You are on page 1of 7

IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 56, NO.

6, NOVEMBER/DECEMBER 2020 6069

Understanding the Effect of Electrode Configuration


on Incident Energy and Arc-Flash Boundary
Adam Reeves , Member, IEEE, Mark Freyenberger, Member, IEEE, and Michael Hodder , Member, IEEE

Abstract—The 2018 update to the IEEE Std. 1584 Guide for discussed in IEEE Std. 1584-2018 that are inside a metal “box”
Performing Arc-Flash Hazard Calculations has introduced new enclosure include VCBB and HCB.
electrode configurations that can drastically affect incident energy It is possible for electrical equipment to have multiple elec-
calculations and labeling. The electrode configurations discussed
in this article are: vertical conductors/electrodes inside a metal trode configurations and in some cases even within the same
box/enclosure (VCB), vertical conductors/electrodes terminated compartment. When multiple electrode configurations are con-
in an insulating barrier inside a metal box/enclosure (VCBB), sidered, it is not always intuitive which electrode configuration
and horizontal conductors/electrodes inside a metal box/enclosure will result in the highest calculated incident energy and arc-flash
(HCB). It is generally understood that at typical working distances, boundary at a single location. The effects of electrode config-
HCB will produce a higher incident energy than VCBB, which
will produce a higher incident energy than VCB with all other uration are now required to be considered when the worst-case
parameters equal. However, there is a counter-intuitive trend for incident energy and arc-flash boundary are reported in an arc
the arc-flash boundary, such that the boundary distance for HCB is flash report and label. The relationships discussed in this arti-
often lower than the boundary for VCBB and VCB. The electrode cle are valid for enclosed equipment ≤600 V. The effects on
configuration will also affect the magnitude of arcing current, equipment locations above 600 V and for open air electrode
which may result in varying fault clearing times depending on
which electrode configuration is selected. This article will discuss configurations are not discussed.
arcing fault current, incident energy, and arc-flash boundary re-
sults for each enclosed electrode configuration that challenge the
assumption that HCB will always yield the worst-case incident II. ARCING FAULT CURRENT
energy and arc-flash boundary. The results of 50 arc flash studies A. Electrode Configurations
have been surveyed and presented in this article to supplement and
validate observations and conclusions. The calculated arcing fault current is dependent on the se-
Index Terms—Arcing fault current, arc flash, arc-flash lected electrode configuration. In general, the arcing fault current
boundary, arc-flash study, electrode configuration, HCB, IEEE of a VCBB fault will have a higher magnitude than the arcing
1584, incident energy, VCB, VCBB, working distance. fault current of a VCB or HCB fault, with all other parameters
equal.
It is expected that during a VCBB fault, the insulating barrier
I. INTRODUCTION will collect and contain the arc plasma at the ends of the con-
FPA 70E-2018 [1]. Annex D encourages users to consult ductors. The containment of arc plasma near the fault location
N the latest version of the IEEE Std. 1584 document.
IEEE Std. 1584-2002 [2] did not include electrode config-
creates a lower impedance arc which results in a higher arcing
fault current magnitude. During a VCB or HCB fault, there is
uration as an input variable to the arc-flash calculation model. no barrier to contain the arc plasma, so the arc can bow out
However, equipment modeled as “arc in a cubic box” using IEEE away from the fault location, creating a longer arc with greater
Std. 1584–2002 equations is equivalent to the VCB configura- impedance.
tion in IEEE Std. 1584-2018 [3]. Other electrode configurations The arcing current for a VCB fault is generally similar to the
arcing current for an HCB fault. The only difference between
the VCB and HCB configurations is the orientation of the
Manuscript received February 7, 2020; accepted July 2, 2020. Date of
publication September 14, 2020; date of current version November 19, 2020.
conductors to the calorimeters that IEEE Std. 1584-2018 used
Paper 2020-ESafC-0203, presented at the 2020 IEEE IAS Electrical Safety to measure incident energy.
Workshop, Reno, NV, USA, Mar. 2–6, and approved for publication in the
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS by the Electrical Safety
Committee of the IEEE Industry Applications Society. (Corresponding author: B. Sample Arcing Fault Current Calculation
Adam Reeves.)
Adam Reeves is with Eaton Corporation, Hanover, MD 21076 USA Consider a sample arcing fault current calculation for a
(e-mail: adamreeves@eaton.com). switchgear work location with the parameters in Table I.
Mark Freyenberger is with Eaton Corporation, Fenton, MO 63026 USA (e-
mail: markafreyenberger@eaton.com). Table II shows the arcing current results using the calculation
Michael Hodder is with Eaton Corporation, Milton, ON L9T 5C3, Canada parameters of Table I.
(e-mail: michaelbhodder@eaton.com). The results in Table II show that the VCBB arcing fault current
Color versions of one or more of the figures in this article are available online
at https://ieeexplore.ieee.org. is higher than the VCB and HCB current as expected. Fig. 1 plots
Digital Object Identifier 10.1109/TIA.2020.3023918 this trend across the entire bolted fault current range of IEEE Std.
0093-9994 © 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.

