Wiring Manual

Series R®
Helical Rotary Liquid Chillers

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-
conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment
by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and
on the tags, stickers, and labels that are attached to the equipment.

April 2013 RTHD-SVE01A-EN


Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings, must also be adhered to for responsible management of
cautions and notices appear at appropriate intervals refrigerants. Know the applicable laws and follow them.
throughout this manual. Warnings are provide to alert
installing contractors to potential hazards that could result
in death or personal injury. Cautions are designed to alert WARNING
personnel to hazardous situations that could result in
personal injury, while notices indicate a situation that Proper Field Wiring and Grounding
could result in equipment or property-damage-only Required!
accidents. All field wiring MUST be performed by qualified
Your personal safety and the proper operation of this personnel. Improperly installed and grounded field
machine depend upon the strict observance of these wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
precautions.
field wiring installation and grounding as described in
Read this manual thoroughly before operating or servicing NEC and your local/state electrical codes. Failure to
this unit. follow code could result in death or serious injury.

ATTENTION: Warnings, Cautions and Notices appear at


appropriate sections throughout this literature. Read WARNING
these carefully: Personal Protective Equipment (PPE)
Required!
Indicates a potentially hazardous
WARNING situation which, if not avoided, could Installing/servicing this unit could result in exposure to
result in death or serious injury. electrical, mechanical and chemical hazards.
Indicates a potentially hazardous • Before installing/servicing this unit, technicians
CAUTIONs situation which, if not avoided, could MUST put on all Personal Protective Equipment (PPE)
result in minor or moderate injury. It recommended for the work being undertaken.
could also be used to alert against ALWAYS refer to appropriate MSDS sheets and OSHA
unsafe practices. guidelines for proper PPE.
NOTICE: Indicates a situation that could result in
equipment or property-damage only • When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
Important OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
Environmental Concerns! protection and handling recommendations.
Scientific research has shown that certain man-made
• If there is a risk of arc or flash, technicians MUST put
chemicals can affect the earth’s naturally occurring
on all Personal Protective Equipment (PPE) in
stratospheric ozone layer when released to the
accordance with NFPA 70E or other country-specific
atmosphere. In particular, several of the identified
requirements for arc flash protection, PRIOR to
chemicals that may affect the ozone layer are refrigerants
servicing the unit.
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and Failure to follow recommendations could result in death
Carbon (HCFCs). Not all refrigerants containing these or serious injury.
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.

Responsible Refrigerant Practices!


Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that

© 2013Trane All rights reserved RTHD-SVE01A-EN


Warnings, Cautions and Notices

WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives or
other energy storing components provided by Trane or
others, refer to the appropriate manufacturer’s literature
for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. Failure to disconnect power
and discharge capacitors before servicing could result in
death or serious injury.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN

NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types
of conductors. Failure to use copper conductors could
result in equipment damage.

Introduction
Revision Summary
RTHD-SVE01A-EN (24 April 2013)
New manual lists RTHD wiring diagrams.

Trademarks
Trane and theTrane logo are trademarks or registered
trademarks ofTrane in the United States and other
countries.Trane is a business of Ingersoll Rand. All
trademarks referenced in this document are the
trademarks of their respective owners.

RTHD-SVE01A-EN 3
Table of Contents
Warnings, Cautions and Notices . . . . . . . . . . 2
Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Electrical Data . . . . . . . . . . . . . . . . . . . . . . 5

4 RTHD-SVE01A-EN
Wiring Schematics
This document provides typical field connection diagrams, electrical schematics for the RTHD units. See RTHD-SVX01*-
EN for Installation, Operation and Maintenance information.
Note: The drawings in this section are provided for reference only.These diagrams may not reflect the actual wiring of
your unit. For specific electrical connection and schematic information, always refer to the wiring diagrams that
were shipped with the unit.

Unit Electrical Data


To determine the specific electrical characteristics of a particular chiller, see the nameplates mounted on the units.

Drawing Description Page


2309-7552 Schematic, page 1 - WYE-DELTA Starter 6
2309-7553 Schematic, page 2 - WYE-DELTA Starter 8
2309-7554 Schematic, page 3 - WYE-DELTA Starter 10
2309-7555 Schematic, page 4 - WYE-DELTA Starter 12
2309-1360 Schematic, page 1 - SOLID STATE Starter 14
2309-1361 Schematic, page 2 - SOLID STATE Starter 16
2309-1362 Schematic, page 3 - SOLID STATE Starter 18
2309-1363 Schematic, page 4 - SOLID STATE Starter 20
2309-7564 Component Location 22
2309-7565 Component Location - Solid State Starter 24
2309-4870 Field Wiring 26
2309-4869 Field Layout 28

RTHD-SVE01A-EN 5
6
1 1
7552
2 ! WARNING ! AVERTISSEMENT ! ADVERTENCIA 2
L1 L2 L3 L1 L2 L3 L1 L2 L3 HAZARDOUS VOLTAGE! TENSION DANGEREUSE! iVOLTAJE PELIGROSO!
3 DISCONNECT ALL ELECTRIC POWER INCLUDING COUPER TOUTES LES TENSIONS ET OUVRIR DESCONECTE TODA LA ENERGÍA ELÉCTRICA, 3
REMOTE DISCONNECTS AND FOLLOW LOCK OUT LES SECTIONNEURS À DISTANCE, PUIS SUIVRE INCLUSO LAS DESCONEXIONES REMOTAS Y SIGA
4 AND TAG PROCEDURES BEFORE SERVICING. LES PROCÉDURES DE VERROUILLAGE ET DES LOS PROCEDIMIENTOS DE CIERRE Y ETIQUETADO 4
INSURE THAT ALL MOTOR CAPACITORS HAVE ÉTIQUETTES AVANT TOUTE INTERVENTION. ANTES DE PROCEDER AL SERVICIO. ASEGÚRESE
DISCHARGED STORED VOLTAGE. UNITS WITH VÉRIFIER QUE TOUS LES CONDENSATEURS DE QUE TODOS LOS CAPACITORES DEL MOTOR
5 1Q1 1S1 1X1 VARIABLE SPEED DRIVE, REFER TO DRIVE DES MOTEURS SONT DÉCHARGÉS. DANS LE CAS HAYAN DESCARGADO EL VOLTAJE ALMACENADO. 5
INSTRUCTIONS FOR CAPACITOR DISCHARGE. D'UNITÉS COMPORTANT DES ENTRAÎNEMENTS PARA LAS UNIDADES CON TRANSMISIÓN
FAILURE TO DO THE ABOVE COULD RESULT À VITESSE VARIABLE, SE REPORTER AUX DE VELOCIDAD VARIABLE, CONSULTE LAS
Unit Electrical Data

6 6
1 2 3 IN DEATH OR SERIOUS INJURY. INSTRUCTIONS DE L'ENTRAÎNEMENT POUR INSTRUCCIONES PARA LA DESCARGA
A A A DÉCHARGER LES CONDENSATEURS. DEL CONDENSADOR.
7 13 B B B UN MANQUEMENT À LA PROCÉDURE NO REALIZAR LO ANTEDICHO PUEDE PROVOCAR 7
C C C CI-DESSUS PEUT ENTRAÎNER DES LA MUERTE O LESIONES GRAVES.
8 D D D BLESSURES GRAVES, VOIRE LA MORT. 8

9 52A 52A 9
3-88

1T2-1
10 53A 53A NOTICE AVIS AVISO 10
3-89
USE COPPER CONDUCTORS ONLY! N'UTILISER QUE DES CONDUCTEURS ¡UTILICE ÚNICAMENTE
11 54A 54A UNIT TERMINALS ARE NOT EN CUIVRE! CONDUCTORES DE COBRE! 11
3-90 DESIGNED TO ACCEPT OTHER LES BORNES DE L'UNITÉ NE SONT LAS TERMINALES DE LA UNIDAD NO
TYPES OF CONDUCTORS. PAS CONÇUES POUR RECEVOIR ESTÁN DISEÑADAS PARA ACEPTAR

1T2-2
12 55A 55A 12
3-91 FAILURE TO DO THE ABOVE COULD D'AUTRES TYPES DE CONDUCTEURS. OTROS TIPOS DE CONDUCTORES.
RESULT IN EQUIPMENT DAMAGE. UN MANQUEMENT À LA PROCÉDURE NO REALIZAR LO ANTEDICHO PUEDE
13 CI-DESSUS PEUT ENTRAÎNER PROVOCAR DAÑOS EN EL EQUIPO. 13
56A 56A
3-92 DES DOMMAGES À L'ÉQUIPEMENT.
14 14

1T2-3
57A 57A
3-93
15 15

16 16

17 17

18 18

19 19
3M 2M 1M
20 20
1F3 1F2 1F1
21 21
22 A 21 A,F 20 A,F
22 22

23 23
13
22B ,C 22A
24 1K1 24
1A ,C 7A,D 1X3-3
13 21B ,C 21F
25 1R3 1K4 25
7B 4A 8C 7A, D 1X3-2
T1 20B ,C 20F
26 1K2 4 1K3 26
1B ,D ,M 8A, B, D 8B, C 8A, D 1X3-1
22C
(BK)

(BK)
22B
20B
21B

20C
21C

27 T6 3M1 27
1K1
2A ,C 9A,D 9A, D
(BK/WH)
(BK/WH)

(BK/WH)

T2 M
28 1R2 1K4 28
9B 5A 10C 10A, D 1T3-3 1T3-2 1T3-1
29 4 T4 29
1K2 1K3
2B ,D ,M 10A ,B, D 10B, C 11A, D
GN

GN
GN

115VAC 115VAC 115VAC


30 T3 30
1K1
3A ,C 11A, D 12A, D
31 T5 31
63A
62A
61A
60A
59A
58A

1R1 1K4
11B 6A 12C
32 1K2 4 1K3 32
3B ,D ,M 12A ,B, D 12B, C
33 33
3-95
3-94

3-99
3-98
3-97
3-96

34 34

35 35

36 36

37 37
WB3
M
38 DUAL PORT 380V 60HZ 38
ELECTRONIC 230V 50HZ
EXPANSION VALVE
39 ACTUATOR 2 4Y21 H1 H2 39

40 40
P
EVAPORATOR 21A 20A
41 575V 60HZ 41
REFRIGERANT
PRESSURE 4B25 230V 60HZ 200V 60HZ
42 H1 H2 H3 H1 460V 60HZ H2 H3 42
M

RTHD-SVE01A-EN
DUAL PORT 1T1
EXPANSION VALVE
39 ACTUATOR 2 4Y21 H1 H2 39

40 40
P

7552-2
EVAPORATOR 21A 20A
41 575V 60HZ 41
REFRIGERANT
PRESSURE 4B25 230V 60HZ 200V 60HZ
42 H1 H2 H3 H1 460V 60HZ H2 H3 42
M
DUAL PORT 1T1
43 ELECTRONIC 43
EXPANSION VALVE 115V 27V
ACTUATOR 1 4Y20
44 380/400/415V 50HZ X1 X2 X3 X4 44
P

