Rapidus Power Factor Controller

• Moduler design
• No connector cables
• No fixing screws
• State of the art technology

Easy mounting on panels


connection to system
Dynamic Capacitor Monitoring
• DCM is a supreme function in Rapidus which enables the user to make pro-active maintenance for compensation cabinets.
• DCM tracks the real time KVAR values of each capacitor and uses the measured KVAR value in compensation calculations.
• If a contactor is broken or a capacitor is out of order, DCM will detect it within 1 or 2 days* and activate the alarm for user.
• DCM has 3,4% accuracy.

* This information is valid for 3 shift operating facilities.

Initial Values

Alarm Level Setup

Contactors C1 C2 C3 C4

Alarm Level %20

5 kvar 10 kvar 10 kvar 20 kvar

After a certain time


Alarm screen indicates the status of 3rd and 4rd steps

Remotely monitor actual


kvar values of each step
in addition to DCM alarms
MOBDUS - RS 485
Pro active maintenance

Highly sensitive compensation


due to realtime kvar
measurements of the steps

Contactors C1 C2 C3 C4

Alarm Level %20

3 kvar 3 kvar 1 kvar 0 kvar

Means Means capacitor is out of order

capacitor should or contactor is out of order


be changed or cable connection problem
or fuse blown
Capacitor/Reactor---1P/3P
• Rapidus can be connected to either single or three phase capacitors or reactors.
• Rapidus can be used in Data Centers or Mining Areas where the load is frequently capacitive.
• Rapidus can be used with a selection of capacitors and reactors in single or three phase connections.

Mono Phase
3 Phase Reactor 1 Phase Reactor 3 Phase Capacitor Capacitor 3 Phase Capacitor

- Fig. A - Fig. B

V1 V1
V2 V2
V3 V3
N N

Advanced Learning Function


• Rapidus can learn the connections and capacitor
or reactor values.
• If there is a fault in the CT or VT connections,
Rapidus detects the fault and corrects it.
It shows the fault on the screen.
L3 K3 L2 K2 L1 K1 V1 V2 V3 N K3 L3 L2 K2 K1 L1 V1 V3 V2 N

Correct connection Wrong connection

Advanced Learning Function

Rapidus detects the wrong connections after learning mode is activated.


Connections are displayed on the screen. Rapidus don't take misconnections into consideration and
operates as if all connections are properly made as shown in Fig A.
Rapidus learns all step values regardless they are capacitor or reactor.
Rapidus = PFC + Energy Analyzer
• In standart compensation cabinets, there are always a multimeter or analyzer to be associated with a power factor controller.
Rapidus, as a two-in-one device meets both requirements of the industry.
• User can reduce the cost of analyzer, wiring and labor by choosing Rapidus.

Saving On
• Extra multimeter / analyzer cost
• Wiring cost
• Labor cost

Rapidus as an Energy Analyzer


Rapidus can measure and monitor the following parameters :

• All electrical parameters


• Min, Max and Average Values for
Hour, Day and Month
• Harmonics upto 51 st
• Demand
• Phasor Diagram

Data Logging
• Rapidus measures 68 different energy parameters.
• Rapidus logs 80 days hourly
240 days daily
36 months monthly real time measurements of 68 parameters.
• Rapidus logs demand values for P. Q, S, I
• Rapidus logs 50 recent alarms with time stamp.
• 1 MB Memory
100 A

Surge Withstand 100 A/1 sec 5A


1 sec.
Rapidus current inputs can withstand surges upto 100 A for 1 second.

In case of a current rise in the secondary winding of the current


transformer, current inputs of the PFC should withstand to these peak
values. If not, current transformer may explode due to open circuit in the
secondary winding.

This may result with shutdown of the compensation system and


compensation penalty for the end-user.

