Professional Documents
Culture Documents
© 1999 American Standard Inc. All rights reserved Volume 28, No. 1 ■
Table 1 Table 2
Weighting Of Part-Load Points IPLV/NPLV Equation And Rating Conditions From ARI Standard 550/590–1998
Weighting, % Expression Of Chiller Efficiency Equation
Part-Load
Point, % 1992 Standard 1998 Standard Coefficient Of Performance–COP, W/W,
or Energy Efficiency Ratio–EER, Btu/h/W IPLV or NPLV = 0.01A + 0.42B + 0.45C + 0.12D
100 17 1
75 39 42 Power Per Ton, kW/ton 1
IPLV or NPLV = -------------------------------------------------------------------
0.01 0.42 0.45 0.12
50 33 45 ----------- + ----------- + ----------- + -----------
A B C D
25 11 12
Chiller Energy Efficiency, Load
A at 100% B at 75% C at 50% D at 25% — at 0%
The combined Standard also replaces the IPLV Rating Conditions
Application Part Load Value (APLV) with a Condenser, water-cooled only:a
Non-Standard Part Load Value (NPLV) for Entering water temperature, F [C] 85 [29.4]b 75 [23.9] 65 [18.3] 65 [18.3] 65 [18.3]
any chiller that cannot operate at ARI Flow rate, gpm/ton [Lps per kW] 3.0 [0.054]c
standard rating conditions for part load. Fouling factor, h·ft2·F/Btu [m2·C/W] 0.00025 [0.000044]
Evaporator:
Table 2 summarizes ARI Standard 550/ Leaving water temperature, F [C] 44 [6.7]b — — — 44 [6.7]
590–1998’s IPLV and NPLV parameters Flow rate, gpm/ton [Lps per kW] 2.4 [0.043]c — — — 2.4 [0.043]
for water-cooled chillers. Of course, a Fouling factor, h·ft2·F/Btu [m2·C/W] 0.0001[0.000018]
building-specific analysis remains the NPLV Rating Conditions
most accurate energy prediction tool.
Condenser, water-cooled only:a
Entering water temperature, F [C] As selectedb — d 65 [18.3] 65 [18.3] 65 [18.3]
Its Effect… When comparing
Flow rate, gpm/ton [Lps per kW] As selectedc
equipment, remember that the IPLV
Fouling factor, h·ft2·F/Btu [m2·C/W] As specified
rating is only valid for chillers expected to
Evaporator:
run at standard IPLV rating conditions…
Leaving water temperature, F [C] As selectedb — — — —
despite the fact that IPLVs and NPLVs are
Flow rate, gpm/ton [Lps per kW] As selectedc — — — —
derived from the same equation using
Fouling factor, h·ft2·F/Btu [m2·C/W] As specified
the same part-load weightings. More
importantly, IPLV/NPLV ratings a If the chiller manufacturer’s recommended minimum entering-condenser water temperature, ECWT, is greater than that
specified above, then it may be used in lieu of the specified value.
describe average, stand-alone chiller b Corrected for fouling-factor allowance by using the calculation method described in C6.3 of ARI Standard 550/590–1998.
performance. Appendix D of ARI c Flow rates are to be held constant at full-load values for all part-load conditions.
Standard 550/590–1998 explains this d For part-load ECWTs, the temperature should vary linearly from the selected ECWT to 65F [18.3C] for loads ranging from
100% to 50%, and should be fixed at 65F [18.3C] for loads ranging from 50% to 0%.
caveat:
80 6000
ARI Standard Annual
550–1992 Operating
Hours 4000
75
Percentage Of
System Design Load
70 2000
ARI Standard
550/590–1998
65 0
100 90 80 70 60 50 40 30 20 10
99/95 F 94/90 F 89/85 F 84/80 F 79/75 F 74/70 F 69/65 F 64/60 F 59/55 F 54/50 F
60
Percentage Of System Design Load By Weather Bin
0 25 50 75 100
optimal system operation. Load, ambient Percentage Of Chiller Capacity By Weather Bin Lead chiller
conditions and the part-load operating Lag chiller
characteristics of the chiller and tower
chiller plant and deliver the greatest considered an 800-ton chilled water
will ultimately determine the optimum
possible energy cost savings, the plant with a system profile defined in
ECWT for a given installation.
designer must account for these facts: terms of weather bins, as summarized in
Figure 2. In the first example, the load
[Engineers Newsletter Vol.24–No.1 ■ Variables other than outdoor air dry
was evenly split between two chillers.
explored the effect of ECWT and bulb—e.g. humidity, solar loads,
optimized tower control on total system operation schedules, use of integrated
Like most plants, the chillers were piped
energy consumption.—Editor] economizers—greatly affect cooling
in parallel so that both would “see”
loads in commercial and industrial
equal loads as long as they produced the
applications.
same system-supply water temperature.