RTHD-SVE01A-EN
CONDENSER 380V 400V 415V
45 REFRIGERANT H1 H2 H3 H4 45

14A
27A
16A
PRESSURE 4B26 17A
46 46

47 47
EVAPORATOR
ENTERING

14A
16A
17A

48 WATER 4B20 48

J1 COMPRESSOR
49 49
DISCHARGE
1F4
1F5
1F6

TEMPERATURE 4B27
J11
50 50

51 51
27A
23B
24B

26D

J1
EVAPORATOR RD
52 LEAVING +24 1 52
WATER 4B21
ETHERNET BK
53 GND 2 53
WB1
J2
1XJ2-3
1XJ2-5
1XJ2-1
1XJ2-2

GN
54 COMM + 3 54

WH
55 COMM - 4 55
1XP2-3
1XP2-5
1XP2-1
1XP2-2

ADAPTIVIEW DISPLAY MONITOR


56 56
1A1
CONDENSATION
ENTERING
57 WATER 4B22 57
26A
27B
24A

23A

58 58
1X5-8
59 1X5-4 59

60 60
5B28
26C
27R

SPLICE SPLICE
CONDENSATION
61 LEAVING 61
OUTDOOR AIR TEMPERATURE 4 4 4
WATER 4B23 FACTORY INSTALLED
62 62
LEAD LENGTH EXTENDED
BY CUSTOMER
63 63
GN BU GY RD WH GN BK RD WH GN BK RD
27Z

1XP2-4

64 64

65 P 65
OIL PRESSURE
1XJ2-4

TRANSDUCER 4 3 2 1 4 3 2 1 4 3 2 1
66 4B24 66
J3 J4 J5
67 67

1A2
68 68
POWER SUPPLY 25A
3
26E
27R

69 69
24A
J2 2
EVAPORATOR
70 REFRIGERANT 70
J11 23A
3-78

LIQUID LEVEL
3-78

1
4B3
71 J1 71

72 72

WB2
73 73
WB2
3-102
74 74

75 75

DRAWN BY: L.CRESON


SCHEMATIC
C TRANE DATE: 07-MAY-2012
R RTHD
MASTER FILE: WYE DELTA STARTER
REVISION DATE:
REPLACES:
THIS DRAWING IS PROPRIETARY
SIMILAR TO: AND SHALL NOT BE COPIED
OR ITS CONTENTS DISCLOSED
TO OUTSIDE PARTIES WITHOUT REV
THE WRITTEN CONSENT OF TRANE
USED BY: SHEET
2
CAD: CREO SCHEMATICS 2309-7552 E

7
Unit Electrical Data
8
7553
76 76

77 77

2-69
2-70
78 78

79 79

26E
27R
80 1K1 AUX 2 4E1 1X5-9 80
28E 1XP1-3 1XJ1-3 28C 1X5-1 28A 27C 27F ,M
26E ,F
81 81
4E2
28B 27D
82 82
Unit Electrical Data

83 4Y3 83
1K1 AUX2
26B ,F 29E 1XP1-4 1XJ1-4 29A 29B 27M
84 84
1X5-2

85 4B29 85
26G ,J 26R (BK) 40A (YE)
86 1X5-5 86
1A3
STARTER MODULE
87 P 31B (RD) 87
1XJ1-5 1XP1-5 1K2 AUX 1
52A 30A 30C 26B
88 2-9 1 + 2 88
TRANSITION J12
53A COMPLETE 27F
89 2-10 2 - 1 89

54A 31A 31A 31B (RD)


90 2-11 3 + 3 90
J7 J10 1X5-3
55A
91 2-12 4 - STOP 2 91

56A
92 2-13 5 + 1 92
1K1 AUX 1
57A 32A 1XP2-6 1XJ2-6 32B 33A,D
93 2-14 6 - 2 93
START 1K1
J8 1XJ1-6 1XP1-6 1XP1-2 1XJ1-2
58A 33B 33D 33A ,E 27AJ 27L 27K ,X
94 2-33 1 + 1 1-24, 27, 30 94
1X5-10 2-81, 83, 93
59A 33C 33E
95 2-33 2 - 3 95
1XJ1-7 1XP1-7
J6 27E 1XP1-1 1XJ1-1 27K
60A
96 2-33 3 + RUN 2 96
J5 1K2
1XP2-7 1XJ2-7 1K3 AUX
61A 35A 35B 36A 27J ,E 1-26, 29, 32
97 2-33 4 - 1 97
2-88
62A 26G
98 2-33 5 + 3 98
J4
63A
99 2-33 6 - SHORTING 2 99
1K3
1K4 AUX
64A (RD) 37A 37B 38A 27G ,J
100 4-170 1 +24 1 1-26, 29, 32 100
1XJ1-8 1XP1-8
2-97
26J
101 2 GND 3 101
J3 J2

2-74
102 3 COM + TRANSITION 2 102
1K4
39A 39B 27G
103 4 COM - 1 1-25, 28, 31 103

WB2
1XJ1-9 1XP1-9 2-100
J1
104 104

105 105
1A4
DUAL HIGH VOLTAGE BINARY INPUT
106 106

40A (YE)
107 2 107
J3 HIGH PRESSURE CUTOUT
27X
108 HIGH PRESSURE CUTOUT 1 108

109 2 109
J2
110 1 110

J11 NOTICE
111 111
USE COPPER CONDUCTORS ONLY!
J1 UNIT TERMINALS ARE NOT DESIGNED TO
112 112
ACCEPT OTHER TYPES OF CONDUCTORS.
FAILURE TO DO THE ABOVE COULD
113 RESULT IN EQUIPMENT DAMAGE. 113
1A5
DUAL TRIAC
114 114

26K 1X5-6 26M


AVIS
115 2 LOAD N'UTILISER QUE DES CONDUCTEURS EN CUIVRE! 115
J3 3Y1 LES BORNES DE L'UNITÉ NE SONT
41A 41A 27P,Q 27P 27T ,U PAS CONÇUES POUR RECEVOIR
116 1 116
D'AUTRES TYPES DE CONDUCTEURS.
SLIDE VALVE UNLOAD/LOAD 1X5-11
26M UN MANQUEMENT À LA PROCÉDURE
117 2 UNLOAD CI-DESSUS PEUT ENTRAÎNER 117
3Y2 DES DOMMAGES À L'ÉQUIPEMENT.
J2
42A 42A 27Q
118 1 118

J11

RTHD-SVE01A-EN
119
AVISO 119
Ú
DUAL TRIAC
114 114

26K 1X5-6 26M


AVIS
115 2 LOAD N'UTILISER QUE DES CONDUCTEURS EN CUIVRE! 115
J3 3Y1 LES BORNES DE L'UNITÉ NE SONT

7553-2
41A 41A 27P,Q 27P 27T ,U PAS CONÇUES POUR RECEVOIR
116 1 116
D'AUTRES TYPES DE CONDUCTEURS.
SLIDE VALVE UNLOAD/LOAD 1X5-11
26M UN MANQUEMENT À LA PROCÉDURE
117 2 UNLOAD CI-DESSUS PEUT ENTRAÎNER 117
3Y2 DES DOMMAGES À L'ÉQUIPEMENT.
J2
42A 42A 27Q
118 1 118

J11 AVISO
119 119
¡UTILICE ÚNICAMENTE CONDUCTORES DE COBRE!

RTHD-SVE01A-EN
J1 LAS TERMINALES DE LA UNIDAD NO
120 120
ESTÁN DISEÑADAS PARA ACEPTAR
OTROS TIPOS DE CONDUCTORES.
121 NO REALIZAR LO ANTEDICHO PUEDE 121
1A6
PROVOCAR DAÑOS EN EL EQUIPO.
DUAL TRIAC
122 122

26P
123 2 FILL 123
J3 4Y1
43A 43A 27R ,S 27R ! WARNING
124 OIL RETURN GAS PUMP 1 124
HAZARDOUS VOLTAGE!
DRAIN/FILL SOLENOID VALVE 26Z
125 2 DRAIN DISCONNECT ALL ELECTRIC POWER INCLUDING 125
4Y2 REMOTE DISCONNECTS AND FOLLOW LOCK OUT
J2
44A 44A 27S AND TAG PROCEDURES BEFORE SERVICING.
126 1 126
INSURE THAT ALL MOTOR CAPACITORS HAVE
J11 DISCHARGED STORED VOLTAGE. UNITS WITH
127 VARIABLE SPEED DRIVE, REFER TO DRIVE 127
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
J1 FAILURE TO DO THE ABOVE COULD RESULT
128 128
IN DEATH OR SERIOUS INJURY.
129 129
1A8
DUAL RELAY OUTPUT
! AVERTISSEMENT
130 130
TENSION DANGEREUSE!
1
COUPER TOUTES LES TENSIONS ET OUVRIR
131 LES SECTIONNEURS À DISTANCE, PUIS SUIVRE 131
LES PROCÉDURES DE VERROUILLAGE ET DES
132 ÉTIQUETTES AVANT TOUTE INTERVENTION. 132
VÉRIFIER QUE TOUS LES CONDENSATEURS
ICE BUILDING DES MOTEURS SONT DÉCHARGÉS. DANS LE CAS
133 D'UNITÉS COMPORTANT DES ENTRAÎNEMENTS 133
STATUS OUTPUT (OPTIONAL) J2 3 À VITESSE VARIABLE, SE REPORTER AUX
ICE MACHINE
134 INSTRUCTIONS DE L'ENTRAÎNEMENT POUR 134
STATUS CUSTOMER DÉCHARGER LES CONDENSATEURS.
7 PROVIDED POWER UN MANQUEMENT À LA PROCÉDURE
135 CI-DESSUS PEUT ENTRAÎNER DES 135
5K20
(ICE MAKING BLESSURES GRAVES, VOIRE LA MORT.
136 136
HARDWARE
J11 9 ONLY PRESENT ! ADVERTENCIA
137 137
IF ORDERED) iVOLTAJE PELIGROSO!
J1
138 DESCONECTE TODA LA ENERGÍA ELÉCTRICA, 138
INCLUSO LAS DESCONEXIONES REMOTAS Y SIGA
LOS PROCEDIMIENTOS DE CIERRE Y ETIQUETADO
139 ANTES DE PROCEDER AL SERVICIO. ASEGÚRESE 139
1A7
DUAL HIGH VOLTAGE BINARY INPUT DE QUE TODOS LOS CAPACITORES DEL MOTOR

26P,Z
140 HAYAN DESCARGADO EL VOLTAJE ALMACENADO. 140
CHILLED WATER PARA LAS UNIDADES CON TRANSMISIÓN
5K1 AUX
1 5S1 DE VELOCIDAD VARIABLE, CONSULTE LAS
141 2 141
INSTRUCCIONES PARA LA DESCARGA
J3 1X6-1 1X5-7 DEL CONDENSADOR.
CONDENSER/CHILLED WATER 27T
142 1 NO REALIZAR LO ANTEDICHO PUEDE PROVOCAR 142
FLOW SWITCH CONDENSER WATER
5K2 AUX LA MUERTE O LESIONES GRAVES.
5S2
143 INTERLOCKS 2 143
J2
27U
144 1 144

