Calculation and Selection report

Projeto

CAUTION
Please understand that we cannot assume the responsibility for the
contents of this report if the content of the report has been revised
by the customer

1
Contents
1. PROJECT INFORMATION .................................................................................................................................... 3

1.1 PROJECT INFORMATION ............................................................................................................................................. 3


1.2 REPORT INFORMATION .............................................................................................................................................. 3

2. WIRING DIAGRAM INFORMATION ........................................................................................................................ 4

2.1 STANDARD .............................................................................................................................................................. 4


2.2 ELEMENTS INFORMATION ........................................................................................................................................... 6

3. SWITCHGEAR INFORMATION .............................................................................................................................. 7

3.1 NUMERICAL PROTECTION RELAY ................................................................................................................................. 7


3.2 LOW VOLTAGE CIRCUIT BREAKERS ............................................................................................................................. 7
3.3 CONTACTORS AND THERMAL RELAYS .......................................................................................................................... 7
3.4 INVERTER ................................................................................................................................................................ 7

4. CALCULATION RESULTS .................................................................................................................................... 8

4.1 LOW VOLTAGE CIRCUIT BREAKERS ............................................................................................................................. 8


4.2 CONTACTORS AND THERMAL RELAYS .......................................................................................................................... 8
4.3 CABLES .................................................................................................................................................................. 8
4.4 BUSBARS ................................................................................................................................................................ 9
4.5 BUSDUCT .............................................................................................................................................................. 10

5. SINGLE WIRING DIAGRAM ..................................................................................................................................11

2
1. Project information
1.1 Project information
Item name Setting Value
Power Distribution system Frequency 60Hz
Default capable voltage drop 5%
Priority to select Breakers Breaker type Adjustable type
LV cables Maximum capable cable cross section 300mm2
Ambient Temperature 30℃
Default Max. capable cable voltage drop 2%
Busbars Ambient Temperature 35℃
Max. capable busbar voltage drop 2%
Busducts Ambient Temperature 40℃
Max. capable busduct voltage drop 2%
Margin Breaker rated current margin of load current 125%
Region Brazil
Remarks

1.2 Report information


Item name Setting Value
Company Company name
Tel
Address
City
Post code
States/Prefecture
Country
Web site
Project Project name
Place
End user
Revision

3
2. Wiring diagram information
2.1 Standard
(1) Standard of Cable, Busbars and installation
IEC 60227-1
Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V
- Part 1: General requirements

IEC 60228:2004
Conductors of insulated cables

IEC 60364-1
Low-voltage electrical installations
- Part 1: Fundamental principles, assessment of general characteristics, definitions

IEC 60364-5-51
Electrical installations of buildings
- Part 5-51: Selection and erection of electrical equipment - Common rules

IEC 60364-5-52
Low-voltage electrical installations
- Part 5-52: Selection and erection of electrical equipment - Wiring systems

IEC 60364-5-53
Low-voltage electrical installations
- Part 5-53: Selection and erection of electrical equipment - Devices for protection for safety, isolation, switching, control and monitoring

IEC 61439-2
Low-voltage switchgear and controlgear assemblies
- Part 2: Power switchgear and controlgear assemblies

4
(2) Standard of Low Voltage Circuit Beakers
IEC 60947-1
Low-voltage switchgear and controlgear
- Part 1: General rules

IEC 60947-2
Low-voltage switchgear and controlgear
- Part 2: Circuit-breakers

5
2.2 Elements information
(1) MV/LV Transformer
Ref.No. Name Primary voltage Secondary voltage Network system Tr capacity Secondary current %Z X/R
1 TR 1 13800V 380V TN-S 300kVA 456A 3,792% 2,602941

(2) Generator
Ref.No. Name Voltage Network system Gen capacity Rated current Transient reactance Subtransient reactance DC time constant Subtransient time constant Stator resistance

(3) LV/LV Transformer


Ref.No. Name Primary voltage Secondary voltage Network system Tr capacity Secondary current %Z X/R

(4) General Load


Ref.No. Name Load current Capacity Output Power factor
1 L1 72,928A 48kVA 45,6kW 0,95
2 L2 85,463A 56,25kVA 45kW 0,8

(5) Motor
Ref.No. Name Voltage Starting method Output Load current
1 M1 380V Direct start 22kW 42A
2 M2 380V Direct start 37kW 65A
3 M3 380V Direct start 75kW 134A

(6) Capacitor bank


Ref.No. Name Voltage Capacity Reactor

6
3. Switchgear information
3.1 Numerical Protection Relay
Ref.No. Name Type
1 OCR 1 COC4-A02S1