Authorized licensed use limited to: Rick Downer. Downloaded on November 29,2020 at 20:13:26 UTC from IEEE Xplore. Restrictions apply.
6070 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 56, NO. 6, NOVEMBER/DECEMBER 2020

TABLE I TABLE III


SAMPLE CALCULATION PARAMETERS INCIDENT ENERGY RESULTS

TABLE II
ARCING CURRENT RESULTS

Fig. 2. Incident energy plot versus bolted fault current with fixed clearing
time.

directed out of the enclosure opening and will yield a


higher incident energy than both VCB and VCBB.

B. Sample Incident Energy Calculation With


Fixed Clearing Time
Table III shows the incident energy results from a sample
Fig. 1. Arcing fault current versus bolted fault current. switchgear installation with same parameters of Table I.
The results in Table III show the HCB incident energy is
higher than the VCBB and VCB incident as expected. Fig. 2
1584-2018 and confirms that VCBB generally yields a higher plots this trend across the entire bolted fault current range of
arcing fault current with all other parameters equal. IEEE Std. 1584-2018 and confirms that HCB yields a higher
incident energy with all other parameters equal.
III. INCIDENT ENERGY
C. Sample Incident Energy Calculation With
A. Electrode Configurations Varied Clearing Time
The calculated incident energy is also dependent on the The calculations in Fig. 2 assume a fixed fault clearing time
selected electrode configuration. VCB will yield the lowest over the entire range of bolted fault current, which is not realistic
incident energy at a typical working distance with all other in distribution systems. As the fault current varies, the line-side
parameters equal. VCBB will yield the next highest incident protective device response time will change the fault duration
energy, followed by HCB. based on the device tripping characteristics.
1) VCB: During a VCB fault, the arc will move away from For example, a 50 kA fault will likely result in an instanta-
the source, and the plasma will be directed off the ends of neous response of a circuit breaker, whereas a 20 kA fault may
the conductors, parallel to the enclosure opening. take longer to clear due to an intentional delay for coordination.
2) VCBB: During a VCBB fault, the arc is expected to move A 20 kA fault that lasts for a longer time may result in a higher
away from the source and terminate at an insulating barrier. incident energy than a 50 kA fault that clears instantaneously.
The barrier will direct some of the arc plasma toward the Even though VCB is intuitively expected to have a lower incident
enclosure opening, resulting in a higher incident energy energy, the higher arcing fault current from VCBB may result in
than VCB. a faster clearing time. This may cause the VCBB result to have
3) HCB: During an HCB fault, the ends of the conductors a lower final incident energy than VCB.
are pointed directly toward the enclosure opening. When Fig. 3 plots the incident energy result over a range of bolted
the arc moves away from the source, the plasma will be fault currents, but instead of a fixed fault clearing time, it