Accuracy Class (0,2s)


Function
Performance Class Other
Function According to IEC Complementary
Symbol Function 61557-12 Measuring Range Characteristics

P Total active power 0,2 10 % Ib ≤ I ≤ Imax 0,5 Ind to 0,8 Cap -

QV Total reactive power 1 5 % Ib ≤ I ≤ Imax 0,25 Ind to 0,25 Cap -


SA Total apparent power 0,2 10 % Ib ≤ I ≤ Imax 0,5 Ind to 0,8 Cap -
EA Total active energy 0,2 0 to 49999999999 IEC 62053-22 Class 0.2S
ERV Total reactive energy 2 0 to 49999999999 IEC 62053-23 Class 2
f Frequency 0,05 45 - 65 Hz -
I Phase current 0,2 20 % Ib ≤ I ≤ Imax -
INc Neutral current 0,5 20 % Ib ≤ I ≤ Imax -
U Voltage 0,2 Umin ≤ U ≤ Umax -
PFA Power factor 0,5 0,5 Ind to 0,8 Cap -
THDV Total harmonic distortion voltage 1 0 % to 20 % -
THDI Total harmonic distortion current 1 0 % to 100 % -

Other Features
• Graphical LCD
• Language Support
• Harmonics Measurement upto 51
• Advanced Alarm Settings
• Real Time Clock
Rapidus Product Selection Chart
606006 RAPIDUS 231R-E 606007 RAPIDUS 232R-E 606011 RAPIDUS 211R 606014 RAPIDUS 212R 606020 RAPIDUS 218R
General
Graphical LCD 6 buttons * * * * *
Password Protection * * * * *
Measurement Type 3 Phase 3 Phase 1 Phase 1 Phase 1 Phase
Supply Voltage AC 95-272 V AC 95-272 V AC 95-272 V AC 95-272 V AC 95-272 V AC
Supply Voltage DC 95-272 V AC 95-272 V AC 95-272 V AC 95-272 V AC 95-272 V AC
Day/Night Input 85-265 V AC 85-265 V AC 85-265 V AC 85-265 V AC 85-265 V AC
Number of Steps 1-12 Selectable 1-24 Selectable 1-12 Selectable 1-24 Selectable 1-8 Selectable
Current Transformer Ratio 1-5000 A 1-5000 A 1-5000 A 1-5000 A 1-5000 A
Voltage Transformer Ratio 1-5000 A 1-5000 A 1-5000 A 1-5000 A 1-5000 A
Connection Type 3P4W 3P4W 3P4W 3P4W 3P4W
Type of Switching Relay Relay Relay Relay Relay
Target cosQ 0,80--1,00 Inductive or Capacitive 0,80--1,00 Inductive or Capacitive 0,80--1,00 Inductive or Capacitive 0,80--1,00 Inductive or Capacitive 0,80--1,00 Inductive or Capacitive
Accuracy Class Voltage 0.2 0.2 0.2 0.2 0.2
Accuracy Class Current 0.2 0.2 0.2 0.2 0.2
Accuracy Class Active Energy 0.5 0.5 0.5 0.5 0.5
Number of Measurement in a period 512 512 512 512 512
Power Consumption < 10VA < 10VA < 10VA < 10VA < 10VA
Power Quality Measurements
Harmonics / current and voltage Upto 51st Upto 51st Upto 51st Upto 51st Upto 51st
THD-Voltage in % * * * * *
THD-Current in % * * * * *
Phasor Diagram * * * * *
Data Logging
Average, Minimum, Maximum Values * * * * *
Alarms * * * * *
Time Stamp * * * * *
Voltage Measurement Input (Supply and
Measurement Inputs are the same node)
Overvoltage Category 300 V Cat III 300 V Cat III 300 V Cat III 300 V Cat III 300 V Cat III
Measured Range L-N 95-272 Vrms 95-272 Vrms 95-272 Vrms 95-272 Vrms 95-272 Vrms
Measured Range L-L 165-470 Vrms 165-470 Vrms 165-470 Vrms 165-470 Vrms 165-470 Vrms
Measured Frequency Range 45-65 Hz 45-65 Hz 45-65 Hz 45-65 Hz 45-65 Hz
Power Consumption <0.1 VA <0.1 VA <0.1 VA <0.1 VA <0.1 VA
Sampling Freq.between 45-65 Hz 25,6 kHz 25,6 kHz 25,6 kHz 25,6 kHz 25,6 kHz
Current Measurement Input
Rated Current 6A 6A 6A 6A 6A
Measurement Range 0.01-6A 0.01-6A 0.01-6A 0.01-6A 0.01-6A
Overvoltage Category 300 V Cat II 300 V Cat II 300 V Cat II 300 V Cat II 300 V Cat II
Measurement Surge Voltage 2 kV 2 kV 2 kV 2 kV 2 kV
Power Consumption <0.2 VA <0.2 VA <0.2 VA <0.2 VA <0.2 VA
Peak current for 1 sec 100 A 100 A 100 A 100 A 100 A
Sampling Freq.between 45-65 Hz 25,6 kHz 25,6 kHz 25,6 kHz 25,6 kHz 25,6 kHz
Input Outputs
• Relay Outputs 12 24 12 24 8
Max. Switching Current 2A 2A 2A 2A 2A
Max. Switching Voltage 250 VAC 250 VAC 250 VAC 250 VAC 250 VAC
Max. Switching Power for a Single Relay 1250 VA 1250 VA 1250 VA 1250 VA 1250 VA
• Alarm Relay Outputs 2 2 2 2 2
Max. Switching Current 4A 4A 4A 4A 4A
Max. Switching Voltage 250 VAC 250 VAC 250 VAC 250 VAC 250 VAC
Max. Switching Power 1000 VA 1000 VA 1000 VA 1000 VA 1000 VA
• GEN Input 1 1 1 1 1
Input range 85 - 265 VAC 85 - 265 VAC 85 - 265 VAC 85 - 265 VAC 85 - 265 VAC
Mechanical Properties
Weight 0,670 kg 0,765 kg 0,653 kg 0,750 kg 0,415 kg
Protection Class IP 40 front, IP 20 rear IP 40 front, IP 20 rear IP 40 front, IP 20 rear IP 40 front, IP 20 rear IP 40 front, IP 20 rear
Assembly Type Panel Mount Panel Mount Panel Mount Panel Mount Panel Mount
Dimensions W144xH144xD78 W144xH144xD78 W144xH144xD78 W144xH144xD78 W96xH96xD72
• Cable Cross Sections
Voltage, Current, All Relay Outputs, Gen Input
Stranded: 2,5 mm2 - 14AWG 2,5 mm2 - 14AWG 2,5 mm2 - 14AWG 2,5 mm2 - 14AWG 2,5 mm2 - 14AWG
Solid: 4mm2 - 12 AWG 4mm2 - 12 AWG 4mm2 - 12 AWG 4mm2 - 12 AWG 4mm2 - 12 AWG
2x1.5 mm2 - 2x16 AWG 2x1.5 mm2 - 2x16 AWG 2x1.5 mm2 - 2x16 AWG 2x1.5 mm2 - 2x16 AWG 2x1.5 mm2 - 2x16 AWG