■ System loads and individual chiller In that scenario, any system load greater
Plants With Multiple Chillers loads in multiple-chiller plants are than 400 tons required the operation of
ARI data shows that more than distinctly different. both chillers. As long as the system load
80 percent of all chillers are installed in was 45 percent, the lead chiller operated
multiple-chiller plants. ARI Standard 550/ ■ Changing loads affect cooling-tower alone and at 90 percent of its capacity.
590–1998 specifically advises that a operation and entering-condenser The lag chiller only ran when the system
comprehensive analysis be used to water temperatures. load exceeded 50 percent.
predict system performance. It also
cautions that “individual chillers The December 1996 Engineers Figure 3 illustrates the individual load
operating within multiple chiller systems Newsletter, “‘Off-Design’ Chiller profiles of each chiller. Notice that the
are more heavily loaded than single Performance,” demonstrates that a lead chiller runs at full capacity about
chillers within single chiller systems.” weather-versus-time system load profile 20 percent of its annual running time…a
bears little resemblance to the load far cry from the less than 1 percent
The upshot is this: To successfully profiles of individual chillers in a suggested by the actual system load
optimize the performance of a multiple- multiple-chiller plant. That publication profile depicted in Figure 2!
Figure 4
Individual Profiles Of Chillers Sized For Equal Operating Hours
The 1996 newsletter then examined the charges have been as much as Develop a basic system load profile
effect of redesigning the same system to $1.86/kWh. using a computerized analysis tool.
equalize the annual operating hours with
a 60/40 split in chiller capacity. This shift Investigate the case for dividing the
in design strategy not only lowered the system load unevenly. Though
first cost of the system, but also cut Recap popular, splitting the load equally
operating costs and total run time. seldom yields the most efficient or
Like its predecessors, ARI Standard 550/
least expensive system operation.
590–1998 establishes requirements for
Don’t Forget Full-Load Efficiency. rating and testing chillers, and thereby
Figure 4 suggests the relevance of that Perform a comprehensive energy
creates a method for representing chiller analysis to estimate system
example to our current discussion of capacity and performance at a set of
chiller performance. A quick comparison operating costs. TRACE® 600 or
standard conditions. Changes DOE-2 software can help.
of profiles reveals that each chiller now implemented in the 1998 Standard
runs at full capacity about 25 percent of attempt to improve that representation
its annual operating hours. When writing specifications:
and promote consistent rating and Specify an evaporator fouling factor
testing methods for all chiller types and allowance of either 0.00010 h·ft2·F/
The disparity between the part-load sizes. How do these changes affect rated
weightings in Figures 3 and 4 clearly Btu for standard ARI rating
performance? It varies from one chiller to conditions or a value that better
demonstrates why the standard IPLV the next, but on average, expect a 12-
equation may poorly predict system represents your application.
percent reduction in IPLV ratings.
operating costs, especially in multiple- However, this improvement does not Specify the condenser relief
chiller plants. But there are other reasons extend to actual performance. schedule per ARI Standard 550/
to specify full-load kilowatts per ton:
590–1998 or a relief schedule that
■ To comply with ASHRAE Standard Remember that the ARI rating is a better represents the application.
90.1–1989R, the chillers must satisfy standardized representation. Most
minimum full-load and part-load chillers, i.e. about 75 percent, do not run Specify full-load COP and part-load
efficiency ratings. at ARI standard rating conditions and IPLV efficiencies that satisfy the
less than 20 percent of large-tonnage minimum ratings ASHRAE Standard
■ Utility pricing is volatile. Though real- chillers are applied in single-chiller 90.1–1989R requires.
time pricing eliminates demand installations. Given the distinct
charges during peak utility periods, differences between system and chiller
these prices still reflect demand and load profiles in multiple-chiller plants, To comment on this article, send a note to
may escalate from 5¢ to 75¢/kWh. expect significant differences between The Trane Company, Engineers Newsletter
Under some programs, real-time ARI-rated performance and the actual Editor, 3600 Pammel Creek Road, La Crosse
performance of a specific chiller in a WI 54601, or visit www.trane.com. Back
specific application. ■ issues of recent Engineers Newsletters,
including the December 1996 cited here,
are available on our Web site.
By Andy Poselenzny, marketing engineer,
Printed on recycled paper as part of and Brenda Bradley, information For more information about ARI Standard
The Trane Company’s recycling program. designer, The Trane Company. 550/590–1998, visit www.ari.org.
■ 4 ENEWS-28/1