Authorized licensed use limited to: Rick Downer. Downloaded on November 29,2020 at 20:13:26 UTC from IEEE Xplore. Restrictions apply.
REEVES et al.: UNDERSTANDING THE EFFECT OF ELECTRODE CONFIGURATION ON INCIDENT ENERGY AND ARC-FLASH BOUNDARY 6071

arcing fault current of VCB has not yet reached the STPU,
so from points 1 to 2, VCB has a higher incident energy
because of the longer clearing time.
3) At point 2, the VCB arcing fault current exceeds the STPU
of the protective device. Between points 2 and 3, both
VCBB and VCB have the same clearing time of 300 ms.
For a fixed clearing time, VCBB has a higher incident
energy.
4) At point 3, the VCBB arcing fault current causes an in-
stantaneous response before the VCB arcing fault current
exceeds the instantaneous pickup (INST). Between points
3 and 4, VCB has a higher incident energy because of the
longer clearing time.
5) Finally, at point 4, the VCB arcing fault current exceeds
Fig. 3. Incident energy plot versus bolted fault current with varied clearing the instantaneous pickup (INST). For fault currents past
time.
point 4, both configurations have the same instantaneous
TABLE IV clearing time. For a fixed clearing time, VCBB has a higher
SAMPLE CIRCUIT BREAKER SETTINGS
incident energy.

IV. ARC-FLASH BOUNDARY


A. Electrode Configurations

considers the response of an upstream protective device with an The calculated arc-flash boundary is also dependent on the
electronic trip unit with Short Time and Instantaneous responses selected electrode configuration but does not follow the same
enabled. Table IV shows the device settings for this sample trend as incident energy. Depending on the bolted fault current
calculation. Note that pickup values shown in Table IV include and clearing time, an HCB fault could either yield the highest
typical trip unit tolerance. arc-flash boundary, or the lowest arc-flash boundary.
Fig. 3 shows that the electrode configuration that yields the Prior to the introduction of electrode configurations, inci-
lowest incident energy will change based on the varying bolted dent energy was always positively correlated to the arc-flash
fault current, which impacts arcing fault current and clearing boundary. This is still true when only considering one electrode
time. configuration. However, due to differences in arc behavior,
1) Point 1 – The VCBB fault reaches the STPU. the highest incident energy does not always correspond to the
2) Point 2 – The VCB fault reaches the STPU. highest arc-flash boundary when multiple configurations are
3) Point 3 – The VCBB fault reaches the INST. considered in IEEE Std. 1584-2018.
4) Point 4 – The VCB fault reaches the INST. As the distance from the arc increases, the incident energy
The first observation is that HCB yields the highest incident will decrease. Because the arc-flash boundary is defined as the
energy over the entire fault current range. This is expected distance at which the incident energy is calculated to be 1.2
because the HCB arcing current is less than or equal to the cal/cm2 , a higher incident energy will correspond to a higher
VCBB and VCB arcing current, so the clearing time of a typical arc-flash boundary with all other parameters equal. However, as
inverse or definite time overcurrent protective device for HCB working distance increases, the rate at which the incident energy
will always be greater than or equal to the VCBB or VCB decreases is not the same for each electrode configuration.
clearing time. In other words, the incident energy from HCB The HCB incident energy decreases at a faster rate as distance
cannot be lower than the energy from VCB or VCBB because increases, so at a large enough distance from the arc, HCB will no
the HCB clearing time is always equal to or greater than VCB longer yield the highest incident energy and will have the lowest
or VCBB clearing time with the same or lower arcing current. boundary. The VCBB incident energy decreases at a faster rate
The second observation in Fig. 3 is that at times the VCBB than VCB, so at a large enough distance from the arc, VCBB will
incident energy is greater than the VCB incident energy, and at have a lower incident energy than VCB and a lower boundary.
other times the VCB incident energy is greater than the VCBB This is due to the differences in how hot air and plasma will
incident energy. Consider the following points on the plot. rise as it is expelled from the enclosure, further explained in
1) For fault currents up to point 1, both the VCB and VCBB Section V.
arcing fault currents are below the STPU of the protective
device. In this example, a maximum of 2 s fault clearing
time is considered. For a fixed clearing time, VCBB is B. Sample Arc-Flash Boundary Calculation With
Fixed Clearing Time
higher than VCB.
2) At point 1, the VCBB arcing fault current causes an STPU Table V shows the arc-flash boundary results from the sample
response of the overcurrent protective device. The lower switchgear installation with parameters of Table I.