RS 485 1,5 mm2 - 16AWG 1,5 mm2 - 16AWG 1,5 mm2 - 16AWG 1,5 mm2 - 16AWG 1,5 mm2 - 16AWG
Stranded: 1.5 mm2 - 16 AWG 1.5 mm2 - 16 AWG 1.5 mm2 - 16 AWG 1.5 mm2 - 16 AWG 1.5 mm2 - 16 AWG
Solid: 2x0.75 mm2 - 2x18 AWG 2x0.75 mm2 - 2x18 AWG 2x0.75 mm2 - 2x18 AWG 2x0.75 mm2 - 2x18 AWG 2x0.75 mm2 - 2x18 AWG
Ambient Conditions
Operating Temperature -20 C …. +60 C.. -20 C …. +60 C.. -20 C …. +60 C.. -20 C …. +60 C.. -20 C …. +60 C..
Storage Temperature -30 C …. +80 C.. -30 C …. +80 C.. -30 C …. +80 C.. -30 C …. +80 C.. -30 C …. +80 C..
Relative Humidity (no condensation) 95% 95% 95% 95% 95%
Communication and Others
Modbus RTU * * * * *
Battery * * * * *
Real Time Clock * * * * *
Standarts in Compliance
Safety requirements for electrical equipment 300 VAC CAT III acc. to IEC 61010-1 300 VAC CAT III acc. to IEC 61010-1 300 VAC CAT III acc. to IEC 61010-1 300 VAC CAT III acc. to IEC 61010-1 300 VAC CAT III acc. to IEC 61010-1
for measurement, control, and laboratory use
Dimensions (mm)

144 7.0
58.0

144

137
Wiring Diagrams

Gen Input

Gen Input

Rapidus 12 Relays (606 011)