TABLE OF CONTENTS
1.0 SCOPE
4.1 General
4.2 Performance Characteristics and Ratings
4.3 Construction
4.4 Nameplate
5.0 TESTS
1.0 SCOPE
This SEC Transmission Material Standard Specification (TMSS) specifies the minimum
technical requirements for design, engineering, manufacture, inspection, testing and
performance of Metal Oxide Surge Arresters for 11kV through 380kV system voltages,
intended to be used in the system of Saudi Electricity Company (SEC), Saudi Arabia.
This Transmission Material Standard Specification shall be read in conjunction with the
SEC General Specification No. 01-TMSS-01, titled "General Requirements for All
Equipment/Materials", which shall be considered as an integral part of this TMSS.
This TMSS shall also be read in conjunction with SEC Purchase Order or Contract
Schedules for project, as applicable.
The latest revisions of the following Codes and Standards shall be applicable for the
equipment/material covered in this TMSS. In case of conflict, thevendor/manufacturer may
propose equipment/material conforming to one group of Industry Codes and Standards
quoted hereunder without jeopardizing the requirements of this TMSS.
3.1 IEC 60099-4 Surge Arresters-Part 4 : Metal-Oxide Surge Arresters without gaps for
a.c system
3.3 IEC 62155 Hollow pressurized and unpressurized ceramic and glass insulators for
use in electricalequipment with rated voltages greater than 1000 V
3.4 IEC 60060-1 High-Voltage Test Techniques Part 1: General Definitions and Test
Requirement
3.5 ANSI/IEEE C62.11 Standard for Metal-Oxide Surge Arresters for AC Power
Circuits.
4.1 General
The surge arrester shall be of metal oxide, gapless type for outdoor / indoor service,
as specified in Data Schedule.
4.2.1 The lightning impulse classifying current for surge arresters shall not be
less than 10kA
Table-1
Table-2
3-48 4
54-360 7.2
4.2.4 Minimum external insulation withstand levels of the surge arrester housing
shall be as specified in IEC 60099-4 or ANSI C62.11 as applicable.
4.3 Construction
4.3.1 General
b. The surge arrester base shall be insulated from ground for 5kV
minimum for outdoor surge arresters.
The surge arrester shall be suitable for base mounting in a vertical position.
The arrester base or end casting shall be furnished with at least three
mounting holes at 120 degrees on a 254 mm or 420mm diameter bolt
circle. The mounting holes shall accommodate either 13mm or 19mm bolt
with flat and lock washers. Surge arresters for the 13.8kV and 34.5kV
system shall be bracket mounted, if specified. Structure is to be designed
for wind load of 2kN per square meter on the arrestor and steel structure.
4.3.5 Fittings
4.3.6 Terminals
The surge arrester line terminal shall be of 4-hole terminal pad with NEMA
Standard drilling, suitable for line conductor of sizes upto 240mm2.The
terminal pad shall be an integral part of the arrester head. The terminal pad
shall be corrosion resistant.
4.3.7 Accessories
b. Surge arresters for system voltages of 69kV and above shall have a
surge (discharge) counter along with a built-in milliammeter to
monitor the leakage/internal current of the surge arrester
continuously.
c. The surge counter shall record the number of lightning and switching
discharges of the surge arrester automatically on a five-digit
cyclometer dial. The surge counter shall be non- resettable and
capable of registering up to 5 discharges per second.
d. The leakage and internal current indicator shall monitor and measure
the sum of leakage current across the external porcelain insulator plus
the internal current flowing through the surge arrester. The scale
range shall be 0-50 mA Peak / 2 (nonlinear scale).
4.3.8 Grounding
Each surge arrester shall be provided with one grounding pad, sized to
accommodate connectors suitable for stranded copper conductor of sizes
up to 70mm2. The connection between surge arrester and discharge
counter/ leakage current indicator shall be made with 70mm2 insulated
stranded copper conductor. Whereas the connection from leakage indicator
to grounding grid shall be made with 2*240mm2 bare stranded copper
conductor (for more details for grounding of surge arrester refer to TES-P-
119.10).
4.4 Nameplate
4.4.1 Each surge arrester shall bear a nameplate permanently and legibly marked
in English with the information listed per IEC 60099-4 or ANSI / IEEE
C62.11 as applicable and the following additional information:
c. 35-TMSS-01, Rev. 0.
4.4.2 The nameplate material shall be stainless steel and shall be fastened to the
equipment by stainless steel screws or rivets. The markings shall be
engraved.
5.0 TESTS
All test results shall be provided for review and acceptance by SEC.
All type tests prescribed in the latest revision IEC 60099-4 or ANSI/IEEE C62.11
standard shall be performed on the representative unit or on the first unit of every
new design or rating to be supplied to SEC.
In lieu of the actual type tests, certified test reports of type (design) tests performed
on an identical unit may be submitted to SEC for review and approval during
bidding stage.
All routine tests prescribed in the latest revision IEC 60099-4 or ANSI/IEEE
C62.11 standard shall be performed on all surge arresters.
Acceptance Tests per the latest revision IEC 60099-4 or Conformance Tests per
ANSI/IEEE C62.11, as applicable, shall be performed on the nearest lower whole
number to the cube root of the number of surge arresters to be supplied.
Special Thermal Stability Test per latest revision of IEC 60099-4 shall be conducted
on the appropriate sample taken from the production lot if this test is mentioned in
the Data Schedule or SOW/ PTS.
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
SYSTEM DATA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Transmission Line
Surge Impedance (ohms) *
Length (kM) *
Underground Cable
Capacitance (µF/kM) *
Length (kM) *
Capacitor Banks
Capacitance (MVAR)
Others
(Power Transformers,Reactors, GIS
etc.,attach details) *
4.1 General
Type *
Model Designation *
Location (Indoor/Outdoor)
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Power frequency Wet Withstand Voltage
*
(kVrms)
Lightning Impulse Withstand Level
(kVpeak) *
Switching Impulse Withstand Level
(kVpeak) *
4.3 Construction
Porcelain Housing
Color *
Creepage Distance (mm) *
Bending Failing Load (kN) *
Cantilever Strength min. (kN) *
Torsional Strength (kN) *
Compression Strength (kNm) *
No. of stacks in each unit *
Height (mm) *
Mounting Arrangement
Mode of mounting(Self
supporting/bracket mounting) *
Bolt circle diameter (mm) *
No. of holes *
Size of bolts (mm) *
Accessories
Scale range of the leakage Ammeter
(mA) *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Terminals
Type Pad
Size (mm2) *
Material (Al or CU) *
Grounding
Size (mm2) *
Material *
- MISCELLANEOUS
Official Seal/Stamp
of the Company & Date