Authorized licensed use limited to: Rick Downer. Downloaded on November 29,2020 at 20:13:26 UTC from IEEE Xplore. Restrictions apply.
6072 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 56, NO. 6, NOVEMBER/DECEMBER 2020

TABLE V
ARC-FLASH BOUNDARY RESULTS

Fig. 6. Incident energy versus working distance.

effect of an upstream protective device with settings shown in


Table IV. Results for the arcing fault current and reduced (MIN)
Fig. 4. Arc-flash boundary versus bolted fault current with fixed clearing time. arcing fault current are plotted and HCB has been removed for
simplicity.
Fig. 5 illustrates that when VCBB and VCB are considered,
the worst-case arc-flash boundary and the worst-case incident
energy are not associated with the same electrode configuration
for most fault current ranges.
1) Between points 1 and 2, VCBB yields the highest incident
energy, but VCB yields the highest arc-flash boundary.
2) Between points 2 and 3, VCB yields both the highest
incident energy and arc-flash boundary.
3) Between points 3 and 4, VCBB yields the highest incident
energy, but VCB yields the highest arc-flash boundary.
4) Between points 4 and 5, VCB yields both the highest
incident energy and arc-flash boundary.

V. WORKING DISTANCE
Fig. 5. Combined plot with varied clearing time.
At typical working distances, HCB is always expected to have
The results in Table V show the VCB arc-flash boundary is the highest incident energy because the arc plasma is forced
higher than the HCB and VCBB arc-flash boundaries. Fig. 4 directly toward the calorimeters in the IEEE Std. 1584-2018
plots this trend across the entire bolted fault current range of tests. However, as the arc plasma is expelled from the enclosure,
IEEE Std. 1584-2018 and confirms that HCB yields the lowest some of the hot air and plasma will rise above the calorimeters
arc-flash boundary for most bolted fault current values with a so the effect of HCB is lessened as distance from the enclosure
fixed 2000 ms fault clearing time. increases. During a VCB or VCBB fault, the arc plasma is first
directed downward due to the vertical orientation. It takes a
greater distance for the hot air and plasma to rise above the
C. Sample Arc-Flash Boundary Calculation With calorimeters. Therefore, as distance increases, the HCB incident
Varied Clearing Time
energy will decrease at a faster rate than the VCBB and VCB
Fig. 4 assumes a fixed fault clearing time over the entire range incident energy. This implies that at some distance from the arc,
of bolted fault current, which is not realistic in distribution HCB will no longer have the highest incident energy.
systems. As the fault current varies, the upstream overcurrent Fig. 6 illustrates how the incident energy will decrease as
protective device operating response will vary the fault duration. working distance increases for each electrode configuration.
Fig. 5 combines the previous incident energy (I.E.) plot with Note that the y-axis is plotted on a logarithmic scale. This
the arc-flash boundary (AFB) results when considering the calculation is performed at a typical switchgear location with

Authorized licensed use limited to: Rick Downer. Downloaded on November 29,2020 at 20:13:26 UTC from IEEE Xplore. Restrictions apply.
REEVES et al.: UNDERSTANDING THE EFFECT OF ELECTRODE CONFIGURATION ON INCIDENT ENERGY AND ARC-FLASH BOUNDARY 6073