4-152
J11
145 145

J1

WB2
146 146

147 147
1A9
DUAL RELAY OUTPUT
148 148

1
149 6 H 149
CUSTOMER PROVIDED POWER 7
150 5 150
5K1 N
4 CHILLED WATER
CONDENSER/CHILLED WATER J2 PUMP STARTER
WATER PUMP STARTER 3 DRAWN BY: L.CRESON
SCHEMATIC
C TRANE DATE: 08-MAY-2012
2 R RTHD
5K2 CONDENSER MASTER FILE: WYE DELTA STARTER
1 WATER REVISION DATE:
J11 PUMP STARTER
REPLACES:
THIS DRAWING IS PROPRIETARY
SIMILAR TO: AND SHALL NOT BE COPIED
J1 OR ITS CONTENTS DISCLOSED
TO OUTSIDE PARTIES WITHOUT REV
THE WRITTEN CONSENT OF TRANE
USED BY: SHEET
3
CAD: CREO SCHEMATICS 2309-7553 C

9
Unit Electrical Data
10
7554
151 151

3-145
152
NOTICE 152
USE COPPER CONDUCTORS ONLY!
153 UNIT TERMINALS ARE NOT DESIGNED TO 153

WB2
ACCEPT OTHER TYPES OF CONDUCTORS.
FAILURE TO DO THE ABOVE COULD
154 RESULT IN EQUIPMENT DAMAGE. 154

155 155
AVIS
156 N'UTILISER QUE DES CONDUCTEURS EN CUIVRE! 156
LES BORNES DE L'UNITÉ NE SONT
157 PAS CONÇUES POUR RECEVOIR 157
DUAL LOW VOLTAGE BINARY INPUT D'AUTRES TYPES DE CONDUCTEURS.
Unit Electrical Data

1A12 UN MANQUEMENT À LA PROCÉDURE


158 CI-DESSUS PEUT ENTRAÎNER 158
5K22
DES DOMMAGES À L'ÉQUIPEMENT.
159 4 EMERGENCY STOP 159

W1 AVISO
160 3 5K21 6 160
AUTO STOP/EMERGENCY STOP J2 ¡UTILICE ÚNICAMENTE CONDUCTORES DE COBRE!
161 2 LAS TERMINALES DE LA UNIDAD NO 161
AUTO STOP
ESTÁN DISEÑADAS PARA ACEPTAR
W2 OTROS TIPOS DE CONDUCTORES.
162 1 NO REALIZAR LO ANTEDICHO PUEDE 162
PROVOCAR DAÑOS EN EL EQUIPO.
J11
163 163

J1
164 164

165 ! WARNING 165

HAZARDOUS VOLTAGE!
166 166
DISCONNECT ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS AND FOLLOW LOCK OUT
167 AND TAG PROCEDURES BEFORE SERVICING. 167
DUAL LOW VOLTAGE BINARY INPUT INSURE THAT ALL MOTOR CAPACITORS HAVE
168 1A11 DISCHARGED STORED VOLTAGE. UNITS WITH 168
VARIABLE SPEED DRIVE, REFER TO DRIVE
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
169 FAILURE TO DO THE ABOVE COULD RESULT 169
4 64A (RD)
3-100 IN DEATH OR SERIOUS INJURY.
LIQUID LEVEL
170 SENSOR 170
3
OIL LOSS LEVEL J2 4B2 ! AVERTISSEMENT
171 65A (BK) 171
2
TENSION DANGEREUSE!
172 66A (WH) COUPER TOUTES LES TENSIONS ET OUVRIR 172
1 LES SECTIONNEURS À DISTANCE, PUIS SUIVRE
8
LES PROCÉDURES DE VERROUILLAGE ET DES
173 J11 ÉTIQUETTES AVANT TOUTE INTERVENTION. 173
VÉRIFIER QUE TOUS LES CONDENSATEURS
174 J1 DES MOTEURS SONT DÉCHARGÉS. DANS LE CAS 174
D'UNITÉS COMPORTANT DES ENTRAÎNEMENTS
À VITESSE VARIABLE, SE REPORTER AUX
175 INSTRUCTIONS DE L'ENTRAÎNEMENT POUR 175
DÉCHARGER LES CONDENSATEURS.
176 UN MANQUEMENT À LA PROCÉDURE 176
CI-DESSUS PEUT ENTRAÎNER DES
177 BLESSURES GRAVES, VOIRE LA MORT. 177

178 ! ADVERTENCIA 178


DUAL ANALOG I/O
3
1A13 iVOLTAJE PELIGROSO!
179 179
DESCONECTE TODA LA ENERGÍA ELÉCTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y SIGA
180 GND 6 LOS PROCEDIMIENTOS DE CIERRE Y ETIQUETADO 180
1A15
0-10VDC ANTES DE PROCEDER AL SERVICIO. ASEGÚRESE
DUAL LOW VOLTAGE BINARY INPUT
181 INPUT 2 5 COMPRESSOR % RLA 5K13 DE QUE TODOS LOS CAPACITORES DEL MOTOR 181
OUTPUT 4 HAYAN DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON TRANSMISIÓN
182 OUTPUT 2 4 11 EXTERNAL BASE LOAD COMMAND DE VELOCIDAD VARIABLE, CONSULTE LAS 182
J2 3 INSTRUCCIONES PARA LA DESCARGA
(OPTIONAL)
183 CONDENSER CONTROL GND 3 5K12 J2 (OPTIONAL) DEL CONDENSADOR. 183
0-10VDC NO REALIZAR LO ANTEDICHO PUEDE PROVOCAR
OUTPUT & COMPRESSOR 2 ICE/EXTERNAL
CONDENSER CONTROL OUTPUT FIELD 10 ICE BUILDING CONTROL LA MUERTE O LESIONES GRAVES.
% RLA OUTPUT BASE LOAD
184 INPUT 1 2 SELECTABLE AS: CONDENSER PRESSURE, (ICE MAKING HARDWARE 184
DELTA PRESSURE, OR CONTROL OUTPUT SIGNAL ONLY PRESENT IF ORDERED) 1
FOR CONDENSER HEAD PRESSURE CONTROL
185 OUTPUT 1 1 185

186 186

J11 J11
187 187

J1 J1
188 188

189 189

190 DUAL ANALOG I/O 190


1A14
191 191

GND 6 CUSTOMER EXTERNAL CHILLED DUAL ANALOG I/O


192 192
WATER SETPOINT INPUT 1A17
INPUT 2 5 2-10VDC OR 4-20mA
193 193
6 GND

RTHD-SVE01A-EN
OUTPUT 2 4
194 (OPTIONAL) EXTERNAL BASELOAD SETPOINT INPUT 194
189 189

190 DUAL ANALOG I/O 190

7554-2
1A14
191 191

GND 6 CUSTOMER EXTERNAL CHILLED DUAL ANALOG I/O


192 192
WATER SETPOINT INPUT 1A17
INPUT 2 5 2-10VDC OR 4-20mA
193 193
6 GND
OUTPUT 2 4
194 (OPTIONAL) EXTERNAL BASELOAD SETPOINT INPUT 194

RTHD-SVE01A-EN
EXTERNAL CURRENT LIMIT J2
5 INPUT 2
& EXTERNAL CHILLED GND 3 CUSTOMER EXTERNAL CURRENT 12 4-20ma/2-10VDC
195 195
WATER SETPOINT LIMIT SETPOINT INPUT
2-10VDC OR 4-20mA 4 OUTPUT 2
INPUT 1 2
196 J2 SETPOINT INPUT 196
3 GND EXTERNAL BASELOAD
OUTPUT 1 1 REFRIGERANT MONITOR INPUT
197 MONITOR INPUT & 197
4-20ma/2-10VDC 2 INPUT 1 REFRIGERANT
198 (OPTIONAL) 198
J11 1 OUTPUT 1
199 199
J1
200 200
J11
201 201
J1
202 1A16 202
COMM 4 MODULE
OR
203 203
LC1-C COMM - 4
TWISTED
TO NEXT UNIT
204 PAIR LEADS 204
COMM + 3
(OPTIONAL) J2 8 1A10
205 QUAD RELAY OUTPUT 205
BAS COMM - 2
TWISTED TO TRACER SUMMIT OR LONTALK
COMMUNICATIONS COMMUNICATION INTERFACE
206 PAIR LEADS 206
COMM + 1
12
H
CUSTOMER PROVIDED POWER 5K4
207 207
1 11
5K5
208 208
7
10
J11
N
209 5 (OPTIONAL) 209
J1 9 OPERATING STATUS
5K6 PROGRAMMABLE
210 210
8 RELAYS
5K7
211 211
7
1A18 J2
212 212
BCI-C 6
5K8
213 BACNET COMM - 4 213
TWISTED 5
COMMUNICATIONS TO NEXT UNIT
PAIR LEADS 5K9
214 (OPTIONAL) COMM + 3 214
IMC J2 8 4
215 COMM - 2 215
TWISTED TO BUILDING AUTOMATION SYSTEM OR 3
PAIR LEADS OTHER TRANE REMOTE DEVICE 5K10
216 COMM + 1 216
2
5K11
217 217
1
218 J11 218
J11

219 J1 219
J1

220 220

221 221

222 222

WB2
223 223

224 224

225 225

DRAWN BY: L.CRESON


SCHEMATIC
C TRANE DATE: 08-MAY-2012
R RTHD
MASTER FILE: WYE DELTA STARTER
REVISION DATE:
REPLACES:
THIS DRAWING IS PROPRIETARY
SIMILAR TO: AND SHALL NOT BE COPIED
OR ITS CONTENTS DISCLOSED
TO OUTSIDE PARTIES WITHOUT REV
THE WRITTEN CONSENT OF TRANE
USED BY: SHEET
4
CAD: CREO SCHEMATICS 2309-7554 E

11
Unit Electrical Data
12
! WARNING ! AVERTISSEMENT ! ADVERTENCIA 7555
HAZARDOUS VOLTAGE! TENSION DANGEREUSE! iVOLTAJE PELIGROSO!
DISCONNECT ALL ELECTRIC POWER INCLUDING COUPER TOUTES LES TENSIONS ET OUVRIR DESCONECTE TODA LA ENERGÍA ELÉCTRICA,
REMOTE DISCONNECTS AND FOLLOW LOCK OUT LES SECTIONNEURS À DISTANCE, PUIS SUIVRE INCLUSO LAS DESCONEXIONES REMOTAS Y SIGA
AND TAG PROCEDURES BEFORE SERVICING. LES PROCÉDURES DE VERROUILLAGE ET DES LOS PROCEDIMIENTOS DE CIERRE Y ETIQUETADO
INSURE THAT ALL MOTOR CAPACITORS HAVE ÉTIQUETTES AVANT TOUTE INTERVENTION. ANTES DE PROCEDER AL SERVICIO. ASEGÚRESE
DISCHARGED STORED VOLTAGE. UNITS WITH VÉRIFIER QUE TOUS LES CONDENSATEURS DE QUE TODOS LOS CAPACITORES DEL MOTOR
VARIABLE SPEED DRIVE, REFER TO DRIVE DES MOTEURS SONT DÉCHARGÉS. DANS LE CAS HAYAN DESCARGADO EL VOLTAJE ALMACENADO.
INSTRUCTIONS FOR CAPACITOR DISCHARGE. D'UNITÉS COMPORTANT DES ENTRAÎNEMENTS PARA LAS UNIDADES CON TRANSMISIÓN
FAILURE TO DO THE ABOVE COULD RESULT À VITESSE VARIABLE, SE REPORTER AUX DE VELOCIDAD VARIABLE, CONSULTE LAS
IN DEATH OR SERIOUS INJURY. INSTRUCTIONS DE L'ENTRAÎNEMENT POUR INSTRUCCIONES PARA LA DESCARGA
DÉCHARGER LES CONDENSATEURS. DEL CONDENSADOR.
UN MANQUEMENT À LA PROCÉDURE NO REALIZAR LO ANTEDICHO PUEDE PROVOCAR
Unit Electrical Data

CI-DESSUS PEUT ENTRAÎNER DES LA MUERTE O LESIONES GRAVES.