3.2 Low Voltage Circuit Breakers


Ref.No. Name Breaker type Rated Breaking Poles Fixed / Earthleakage Selective Breaking Cascade Breaking
current capacity Adjustable Protection Main breaker Breaking Main breaker Breaking
Name Type capacity Name Type capacity
1 CB 1 NF800-SEW 500A 50kA 4P(3P+N) Adjustable No
type
2 CB 2 NF630-SEW 350A 50kA 4P(3P+N) Adjustable No
type
3 CB 3 NF125-CV 75A 10kA 3P No
4 CB 4 NF125-CV 100A 10kA 3P No
5 CB 5 NF250-CV 225A 25kA 3P No
6 CB 7 NF125-SEV 94,25A 36kA 4P(3P+N) Adjustable No
type
7 CB 8 NF250-SEV 112A 36kA 4P(3P+N) Adjustable No
type

3.3 Contactors and Thermal relays


Ref.No. Name Contactor type Thermal relay type
1 MC 1 S-T50 TH-T65 42A
2 MC 2 S-T80 TH-T100 67A
3 MC 3 S-N150 TH-N120TA 125A

3.4 Inverter
Ref.No. Name Type AC reactor DC reactor Multiple ratings

7
4. Calculation Results
4.1 Low Voltage Circuit Breakers
Ref.No. Name Type Poles Rated Voltage Priority Breaking 3 phase Phase – Phase Phase – Neutral Phase – PE
current to capacity short-circuit short-circuit short-circuit short-circuit
select current (Ik3) current (Ik2) current (Ik1) current (Ik1(PE))
1 CB 1 NF800-SEW 4P(3P 500A 380V Icu 50kA 13,486kA 13,479kA 13,479kA
+N)
2 CB 2 NF630-SEW 4P(3P 350A 380V Icu 50kA 12,916kA 12,384kA 12,384kA
+N)
3 CB 3 NF125-CV 3P 75A 380V Icu 10kA 8,179kA 5,736kA
4 CB 4 NF125-CV 3P 100A 380V Icu 10kA 8,186kA 5,745kA
5 CB 5 NF250-CV 3P 225A 380V Icu 25kA 8,196kA 5,756kA
6 CB 7 NF125-SEV 4P(3P 94,25A 380V Icu 36kA 12,899kA 12,351kA 12,351kA
+N)
7 CB 8 NF250-SEV 4P(3P 112A 380V Icu 36kA 12,899kA 12,351kA 12,351kA
+N)

4.2 Contactors and Thermal relays


Ref.No. Name Contactor type Thermal relay type Voltage
1 MC 1 S-T50 TH-T65 42A 380V
2 MC 2 S-T80 TH-T100 67A 380V
3 MC 3 S-N150 TH-N120TA 125A 380V

4.3 Cables
Ref.No. Name Conductor Insulation Core Installation Cross Permissible Length 3 phase Phase – Phase Phase – Neutral Phase – PE Operational Resistance Reactance Voltage Voltage
material material configuration section current short-circuit short-circuit short-circuit short-circuit Voltage drop retention
current (Ik3) current (Ik2) current (Ik1) current (Ik1(PE))
rate
1 CABLE 1 Cu PVC Single core 31F 300mm2 × 1 575,26A 0,1m 13,486kA 13,479kA 13,479kA 380V 0,05973moh 0,07151mohm 379,995 99,999%
m/m /m V
2 CABLE 2 Cu PVC Single core 31F 300mm2 × 1 575,26A 8m 12,925kA 12,400kA 12,400kA 380V 0,05973moh 0,07151mohm 379,581 99,890%
m/m /m V
3 CABLE 3 Cu PVC Single core 31F 150mm2 × 1 364,56A 0,1m 12,916kA 12,384kA 12,384kA 380V 0,1195mohm 0,07219mohm 379,574 99,888%
/m /m V
4 CABLE 4 Cu PVC Single core 31F 150mm2 × 1 364,56A 80m 8,201kA 5,761kA 5,761kA 380V 0,1195mohm 0,07219mohm 373,778 98,363%
/m /m V
5 CABLE 5 Cu PVC Single core 31F 16mm2 × 1 83,3A 0,1m 8,179kA 5,736kA 380V 1,12mohm/m 0,07989mohm 373,764 98,359%
/m V
6 CABLE 6 Cu PVC Single core 31F 16mm2 × 1 83,3A 30m 3,986kA 2,218kA 380V 1,12mohm/m 0,07989mohm 369,399 97,210%
/m V
7 CABLE 7 Cu PVC Single core 31F 25mm2 × 1 111,72A 0,1m 8,186kA 5,745kA 380V 0,7167mohm 0,07918mohm 373,766 98,359%
/m /m V
8 CABLE 8 Cu PVC Single core 31F 25mm2 × 1 111,72A 40m 4,303kA 2,434kA 380V 0,7167mohm 0,07918mohm 368,800 97,053%
/m /m V
9 CABLE 9 Cu PVC Single core 31F 95mm2 × 1 269,5A 0,1m 8,196kA 5,756kA 380V 0,1886mohm 0,07354mohm 373,771 98,361%
/m /m V
10 CABLE 10 Cu PVC Single core 31F 95mm2 × 1 269,5A 60m 5,836kA 3,602kA 380V 0,1886mohm 0,07354mohm 369,361 97,200%
/m /m V
11 CABLE 13 Cu PVC Single core 31F 25mm2 × 1 111,72A 0,1m 12,899kA 12,351kA 12,351kA 380V 0,7167mohm 0,07918mohm 379,569 99,887%
/m /m V
12 CABLE 14 Cu PVC Single core 31F 25mm2 × 1 111,72A 20m 8,125kA 5,407kA 5,407kA 380V 0,7167mohm 0,07918mohm 377,229 99,271%
/m /m V

