6201 OVP

Alarm # Ericsson Alarm Script Alarm Means


1 RBS DC MJ) Power Plant Major Fault
2 RBS DC MN Power Plant Minor Fault
3 RBS COMMERCIAL POWER FAIL AC Power Failure
4 RBS DC DIST BREAKER FUSE FAIL Fuse, Circuit Breaker or Battery Disc
5 RBS BATT ON DISCHARGE Site is Running on Batteries
6 RBS SMOKE Fire or smoke in building
7 RBS INTRUSION Buiding Door Open
8 RBS HVAC #1 FAIL Heating or Cooling system Failure
9 RBS HVAC #2 FAIL Heating or Cooling system Failure
10 RBS HYDROGEN GAS Hydrogen Gas Leak
11 RBS HIGH TEMPERATURE High Temperature
12 RBS LOW TEMPERATURE Low Temperature
13 For Future Growth
14 For Future Growth
15 For Future Growth
16 For Future Growth
17 For Future Growth
18 For Future Growth
19 For Future Growth
20 For Future Growth
21 For Future Growth
22 For Future Growth
23 For Future Growth
24 For Future Growth
25 For Future Growth
26 For Future Growth
27 For Future Growth
28 For Future Growth
29 For Future Growth
30 For Future Growth
31 For Future Growth
32 For Future Growth
*ERICSSON RJ45 ALARM PIN CONNECTIONS Use
installed

1st Alarm
2nd Alarm
3rd Alarm
4th Alarm
Connects
To RBS
alarm
Alarm Terminals RBS SAU
Type , if Connects to LEFT SIDE of RJ48 Alarm
Severity NO/NC Installed* Building Alarm 66 Block Jack

Alarm Inputs 5- Alarm Inputs 1-


MAJOR NC OVP1 A1 Building Alarm 66 block pair 1
MAJOR NC OVP1 A2 Building Alarm 66 block pair 2

4
CRITICAL NC OVP1 A3 Building Alarm 66 block pair 3
MAJOR NC OVP1 A4 Building Alarm 66 block pair 4
CRITICAL NC OVP1 A5 Building Alarm 66 block pair 5
CRITICAL NC OVP1 A6 Building Alarm 66 block pair 6

8
MINOR NC OVP1 A7 Building Alarm 66 block pair 7
MAJOR NC OVP1 A8 Building Alarm 66 block pair 8
MAJOR NC OVP2 A1 Building Alarm 66 block pair 9

Alarm Inputs
CRITICAL NC OVP2 A2 Building Alarm 66 block pair 10

9-12
CRITICAL NC OVP2 A3 Building Alarm 66 block pair 11
MAJOR NC OVP2 A4 Building Alarm 66 block pair 12
NC OVP2 A5 Building Alarm 66 block pair 13

Alarm Inputs
NC OVP2 A6 Building Alarm 66 block pair 14

13-16
NC OVP2 A7 Building Alarm 66 block pair 15
NC OVP2 A8 Building Alarm 66 block pair 16
NC OVP3 A1 Building Alarm 66 block pair 17 Alarm Inputs
NC OVP3 A2 Building Alarm 66 block pair 18 17-20

