Data sheet for three-phase Squirrel-Cage-Motors SIMOTICS

Motor type : 1CV3407B SIMOTICS SD Pro - 400 - IM B3 - 4p


Client order no. Item-No. Offer no.

Order no. Consignment no. Project

Remarks

Electrical data Safe Area

U Δ/Y f P P I n M η 3) cosφ 3) IA/IN MA/MN MK/MN IE-CL


[V] [Hz] [kW] [hp] [A] [1/min] [Nm] 4/4 3/4 2/4 4/4 3/4 2/4 II/IN TI/TN TB/TN
690 Δ 50 690.00 -/- 680.00 1492 4400.0 96.4 96.5 96.2 0.88 0.84 0.77 7.0 2.0 2.7 IE3

IM B3 / IM10013) SF: 1.05 FS 400 3200 kg IP55 IEC/EN 60034

Environmental conditions : -20 °C - +40 °C / 1000 m Locked rotor time (hot / cold) : 3 s | 6 s

Mechanical data

Moment of inertia 16.5000 kg m² Vibration severity grade Grade A


155(F) to 155(F)
Bearing DE | NDE DIN625-6224-C3 DIN625-6224-C3 Insulation
permissible lateral force on (Nm) x0: x0,5: xmax: Duty type S1
(Nm) N/A N/A N/A
bearing lifetime Direction of rotation bidirectional
cast iron
L10mh FRad max acc. catalogue 50|60Hz 1) 40000 h -/- Frame material
40 g | 40 g
Relubrication interval/quantity DE | NDE Net weight of the motor 3200 kg
6000 h
Lubricants SHELL GADUS S2 V100 3 Coating (paint finish) Special paint finish C3
(Standard) Flat type lubricating nipple acc. DIN
Regreasing device 3404 Color, paint shade RAL7030

Grease nipple M10x1 DIN 3404 A Motor protection 6 resistance thermometers PT100 (12 terminals)

Type of bearing Locating bearing DE Method of cooling IC411 - self ventilated, surface cooled
(Standard) Yes
Condensate drainage holes 'SIMOTICS Connect 400' in IP54 No
(Standard) Yes
External earthing terminal

Terminal box

Terminal box position box at the top, socket right Max. cross-sectional area 240.0 mm2
Cable diameter from ... to ...
Material of terminal box cast iron 56.0 mm - 64.5 mm

Type of terminal box TB3R61 Cable entry 4xM80x2 - 2xM25x1,5

Contact screw thread 12xM16 Cable gland 6 plugs

Notes:
IA/IN = locked rotor current / current nominal 1) L10mh according to DIN ISO 281 10/2010 3) Value is valid only for DOL operation with motor design IC411
MA/MN = locked rotor torque / torque nominal 2) at rated power / at full load 4) For IM B5 design additionally support foot (not scope of delivery) is required
MK/MN = break down torque / nominal torque

responsible dep. technical reference created by approved by Technical data are subject to change! There may be discrepancies
between calculated and rating plate values.
DI MC LVM DT Configurator
document type document status customer

datasheet released
title document number

1LE5583-4AB74-7AJ1-Z
B92+L51+Q01+Q02+Q72+Q81+R62+S02 rev. creation date language Page

© Siemens AG 2021 01 2021-06-23 15:18 en 1/2


Data sheet for three-phase Squirrel-Cage-Motors SIMOTICS

Motor type : 1CV3407B SIMOTICS SD Pro - 400 - IM B3 - 4p

Special design
B92 Q72 2 Pt100 resistance thermometers in basic configuration for bearings (4
Documentation Package "Projects" terminals)
L51 Q81 Extension of the liability for defects by 18 months to a total of 36
Bearing insulation NDE months (3 years) from delivery
Q01 R62
Measuring nipple for SPM shock pulse measurement to monitor bearings Cast iron auxiliary terminal box (small)
Q02 S02
Anti-condensation heating for 230 V (2 terminals) Special paint finish C3

Additional information:
Space heaters

Technical data: 1-phase, 230V, 240W

Notes:

responsible dep. technical reference created by approved by Technical data are subject to change! There may be discrepancies
between calculated and rating plate values.
DI MC LVM DT Configurator
document type document status customer

datasheet released
title document number

1LE5583-4AB74-7AJ1-Z
B92+L51+Q01+Q02+Q72+Q81+R62+S02 rev. creation date language Page

© Siemens AG 2021 01 2021-06-23 15:18 en 2/2