensions and devices. nonmetallic … extensions and devices.
(2) … (3) … (4) … (5) … (6) … (1) … (2) … (3) … (4) … (5) …
3.82.2.1 Uses Permitted. 3.82.2.1 Uses Permitted.
256 (A) From an Existing Outlet. The extension … (A) From an Existing Outlet. The extension …
with 250.130(C), 4.6.1.4(D)(2)(b), … with 2.50.7.1(C), 4.6.1.4(D)(2)(b), …
3.84.2.11 Size of Conductors. No conductor 3.84.2.12 Size of Conductors. No conductor
258 larger than that for which the raceway is listed larger than that for which the raceway is listed
shall be installed in strut-type channel raceways. shall be installed in strut-type channel raceways.
Section 3.92.2.71(A) Section 3.92.2.71(A)
Ampacity of Cables, Rated 2000 Volts or Ampacity of Cables, Rated 2000 Volts or
268 Less, in Cable Trays. Less, in Cable Trays.
FPN: See 1.10.1.14(C) for conductor temperature limitations FPN: See 1.10.1.15(C) for conductor temperature limitations
due to termination provisions. due to termination provisions.
3.96.3.21 Messenger. 3.96.2.21 Messenger.
(A) Support. The messenger shall be supported (A) Support. The messenger shall be supported
275
at dead ends and at intermediate locations so as at dead ends and at intermediate locations so as
to eliminate tension … to eliminate tension …

Page 10 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
Section 4.0.1.13 Splices. Section 4.0.1.13 Splices.
… spliced in accordance with 1.10.1.14(B) and … spliced in accordance with 1.10.1.15(B) and
286
the completed splice retains the insulation, outer the completed splice retains the insulation, outer
sheath properties, and … sheath properties, and …
Section 4.0.3.7 Splices and Terminations. Section 4.0.3.7 Splices and Terminations.
… are of the permanent molded, vulcanized … are of the permanent molded, vulcanized
288
types in accordance with 1.10.1.14(B). types in accordance with 1.10.1.15(B).
Terminations on … Terminations on …
Section 4.8.1.3(E)(1) Section 4.8.1.3(E)(1)
AC Phase Arrangement. AC Phase Arrangement.
301 FPN: See 1.10.1.15 for requirements on marking the busbar FPN: See 1.10.1.16 for requirements on marking the
or phase conductor having the higher voltage to ground where busbar or phase conductor having the higher voltage to ground
supplied from a 4-wire, delta-connected system. where supplied from a 4-wire, delta-connected system.
4.8.2.6 Grounding of Instruments, Relays, 4.8.2.7 Grounding of Instruments, Relays,
Meters, and Instrument Transformers on Meters, and Instrument Transformers on
302 Switchboards and Switchgear. Instruments, Switchboards and Switchgear. Instruments,
relays, meters, and instrument transformers relays, meters, and instrument transformers
located on switchboards and … located on switchboards and …
Section 4.10.6.9(D) Section 4.10.6.9(D)
Splices and Taps. No unnecessary splices or Splices and Taps. No unnecessary splices or
311 taps shall be made within or on a luminaire. taps shall be made within or on a luminaire.
FPN: For approved means of making connections, see FPN: For approved means of making connections, see
1.10.1.14. 1.10.1.15.
Section 4.27.3.6(B) Section 4.27.3.6(B)
Circuit Connections. Splices and terminations Circuit Connections. Splices and terminations
339 outside the thermal insulation shall be installed outside the thermal insulation shall be installed
in a box or fitting in accordance with 1.10.1.14 in a box or fitting in accordance with 1.10.1.15
and 3.0.1.15. and 3.0.1.15.
Section 4.30.2.1 General. Section 4.30.2.1 General.
347 (See last FPN) (See last FPN)
FPN: See 1.10.1.14(C) and 4.30.1.9(B) for equipment device FPN: See 1.10.1.15(C) and 4.30.1.9(B) for equipment device
terminal requirements. terminal requirements.
4.30.10.10 Branch-Circuit Short-Circuit 4.30.10.11 Branch-Circuit Short-Circuit
and Ground-Fault Protection for Single and Ground-Fault Protection for Single
367 Motor Circuits Containing Power Motor Circuits Containing Power
Conversion Equipment. Conversion Equipment.
4.30.10.11 Several Motors or Loads on One 4.30.10.12 Several Motors or Loads on One
367 Branch Circuit Including Power Conversion Branch Circuit Including Power Conversion
Equipment. For installations meeting … Equipment. For installations meeting …
4.60.2.1 Overcurrent Protection. 4.60.2.2 Overcurrent Protection.
394 (A) Provided to Detect and Interrupt Fault (A) Provided to Detect and Interrupt Fault
Current. A means shall be … Current. A means shall be …
5.5.1.6 Material Groups. 5.5.1.6 Material Groups.
441 FPN No. 1: Group I is intended for use in describing FPN No. 1: Group I is intended for use in describing
atmospheres that contain … This Code does not apply to atmospheres that contain … This Code does not apply to
installations underground in mines. See 1.0.1.2(B). installations underground in mines.