TABLE VI
RESULTS OF ARC FLASH STUDY SURVEY OF 2901 BUSES

and arc-flash boundary. This article challenges the assump-


tion that HCB will yield the highest incident energy and arc
flash-boundary and VCB will yield the lowest incident energy
and arc-flash boundary.
To better understand when this assumption does not hold, the
results of 50 recent arc-flash studies performed using the IEEE
Std. 1584-2018 calculation process for facilities across North
America were examined. Of 2901 bus locations reviewed, 42%
had results that did not follow this assumption. The results for
Fig. 7. Incident energy versus working distance. 429 buses reported a VCB incident energy that is higher than
the VCBB incident energy and 1029 reported a VCB arc-flash
a fixed bolted fault current of 50 kA and fault clearing time of boundary higher than the VCBB arc-flash boundary. The results
500 ms. for 127 locations reported a VCB arc-flash boundary higher than
The incident energy for each configuration decreases at a the HCB arc-flash boundary. The results of the arc-flash study
different rate. Fig. 7 expands an area of Fig. 6 to show the points survey are summarized in Table VI.
where the incident energy lines for each electrode configuration Although it is possible with a combination of certain fault
intersect. current and clearing time parameters, the survey of arc flash
1) Prior to point 1, the HCB incident energy is highest, results did not find any locations where the VCBB arc-flash
followed by VCBB and VCB. boundary was greater than both the HCB and VCB arc-flash
2) At point 1, the HCB incident energy decreases and is now boundaries. One such combination is a 200 ms clearing time
lower than the VCBB incident energy, but higher than the with 50 kA of bolted fault current in a 480 V switchgear bus
VCB incident energy. with typical equipment gap and enclosure size.
3) At point 2, the HCB incident energy decreases further The survey did not find any bus locations in which HCB did
and is now lower than both the VCBB and VCB incident not yield the highest incident energy, which is consistent with
energy. the observations of Fig. 3.
4) At point 3, the HCB and VCBB incident energy decrease As discussed in Section III, the HCB will always yield the
further and VCB now yields the highest incident energy. highest incident energy compared to VCB and VCBB with all
5) At point 4, the HCB is the first electrode configuration to parameters equal.
reach 1.2 cal/cm2 at a distance of 146 in. VCB will yield a higher incident energy compared to VCBB
6) At point 5, the VCBB incident energy reaches 1.2 cal/cm2 (15% of cases in the sample survey) when a lower arcing current
at a distance of 158 in. results in a longer clearing time.
7) At point 6, the VCB incident energy reaches 1.2 cal/cm2 As discussed in Sections IV and V, the electrode configuration
at a distance of 165 in. that yields the highest arc-flash boundary depends on the rela-
The distances at which each configuration is calculated to tionship between magnitude of fault current and clearing time
have an incident energy of 1.2 cal/cm2 are defined as the arc- and is not easily predicted. This highlights the importance of
flash boundary. In this example and many other cases, the HCB ensuring that all relevant electrode configurations are evaluated
configuration has the smallest arc-flash boundary, even though with the worst-case reported.
it has the highest incident energy at a typical working distance.
B. Reporting of Incident Energy
VI. REAL WORLD APPLICATION It is critical that the worst-case incident energy from all
considered electrode configurations be reported in an arc-flash
A. Survey of Arc Flash Studies
study report and label. This is even more important when the
As a part of the IEEE Std. 1584-2018 calculation process, incident energy results from two electrode configurations fall
engineering judgement should be used to select one or more across typical ratings of a PPE clothing system.
of the electrode configurations for each equipment location. Two points of concern are 1.2 cal/cm2 and 8 cal/cm2 be-
Annex C of IEEE Std. 1584-2018 offers guidance for selecting cause these are common thresholds for choosing arc rated PPE
electrode configurations based on equipment configuration. If for energized work. The level 40 cal/cm2 is also important
more than one electrode configuration is considered given the to note because this is also a common PPE arc rating and
physical construction of the equipment, multiple calculations historically considered an upper limit for performing energized
should be performed to determine the worst-case incident energy work.