8
Ref.No. Name Conductor Insulation Core Installation Cross Permissible Length 3 phase Phase – Phase Phase – Neutral Phase – PE Operational Resistance Reactance Voltage Voltage
material material configuration section current short-circuit short-circuit short-circuit short-circuit Voltage drop retention
current (Ik3) current (Ik2) current (Ik1) current (Ik1(PE))
rate
13 CABLE 15 Cu PVC Single core 31F 25mm2 × 1 111,72A 0,1m 12,899kA 12,351kA 12,351kA 380V 0,7167mohm 0,07918mohm 379,567 99,886%
/m /m V
14 CABLE 16 Cu PVC Single core 31F 25mm2 × 1 111,72A 15m 9,109kA 6,447kA 6,447kA 380V 0,7167mohm 0,07918mohm 377,482 99,337%
/m /m V

4.3.1 Neutral wire


(1)Cables
Ref.No. Name Conductor Cross section Length Resistance Reactance
material
1 CABLE 1 Cu 300mm2 × 1 0,1m 0,05973mohm/ 0,07151mohm/
m m
2 CABLE 2 Cu 300mm2 × 1 8m 0,05973mohm/ 0,07151mohm/
m m
3 CABLE 3 Cu 150mm2 × 1 0,1m 0,1195mohm/m 0,07219mohm/
m
4 CABLE 4 Cu 150mm2 × 1 80m 0,1195mohm/m 0,07219mohm/
m
5 CABLE 5 Cu 16mm2 × 1 0,1m 1,12mohm/m 0,07989mohm/
m
6 CABLE 6 Cu 16mm2 × 1 30m 1,12mohm/m 0,07989mohm/
m
7 CABLE 7 Cu 25mm2 × 1 0,1m 0,7167mohm/m 0,07918mohm/
m
8 CABLE 8 Cu 25mm2 × 1 40m 0,7167mohm/m 0,07918mohm/
m
9 CABLE 9 Cu 95mm2 × 1 0,1m 0,1886mohm/m 0,07354mohm/
m
10 CABLE 10 Cu 95mm2 × 1 60m 0,1886mohm/m 0,07354mohm/
m
11 CABLE 13 Cu 25mm2 × 1 0,1m 0,7167mohm/m 0,07918mohm/
m
12 CABLE 14 Cu 25mm2 × 1 20m 0,7167mohm/m 0,07918mohm/
m
13 CABLE 15 Cu 25mm2 × 1 0,1m 0,7167mohm/m 0,07918mohm/
m
14 CABLE 16 Cu 25mm2 × 1 15m 0,7167mohm/m 0,07918mohm/
m

(2)Busbars
Ref.No. Name Conductor Size Length Resistance Reactance
material

4.4 Busbars
Ref.No. Name Conducto Size Permissible Length 3 phase Phase – Phase Phase – Neutral Phase – PE Operational Resistance Reactance Voltage Voltage
r material current short-circuit short-circuit short-circuit short-circuit Voltage drop retentio
current (Ik3) current (Ik2) current (Ik1) current (Ik1(PE))
n rate

9
4.4.1 Neutral wire
(1)Cables
Ref.No. Name Conductor Cross section Length Resistance Reactance
material

(2)Busbars
Ref.No. Name Conductor Size Length Resistance Reactance
material

4.5 Busduct
Ref.No. Name Conductor Rated Size Length 3 phase Phase – Phase Phase – Neutral Phase – PE
material current short-circuit short-circuit short-circuit short-circuit
current (Ik3) current (Ik2) current (Ik1) current (Ik1(PE))

4.5.1 Neutral wire


(1)Cables
Ref.No. Name Conductor Cross section Length Resistance Reactance
material

(2)Busbars
Ref.No. Name Conductor Size Length Resistance Reactance
material

10
5. Single wiring diagram

11