You are on page 1of 20

Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT

GPI Project No.: 2021 - 006


Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-1 NS depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 793.00 65.90 12.00 22.70
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 425.00 54.30 7.82 29.50
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 474.00 65.20 7.27 41.10
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 340.00 60.20 5.64 63.80
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 284.00 59.50 4.77 89.90
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 237.00 59.20 4.00 151.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 274.00 86.70 3.16 179.00

"a" 0.30 0.60 0.90 1.80 3.00 6.00 9.00


AVE (Ω-M) 22.90 31.05 41.60 62.90 93.05 150.50 181.50
AVE (Ω) 12.10 8.24 7.36 5.56 4.94 3.99 3.21
Average Value (Orthogonal Measurements)
(Ω-M) (Ω)
TSR Average 72.94 5.67

1
Not required if using AGI meters.
Note: Due to soil conductivity, the electrode depth may have to be increased. However, electrode depth shall not exceed 10% of “a” spacing.
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-1 EW depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 946.00 77.30 12.20 23.10
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 691.00 79.80 8.66 32.60
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 448.00 60.10 7.45 42.10
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 369.00 67.40 5.48 62.00
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 339.00 66.40 5.11 96.20
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 212.00 53.40 3.97 150.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 146.00 44.90 3.25 184.00

Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
1 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-2 NS depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage Injected, I Resistance Resistivity
(m)
Depth Depth 0 (V) (mV) 1 (mA) (Ohm) (Ohm-m)
(cm) (cm) (m) (m) (m) (m)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 912.00 79.20 11.50 21.70
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 899.00 98.70 9.11 34.40
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 857.00 95.10 9.01 51.00
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 528.00 68.10 7.74 87.60
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 455.00 74.80 6.09 115.00
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 426.00 84.80 5.03 190.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 252.00 64.40 3.91 221.00

"a" 0.30 0.60 0.90 1.80 3.00 6.00 9.00


AVE (Ω-M) 22.10 35.05 50.20 86.20 119.00 183.00 221.00
AVE (Ω) 11.70 9.30 8.88 7.62 6.31 4.85 3.91
Average Value (Orthogonal Measurements)
(Ω-M) (Ω)
TSR Average 89.57 6.57
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-2 EW depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage Injected, I Resistance Resistivity
(m)
Depth Depth 0 (V) (mV) 1 (mA) (Ohm) (Ohm-m)
(cm) (cm) (m) (m) (m) (m)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 1.23 104.00 11.90 22.5
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 792.00 83.50 9.48 35.7
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 703.00 80.40 8.74 49.4
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 513.00 68.40 7.50 84.8
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 357.00 54.70 6.53 123
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 211.00 45.30 4.67 176
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 204.00 52.10 3.91 221

Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
2 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-3 NS depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 1.48 89.80 15.50 31.10
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 903.00 85.50 10.60 39.80
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 861.00 93.80 9.18 51.90
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 537.00 71.10 7.56 85.50
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 473.00 84.40 5.60 106.00
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 246.00 71.20 3.45 130.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 215.00 82.60 2.61 147.00

"a" 0.30 0.60 0.90 1.80 3.00 6.00 9.00


AVE (Ω-M) 26.90 34.65 46.50 74.65 97.95 140.50 163.00
AVE (Ω) 13.75 9.21 8.23 6.60 5.19 3.73 2.89
Average Value (Orthogonal Measurements)

TSR Average 78.83 6.20


Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using
the 4-point Wenner-Test- Configuration, wherein the four
Project Location: Ilijan, Batangas
(4) probes are spaced at equal distances to approximate
Date: 08/07/2021
the depth of the soil to be tested. Each VES point is
Measurement No. & Orientation: TSR-3 EW labeled TSR-1, 2, . . . . . 10 as in Test Shallow
Description of Terrain & Probe Resistivity. TSR () NS and TSR ( ) EW is aligned
Hilly, Coastal Ridge - 2.5 to 15 cm.
Insertion: towards north-south and east-west direction,
Weather (Present and Recent): SUNNY and FAIR respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 793.00 65.90 12.00 22.70
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 425.00 54.30 7.82 29.50
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 474.00 65.20 7.27 41.10
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 340.00 60.20 5.64 63.80
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 284.00 59.50 4.77 89.90
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 237.00 59.20 4.00 151.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 274.00 86.70 3.16 179.00

Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
3 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using
Project Location: Ilijan, Batangas the 4-point Wenner-Test- Configuration, wherein the four
(4) probes are spaced at equal distances to approximate
Date: 08/07/2021
the depth of the soil to be tested. Each VES point is
Measurement No. & Orientation: TSR-4 NS
labeled TSR-1, 2, . . . . . 10 as in Test Shallow
Description of Terrain & Probe Resistivity. TSR () NS and TSR ( ) EW is aligned
Hilly, Coastal Ridge - 2.5 to 15 cm.
Insertion: towards north-south and east-west direction,
Weather (Present and Recent): SUNNY and FAIR respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 850.00 119.00 7.12 13.40
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 607.00 120.00 5.03 19.00
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 486.00 105.00 4.62 26.10
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 457.00 110.00 4.17 47.10
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 433.00 111.00 3.90 73.50
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 247.00 78.40 3.47 131.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 239.00 88.30 2.71 153.00

"a" 0.30 0.60 0.90 1.80 3.00 6.00 9.00


AVE (Ω-M) 13.20 19.75 26.60 47.20 74.60 122.00 134.50
AVE (Ω) 7.00 5.24 4.71 4.18 3.96 3.24 2.38
Average Value (Orthogonal Measurements)

TSR Average 54.73 3.84


Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-4 EW depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 902.00 131.00 6.88 13.00
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 676.00 124.00 5.44 20.50
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 550.00 115.00 4.79 27.10
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 485.00 116.00 4.18 47.30
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 453.00 113.00 4.02 75.70
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 292.00 97.20 3.00 113.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 223.00 109.00 2.05 116.00

Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
4 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-5 NS depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 1.07 90.30 11.80 22.30
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 557.00 74.50 7.48 28.20
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 490.00 88.30 5.56 31.40
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 280.00 84.80 3.30 37.40
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 201.00 83.60 2.40 45.30
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 162.00 90.30 1.80 67.70
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 177.00 108.00 1.64 92.50

"a" 0.30 0.60 0.90 1.80 3.00 6.00 9.00


AVE (Ω-M) 22.35 29.70 32.90 36.75 44.20 68.70 93.60
AVE (Ω) 11.85 7.89 5.82 3.25 2.35 1.83 1.66
Average Value (Orthogonal Measurements)

TSR Average 41.03 4.33


Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-5 EW depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 1.13 94.80 11.90 22.40
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 694.00 83.80 8.29 31.20
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 639.00 105.00 6.08 34.40
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 2.76 86.50 3.19 36.10
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 199.00 87.30 2.29 43.10
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 180.00 97.40 1.85 69.70
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 166.00 99.10 1.68 94.70

Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
5 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using
Project Location: Ilijan, Batangas
the 4-point Wenner-Test- Configuration, wherein the four
(4) probes are spaced at equal distances to approximate
Date: 08/07/2021
the depth of the soil to be tested. Each VES point is
Measurement No. & Orientation: TSR-6 NS labeled TSR-1, 2, . . . . . 10 as in Test Shallow
Description of Terrain & Probe Resistivity. TSR () NS and TSR ( ) EW is aligned
Hilly, Coastal Ridge - 2.5 to 15 cm.
Insertion: towards north-south and east-west direction,
Weather (Present and Recent): SUNNY and FAIR respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage Injected, I Resistance Resistivity
(m)
Depth Depth 0 (V) (mV) 1 (mA) (Ohm) (Ohm-m)
(cm) (cm) (m) (m) (m) (m)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 779.00 107.00 7.28 13.70
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 379.00 88.50 4.29 16.20
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 315.00 92.60 3.40 19.20
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 270.00 129.00 2.09 23.70
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 203.00 124.00 1.64 30.90
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 209.00 138.00 1.51 56.80
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 126.00 82.50 1.53 86.50