Page 11 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
On the right column of the page, just above “(5) (4) Where exhaust air is not recirculated, the
Limited Finishing Workstations”, the item “(3) interior of fresh air supply ducts and fresh air
Where exhaust air is not recirculated, the interior supply plenums shall be unclassified.
480 of fresh air supply ducts and fresh air supply
plenums shall be unclassified.”, should be
renumbered “(4)”.
5.16.1.16 Grounding. All metal raceways, the 5.16.3.12 Grounding. All metal raceways, the
metal armors or metallic sheath on cables, and all metal armors or metallic sheath on cables, and all
487 non–current- carrying metal parts of fixed or non–current- carrying metal parts of fixed or
portable … portable …
Item (I) Single-Pole Separable Connectors. is (I) Single-Pole Separable Connectors. Where
missing. Add as shown. single-pole portable cable connectors are used,
they shall be listed and of the locking type.
521
Sections 4.6.1.7 and 4.6.1.8 shall not apply to
listed single-pole separable connectors and
single-conductor cable assemblies utilizing
listed single-pole separable connectors.
521 (I) Supply Neutral Conductor. (J) Supply Neutral Conductor.
Section 5.51.4.11 Connection of Terminals Section 5.51.4.11 Connection of Terminals
and Splices. Conductor splices and connections and Splices. Conductor splices and connections
557 at terminals shall be in accordance with at terminals shall be in accordance with
1.10.1.14. 1.10.1.15.
Section 5.52.4.12 Connection of Terminals Section 5.52.4.12 Connection of Terminals
and Splices. Conductor splices and connections and Splices. Conductor splices and connections
571 at terminals shall be in accordance with at terminals shall be in accordance with
1.10.1.14. 1.10.1.15.
6.0.1.5 Branch Circuits. 6.0.1.5 Branch Circuits.
(B) Rating. (B) Rating.
582 (2) All Other Signs. Branch circuits that supply (2) All Other Signs. Branch circuits that supply
all other signs and outline lightiGng systems all other signs and outline lighting systems shall
shall be rated not to exceed 20 amperes. be rated not to exceed 20 amperes.
6.0.1.10 Portable or Mobile Signs. 6.0.1.10 Portable or Mobile Signs.
(C) Wet or Damp Location. Portable or mobile (C) Wet or Damp Location. Portable or mobile
584
signs in wet or damp locations shall comply with signs in wet or damp locations shall comply with
6.0.1.10(c)(1) and (c)(2). 6.0.1.10(C)(1) and (C)(2).
6.20.2.1 Insulation of Conductors. The 6.20.2.1 Insulation of Conductors. The
599 insulation of conductors shall comply with insulation of conductors shall comply with
6.20.2.1(a) through (d). 6.20.2.1(A) through (D).
6.20.3.1 Wiring Methods. 6.20.3.1 Wiring Methods.
(A) Elevators. (A) Elevators.
601
(1) Hoistways and Pits. (1) Hoistways and Pits.
(1) sFlexible cords and cables, or … (1) Flexible cords and cables, or …

