Not required if using AGI meters.
Note: Due to soil conductivity, the electrode depth may have to be increased. However, electrode depth shall not exceed 10% of “a” spacing.
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-1 EW depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 946.00 77.30 12.20 23.10
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 691.00 79.80 8.66 32.60
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 448.00 60.10 7.45 42.10
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 369.00 67.40 5.48 62.00
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 339.00 66.40 5.11 96.20
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 212.00 53.40 3.97 150.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 146.00 44.90 3.25 184.00
Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
1 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-2 NS depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage Injected, I Resistance Resistivity
(m)
Depth Depth 0 (V) (mV) 1 (mA) (Ohm) (Ohm-m)
(cm) (cm) (m) (m) (m) (m)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 912.00 79.20 11.50 21.70
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 899.00 98.70 9.11 34.40
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 857.00 95.10 9.01 51.00
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 528.00 68.10 7.74 87.60
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 455.00 74.80 6.09 115.00
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 426.00 84.80 5.03 190.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 252.00 64.40 3.91 221.00
Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
2 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-3 NS depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 1.48 89.80 15.50 31.10
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 903.00 85.50 10.60 39.80
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 861.00 93.80 9.18 51.90
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 537.00 71.10 7.56 85.50
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 473.00 84.40 5.60 106.00
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 246.00 71.20 3.45 130.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 215.00 82.60 2.61 147.00
Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
3 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using
Project Location: Ilijan, Batangas the 4-point Wenner-Test- Configuration, wherein the four
(4) probes are spaced at equal distances to approximate
Date: 08/07/2021
the depth of the soil to be tested. Each VES point is
Measurement No. & Orientation: TSR-4 NS
labeled TSR-1, 2, . . . . . 10 as in Test Shallow
Description of Terrain & Probe Resistivity. TSR () NS and TSR ( ) EW is aligned
Hilly, Coastal Ridge - 2.5 to 15 cm.
Insertion: towards north-south and east-west direction,
Weather (Present and Recent): SUNNY and FAIR respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 850.00 119.00 7.12 13.40
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 607.00 120.00 5.03 19.00
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 486.00 105.00 4.62 26.10
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 457.00 110.00 4.17 47.10
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 433.00 111.00 3.90 73.50
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 247.00 78.40 3.47 131.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 239.00 88.30 2.71 153.00
Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
4 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-5 NS depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 1.07 90.30 11.80 22.30
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 557.00 74.50 7.48 28.20
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 490.00 88.30 5.56 31.40
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 280.00 84.80 3.30 37.40
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 201.00 83.60 2.40 45.30
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 162.00 90.30 1.80 67.70
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 177.00 108.00 1.64 92.50
Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
5 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using
Project Location: Ilijan, Batangas
the 4-point Wenner-Test- Configuration, wherein the four
(4) probes are spaced at equal distances to approximate
Date: 08/07/2021
the depth of the soil to be tested. Each VES point is
Measurement No. & Orientation: TSR-6 NS labeled TSR-1, 2, . . . . . 10 as in Test Shallow
Description of Terrain & Probe Resistivity. TSR () NS and TSR ( ) EW is aligned
Hilly, Coastal Ridge - 2.5 to 15 cm.
Insertion: towards north-south and east-west direction,
Weather (Present and Recent): SUNNY and FAIR respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage Injected, I Resistance Resistivity
(m)
Depth Depth 0 (V) (mV) 1 (mA) (Ohm) (Ohm-m)
(cm) (cm) (m) (m) (m) (m)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 779.00 107.00 7.28 13.70
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 379.00 88.50 4.29 16.20
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 315.00 92.60 3.40 19.20
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 270.00 129.00 2.09 23.70
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 203.00 124.00 1.64 30.90
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 209.00 138.00 1.51 56.80
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 126.00 82.50 1.53 86.50
Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
6 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using
Project Location: Ilijan, Batangas
the 4-point Wenner-Test- Configuration, wherein the four
(4) probes are spaced at equal distances to approximate
Date: 08/07/2021
the depth of the soil to be tested. Each VES point is
Measurement No. & Orientation: TSR-7 NS labeled TSR-1, 2, . . . . . 10 as in Test Shallow
Description of Terrain & Probe Resistivity. TSR () NS and TSR ( ) EW is aligned
Hilly, Coastal Ridge - 2.5 to 15 cm.