BLESSURES GRAVES, VOIRE LA MORT.

NOTICE AVIS AVISO


USE COPPER CONDUCTORS ONLY! N'UTILISER QUE DES CONDUCTEURS ¡UTILICE ÚNICAMENTE
UNIT TERMINALS ARE NOT EN CUIVRE! CONDUCTORES DE COBRE!
DESIGNED TO ACCEPT OTHER LES BORNES DE L'UNITÉ NE SONT LAS TERMINALES DE LA UNIDAD NO
TYPES OF CONDUCTORS. PAS CONÇUES POUR RECEVOIR ESTÁN DISEÑADAS PARA ACEPTAR
FAILURE TO DO THE ABOVE COULD D'AUTRES TYPES DE CONDUCTEURS. OTROS TIPOS DE CONDUCTORES.
RESULT IN EQUIPMENT DAMAGE. UN MANQUEMENT À LA PROCÉDURE NO REALIZAR LO ANTEDICHO PUEDE
CI-DESSUS PEUT ENTRAÎNER PROVOCAR DAÑOS EN EL EQUIPO.
DES DOMMAGES À L'ÉQUIPEMENT.

DEVICE DESCRIPTION ZONE CPT FUSE REPLACEMENT TABLE


1K20
1A1 ADAPTIVIEW DISPLAY MONITOR 2-52 FUSE-VOLTAGE 200V 230V 380-415V 460-575V
1A10 (OPTIONAL) OPERATING STATUS PROGRAMMABLE RELAYS 4-217 1F1 10 8 5 4
IDENTIFICATION COLOR CODE
1A11 OIL LOSS LEVEL 4-172 1F2 10 8 5 4
CLASSIFICATION BK BLACK
1A12 AUTO STOP/EMERGENCY STOP 4-162 1F3 3 3 3 3
LOCATION CODE BN BROWN
1A13 (OPTIONAL) CONDENSER CONTROL OUTPUT & COMPRESSOR % RLA OUTPUT 4-185 1F4 10 10 10 10
BU BLUE
1A14 (OPTIONAL) EXTERNAL CURRENT LIMIT AND EXTERNAL CHILLED WATER SETPOINT 4-197 1F5 6 6 6 6
1A15 (OPTIONAL) ICE/EXTERNAL BASE LOAD 4-184 LOCATION GY GRAY
1F6 6 6 6 6
1A16 (OPTIONAL) BAS COMMUNICATIONS 4-206 RD RED
1A17 (OPTIONAL) REFRIGERANT MONITOR INPUT & EXTERNAL BASELOAD SETPOINT INPUT 4-199 1 CONTROL PANEL WH WHITE
1A2 POWER SUPPLY MODULE 2-70 2 NOT USED GN GREEN
1A3 STARTER MODULE 3-103 3 COMPRESSOR OG ORANGE
1A4 HIGH PRESSURE CUTOUT & SOLID STATE STARTER FAULT 3-110 YE YELLOW TRANE WIRING
4 UNIT MTD
1A5 SLIDE VALVE UNLOAD/LOAD 3-118 CUSTOMER WIRING
5 CUSTOMER PROVIDED
1A6 OIL RETURN GAS PUMP DRAIN/FILL SOLENOID VALVE 3-126 OPTIONS
1A7 CONDENSER/CHILLED WATER FLOW SWITCH INTERLOCKS 3-144
1A8 ICE BUILDING AND MASTER OIL LINE SOL VALVE 3-136
1A9 CONDENSER/CHILLED WATER WATER PUMP STARTER 3-0
1F1 PRIMARY FUSES-CONTROL POWER TRANSFORMER, UNDER/OVER VOLTAGE MODULE 2-20
1F2 PRIMARY FUSES-CONTROL POWER TRANSFORMER, UNDER/OVER VOLTAGE MODULE 2-20
1F3 PRIMARY FUSES-CONTROL POWER TRANSFORMER, UNDER/OVER VOLTAGE MODULE 2-20
1F4 SECONDARY FUSE-CONTROL POWER TRANSFORMER, 115V 2-49
1F5 SECONDARY FUSE-CONTROL POWER TRANSFORMER, 27V 2-49
1F6 SECONDARY FUSE-CONTROL POWER TRANSFORMER, 27V 2-49 RESISTOR CONFIGURATION
1K1 START CONTACTOR 3-93 TABLE 1
1K2 RUN CONTACTOR 3-97 3WW 6WW 3EW TRANSITION RESISTOR CONFIGURATION
1K3 SHORTING CONTACTOR 3-100 WIRE WOUND WIRE WOUND EDGE WOUND VOLTS RLA CONFIGURATION
1K4 TRANSITION CONTACTOR 3-103 200 477-606 6WW
1Q1 CIRCUIT BREAKER 2-5 607-779 6WW
1R1 TRANSITION RESISTOR 2-32
399-476 6WW
1R2 TRANSITION RESISTOR 2-29 1R3 1R3 1R3
230 477-606 6WW
1R3 TRANSITION RESISTOR 2-26
1S1 DISCONNECT SWITCH 2-4 607-779 3EW
1T1 CONTROL POWER TRANSFORMER 2-44 0-277 6WW
1T2-1 CURRENT TRANSFORMERS 2-10 278-364 6WW
1R2 1R2 1R2
1T2-2 CURRENT TRANSFORMERS 2-12 346-480 365-398 6WW
1T2-3 CURRENT TRANSFORMERS 2-14 399-476 3EW
1T3-1 UNDER OVER VOLTAGE TRANSFORMERS 2-30 477-606 3EW
1T3-2 UNDER OVER VOLTAGE TRANSFORMERS 2-30 0-277 6WW
1R1 1R1 1R1
1T3-3 UNDER OVER VOLTAGE TRANSFORMERS 2-30 550-600 278-364 3EW
1X1 POWER TERMINAL BLOCK 2-0 399-476 3EW
1X3-1 UNDER OVER VOLTAGE TERMINAL BLOCK 2-26

RTHD-SVE01A-EN
1X5-1 CONTROL TERMINAL BLOCK 115V 3-81
1X5-1 CONTROL TERMINAL BLOCK 115V 3-81
1X6-1 FIELD FLOW SWITCH TERMINAL BLOCK 3-141
1XJ1 CONTROL HARNESS JACK 1 3-99
1XJ2 CONTROL HARNESS JACK 2 3-105

7555-2
1XP1 CONTROL HARNESS PLUG 1 3-99
1XP2 CONTROL HARNESS PLUG 2 3-105
NOTES:
3M1 COMPRESSOR MOTOR 2-26
3Y1 LOAD 3-116
1 CLASS 1 FIELD WIRED MODULE
3Y2 UNLOAD 3-118
4B2 OIL LOSS LEVEL OPTICAL SENSOR 4-170
4B20 EVAPORATOR ENTRANCE WATER 2-47 2 CLASS 1 FIELD WIRING INSULATION RATING IS REQUIRED TO BE EQUAL TO
4B21 EVAPORATOR LEAVING WATER 2-52 OR GREATER THAN THE EQUIPMENT SUPPLY VOLTAGE RATING.
4B22 CONDENSER ENTRANCE WATER 2-57 CLASS 2 FIELD WIRE INSULATION TO BE RATED AT 300V MINIMUM.

RTHD-SVE01A-EN
4B23 CONDENSER LEAVING WATER 2-61
4B24 OIL PRESSURE TRANSDUCER 2-66 3 OPTIONAL MODULES. REFER TO FIELD WIRING DIAGRAM FOR SUGGESTED WIRING.
4B25 EVAPORATOR REFRIGERANT PRESSURE 2-41
4B26 CONDENSER REFRIGERANT PRESSURE 2-45 4 TRANSITION RESISTORS SHOWN MAY BE COMPRISED OF ONE OR TWO
4B27 COMPRESSOR DISCHARGE TEMPERATURE 2-49 RESISTORS, DEPENDING ON RLA RATING OF COMPRESSOR. REFER
4B29 HIGH PRESSURE CUTOUT SWITCH 3-86 TO TABLE 1 FOR RESISTOR CONFIGURATION.
4B3 EVAPORATOR REFRIGERANT LIQUID LEVEL 2-70
4E1 OIL SUMP HEATERS 3-81
5 FIELD ASSIGNED PROGRAMMABLE RELAYS.
4E2 OIL SUMP HEATERS 3-82
4Y1 FILL 3-124
6 AUTO/STOP, EMERGENCY STOP THE CONTACTS ARE JUMPED AT THE FACTORY BY
4Y2 DRAIN 3-126
4Y20 DUAL PORT ELECTRONIC EXPANSION VALVE ACTUATOR 1 2-43 JUMPERS W1 & W2 TO ENABLE UNIT OPERATION. IF REMOTE CONTROL IS DESIRED
4Y21 DUAL PORT ELECTRONIC EXPANSION VALVE ACTUATOR 2 2-39 REMOVE THE JUMPERS AND CONNECT TO THE DESIRED CONTROL CIRCUIT.
4Y3 MASTER OIL LINE SOLENOID 3-84
5B28 OUTDOOR AIR TEMPERATURE 2-60 7 RELAY AT 120VAC: 7.2 AMPS RESISTIVE, 2.88 AMPS PILOT DUTY, 1/3 HP, 7.2 FLA
5K1 CHILLED WATER PUMP STARTER 3-141 AT 240VAC: 5 AMPS GENERAL PURPOSE.
5K1 CHILLED WATER PUMP STARTER 3-0
5K10 UNIT STATUS RELAYS 4-216 8 IF SHIELD IS PRESENT, DO NOT WIRE SHIELD TO GROUND IN CONTROL PANEL. IF USED,
5K11 UNIT STATUS RELAYS 4-217 SHIELD IS TO BE GROUNDED EXTERNALLY TO CONTROL PANEL.
5K12 ICE BUILDING CONTROL 4-183 REFERENCE FIELD WIRING DIAGRAM FOR RECOMMENDED WIRE TYPE.
5K13 EXTERNAL BASE LOAD ENABLE 4-181
5K2 CONDENSER WATER PUMP STARTER 3-0 9 RELAY ENERGIZED WHILE MAKING ICE.
5K2 CONDENSER WATER PUMP STARTER 3-143
5K21 EXTERNAL AUTO STOP 4-161
10 CONTACT CLOSURE ENABLES ICE MAKING.
5K22 EXTERNAL EMERGENCY STOP 4-159
5K4 UNIT STATUS RELAYS 4-207
11 CLOSED CONTACT COMMANDS BASE LOADING OPERATION.
5K5 UNIT STATUS RELAYS 4-208
5K6 UNIT STATUS RELAYS 4-210
5K7 UNIT STATUS RELAYS 4-211 12 ACTUAL BASE LOADING SETPOINT USED IS SETABLE AT FRONT PANEL. REFER TO IOM
5K8 UNIT STATUS RELAYS 4-213 FOR DETAILS.
5K9 UNIT STATUS RELAYS 4-214
13 WIRES 1C, 1D, 2C, 2D, 3C, 3D, 7D, 8D, 9D,10D, 11D, 12D ARE ONLY PRESENT WHERE
5S1 CHILLED WATER 3-141
5S2 CONDENSER WATER 3-143 PARALLEL WIRE SETS ARE USED.