Authorized licensed use limited to: Rick Downer. Downloaded on November 29,2020 at 20:13:26 UTC from IEEE Xplore. Restrictions apply.
6074 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 56, NO. 6, NOVEMBER/DECEMBER 2020

Consider the example shown in Fig. 5 with a bolted fault B. Worst Case Arc-Flash Boundary
current between points 2 and 3. If only the VCBB incident
When multiple electrode configurations are considered at an
energy is reported because it is assumed it will be higher than equipment location, the configuration that results in the largest
VCB, then the result is approximately 12 cal/cm2 . However, the
arc-flash boundary is not always the one that yields the highest
VCB incident energy from the same location is approximately
incident energy for specific tasks.
53 cal/cm2 . The result that is reported will determine whether
At lower bolted fault current values and/or lower fault clearing
energized work can be performed at this location with PPE rated
times, HCB will generally yield the highest arc-flash boundary.
40 cal/cm2 .
At higher bolted fault currents and/or higher fault clearing
Referring again to Fig. 5 with a bolted fault current between
times, VCB or VCBB will generally yield the largest arc-flash
points 4 and 5. If only the VCBB incident energy is reported
boundary.
because it is assumed it will be higher than VCB, the result is
The electrode configuration that yields the worst-case arc-
approximately 3.5 cal/cm2 . However, the VCB incident energy
flash boundary will change depending on the system parameters.
is approximately 13 cal/cm2 . The difference in these incident
In addition, the electrode configuration that yields the largest
energies will likely affect the choice of arc rated PPE.
arc-flash boundary does not always correspond to the electrode
configuration that yields the worst-case incident energy.
C. Reporting of Arc-Flash Boundary
C. Reporting Incident Energy and Arc-Flash
For similar reasons, it is critical that the worst-case arc-flash
Boundary Results
boundary from all relevant electrode configurations is reported
in an arc-flash study report and warning labels. If the worst-case IEEE Std. 1584-2018 requires the selection of at least one
arc-flash boundary is higher than the boundary shown on the electrode configuration for each arc flash calculation. It is likely
warning label, the physical barrier could be incorrectly set too that many real-world equipment installations contain more than
close to the hazard. one configuration. This requires the qualified person perform-
Consider the example shown in Fig. 5 with a bolted fault ing the arc-flash study to perform multiple calculations for a
current between points 2 and 3. If only the VCBB arc-flash single location because the variations in arcing current and
boundary is reported because it is assumed it will be higher than arc-flash boundary make it difficult to determine which config-
VCB, then the result is approximately 85 in. However, the VCB urations will yield a higher result without performing detailed
arc-flash boundary from the same location is approximately calculations.
255 in. It is critical that the qualified person performing the arc-flash
Referring again to Fig. 5 with a bolted fault current between study understand the electrode configurations used for each
points 4 and 5. If only the VCBB arc-flash boundary is reported calculation and consider not only the worst-case incident energy,
because it is assumed it will be higher than VCB, the result but also the worst-case arc-flash boundary when reporting results
is approximately 47 in. However, the VCB arc-flash bound- in an arc-flash study report and label.
ary is approximately 106 in. The difference in these arc-flash The results of the arc-flash study survey validate these conclu-
boundaries will affect the physical barrier setup around the work sions. Therefore, it is important that the ability to evaluate and
location. report the worst-case results is a feature of the software chosen
to complete an arc-flash study.

