Professional Documents
Culture Documents
Specialized Knowledge of High Voltage Switchgear
Specialized Knowledge of High Voltage Switchgear
1. Introduction
In recent years, container vessels and LNG carriers have significantly increased in size.
Mainstream container vessels are now 8,000 TEU. Supersized vessels of 14,000 TEU and over
200,000 m3 LNG carriers have been built. With the size increase of these vessels, inboard power
supply systems have also been required to increase their capacities. However, since capacities of
generators are limited, applicable voltages have been increased from AC440V to AC3.3kV or
AC6.6kV to satisfy the increased capacity. The number of vessels with high voltage power
management systems is expected to increase in the future; therefore it is necessary for engineers
in the marine industry to have an advanced understanding of high voltage power distribution
systems. In this article, system voltages, power distribution systems and earthing systems which
are applied to vessels with high voltage systems are explained by using single line system
diagrams and other materials. In addition to the above, this article includes characteristics of high
voltage systems, such as the boundary between low voltage systems and high voltage systems,
their advantages and disadvantages, requirements of classification and standard.
2.1 Introduction
When an inboard capacity of a power distribution is increased, voltage is required to be increased
accordingly. In general, for a commercial vessel, a high voltage power distribution system is
applied when the total capacity of a generator is over approximately 10 MVA. Electric propulsion
plants with single propulsion motors having a capacity over approximately 0.3 MW, and bow
thrusters having a capacity over approximately 1 MW as a partial high voltage system, in these
cases the application of a high voltage power distribution system is considered.
When the voltage of the power distribution system for a vessel is determined, first, the points below
concerning low voltage power distribution systems have to be considered carefully. In addition to
that, a careful decision should be made to choose either a low voltage power distribution system or
a high voltage power distribution system in consideration of safety, reliability and a comprehensive
point of view to the cost effectiveness.
1
2.2 Points to be considered
Table 1: The maximum capacity of the protective device for the low voltage power
distribution
Rated Interrupting Power distribution system to be examined
current current
ACB 6,300 A 135 kA In case that the total capacity of the power supply is
1,200 A 120 ~180 kA over 10 MVA, or the capacity of the single generator is
MCCB over 4.5 MVA.
1,600 A 85 kA
2
2.2.4 Selection of earthing system
For a low voltage power distribution system, normally a 3 phase - 3 wire neutral insulation system
(unearthing system) is applied. And, for a high voltage power distribution system, sometimes a 3
phase - 3 wire neutral insulation system (unearthing system) is applied, but in this case, the
application of a neutral insulation system has also to be determined carefully considering cost
effectiveness and safety. According to the rules of the class society, the application of an earthing
distribution system for vessels carrying dangerous goods is prohibited in principle, however if
measures are taken such as preventing the earthing current flow to a hazardous area, it is
approved as an exception. Therefore it requires careful attention when deciding on an earthing
system.
When the type of the earthing system is selected, several matters should be evaluated
comprehensively such as its advantages and disadvantages, the type of vessel, requirement of the
class society, rated voltages, etc.
1) Considering the capacity of the generator and the starting motor, reduced-voltage starting is
necessary. The transformer for reduced-voltage starting can be used as a step-up transformer,
which leads to cost reduction. However, this method demands careful attention to the inrush
current by switching the taps which may affect negatively on this system.
2) Due to long power distribution length, the cost of wiring has a major influence on the decision of
the system application.
3
3. Power Distribution System
3.1 General
The power distribution plans of a vessel have to be decided considering various factors such as an
examination of the inboard load, determination of the generator capacity, selection of the applied
voltage, power supply system, earthing system and protection system. These have to be examined
based on the applied regulation, the classification rules, the type of vessel, and purpose. The high
voltage systems applied to vessels are organized as per Table 2. In addition, the planning
procedures of power distribution are shown in Figure1.
A wide variety of systems can be determined according to the type of vessel, usage and purpose.
This article documents the basic planning of the main power distribution system, and the technical
problems of these items which have to be considered.
Selection of the
Examination of the distribution system Calculation of the breaking capacity earthing protection
device
Examination of the cables Calculation of the earth fault current Examination of the
number of protective
devices
Outfitting plan
5
Table 3: Application of the voltage
Application range Over 1 kV, and 15 kV or less Over 500 V, and 15 kV or less
Application range Over 1 kV, and 15 kV or less Over 1 kV, and 15 kV or less
Recommended
Not specified Not specified
voltage
Other special
instruction
6
3.3.1 Tree-like distribution system
As shown in Figure 2, the distribution lines of this system branches from the bus bar like a tree. The
characteristic of this system is as shown below.
1) A small quantity of protective devices and a simple protection system can be provided.
2) There is a possibility of blackout at bus bar fault.
3) The facility is low in cost.
G G
G G Generator
CB CB CB CB CB CB CB High voltage
circuit breaker
Step-down
Tr
High voltage Tr Tr High voltage transformer
consumer consumer
ACB Low voltage air
ACB ACB circuit breaker
MCCB MCCB
According to SOLAS, “the main bus bar is to be divided at least into two bus bars, and these are to
be connected by a circuit breaker or other approved method. As far as it is practicable, the
generator and vital equipment with redundancy are to be arranged equally in each bus bar”.
The power distribution system is as shown in Figure 2.
1) Vital equipment of which several units are provided should be equally arranged in each
individual part.