Page 12 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
Section 6.94.4.1(B) Section 6.94.4.1(B)
Flexible Cords and Cables. Flexible Cords and Cables.
689 … Flexible, fine-stranded cables shall be … Flexible, fine-stranded cables shall be
terminated only with terminals, lugs, devices, or terminated only with terminals, lugs, devices, or
connectors in accordance with 1.10.1.14(A). connectors in accordance with 1.10.1.15(A).
6.95.1.3 Power Source(s) for Electric Motor- 6.95.1.3 Power Source(s) for Electric Motor-
Driven Fire Pumps. Driven Fire Pumps.
(A) (A)
691 (3) Dedicated Feeder. A dedicated feeder (3) Dedicated Feeder. A dedicated feeder
shall be permitted where it is derived from a shall be permitted where it is derived from a
service connection as described in service connection as described in
6.95.1.3(a)(1). 6.95.1.3(A)(1).
6.95.1.3 Power Source(s) for Electric Motor- 6.95.1.3 Power Source(s) for Electric Motor-
Driven Fire Pumps. Driven Fire Pumps.
691 (B) Multiple Sources. If reliable power cannot (B) Multiple Sources. If reliable power cannot
be obtained from a source described in be obtained from a source described in
6.95.1.3(a), power … 6.95.1.3(A), power …
6.95.1.17 Voltage Drop. 6.95.1.7 Voltage Drop.
695 (A) Starting. The voltage at the fire pump (A) Starting. The voltage at the fire pump
controller line terminals … controller line terminals …
7.5.2.37 Ampacity of Neutral Conductor. 7.5.2.36 Ampacity of Neutral Conductor.
714 The ampacity of the neutral conductors shall The ampacity of the neutral conductors shall
comply with either (A) or (B). comply with either (A) or (B).
Section 7.6.3.3 Battery Interconnections. Section 7.6.3.3 Battery Interconnections.
… Flexible, fine-stranded cables shall only be … Flexible, fine-stranded cables shall only be
720
used with terminals, lugs, devices, or connectors used with terminals, lugs, devices, or connectors
in accordance with 1.10.1.14. in accordance with 1.10.1.15.
8.0.1.1 Scope. This article covers 8.0.1.1 Scope. This article covers
communications circuits and equipment. communications circuits and equipment.
767 FPN No. 1: See 1.0.1.2(B)(4) for installations of FPN No. 1: Installations of communications facilities and
communications circuits and equipment that are not covered. equipment under the exclusive control of communications
utilities are not included in the scope.
8.0.1.2 Definitions. See Part 1.0.1. For the 8.0.1.2 Definitions. See Part 1.1.1. For the
767 purposes of this article, the following additional purposes of this article, the following additional
definitions apply. definitions apply.
8.0.1.2 Definitions. 8.0.1.2 Definitions.
Exposed (to Accidental Contact). A circuit that Exposed (to Accidental Contact). A circuit that
767
is in such … another circuit may result. is in such … another circuit may result.
FPN: See Part 1.0.1 for two other definitions of Exposed. FPN: See Part 1.1.1 for two other definitions of Exposed.
8.0.5.1 Raceways and Cable Routing … 8.0.5.1 Raceways and Cable Routing …
773 (a) Types of Raceways. Communications wires (A) Types of Raceways. Communications wires
and cables shall be permitted … and cables shall be permitted …

Page 13 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
8.0.5.1 Raceways and Cable Routing … 8.0.5.1 Raceways and Cable Routing …
(A) Types of Raceways. (A) Types of Raceways.
773 (2) Communications Raceways. (2) Communications Raceways.
Communications wires and cables … with the Communications wires and cables … with the
provisions of Table 8.0.5.45, listed in … provisions of Table 8.0.5.45(B), listed in …
8.0.5.4 Installation of Communications Wires, 8.0.5.4 Installation of Communications Wires,
Cables and Raceways, … Cables and Raceways, …
774
… cable routing assemblies shall comply with … cable routing assemblies shall comply with
8.0.5.4(a) through (l). Installation of … 8.0.5.4(A) through (L). Installation of …
8.0.5.4 Installation of Communications Wires, 8.0.5.4 Installation of Communications Wires,
Cables and Raceways, … Cables and Raceways, …
776 (J) Other Building Locations. The following (J) Other Building Locations. The following
wires, cables, raceways, and cable … locations wires, cables, raceways, and cable … locations
covered in 8.0.5.4(b) through (i): covered in 8.0.5.4(B) through (I):
Table title: Table title:
778
Table 8.0.5.45(d) Cable Substitutions Table 8.0.5.45(D) Cable Substitutions
8.0.5.1 Equipment. Communications 8.0.6.1 Equipment. Communications
equipment shall be listed as being suitable for equipment shall be listed as being suitable for
778 electrical connection to a communications electrical connection to a communications
network. network.
Table title: Table title:
Table 8.0.5.45(a) Applications of Listed Table 8.0.5.45(A) Applications of Listed
779
Communications Wires and Cables in Communications Wires and Cables in
Buildings Buildings
Table title: Table title:
780 Table 8.0.5.45(b) Applications of Listed Table 8.0.5.45(B) Applications of Listed
Communications Raceways in Buildings Communications Raceways in Buildings
Table title: Table title:
781 Table 8.0.5.45(c) Applications of Listed Cable Table 8.0.5.45(C) Applications of Listed
Routing Assemblies in Buildings Cable Routing Assemblies in Buildings
8.0.6.13 Cable Routing Assemblies … 8.0.6.13 Cable Routing Assemblies …
Cable routing assemblies and … with Table Cable routing assemblies and … with Table
782
8.0.6.13(a). Communications raceways shall be 8.0.6.13(A). Communications raceways shall be
marked in accordance with Table 8.0.6.13(b). marked in accordance with Table 8.0.6.13(B).
Table title: Table title:
783 Table 8.0.6.13(a) Cable Routing Assembly Table 8.0.6.13(A) Cable Routing Assembly
Markings Markings
Table title: Table title:
783 Table 8.0.6.13(b) Communications Raceway Table 8.0.6.13(B) Communications Raceway
Markings Markings
8.10.1.3 Other Articles. Wiring from the source 8.10.1.3 Other Articles. Wiring from the source
783 … equipment shall comply with Article 640. … equipment shall comply with Article 6.40.
Coaxial cables … Coaxial cables …