DRAWN BY: L.CRESON


SCHEMATIC
C TRANE DATE: 07-MAY-2012
R RTHD
MASTER FILE: WYE DELTA STARTER
REVISION DATE:
REPLACES:
THIS DRAWING IS PROPRIETARY
SIMILAR TO: AND SHALL NOT BE COPIED
OR ITS CONTENTS DISCLOSED
TO OUTSIDE PARTIES WITHOUT REV
THE WRITTEN CONSENT OF TRANE
USED BY: SHEET
1
CAD: CREO SCHEMATICS 2309-7555 E

13
Unit Electrical Data
14
1360
1 1

2 ! WARNING ! AVERTISSEMENT ! ADVERTENCIA 2


L1 L2 L3 HAZARDOUS VOLTAGE! TENSION DANGEREUSE! iVOLTAJE PELIGROSO!
3 DISCONNECT ALL ELECTRIC POWER INCLUDING COUPER TOUTES LES TENSIONS ET OUVRIR DESCONECTE TODA LA ENERGÍA ELÉCTRICA, 3
REMOTE DISCONNECTS AND FOLLOW LOCK OUT LES SECTIONNEURS À DISTANCE, PUIS SUIVRE INCLUSO LAS DESCONEXIONES REMOTAS Y SIGA
4 AND TAG PROCEDURES BEFORE SERVICING. LES PROCÉDURES DE VERROUILLAGE ET DES LOS PROCEDIMIENTOS DE CIERRE Y ETIQUETADO 4
INSURE THAT ALL MOTOR CAPACITORS HAVE ÉTIQUETTES AVANT TOUTE INTERVENTION. ANTES DE PROCEDER AL SERVICIO. ASEGÚRESE
DISCHARGED STORED VOLTAGE. UNITS WITH VÉRIFIER QUE TOUS LES CONDENSATEURS DE QUE TODOS LOS CAPACITORES DEL MOTOR
5 1Q1 VARIABLE SPEED DRIVE, REFER TO DRIVE DES MOTEURS SONT DÉCHARGÉS. DANS LE CAS HAYAN DESCARGADO EL VOLTAJE ALMACENADO. 5
INSTRUCTIONS FOR CAPACITOR DISCHARGE. D'UNITÉS COMPORTANT DES ENTRAÎNEMENTS PARA LAS UNIDADES CON TRANSMISIÓN
6 FAILURE TO DO THE ABOVE COULD RESULT À VITESSE VARIABLE, SE REPORTER AUX DE VELOCIDAD VARIABLE, CONSULTE LAS 6
1 2 3 IN DEATH OR SERIOUS INJURY. INSTRUCTIONS DE L'ENTRAÎNEMENT POUR INSTRUCCIONES PARA LA DESCARGA
F F F DÉCHARGER LES CONDENSATEURS. DEL CONDENSADOR.
7 7
Unit Electrical Data

G G G UN MANQUEMENT À LA PROCÉDURE NO REALIZAR LO ANTEDICHO PUEDE PROVOCAR


CI-DESSUS PEUT ENTRAÎNER DES LA MUERTE O LESIONES GRAVES.
8 BLESSURES GRAVES, VOIRE LA MORT. 8

9 52A 52A 9
3-88

1T2-1
10 53A 53A NOTICE AVIS AVISO 10
3-89
USE COPPER CONDUCTORS ONLY! N'UTILISER QUE DES CONDUCTEURS ¡UTILICE ÚNICAMENTE
11 54A 54A UNIT TERMINALS ARE NOT EN CUIVRE! CONDUCTORES DE COBRE! 11
3-90 DESIGNED TO ACCEPT OTHER LES BORNES DE L'UNITÉ NE SONT LAS TERMINALES DE LA UNIDAD NO
TYPES OF CONDUCTORS. PAS CONÇUES POUR RECEVOIR ESTÁN DISEÑADAS PARA ACEPTAR

1T2-2
12 55A 55A 12
3-91 FAILURE TO DO THE ABOVE COULD D'AUTRES TYPES DE CONDUCTEURS. OTROS TIPOS DE CONDUCTORES.
RESULT IN EQUIPMENT DAMAGE. UN MANQUEMENT À LA PROCÉDURE NO REALIZAR LO ANTEDICHO PUEDE
13 CI-DESSUS PEUT ENTRAÎNER PROVOCAR DAÑOS EN EL EQUIPO. 13
56A 56A
3-92 DES DOMMAGES À L'ÉQUIPEMENT.
14 14

1T2-3
57A 57A
3-93
15 15

16 16

17 17

18 18

19 19
3K 2K 1K
20 20
1F3 1F2 1F1
21 21
22A 21A ,F 20A ,F
22 22

23 23

1U1-A 22B ,C 22A


24 24
1X3-3
21B ,C 21F
25 25
1F,K 7C 7C 1X3-2
T1 20B ,C 20F
26 26
1G 1X3-1
22C
(BK)

(BK)
22B
20B
21B

20C
21C

27 T6 3M1 27

MOV1
9C
(BK/WH)
(BK/WH)

(BK/WH)

T2 M
28 28
2F,K 9C 2G 1T3-3 1T3-2 1T3-1
29 T4 29
11C
GN

GN
GN

115VAC 115VAC 115VAC


30 T3 30

MOV2
MOV3
3G
31 T5 31
63A
62A
61A
60A
59A
58A

3F,K 11C
32 32

33 33
3-95
3-94

3-99
3-98
3-97
3-96

34 34

35 35

36 36

37 37
WB3
M
38 DUAL PORT 380V 60HZ 38
ELECTRONIC 230V 50HZ
EXPANSION VALVE
39 ACTUATOR 2 4Y21 H1 H2 39

40 40
P
EVAPORATOR 21A 20A
41 575V 60HZ 41
REFRIGERANT
PRESSURE 4B25 230V 60HZ 200V 60HZ
42 H1 H2 H3 H1 460V 60HZ H2 H3 42
M
DUAL PORT 1T1
43 ELECTRONIC 43
EXPANSION VALVE

RTHD-SVE01A-EN
4Y20 115V 27V
ACTUATOR 1
38 DUAL PORT 380V 60HZ 38
ELECTRONIC 230V 50HZ
EXPANSION VALVE
39 ACTUATOR 2 4Y21 H1 H2 39

1360-2
40 40
P
EVAPORATOR 21A 20A
41 575V 60HZ 41
REFRIGERANT
PRESSURE 4B25 230V 60HZ 200V 60HZ
42 H1 H2 H3 H1 460V 60HZ H2 H3 42
M
DUAL PORT 1T1
43 ELECTRONIC 43
EXPANSION VALVE 115V 27V
ACTUATOR 1 4Y20

RTHD-SVE01A-EN
44 380/400/415V 50HZ X1 X2 X3 X4 44
P
CONDENSER 380V 400V 415V
45 REFRIGERANT H1 H2 H3 H4 45

14A
16A
17A

27AG
PRESSURE 4B26
46 46

47 47
EVAPORATOR
ENTERING

14A
16A
17A

48 WATER 4B20 48

J1 COMPRESSOR
49 49
DISCHARGE
1F4
1F5
1F6

TEMPERATURE 4B27
J11
50 50

51 51
23D
24D

J1
26AC

EVAPORATOR RD
52 LEAVING +24 1 52
WATER 4B21
ETHERNET BK
23D
24D

27AG

53 GND 2 53
WB1
J2
GN
1XP3-3
1XP3-6
1XP3-1
1XP3-2

54 COMM + 3 54

WH
55 COMM - 4 55
1XJ3-3
1XJ3-6
1XJ3-1
1XJ3-2

ADAPTIVIEW DISPLAY MONITOR


23C
24C

56 56
1A1
CONDENSATION
ENTERING
57 WATER 4B22 57

58 58
26AB
27AD

1X5-8
59 1X5-4 59

60 60
26U

5B28
27R,Y

SPLICE SPLICE
CONDENSATION
61 LEAVING 61
OUTDOOR AIR TEMPERATURE 4 4 4
WATER 4B23 FACTORY INSTALLED
1XJ3-5

62 62
LEAD LENGTH EXTENDED
BY CUSTOMER
63 63
GN BU GY RD WH GN BK RD WH GN BK RD
1XP3-5
27Z

64 64

65 P 65
OIL PRESSURE
TRANSDUCER 4 3 2 1 4 3 2 1 4 3 2 1
66 4B24 66
J3 J4 J5
67 67
26Y

1A2
68 68
POWER SUPPLY 25A
3
27R,Y

69 69
24C
J2 2
EVAPORATOR
70 REFRIGERANT 70
LIQUID LEVEL J11 23C
3-79
3-78

1
4B3
71 J1 71

72 72

WB2
73 73
WB2
3-102
74 74

75 75

DRAWN BY: L.CRESON


SCHEMATIC
C TRANE DATE: 07-MAY-2012
R RTHD
MASTER FILE: SOLID STATE STARTER
REVISION DATE:
REPLACES:
THIS DRAWING IS PROPRIETARY
SIMILAR TO: AND SHALL NOT BE COPIED
OR ITS CONTENTS DISCLOSED
TO OUTSIDE PARTIES WITHOUT REV
THE WRITTEN CONSENT OF TRANE
USED BY: SHEET
2
CAD: CREO SCHEMATICS 2309-1360 C

