Professional Documents
Culture Documents
Design Background : This spreadsheet focuses on Design Calculation of Outbreathing Flowrates for an Expansion Ta
and Inlet liquid flowrates are considered and the Tank Air Outbreathing Flowrates are calculated. Upon considering
Valve with a given Cv is selected and the calculated Cv required is compared against it. The ratio of the two gives the
Parameter Units
Service (Tank)
Service (PCV)
Insulation Parameters
Inside Heat Transfer Coefficient (Typically 4 W/m2.K for Tanks) (h) W/m2.K
Normal Temp K
Normal Pressure kpaa
Std. Temp K
Std. Pressure kpaa
Actual Temp. K
Actual Pressure kpaa
NOTE : Sizing has been done based on English Units (Psi, Lb/ft3, inch etc.) since Cv is based on those units. The final Output
is the same since the required answers are in Ratios or percentages. Wherever required the conversions have been made for a
Valve Manufacturer
Valve Model Selected
Selected Valve Rated Maximum (Flow Coefficient) CV1
Selected Valve Rated Pressure Drop Ratio Factor
(From Manufacturer or the Table) (Xt)
Criticality By %
Conclusions :
a. The Outbreathing Requirements are calculated as per the new API Method as stated in API 2000, 7th Edition, 3.3.
There is an alternative method for snall sized tanks that satisfy specific criteria given in Annex A of the API std. The n
b. In general, Valves can also be allowed to operate under Choked Flow Conditions. If valves operate at higher press
drop ratio possible is the rated valve critical pressure drop ratio. In non choked (Non-critical) flows, the pressure dro
c. For Valve Openings which are too low, verify the acceptability and whether the valve opens or not for that flowra
Generally never select a valve greater than the line size.
d. If the Liquid stored in the Tank is volatile, the outbreathing requirements change, but that has been accounted fo
NOTES
1. General Rule of Thumb = For liquids Velocity should be limited to 50 ft/s or 15 m/s
2. Limit Valve Opening to between 10-80 %
EXPANSION TANK - OUTLET CONTROL VALVE SIZING (GAS)
utbreathing Flowrates for an Expansion Tank and the Sizing of the Outlet PCV based mainly on the Revised API 2000 Method (7t
owrates are calculated. Upon considering these values, a valve is selected and suitability is checked. This flowsheet is only valid
ed against it. The ratio of the two gives the valve opening required.
Value Value
Cushion Gas Inlet for PCV Cushion Gas Inlet for PCV
Air Air
1.50 1.50
11.75 11.75
-2.95 -2.95
81.00 81.00
0.81 0.81
0.81 0.81
-0.22 -0.22
44.06 44.06
6.70 6.70
28.949 28.949
1.000 1.000
1.222 1.222
0.00 0.00
14.70 14.70
101.33 101.33
1.01 1.01
0.00 0.00
-17.78 -17.78
92.00 92.00
33.33 33.33
44.07 44.07
6.70 6.70
1.008 1.008
0.063 0.063
1.000 1.000
4.00 4.00
0.00 0.00
1.00 1.00
1.00 1.00
1.00 1.00
0.000 0.000
0.000 0.000
0.000 0.000
6.70 6.70
44.06 44.06
Below 25 oC Below 25 oC
0.000 0.000
0.000 0.000
0.050 0.050
0.375 0.375
NO NO
40.58 40.58
Below 42 Below 42
4.000 4.000
0.320 0.320
273.15 273.15
101.325 101.325
288.75 288.75
101.325 101.325
279.85 279.85
81.000 81.000
0.425 0.425
0.449 0.449
0.545 0.545
0.549 0.549
0.545 0.545
0.549 0.549
0.549 0.549
1.210 1.210
1.30 1.30
0.714 0.714
1.573 1.573
1.40 1.40
1.00 1.00
1.008 1.008
0.063 0.063
1.00 1.00
25.40 25.40
1.00 1.00
25.40 25.40
0.000 0.000
0.000 0.000
1.00 1.00
25.40 25.40
0.000 0.000
0.000 0.000
0.000 0.000
0.000 0.000
Carraro Carraro
UBAN UB Regulator Series UBAN UB Regulator Series
1", Nozzle 1 1", Nozzle 1
0.031 0.031
0.700 0.700
1.000 1.000
0.700 0.700
0.700 0.700
63.30 63.30
276.00 276.00
40.02 40.02
2.76 2.76
101.33 101.33
14.69 14.69
1.01 1.01
174.68 174.68
25.33 25.33
1.75 1.75
0.633 0.633
0.633 0.633
0.699 0.699
0.00089 0.00089
0.03100 0.03100
2.87 2.87
Suitable Suitable
But Take Care due to Very Low Inlet Flow
No Criticality No Criticality
ts change, but that has been accounted for in the Outbreathing Requirements (due to flow) formula.