"a" 0.30 0.60 0.90 1.80 3.00 6.00 9.00


AVE (Ω-M) 43.60 17.25 19.55 23.90 31.40 55.30 83.75
AVE (Ω) 7.22 4.57 3.47 2.11 1.67 1.47 1.48
Average Value (Orthogonal Measurements)

TSR Average 34.34 2.75


Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using
the 4-point Wenner-Test- Configuration, wherein the four
Project Location: Ilijan, Batangas
(4) probes are spaced at equal distances to approximate
Date: 08/07/2021
the depth of the soil to be tested. Each VES point is
Measurement No. & Orientation: TSR-6 EW labeled TSR-1, 2, . . . . . 10 as in Test Shallow
Description of Terrain & Probe Resistivity. TSR () NS and TSR ( ) EW is aligned
Hilly, Coastal Ridge - 2.5 to 15 cm.
Insertion: towards north-south and east-west direction,
Weather (Present and Recent): SUNNY and FAIR respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 910.00 127.00 7.16 73.50
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 580.00 120.00 4.84 18.30
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 429.00 122.00 3.53 19.90
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 223.00 105.00 2.13 24.10
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 189.00 12.00 1.69 31.90
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 184.00 129.00 1.43 53.80
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 159.00 111.00 1.43 81.00

Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
6 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using
Project Location: Ilijan, Batangas
the 4-point Wenner-Test- Configuration, wherein the four
(4) probes are spaced at equal distances to approximate
Date: 08/07/2021
the depth of the soil to be tested. Each VES point is
Measurement No. & Orientation: TSR-7 NS labeled TSR-1, 2, . . . . . 10 as in Test Shallow
Description of Terrain & Probe Resistivity. TSR () NS and TSR ( ) EW is aligned
Hilly, Coastal Ridge - 2.5 to 15 cm.
Insertion: towards north-south and east-west direction,
Weather (Present and Recent): SUNNY and FAIR respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage Injected, I Resistance Resistivity
(m)
Depth Depth 0 (V) (mV) 1 (mA) (Ohm) (Ohm-m)
(cm) (cm) (m) (m) (m) (m)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 971.00 51.20 19.00 35.80
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 672.00 55.30 12.10 45.80
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 467.00 53.00 8.82 49.90
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 293.00 55.10 5.31 60.10
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 282.00 60.30 4.67 88.10
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 211.00 54.50 3.86 146.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 145.00 50.20 2.89 163.00

"a" 0.30 0.60 0.90 1.80 3.00 6.00 9.00


AVE (Ω-M) 33.55 41.05 43.40 60.70 89.80 144.00 155.00
AVE (Ω) 11.83 10.86 7.67 5.37 4.76 3.81 2.74
Average Value (Orthogonal Measurements)
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-7 EW depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 813.00 813.00 4.66 31.30
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 525.00 54.50 9.62 36.30
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 447.00 68.50 6.52 36.90
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 345.00 63.70 5.42 61.30
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 298.00 63.10 4.85 91.50
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 251.00 66.70 3.76 142.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 51.30 19.80 2.59 147.00

Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
7 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR- 8 NS depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage Injected, I Resistance Resistivity
(m)
Depth Depth 0 (V) (mV) 1 (mA) (Ohm) (Ohm-m)
(cm) (cm) (m) (m) (m) (m)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 1.15 130.00 8.83 16.60
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 902.00 122.00 7.38 27.80
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 829.00 132.00 6.30 35.60
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 585.00 104.00 5.62 63.50
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 483.00 96.50 5.00 94.30
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 405.00 90.30 4.49 169.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 403.00 91.90 4.39 248.00

"a" 0.30 0.60 0.90 1.80 3.00 6.00 9.00


AVE (Ω-M) 16.65 27.85 36.00 61.50 92.45 178.50 256.00
AVE (Ω) 8.84 7.40 6.37 5.44 4.90 4.74 4.53
Average Value (Orthogonal Measurements)