15
Unit Electrical Data
16
1361
76 76

77 77

2-70
78 78

2-70
79 79

27R,Y

26Y
80 4E1 1X5-9 80
28D 1X5-1 28A 27C 27F ,M
81 81
4E2
28B 27D
Unit Electrical Data

82 82

83 83

84 84

85 4B29 85
26S 26R (BK) 40A (YE)
86 1X5-5 86
1A3
STARTER MODULE
87 P 31B (RD) 87

52A 30B 30D


88 2-9 1 + 2 88
J12 1XJ3-10 1XP3-10
TRANSITION
53A COMPLETE 27F
89 2-10 2 - 1 89

54A 31A 31A 31B (RD)


90 2-11 3 + 3 90
J7 J10 1X5-3
55A 1K11
91 2-12 4 - STOP 2 91
46A ,B 27AF 27AF 1X5-10 27W,X
3-93, 95
28D

56A A1 A2 1XP3-11 1XJ3-11


92 2-13 5 + 1 47B 92
1K11 1U1-B

27V
57A 45A 46A,C 26S 26X 47A
93 2-14 6 - 2 L G 93
START 1 3 1XJ3-4 1XP3-4
J8 1XP3-7 1XJ3-7
58A 46B 27AB
1XJ3-8

94 2-33 1 + 1 N 94
1K11 1XJ3-12 1XP3-12
59A 46C
95 2-33 2 - 3 START 95
4 6 50A 50B
1XP3-8

J6
60A
96 2-33 3 + RUN 2 96
J5 30D
61A
28F

97 2-33 4 - 1 NO3 97

62A 26W
98 2-33 5 + 3 RC3 98
J4 1XJ4-1
63A 26T ,W 27Y 1XJ3-14 1XP3-14 27AK 1XP4-1
99 2-33 6 - SHORTING 2 RC1 99

64A (RD) 67A 67A 1XP4-2 1XJ4-2 67B 27AA


100 4-170 1 +24 1 NO1 100

51B
101 2 GND 3 NC1 1Q1 SHUNT TRIP 101
J3 J2

2-74
26T,Y
102 3 COM + TRANSITION 2 RC2 102

29F
103 4 COM - 1 NO2 103

WB2
J1 28F
104 NC2 104

105 105
1A4
DUAL HIGH VOLTAGE BINARY INPUT 26Y
106 106

40A (YE)
107 2 107
J3 HIGH PRESSURE CUTOUT
27X
108 HIGH PRESSURE CUTOUT 1 108
& SSS FAULT 51A 51A 51B
109 2 109
1XJ3-13 1XP3-13
J2 SSS FAULT
27W
110 1 110

J11 NOTICE
111 111
USE COPPER CONDUCTORS ONLY!
J1 UNIT TERMINALS ARE NOT DESIGNED TO
112 112
ACCEPT OTHER TYPES OF CONDUCTORS.
FAILURE TO DO THE ABOVE COULD
113 RESULT IN EQUIPMENT DAMAGE. 113
1A5
DUAL TRIAC
114 114

26K 1X5-6 26M,V


AVIS
115 2 LOAD N'UTILISER QUE DES CONDUCTEURS EN CUIVRE! 115
J3 3Y1 LES BORNES DE L'UNITÉ NE SONT
41A 41A 27P,Q 27P 27T ,U PAS CONÇUES POUR RECEVOIR
116 1 116
D'AUTRES TYPES DE CONDUCTEURS.
SLIDE VALVE UNLOAD/LOAD 1X5-11
26M UN MANQUEMENT À LA PROCÉDURE
117 2 UNLOAD CI-DESSUS PEUT ENTRAÎNER 117
3Y2 DES DOMMAGES À L'ÉQUIPEMENT.
J2
42A 42A 27Q
118 1 118

RTHD-SVE01A-EN
J11 AVISO
113 RESULT IN EQUIPMENT DAMAGE. 113
1A5
DUAL TRIAC
114 114

26K 1X5-6 26M,V


AVIS
115 2 LOAD N'UTILISER QUE DES CONDUCTEURS EN CUIVRE! 115

1361-2
J3 3Y1 LES BORNES DE L'UNITÉ NE SONT
41A 41A 27P,Q 27P 27T ,U PAS CONÇUES POUR RECEVOIR
116 1 116
D'AUTRES TYPES DE CONDUCTEURS.
SLIDE VALVE UNLOAD/LOAD 1X5-11
26M UN MANQUEMENT À LA PROCÉDURE
117 2 UNLOAD CI-DESSUS PEUT ENTRAÎNER 117
3Y2 DES DOMMAGES À L'ÉQUIPEMENT.
J2
42A 42A 27Q
118 1 118

J11

RTHD-SVE01A-EN
119
AVISO 119
¡UTILICE ÚNICAMENTE CONDUCTORES DE COBRE!
J1 LAS TERMINALES DE LA UNIDAD NO
120 120
ESTÁN DISEÑADAS PARA ACEPTAR
OTROS TIPOS DE CONDUCTORES.
121 NO REALIZAR LO ANTEDICHO PUEDE 121
1A6
PROVOCAR DAÑOS EN EL EQUIPO.
DUAL TRIAC
122 122

26P
123 2 FILL 123
J3 4Y1
43A 43A 27R ,S 27R ! WARNING
124 OIL RETURN GAS PUMP 1 124
HAZARDOUS VOLTAGE!
DRAIN/FILL SOLENOID VALVE 26Z
125 2 DRAIN DISCONNECT ALL ELECTRIC POWER INCLUDING 125
4Y2 REMOTE DISCONNECTS AND FOLLOW LOCK OUT
J2
44A 44A 27S AND TAG PROCEDURES BEFORE SERVICING.
126 1 126
INSURE THAT ALL MOTOR CAPACITORS HAVE
J11 DISCHARGED STORED VOLTAGE. UNITS WITH
127 VARIABLE SPEED DRIVE, REFER TO DRIVE 127
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
J1 FAILURE TO DO THE ABOVE COULD RESULT
128 128
IN DEATH OR SERIOUS INJURY.
129 129
1A8
DUAL RELAY OUTPUT
! AVERTISSEMENT
130 130
TENSION DANGEREUSE!
1
26V COUPER TOUTES LES TENSIONS ET OUVRIR
131 6 29C 29F 131
LES SECTIONNEURS À DISTANCE, PUIS SUIVRE
1XJ3-9 1XP3-9 LES PROCÉDURES DE VERROUILLAGE ET DES
ÉTIQUETTES AVANT TOUTE INTERVENTION.

29C
132 5 132
4Y3 VÉRIFIER QUE TOUS LES CONDENSATEURS
ICE BUILDING 29D 29D 29B 27M DES MOTEURS SONT DÉCHARGÉS. DANS LE CAS
133 4 D'UNITÉS COMPORTANT DES ENTRAÎNEMENTS 133
STATUS OUTPUT (OPTIONAL) 1X5-2
J2 3 ICE MACHINE À VITESSE VARIABLE, SE REPORTER AUX
134 AND MASTER OIL LINE 3 INSTRUCTIONS DE L'ENTRAÎNEMENT POUR 134
STATUS CUSTOMER DÉCHARGER LES CONDENSATEURS.
SOLENOID VALVE 7 UN MANQUEMENT À LA PROCÉDURE
135 2 PROVIDED POWER 135
5K20 CI-DESSUS PEUT ENTRAÎNER DES
(ICE MAKING BLESSURES GRAVES, VOIRE LA MORT.
136 1 136
HARDWARE
J11 9 ONLY PRESENT ! ADVERTENCIA
137 137
IF ORDERED) iVOLTAJE PELIGROSO!
J1
138 DESCONECTE TODA LA ENERGÍA ELÉCTRICA, 138
INCLUSO LAS DESCONEXIONES REMOTAS Y SIGA
LOS PROCEDIMIENTOS DE CIERRE Y ETIQUETADO
139 ANTES DE PROCEDER AL SERVICIO. ASEGÚRESE 139
1A7
DUAL HIGH VOLTAGE BINARY INPUT DE QUE TODOS LOS CAPACITORES DEL MOTOR

26P,Z
140 HAYAN DESCARGADO EL VOLTAJE ALMACENADO. 140
CHILLED WATER PARA LAS UNIDADES CON TRANSMISIÓN
5K1 AUX
1 5S1 DE VELOCIDAD VARIABLE, CONSULTE LAS
141 2 141
INSTRUCCIONES PARA LA DESCARGA
J3 1X6-1 1X5-7 DEL CONDENSADOR.
CONDENSER/CHILLED WATER 27T
142 1 NO REALIZAR LO ANTEDICHO PUEDE PROVOCAR 142
FLOW SWITCH CONDENSER WATER
5K2 AUX LA MUERTE O LESIONES GRAVES.
5S2
143 INTERLOCKS 2 143
J2
27U
144 1 144

4-152
J11
145 145

J1

WB2
146 146

147 147
1A9
DUAL RELAY OUTPUT
148 148

1
149 6 H 149
CUSTOMER PROVIDED POWER 7
150 5 150
5K1 N
4 CHILLED WATER
CONDENSER/CHILLED WATER J2 PUMP STARTER
WATER PUMP STARTER 3 DRAWN BY: L.CRESON
SCHEMATIC
C TRANE DATE: 08-MAY-2012
2 R RTHD
5K2 CONDENSER MASTER FILE: SOLID STATE STARTER
1 WATER REVISION DATE:
J11 PUMP STARTER
REPLACES:
THIS DRAWING IS PROPRIETARY
SIMILAR TO: AND SHALL NOT BE COPIED
J1 OR ITS CONTENTS DISCLOSED
TO OUTSIDE PARTIES WITHOUT REV
THE WRITTEN CONSENT OF TRANE
USED BY: SHEET
3
CAD: CREO SCHEMATICS 2309-1361 C

17
Unit Electrical Data
18
1362
151 151

3-145
152
NOTICE 152
USE COPPER CONDUCTORS ONLY!
153 UNIT TERMINALS ARE NOT DESIGNED TO 153

WB2
ACCEPT OTHER TYPES OF CONDUCTORS.
FAILURE TO DO THE ABOVE COULD
154 RESULT IN EQUIPMENT DAMAGE. 154

155 155
AVIS
156 N'UTILISER QUE DES CONDUCTEURS EN CUIVRE! 156
LES BORNES DE L'UNITÉ NE SONT
PAS CONÇUES POUR RECEVOIR
Unit Electrical Data

157 157
DUAL LOW VOLTAGE BINARY INPUT D'AUTRES TYPES DE CONDUCTEURS.
1A12 UN MANQUEMENT À LA PROCÉDURE
158 CI-DESSUS PEUT ENTRAÎNER 158
5K22
DES DOMMAGES À L'ÉQUIPEMENT.
159 4 EMERGENCY STOP 159