s or 15 m/s
ALVE SIZING (GAS)
nly on the Revised API 2000 Method (7th Edition) general Case and Masoneilan Control Valve Sizing. The Outlet Blanket Gas
is checked. This flowsheet is only valid for Gas Cushioned Expansion Tanks. Upon calculating the Breathing requirements, a
Value Value
Cushion Gas Inlet for PCV Cushion Gas Inlet for PCV
Air Air
1.50 1.50
11.75 11.75
-2.95 -2.95
81.00 81.00
0.81 0.81
0.81 0.81
-0.22 -0.22
44.06 44.06
6.70 6.70
28.949 28.949
1.000 1.000
1.222 1.222
0.00 0.00
14.70 14.70
101.33 101.33
1.01 1.01
0.00 0.00
-17.78 -17.78
92.00 92.00
33.33 33.33
44.07 44.07
6.70 6.70
1.008 1.008
0.063 0.063
1.000 1.000
4.00 4.00
0.00 0.00
1.00 1.00
1.00 1.00
1.00 1.00
0.000 0.000
0.000 0.000
0.000 0.000
6.70 6.70
44.06 44.06
Below 25 oC Below 25 oC
0.000 0.000
0.000 0.000
0.050 0.050
0.375 0.375
NO NO
40.58 40.58
Below 42 Below 42
4.000 4.000
0.320 0.320
273.15 273.15
101.325 101.325
288.75 288.75
101.325 101.325
279.85 279.85
81.000 81.000
0.425 0.425
0.449 0.449
0.545 0.545
0.549 0.549
0.545 0.545
0.549 0.549
0.549 0.549
1.210 1.210
1.30 1.30
0.714 0.714
1.573 1.573
1.40 1.40
1.00 1.00
1.008 1.008
0.063 0.063
1.00 1.00
25.40 25.40
1.00 1.00
25.40 25.40
0.000 0.000
0.000 0.000
1.00 1.00
25.40 25.40
0.000 0.000
0.000 0.000
0.000 0.000
0.000 0.000
nd constants are based on english units hence the spreadsheet has been formulated this way
Carraro Carraro
UBAN UB Regulator Series UBAN UB Regulator Series
1", Nozzle 1 1", Nozzle 1
0.031 0.031
0.700 0.700
1.000 1.000
0.700 0.700
0.700 0.700
63.30 63.30
276.00 276.00
40.02 40.02
2.76 2.76
101.33 101.33
14.69 14.69
1.01 1.01
174.68 174.68
25.33 25.33
1.75 1.75
0.633 0.633
0.633 0.633
0.699 0.699
0.00089 0.00089
0.03100 0.03100
2.87 2.87
Suitable Suitable
No Criticality No Criticality
onservative than the Old method with the introduction of new parameters such as Latitude, C-Factor, Y-Factor etc.
hen the effective pressure drop ratio becomes the critical pressure drop ratio since at Choked Flow, the highest pressure
(Upstream-downstream) across the valve.
ow) formula.
an Control Valve Sizing. The Outlet Blanket Gas
Upon calculating the Breathing requirements, a
Basis of Calculation
if N2 then 28.01.
at 15.6 oC
Atmospheric Conditions
Calculated
d this way
VP>HEXANE (Volatile)
Below 25 oC Above and Equal 25 oC
Below 42 6.5 6.5
Between 42 and 58 5 5
Above 58 4 4