Page 14 of 15
SUPPLEMENT 09/2018
Table of Corrections

Description
Page
As Printed Correction
8.20.5.1 Raceways and Cable Routing … 8.20.5.1 Raceways and Cable Routing …
(C) Cable Routing Assemblies. Coaxial cables (C) Cable Routing Assemblies. Coaxial cables
793
… in accordance with Table 8.0.5.45(c), listed in … in accordance with Table 8.0.5.45(C), listed
accordance with … in accordance with …
Table title: Table title:
796 Table 8.20.5.45(a) Applications of Listed Table 8.20.5.45(A) Applications of Listed
Coaxial Cables in Buildings Coaxial Cables in Buildings
Table title: Table title:
797 Table 8.20.5.45(b) Coaxial Cable Uses and Table 8.20.5.45(B) Coaxial Cable Uses and
Permitted Substitutions Permitted Substitutions
8.30.1.1 Scope. This article covers network- 8.30.1.1 Scope. This article covers network-
powered broadband … powered broadband …
797 FPN No. 2: See 1.0.1.2(B)(4) for installations of broadband FPN No. 2: Installations of communications facilities and
communications systems that are not covered. equipment under the exclusive control of communications
utilities are not included in the scope.
8.30.1.2 Definitions. See Part 1.0.1. For 8.30.1.2 Definitions. See Part 1.1.1. For
797 purposes of this article, the following additional purposes of this article, the following additional
definitions apply. definitions apply.
8.30.1.2 Definitions. 8.30.1.2 Definitions.
Exposed (to Accidental Contact). A circuit in Exposed (to Accidental Contact). A circuit in
798 such … another circuit may result. such … another circuit may result.
FPN: See Part 1.0.1 for two other definitions of Exposed. FPN: See Part 1.1.1 for two other definitions of Exposed.
Exposed (as applied to live parts) and Exposed (as applied to Exposed (as applied to live parts) and Exposed (as applied to
wiring methods). wiring methods).
8.30.5.1 Raceways and Cable Routing … 8.30.5.1 Raceways and Cable Routing …
(A) Types of Raceways. (A) Types of Raceways.
806 (2) Communications Raceways. Low- (2) Communications Raceways. Low-
power network-powered … in accordance with power network-powered … in accordance with
Table 8.0.5.45, listed in accordance with … Table 8.0.5.45(B), listed in accordance with …
8.30.5.1 Raceways and Cable Routing … 8.30.5.1 Raceways and Cable Routing …
(C) Cable Routing Assemblies. Low-power (C) Cable Routing Assemblies. Low-power
806
network-powered … in accordance with Table network-powered … in accordance with Table
8.0.5.45(c), listed in … 8.0.5.45(C), listed in …
Table title: Table title:
Table 8.30.5.45(a) Applications of Network- Table 8.30.5.45(A) Applications of Network-
810
Powered Broadband Cables in Buildings Powered Broadband Cables in Buildings

Table title: Table title:


810 Table 8.30.5.45(b) Cable Substitutions Table 8.30.5.45(B) Cable Substitutions

8.40.6.11 Grounding Devices. Where bonding 8.40.7.11 Grounding Devices. Where bonding
or grounding is required, devices used to connect or grounding is required, devices used to connect
815
a shield, a sheath, or non–current-carrying a shield, a sheath, or non–current-carrying
metallic … metallic …