W1 AVISO
160 3 5K21 6 160
AUTO STOP/EMERGENCY STOP J2 ¡UTILICE ÚNICAMENTE CONDUCTORES DE COBRE!
161 2 LAS TERMINALES DE LA UNIDAD NO 161
AUTO STOP
ESTÁN DISEÑADAS PARA ACEPTAR
W2 OTROS TIPOS DE CONDUCTORES.
162 1 NO REALIZAR LO ANTEDICHO PUEDE 162
PROVOCAR DAÑOS EN EL EQUIPO.
J11
163 163

J1
164 164

165 ! WARNING 165

HAZARDOUS VOLTAGE!
166 166
DISCONNECT ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS AND FOLLOW LOCK OUT
167 AND TAG PROCEDURES BEFORE SERVICING. 167
DUAL LOW VOLTAGE BINARY INPUT INSURE THAT ALL MOTOR CAPACITORS HAVE
168 1A11 DISCHARGED STORED VOLTAGE. UNITS WITH 168
VARIABLE SPEED DRIVE, REFER TO DRIVE
INSTRUCTIONS FOR CAPACITOR DISCHARGE.
169 FAILURE TO DO THE ABOVE COULD RESULT 169
4 64A (RD)
3-100 IN DEATH OR SERIOUS INJURY.
LIQUID LEVEL
170 SENSOR 170
3
OIL LOSS LEVEL J2 4B2 ! AVERTISSEMENT
171 65A (BK) 171
2
TENSION DANGEREUSE!
172 66A (WH) COUPER TOUTES LES TENSIONS ET OUVRIR 172
1 LES SECTIONNEURS À DISTANCE, PUIS SUIVRE
8
LES PROCÉDURES DE VERROUILLAGE ET DES
173 J11 ÉTIQUETTES AVANT TOUTE INTERVENTION. 173
VÉRIFIER QUE TOUS LES CONDENSATEURS
174 J1 DES MOTEURS SONT DÉCHARGÉS. DANS LE CAS 174
D'UNITÉS COMPORTANT DES ENTRAÎNEMENTS
À VITESSE VARIABLE, SE REPORTER AUX
175 INSTRUCTIONS DE L'ENTRAÎNEMENT POUR 175
DÉCHARGER LES CONDENSATEURS.
176 UN MANQUEMENT À LA PROCÉDURE 176
CI-DESSUS PEUT ENTRAÎNER DES
177 BLESSURES GRAVES, VOIRE LA MORT. 177

178 ! ADVERTENCIA 178


DUAL ANALOG I/O
3
1A13 iVOLTAJE PELIGROSO!
179 179
DESCONECTE TODA LA ENERGÍA ELÉCTRICA,
INCLUSO LAS DESCONEXIONES REMOTAS Y SIGA
180 GND 6 LOS PROCEDIMIENTOS DE CIERRE Y ETIQUETADO 180
1A15
0-10VDC ANTES DE PROCEDER AL SERVICIO. ASEGÚRESE
DUAL LOW VOLTAGE BINARY INPUT
181 INPUT 2 5 COMPRESSOR % RLA 5K13 DE QUE TODOS LOS CAPACITORES DEL MOTOR 181
OUTPUT 4 HAYAN DESCARGADO EL VOLTAJE ALMACENADO.
PARA LAS UNIDADES CON TRANSMISIÓN
182 OUTPUT 2 4 11 EXTERNAL BASE LOAD COMMAND DE VELOCIDAD VARIABLE, CONSULTE LAS 182
J2 3 INSTRUCCIONES PARA LA DESCARGA
(OPTIONAL)
183 CONDENSER CONTROL GND 3 5K12 J2 (OPTIONAL) DEL CONDENSADOR. 183
0-10VDC NO REALIZAR LO ANTEDICHO PUEDE PROVOCAR
OUTPUT & COMPRESSOR 2 ICE/EXTERNAL
CONDENSER CONTROL OUTPUT FIELD 10 ICE BUILDING CONTROL LA MUERTE O LESIONES GRAVES.
% RLA OUTPUT BASE LOAD
184 INPUT 1 2 SELECTABLE AS: CONDENSER PRESSURE, (ICE MAKING HARDWARE 184
DELTA PRESSURE, OR CONTROL OUTPUT SIGNAL ONLY PRESENT IF ORDERED) 1
FOR CONDENSER HEAD PRESSURE CONTROL
185 OUTPUT 1 1 185

186 186

J11 J11
187 187

J1 J1
188 188

189 189

190 DUAL ANALOG I/O 190


1A14
191 191

GND 6 CUSTOMER EXTERNAL CHILLED DUAL ANALOG I/O


192 192
WATER SETPOINT INPUT 1A17
INPUT 2 5 2-10VDC OR 4-20mA
193 193

RTHD-SVE01A-EN
6 GND
J1 J1
188 188

189 189

1362-2
190 DUAL ANALOG I/O 190
1A14
191 191

GND 6 CUSTOMER EXTERNAL CHILLED DUAL ANALOG I/O


192 192
WATER SETPOINT INPUT 1A17
INPUT 2 5 2-10VDC OR 4-20mA
193 193

RTHD-SVE01A-EN
6 GND
OUTPUT 2 4
194 (OPTIONAL) EXTERNAL BASELOAD SETPOINT INPUT 194
EXTERNAL CURRENT LIMIT J2
5 INPUT 2
& EXTERNAL CHILLED GND 3 CUSTOMER EXTERNAL CURRENT 12 4-20ma/2-10VDC
195 195
WATER SETPOINT LIMIT SETPOINT INPUT
2-10VDC OR 4-20mA 4 OUTPUT 2
INPUT 1 2
196 J2 SETPOINT INPUT 196
3 GND EXTERNAL BASELOAD
OUTPUT 1 1 REFRIGERANT MONITOR INPUT
197 MONITOR INPUT & 197
4-20ma/2-10VDC 2 INPUT 1 REFRIGERANT
198 (OPTIONAL) 198
J11 1 OUTPUT 1
199 199
J1
200 200
J11
201 201
J1
202 1A16 202
COMM 4 MODULE
OR
203 203
LC1-C COMM - 4
TWISTED
TO NEXT UNIT
204 PAIR LEADS 204
COMM + 3
(OPTIONAL) J2 8 1A10
205 QUAD RELAY OUTPUT 205
BAS COMM - 2
TWISTED TO TRACER SUMMIT OR LONTALK
COMMUNICATIONS COMMUNICATION INTERFACE
206 PAIR LEADS 206
COMM + 1
12
H
CUSTOMER PROVIDED POWER 5K4
207 207
1 11
5K5
208 208
7
10
J11
N
209 5 (OPTIONAL) 209
J1 9 OPERATING STATUS
5K6 PROGRAMMABLE
210 210
8 RELAYS
5K7
211 211
7
1A18 J2
212 212
BCI-C 6
5K8
213 BACNET COMM - 4 213
TWISTED 5
COMMUNICATIONS TO NEXT UNIT
PAIR LEADS 5K9
214 (OPTIONAL) COMM + 3 214
IMC J2 8 4
215 COMM - 2 215
TWISTED TO BUILDING AUTOMATION SYSTEM OR 3
PAIR LEADS OTHER TRANE REMOTE DEVICE 5K10
216 COMM + 1 216
2
5K11
217 217
1
218 J11 218
J11

219 J1 219
J1

220 220

221 221

222 222

WB2
223 223

224 224

225 225

DRAWN BY: L.CRESON


SCHEMATIC
C TRANE DATE: 08-MAY-2012
R RTHD
MASTER FILE: SOLID STATE STARTER
REVISION DATE:
REPLACES:
THIS DRAWING IS PROPRIETARY
SIMILAR TO: AND SHALL NOT BE COPIED
OR ITS CONTENTS DISCLOSED
TO OUTSIDE PARTIES WITHOUT REV
THE WRITTEN CONSENT OF TRANE
USED BY: SHEET
4
CAD: CREO SCHEMATICS

19
Unit Electrical Data

2309-1362 D
20
! WARNING ! AVERTISSEMENT ! ADVERTENCIA 1363
HAZARDOUS VOLTAGE! TENSION DANGEREUSE! iVOLTAJE PELIGROSO!
DISCONNECT ALL ELECTRIC POWER INCLUDING COUPER TOUTES LES TENSIONS ET OUVRIR DESCONECTE TODA LA ENERGÍA ELÉCTRICA,
REMOTE DISCONNECTS AND FOLLOW LOCK OUT LES SECTIONNEURS À DISTANCE, PUIS SUIVRE INCLUSO LAS DESCONEXIONES REMOTAS Y SIGA
AND TAG PROCEDURES BEFORE SERVICING. LES PROCÉDURES DE VERROUILLAGE ET DES LOS PROCEDIMIENTOS DE CIERRE Y ETIQUETADO
INSURE THAT ALL MOTOR CAPACITORS HAVE ÉTIQUETTES AVANT TOUTE INTERVENTION. ANTES DE PROCEDER AL SERVICIO. ASEGÚRESE
DISCHARGED STORED VOLTAGE. UNITS WITH VÉRIFIER QUE TOUS LES CONDENSATEURS DE QUE TODOS LOS CAPACITORES DEL MOTOR
VARIABLE SPEED DRIVE, REFER TO DRIVE DES MOTEURS SONT DÉCHARGÉS. DANS LE CAS HAYAN DESCARGADO EL VOLTAJE ALMACENADO.
INSTRUCTIONS FOR CAPACITOR DISCHARGE. D'UNITÉS COMPORTANT DES ENTRAÎNEMENTS PARA LAS UNIDADES CON TRANSMISIÓN
FAILURE TO DO THE ABOVE COULD RESULT À VITESSE VARIABLE, SE REPORTER AUX DE VELOCIDAD VARIABLE, CONSULTE LAS
IN DEATH OR SERIOUS INJURY. INSTRUCTIONS DE L'ENTRAÎNEMENT POUR INSTRUCCIONES PARA LA DESCARGA
DÉCHARGER LES CONDENSATEURS. DEL CONDENSADOR.
Unit Electrical Data

UN MANQUEMENT À LA PROCÉDURE NO REALIZAR LO ANTEDICHO PUEDE PROVOCAR


CI-DESSUS PEUT ENTRAÎNER DES LA MUERTE O LESIONES GRAVES.
BLESSURES GRAVES, VOIRE LA MORT.

NOTICE AVIS AVISO


USE COPPER CONDUCTORS ONLY! N'UTILISER QUE DES CONDUCTEURS ¡UTILICE ÚNICAMENTE
UNIT TERMINALS ARE NOT EN CUIVRE! CONDUCTORES DE COBRE!
DESIGNED TO ACCEPT OTHER LES BORNES DE L'UNITÉ NE SONT LAS TERMINALES DE LA UNIDAD NO
TYPES OF CONDUCTORS. PAS CONÇUES POUR RECEVOIR ESTÁN DISEÑADAS PARA ACEPTAR
FAILURE TO DO THE ABOVE COULD D'AUTRES TYPES DE CONDUCTEURS. OTROS TIPOS DE CONDUCTORES.
RESULT IN EQUIPMENT DAMAGE. UN MANQUEMENT À LA PROCÉDURE NO REALIZAR LO ANTEDICHO PUEDE
CI-DESSUS PEUT ENTRAÎNER PROVOCAR DAÑOS EN EL EQUIPO.
DES DOMMAGES À L'ÉQUIPEMENT.