TSR Average 83.62 5.28


Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using
the 4-point Wenner-Test- Configuration, wherein the four
Project Location: Ilijan, Batangas
(4) probes are spaced at equal distances to approximate
Date: 08/07/2021
the depth of the soil to be tested. Each VES point is
Measurement No. & Orientation: TSR-8 EW labeled TSR-1, 2, . . . . . 10 as in Test Shallow
Description of Terrain & Probe Resistivity. TSR () NS and TSR ( ) EW is aligned
Hilly, Coastal Ridge - 2.5 to 15 cm.
Insertion: towards north-south and east-west direction,
Weather (Present and Recent): SUNNY and FAIR respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 1.04 118.00 8.85 16.70
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 958.00 129.00 7.41 27.90
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 759.00 118.00 6.44 36.40
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 481.00 31.50 5.26 59.50
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 497.00 103.00 4.80 90.60
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 461.00 92.40 4.99 188.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 280.00 60.00 4.67 264.00

Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
8 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-9 NS depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage Injected, I Resistance Resistivity
(m)
Depth Depth 0 (V) (mV) 1 (mA) (Ohm) (Ohm-m)
(cm) (cm) (m) (m) (m) (m)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 876.00 88.10 9.95 18.80
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 512.00 68.70 7.46 28.10
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 367.00 63.40 5.79 32.80
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 348.00 87.80 3.96 44.80
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 322.00 80.90 3.99 75.10
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 274.00 73.20 3.74 141.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 217.00 64.90 3.35 189.00

"a" 0.30 0.60 0.90 1.80 3.00 6.00 9.00


AVE (Ω-M) 19.30 26.65 61.60 43.80 74.20 141.50 201.00
AVE (Ω) 57.48 7.08 5.59 3.87 3.94 3.75 3.57
Average Value (Orthogonal Measurements)

TSR Average 71.01 10.66


Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house
Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-9 EW depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
east-west direction, respectively.
Weather (Present and Recent): SUNNY and FAIR
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 1.00 95.40 105.00 19.80
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 468.00 71.10 6.69 25.20
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 360.00 66.90 5.39 90.40
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 263.00 69.60 3.78 42.80
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 277.00 582.00 3.89 73.30
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 222.00 59.10 3.76 142.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 211.00 58.60 3.78 213.00

Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
9 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using
Project Location: Ilijan, Batangas
the 4-point Wenner-Test- Configuration, wherein the four
(4) probes are spaced at equal distances to approximate
Date: 08/07/2021
the depth of the soil to be tested. Each VES point is
Measurement No. & Orientation: TSR-10 NS labeled TSR-1, 2, . . . . . 10 as in Test Shallow
Description of Terrain & Probe Resistivity. TSR () NS and TSR ( ) EW is aligned
Hilly, Coastal Ridge - 2.5 to 15 cm.
Insertion: towards north-south and east-west direction,
Weather (Present and Recent): SUNNY and FAIR respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 1.36 96.00 14.10 26.60
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 1.06 80.00 13.20 49.70
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 963.00 76.20 12.60 71.50
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 519.00 52.50 9.88 112.00
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 527.00 65.90 8.00 151.00
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 433.00 66.30 6.53 246.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 339.00 66.70 5.08 287.00

"a" 0.30 0.60 0.90 1.80 3.00 6.00 9.00


AVE (Ω-M) 25.95 47.40 68.25 109.50 157.50 253.00 304.00
AVE (Ω) 13.75 12.60 12.05 9.69 8.35 6.72 5.38
Average Value (Orthogonal Measurements)

TSR Average 120.70 8.57


Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house
Notes: The soil resistivity survey was conducted using the 4-
Project Location: Ilijan, Batangas point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-10 EW depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
SUNNY and FAIR
east-west direction, respectively.
Weather (Present and Recent):
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Electrode Configuration
Electrode Actual Source VM-N Current Apparent Apparent
Electrode
"a" Spacing Electrode Depth A M N B Voltage 1 Injected, I Resistance Resistivity
Depth 0 (mV)
(m) (cm) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm)
0.30 3.00 5.00 0.45 0.15 0.15 0.45 32 1.32 98.30 13.40 25.30
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 973.00 81.30 12.00 45.10
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 904.00 78.60 11.50 65.00
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 829.00 87.20 9.50 107.00
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 746.00 85.90 8.69 164.00
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 563.00 81.50 6.91 260.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 301.00 53.10 5.67 321.00

Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-10
NS'