OVP3 A3
OVP3 A4
OVP3 A5
Alarm Inputs

OVP3 A6
21-24

OVP3 A7
OVP3 A8
OVP4 A1
Alarm Inputs

OVP4 A2
25-28

OVP4 A3
OVP4 A4
OVP4 A5
Alarm Inputs

OVP4 A6
29-32

OVP4 A7
OVP4 A8
M PIN CONNECTIONS Use these if no OVP
installed
PIN (-) PIN
(Common/Return)
5 4
2 1
6 3
8 7
6601 OVP
Alarm # Ericsson Alarm Script Alarm Means Severity
1 RBS INTRUSION Buiding Door Open MINOR
2 RBS TEMP OUT OF RANGE Building HighTemp (Low not connected) CRITICAL
3 RBS HVAC FAIL Heating or Cooling system Failure MAJOR
4 RBS DC MN Power Plant Minor Fault MAJOR
5 RBS DC MJ Power Plant Major Fault MAJOR
6 RBS SMOKE Fire or smoke in building CRITICAL
7 RBS PWR AC SPD Surge Protector Failure-AC MAJOR
8 RBS COMMERCIAL POWER FAIL AC Power Failure CRITICAL
9 RBS LNA FAIL RXAIT or TMA Failure (SCPA GSM*) MAJOR
10 RBS GENERATOR RUNNING Generator Running MAJOR
11 RBS GENERATOR FAIL Generator Fault and or Low Fuel MAJOR
12 RBS TOWER LIGHT FAIL Tower Light Beacon Failure MAJOR
13 RBS SIDE LIGHT FAIL Tower Sidelamps Failure MAJOR
14 RBS CCIC TWR LIGHT SUMM Crown Site Tower Light Failure MAJOR
15 RBS LTE RRU AT DC SYS SPD Raycap surge arrestor alarm MAJOR
16 RBS MW FAIL Microwave or Misc System Failure MAJOR
17 RBS HYDROGEN DETECTED Hi Levels of Hydrogen Gas detected CRITICAL
18 RBS SMOKE Fire or smoke in building CRITICAL
19 RBS HUMIDITY HIGH Building High Humdity MAJOR
20 RBS BATT ON DISCHARGE Site is Running on Batteries CRITICAL
21 For Future Growth
22 For Future Growth
23 For Future Growth
24 For Future Growth
25 For Future Growth
26 For Future Growth
27 For Future Growth
28 For Future Growth
29 For Future Growth
30 For Future Growth
31 For Future Growth
32 For Future Growth
*ERICSSON RJ45 ALARM PIN CONNECTIONS Use these if no OVP
installed
PIN (-)

1st Alarm 5

2 nd
Alarm 2

3 rd
Alarm 6

4 th
Alarm 8
Connects
To RBS
alarm
Alarm Terminals RBS SAU
Type , if Connects to LEFT SIDE of RJ48 Alarm
NO/NC Installed* Building Alarm 66 Block Jack

Alarm Inputs 5- Alarm Inputs 1-


NC OVP1 A1 Building Alarm 66 block pair 1
NC OVP1 A2 Building Alarm 66 block pair 2

4
NC OVP1 A3 Building Alarm 66 block pair 3
NC OVP1 A4 Building Alarm 66 block pair 4
NC OVP1 A5 Building Alarm 66 block pair 5
NC OVP1 A6 Building Alarm 66 block pair 6

8
NC OVP1 A7 Building Alarm 66 block pair 7
NC OVP1 A8 Building Alarm 66 block pair 8
NC OVP2 A1 Building Alarm 66 block pair 9

Alarm Inputs
NC OVP2 A2 Building Alarm 66 block pair 10

9-12
NC OVP2 A3 Building Alarm 66 block pair 11
NC OVP2 A4 Building Alarm 66 block pair 12
NC OVP2 A5 Building Alarm 66 block pair 13
Alarm Inputs
NC OVP2 A6 Building Alarm 66 block pair 14 13-16
NC OVP2 A7 Building Alarm 66 block pair 15
NC OVP2 A8 Building Alarm 66 block pair 16
NC OVP3 A1 Building Alarm 66 block pair 17
Alarm Inputs

NC OVP3 A2 Building Alarm 66 block pair 18


17-20

NC OVP3 A3 Building Alarm 66 block pair 19


NC OVP3 A4 Building Alarm 66 block pair 20
OVP3 A5 Building Alarm 66 block pair 21
Alarm Inputs

OVP3 A6 Building Alarm 66 block pair 22


21-24

OVP3 A7 Building Alarm 66 block pair 23


OVP3 A8 Building Alarm 66 block pair 24
OVP4 A1
Alarm Inputs

OVP4 A2
25-28

OVP4 A3
OVP4 A4
OVP4 A5
Alarm Inputs

OVP4 A6
29-32

OVP4 A7
OVP4 A8
NECTIONS Use these if no OVP
d
PIN
(Common/Return)
4
1
3
7
Building End Device Wire Points and connects to RIGHT
SIDE of Alarm 66 Block
Door Switch
Hi Temp Thermostat
HVAC system
Power Plant Alarms
Power Plant Alarms
Smoke Alarm
AC Panel Surge Protector
AC Fail Relay
CCI RXAIT's & TMA PDU's in Series*
Generator
Generator, wire low fuel in series if not annuciated with common fault
Tower Light Controller
Tower Light Controller
Crown Castle Tower Alarm Box
Raycap Surge Arrestor Rear TB NC & COM
Microwave System
Hydrogen Gas Detector
Smoke Alarm
Humidistat
Power Plant Alarms