DEVICE DESCRIPTION ZONE


1A1 ADAPTIVIEW DISPLAY MONITOR 2-52
TRANE WIRING
1A10 (OPTIONAL) OPERATING STATUS PROGRAMMABLE RELAYS 4-217
1K20 CUSTOMER WIRING
1A11 OIL LOSS LEVEL 4-172
1A12 AUTO STOP/EMERGENCY STOP 4-162 OPTIONS
1A13 (OPTIONAL) CONDENSER CONTROL OUTPUT & COMPRESSOR % RLA OUTPUT 4-185 IDENTIFICATION
1A14 (OPTIONAL) EXTERNAL CURRENT LIMIT AND EXTERNAL CHILLED WATER SETPOINT 4-197 CLASSIFICATION
COLOR CODE
1A15 (OPTIONAL) ICE/EXTERNAL BASE LOAD 4-184 LOCATION CODE
BK BLACK
1A16 (OPTIONAL) BAS COMMUNICATIONS 4-206 BN BROWN
1A17 (OPTIONAL) REFRIGERANT MONITOR INPUT & EXTERNAL BASELOAD SETPOINT INPUT 4-199 LOCATION
BU BLUE
1A2 POWER SUPPLY MODULE 2-70
GY GRAY
1A3 STARTER MODULE 3-103 1 CONTROL PANEL
RD RED
1A4 HIGH PRESSURE CUTOUT & SOLID STATE STARTER FAULT 3-110 2 NOT USED
1A5 SLIDE VALVE UNLOAD/LOAD 3-118 WH WHITE
3 COMPRESSOR
1A6 OIL RETURN GAS PUMP DRAIN/FILL SOLENOID VALVE 3-126 GN GREEN
4 UNIT MTD
1A7 CONDENSER/CHILLED WATER FLOW SWITCH INTERLOCKS 3-144 OG ORANGE
5 CUSTOMER PROVIDED
1A8 ICE BUILDING AND MASTER OIL LINE SOL VALVE 3-136 YE YELLOW
1A9 CONDENSER/CHILLED WATER WATER PUMP STARTER 3-0
1F1 PRIMARY FUSES-CONTROL POWER TRANSFORMER, UNDER/OVER VOLTAGE MODULE 2-20
1F2 PRIMARY FUSES-CONTROL POWER TRANSFORMER, UNDER/OVER VOLTAGE MODULE 2-20
1F3 PRIMARY FUSES-CONTROL POWER TRANSFORMER, UNDER/OVER VOLTAGE MODULE 2-20
1F4 SECONDARY FUSE-CONTROL POWER TRANSFORMER, 115V 2-49
1F5 SECONDARY FUSE-CONTROL POWER TRANSFORMER, 27V 2-49
1F6 SECONDARY FUSE-CONTROL POWER TRANSFORMER, 27V 2-49
1K11 START CONTACTOR 3-89
1Q1 CIRCUIT BREAKER 2-5 CPT FUSE REPLACEMENT TABLE
1T1 CONTROL POWER TRANSFORMER 2-44 FUSE-VOLTAGE 200V 230V 380-415V 460-575V
1T2-1 CURRENT TRANSFORMERS 2-10 1F1 10 8 5 4
1T2-2 CURRENT TRANSFORMERS 2-12 1F2 10 8 5 4
1T2-3 CURRENT TRANSFORMERS 2-14 1F3 3 3 3 3
1T3-1 UNDER OVER VOLTAGE TRANSFORMERS 2-30 1F4 10 10 10 10
1T3-2 UNDER OVER VOLTAGE TRANSFORMERS 2-30 1F5 6 6 6 6
1T3-3 UNDER OVER VOLTAGE TRANSFORMERS 2-30 1F6 6 6 6 6
1U1 SOLID STATE STARTER 2-0
1X3-1 UNDER OVER VOLTAGE TERMINAL BLOCK 2-26
1X5-1 CONTROL TERMINAL BLOCK 115V 3-81

RTHD-SVE01A-EN
1X6 1 FIELD FLOW SWITCH TERMINAL BLOCK 3 141
1X3-1 UNDER OVER VOLTAGE TERMINAL BLOCK 2-26
1X5-1 CONTROL TERMINAL BLOCK 115V 3-81
1X6-1 FIELD FLOW SWITCH TERMINAL BLOCK 3-141
1XJ3 CONTROL HARNESS JACK 3 3-99

1363-2
1XJ4 SHUNT TRIP HARNESS JACK 4 3-97
1XP3 CONTROL HARNESS PLUG 3 3-99
1XP4 SHUNT TRIP HARNESS PLUG 4 3-97
3M1 COMPRESSOR MOTOR 2-26 NOTES:
3Y1 LOAD 3-116
3Y2 UNLOAD 3-118 1 CLASS 1 FIELD WIRED MODULE
4B2 OIL LOSS LEVEL OPTICAL SENSOR 4-170
4B20 EVAPORATOR ENTRANCE WATER 2-47 2 CLASS 1 FIELD WIRING INSULATION RATING IS REQUIRED TO BE EQUAL TO

RTHD-SVE01A-EN
4B21 EVAPORATOR LEAVING WATER 2-52 OR GREATER THAN THE EQUIPMENT SUPPLY VOLTAGE RATING.
4B22 CONDENSER ENTRANCE WATER 2-57 CLASS 2 FIELD WIRE INSULATION TO BE RATED AT 300V MINIMUM.
4B23 CONDENSER LEAVING WATER 2-61
4B24 OIL PRESSURE TRANSDUCER 2-66 3 OPTIONAL MODULES. REFER TO FIELD WIRING DIAGRAM FOR SUGGESTED WIRING.
4B25 EVAPORATOR REFRIGERANT PRESSURE 2-41
4B26 CONDENSER REFRIGERANT PRESSURE 2-45
4B27 COMPRESSOR DISCHARGE TEMPERATURE 2-49
4B29 HIGH PRESSURE CUTOUT SWITCH 3-86
4B3 EVAPORATOR REFRIGERANT LIQUID LEVEL 2-70
4E1 OIL SUMP HEATERS 3-81
4E2 OIL SUMP HEATERS 3-82 5 FIELD ASSIGNED PROGRAMMABLE RELAYS.
4Y1 FILL 3-124
4Y2 DRAIN 3-126 6 AUTO/STOP, EMERGENCY STOP THE CONTACTS ARE JUMPED AT THE FACTORY BY
4Y20 DUAL PORT ELECTRONIC EXPANSION VALVE ACTUATOR 1 2-43 JUMPERS W1 & W2 TO ENABLE UNIT OPERATION. IF REMOTE CONTROL IS DESIRED
4Y21 DUAL PORT ELECTRONIC EXPANSION VALVE ACTUATOR 2 2-39 REMOVE THE JUMPERS AND CONNECT TO THE DESIRED CONTROL CIRCUIT.
4Y3 MASTER OIL LINE SOLENOID 3-133
5B28 OUTDOOR AIR TEMPERATURE 2-60 7 RELAY AT 120VAC: 7.2 AMPS RESISTIVE, 2.88 AMPS PILOT DUTY, 1/3 HP, 7.2 FLA
5K1 CHILLED WATER PUMP STARTER 3-141 AT 240VAC: 5 AMPS GENERAL PURPOSE.
5K1 CHILLED WATER PUMP STARTER 3-0
5K10 UNIT STATUS RELAYS 4-216 8 IF SHIELD IS PRESENT, DO NOT WIRE SHIELD TO GROUND IN CONTROL PANEL. IF USED,
5K11 UNIT STATUS RELAYS 4-217 SHIELD IS TO BE GROUNDED EXTERNALLY TO CONTROL PANEL.
5K12 ICE BUILDING CONTROL 4-183
REFERENCE FIELD WIRING DIAGRAM FOR RECOMMENDED WIRE TYPE.
5K13 EXTERNAL BASE LOAD ENABLE 4-181
5K2 CONDENSER WATER PUMP STARTER 3-143
9 RELAY ENERGIZED WHILE MAKING ICE.
5K2 CONDENSER WATER PUMP STARTER 3-0
5K21 EXTERNAL AUTO STOP 4-161
5K22 EXTERNAL EMERGENCY STOP 4-159 10 CONTACT CLOSURE ENABLES ICE MAKING.
5K4 UNIT STATUS RELAYS 4-207
5K5 UNIT STATUS RELAYS 4-208 11 CLOSED CONTACT COMMANDS BASE LOADING OPERATION.
5K6 UNIT STATUS RELAYS 4-210
5K7 UNIT STATUS RELAYS 4-211 12 ACTUAL BASE LOADING SETPOINT USED IS SETABLE AT FRONT PANEL. REFER TO IOM
5K8 UNIT STATUS RELAYS 4-213 FOR DETAILS.
5K9 UNIT STATUS RELAYS 4-214
5S1 CHILLED WATER 3-141
5S2 CONDENSER WATER 3-143

DRAWN BY: L.CRESON


SCHEMATIC
C TRANE DATE: 07-MAY-2012
R RTHD
MASTER FILE: SOLID STATE STARTER
REVISION DATE:
REPLACES:
THIS DRAWING IS PROPRIETARY
SIMILAR TO: AND SHALL NOT BE COPIED
OR ITS CONTENTS DISCLOSED
TO OUTSIDE PARTIES WITHOUT REV
THE WRITTEN CONSENT OF TRANE
USED BY: SHEET
1
CAD: CREO SCHEMATICS 2309-1363 D

21
Unit Electrical Data
Unit Electrical Data

7564

22 RTHD-SVE01A-EN
Unit Electrical Data

7564-2

1 1 E
COMPONENT LOCATION
PBL 3-13-03 RTHD

RTHD-SVE01A-EN 23
Unit Electrical Data

7565

24 RTHD-SVE01A-EN
Unit Electrical Data

7565-2

1 1 E
COMPONENT LOCATION
PBL 3-13-03 RTHD

RTHD-SVE01A-EN 25
Unit Electrical Data

4870

26 RTHD-SVE01A-EN
Unit Electrical Data

4870-2

23094870 1 1 F
FIELD WIRING
PBL 3-12-03
RTHD

RTHD-SVE01A-EN 27
Unit Electrical Data

4869

28 RTHD-SVE01A-EN
Unit Electrical Data

4869-2

23094869 1 1 E
FIELD LAYOUT DIAGRAM
PBL 1-21-03 RTHD

RTHD-SVE01A-EN 29
Unit Electrical Data

30 RTHD-SVE01A-EN
Unit Electrical Data

RTHD-SVE01A-EN 31
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

© 2013Trane All rights reserved