VII. CONCLUSION
ACKNOWLEDGMENT
A. Worst Case Incident Energy The authors would like to thank the IEEE 1584 working
When multiple electrode configurations are considered at an group for their work in updating IEEE Std. 1584-2018 Guide for
equipment location, determining the electrode configuration that Performing Arc-Flash Hazard Calculations, as well as previous
results in the highest incident energy is not always intuitive presentations and tutorials presented at the IEEE Electrical
because it depends on the conditions for which the incident Safety Workshop (IEEE ESW) and IEEE IAS Petroleum and
energy is being calculated. Chemical Industry Committee (IEEE PCIC) conferences that
HCB will always yield a higher incident energy than VCBB have facilitated discussions and led to this article. The authors
and VCB for a typical working distance with all other parameters would also like to thank Dr. Wei-Jen Lee for his input and
equal. The next highest incident energy can be either VCBB or discussions relating to the behavior of arc plasma during arc
VCB, depending on the arcing fault current and device clearing flash testing.
time and cannot be easily determined without detailed calcula-
tions. REFERENCES
At larger working distances, HCB may no longer yield the
[1] Standard for Electrical Safety in the Workplace, NFPA 70E-2018, NFPA,
highest incident energy because as distance from the arc in- Quincy, MA, USA, 2018.
creases, the HCB incident energy decreases at a faster rate than [2] IEEE Guide for Performing Arc-Flash Hazard Calculations, IEEE Std
the VCBB and VCB incident energy. 1584-2002, IEEE, New York, NY, USA, 2002.

Authorized licensed use limited to: Rick Downer. Downloaded on November 29,2020 at 20:13:26 UTC from IEEE Xplore. Restrictions apply.
REEVES et al.: UNDERSTANDING THE EFFECT OF ELECTRODE CONFIGURATION ON INCIDENT ENERGY AND ARC-FLASH BOUNDARY 6075

[3] IEEE Guide for Performing Arc-Flash Hazard Calculations, IEEE Std Mark Freyenberger (Member, IEEE) received the B.Sc. degree in electrical
1584-2018, IEEE, New York, NY, USA. engineering from Kansas State University, Manhattan, KS, USA, in 2007.
[4] A. Reeves, M. Freyenberger, and M. Hodder, “Understanding the effect He joined Eaton in 2013. He is currently working as Power Systems Engineer
of electrode configuration on incident energy and Arc-flash boundary,” in Project Leader for Eaton’s Electrical Engineering Services and Systems. His
Proc. IEEE IAS Elect. Saf. Workshop, Reno, NV, USA, 2020, pp. 1–6. main responsibilities include performing power system studies, training regard-
ing electrical safety, and project management for national accounts.
Mr. Freyenberger is a registered Professional Engineer in six states.

Michael Hodder (Member, IEEE) received the B.A.Sc. degree in electrical


Adam Reeves (Member, IEEE) received the B.Sc. degree in electrical engineer- engineering from the University of Waterloo, Waterloo, ON, Canada, in 1977.
ing from the University of Maryland, College Park, MD, USA, in 2012. He is currently working as an Advisory Power Systems Engineer for Eaton’s
He joined Eaton in 2012. He is currently working as a Lead Power Systems Electrical Engineering Services and Systems. His main responsibilities include
Engineer for Eaton’s Electrical Engineering Services and Systems. His main performing power system studies and training regarding electrical safety and
responsibilities include performing power system studies and training regarding power system studies.
short circuit, coordination, arc flash, and power quality. Mr. Hodder is a member of Eaton’s National Safety Council. He is also a
Mr. Reeves is the Chairman of Eaton’s Arc Flash Committee and is responsible member of the Technical Committee on Workplace Electrical Safety (CSA
for the standardization and improvement of arc flash methods at Eaton Electrical. Z462). He is a member of the IEEE Industrial Application Society and is a
He is a registered Professional Engineer with the State of Maryland. registered Professional Engineer in the province of Ontario.

Authorized licensed use limited to: Rick Downer. Downloaded on November 29,2020 at 20:13:26 UTC from IEEE Xplore. Restrictions apply.

You might also like