Insertion: towards north-south and east-west direction,
Weather (Present and Recent): SUNNY and FAIR respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage Injected, I Resistance Resistivity
(m)
Depth Depth 0 (V) (mV) 1 (mA) (Ohm) (Ohm-m)
(cm) (cm) (m) (m) (m) (m)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 971.00 51.20 19.00 35.80
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 672.00 55.30 12.10 45.80
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 467.00 53.00 8.82 49.90
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 293.00 55.10 5.31 60.10
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 282.00 60.30 4.67 88.10
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 211.00 54.50 3.86 146.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 145.00 50.20 2.89 163.00
Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
7 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR- 8 NS depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage Injected, I Resistance Resistivity
(m)
Depth Depth 0 (V) (mV) 1 (mA) (Ohm) (Ohm-m)
(cm) (cm) (m) (m) (m) (m)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 1.15 130.00 8.83 16.60
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 902.00 122.00 7.38 27.80
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 829.00 132.00 6.30 35.60
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 585.00 104.00 5.62 63.50
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 483.00 96.50 5.00 94.30
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 405.00 90.30 4.49 169.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 403.00 91.90 4.39 248.00
Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
8 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using the
Project Location: Ilijan, Batangas 4-point Wenner-Test- Configuration, wherein the four (4)
Date: 08/07/2021 probes are spaced at equal distances to approximate the
Measurement No. & Orientation: TSR-9 NS depth of the soil to be tested. Each VES point is labeled
Description of Terrain & Probe TSR-1, 2, . . . . . 10 as in Test Shallow Resistivity. TSR ()
Hilly, Coastal Ridge - 2.5 to 15 cm. NS and TSR ( ) EW is aligned towards north-south and
Insertion:
Weather (Present and Recent): SUNNY and FAIR east-west direction, respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage Injected, I Resistance Resistivity
(m)
Depth Depth 0 (V) (mV) 1 (mA) (Ohm) (Ohm-m)
(cm) (cm) (m) (m) (m) (m)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 876.00 88.10 9.95 18.80
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 512.00 68.70 7.46 28.10
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 367.00 63.40 5.79 32.80
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 348.00 87.80 3.96 44.80
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 322.00 80.90 3.99 75.10
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 274.00 73.20 3.74 141.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 217.00 64.90 3.35 189.00
Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-
9 NS'
Project Name: BATANGAS ILIJAN COMBINED CYCLE POWER PLANT
GPI Project No.: 2021 - 006
Supplier Name & Operator In house Notes: The soil resistivity survey was conducted using
Project Location: Ilijan, Batangas
the 4-point Wenner-Test- Configuration, wherein the four
(4) probes are spaced at equal distances to approximate
Date: 08/07/2021
the depth of the soil to be tested. Each VES point is
Measurement No. & Orientation: TSR-10 NS labeled TSR-1, 2, . . . . . 10 as in Test Shallow
Description of Terrain & Probe Resistivity. TSR () NS and TSR ( ) EW is aligned
Hilly, Coastal Ridge - 2.5 to 15 cm.
Insertion: towards north-south and east-west direction,
Weather (Present and Recent): SUNNY and FAIR respectively.
Meter Model Type: TERCA 3, Chauvin Arnoux
Serial No. & Calibration Date: (IEC 61557)
Preferred Actual Electrode Configuration
Electrode Source VM-N Current Apparent Apparent
Electrode Electrode
"a" Spacing A M N B Voltage 1 Injected, I Resistance Resistivity
Depth Depth 0 (mV)
(m) (m) (m) (m) (m) (V) (mA) (Ohm) (Ohm-m)
(cm) (cm)
0.30 3.00 2.50 0.45 0.15 0.15 0.45 32 1.36 96.00 14.10 26.60
0.60 6.00 5.00 0.90 0.30 0.30 0.90 32 1.06 80.00 13.20 49.70
0.90 9.00 10.00 1.35 0.45 0.45 1.35 32 963.00 76.20 12.60 71.50
1.80 18.00 15.00 2.70 0.90 0.90 2.70 32 519.00 52.50 9.88 112.00
3.00 30.00 15.00 4.50 1.50 1.50 4.50 32 527.00 65.90 8.00 151.00
6.00 60.00 15.00 9.00 3.00 3.00 9.00 32 433.00 66.30 6.53 246.00
9.00 90.00 15.00 13.50 4.50 4.50 13.50 32 339.00 66.70 5.08 287.00
Note : Average value of the NS and EW Measurements are indicated in Sheet 'TSR-10