2) Several step-down transformers should be provided in order to supply power to the low voltage
consumers and each of them should be given enough capacity to supply the power to the low
voltage load individually.
3) A bus tie air circuit breaker should be provided for the low voltage bus bar.
This plan will contribute to the significant improvement of reliability. Normally in this power
distribution system, the bus tie circuit breaker at the high voltage side is always closed and the
bus tie circuit breaker at the low voltage side is always open.
7
3.3.2 Ring net power distribution system
As shown in Figure 3, this is the method which arranges the bus bar in a circle and which supplies
power to the load in each independent segment. It has been applied to cruise ships and naval
vessels which especially require reliability of power supply.
The characteristic of this system is as shown below;
1) Higher reliability in comparison to that of the tree-like distribution system
2) A large quantity of protective devices with a complicated protection and control system
3) High cost facility.
By applying this system, the balanced consumer in each independent segment and the power flow
control will improve reliability. This is achieved by reducing voltage fluctuation and power loss or by
controlling power oscillation at the time of a bus bar incident.
G G G G
High voltage
bus bar
CB CB CB CB
CB CB CB CB
CB CB CB CB CB CB
CB CB CB CB CB CB
CB CB
CB CB
CB CB CB CB
G G G G
8
3.3.3 Partial high voltage system
As shown in Figure 4, high voltage equipment is provided for the specific consumer on the line in
which a low voltage system is adapted to the main power distribution system.
High voltage is partially applied only to these consumer circuits.
ACB ACB
High voltage supplying line
G M
Step-up transformer
Low voltage bus bar
450 V
This system is applied when the specific consumer with a large capacity is a long distance from the
main switchgear, and when a great advantage is expected in the cost and space reduction of
wiring. This system is commonly used for the bow thruster of a commercial vessel.
If the capacity of the step-up transformer and the motor is large compared with that of the
generator, due consideration should be given to the following points.
1) The exciting inrush current of the step-up transformer shall not cause an activation of the
trip of the ACB and the voltage drop of the bus bar is within allowance level.
Where necessary, the inrush current shall be suppressed by the reactor.
2) The reduced-voltage start of the motor shall be performed, using the tap changing of the
step-up transformer which leads to cost reduction. Countermeasures should be taken for the
inrush current caused by the tap changing.
9
3.4.1 Neutral insulation system
In this system, the neutral point is not earthed intentionally except when the system is being
earthed with high impedance for an indication meter or for earth fault detection.
The characteristic of this system is shown below.
1) Only the charging current by the capacitance to earth (or to vessel body) flows as the earth
fault current due to the single line-to-earth fault, therefore the continuity of the power supply
will be maintained.
2) It is difficult to identify the earthing line due to an extremely small earth fault current.
3) The single line-to-earth fault increases the voltage to earth of the healthy phases, causing an
intermittent arc and a harmonic oscillating current due to the static capacity of the cable or
equipment depending on the system condition. To avoid this situation, the dielectric strength
of the equipment should be increased to a satisfactory extent.
NEUTRAL EARTHING
Name of the system NEUTRAL INSULATION HIGH RESISTANCE EARTHING
NEUTRAL DIRECT EARTHING NEUTRAL RESISTANCE EARTHING
CB CB CB CB CB CB CB
CB
CB CB
GVT
Basic circuit
51G/67G 51G/67G ET
GS G G
GS
S S
GS 51G 51G
GS
FEEDER 59G 51G 51G R R
FEEDER
& MOTOR R
& MOTOR
・The earthing over-voltage at the secondary side of the GVT is detected by the earth ・The earthing transformer is provided for each bus bar, detecting the The neutral point of the generator is ・The neutral point of the generator is earthed
detection. current limited by the resistance at the secondary side of the earthing directly earthed to detect the earth fault through the resistance, detecting the earth
・A common alarm of each main bus bar is issued at the time of the earth fault. transformer. (The relay is provided for each circuit.) current. current flown to the resistance.
Circuit explanation ・The ground relay does not operate correctly due to a small earth fault current at the ・The selective trip coordination is possible, however, the earth current ・This system is divided into the neutral high
single line-to-earth fault, making the selective trip coordination difficult. should be considered to avoid a activation of the relay caused by the resistance earthing system and the neutral low
electrostatic current to ground in each circuit. * The directional earth fault resistance earthing system depending on the
relay can prevent the false operation of the relay. resistance of the earthing resistor.
・The smallest earth current flows. The resistance provided for the secondary side of the earthing transformer The largest earth current flows The resistance of the resistor provided for the
Earth current ・Only the electrostatic current and the active current which is limited by interval allows the earth current to be set arbitrarily. because the neutral point of the neutral point allows the active earth fault
resistance inside of the relay at the secondary side of the GVT flows. generator is directly earthed. current to be set arbitrarily. Mostly, the current
is suppressed to 30 A at maximum.
・The continuity of the power supplying is maintained because only the electrostatic ・It does not require the neutral point in the generator. ・The abnormal voltage is avoided at ・The selective coordination is ensured at the
current and the active current which is limited by interval resistance inside of the relay at ・Only 1 set of the earthing transformer needs to be provided for each bus the time of the single line-to-earth fault time of the earth fault, however, the large earth
the secondary side of the GVT flows at the time of the single line-to-earth fault. bar even in case of several generators. and the dielectric strength of the current flows.
・A small earth fault current makes the detection of the earthed circuit difficult. ・The small and low voltage type of the resistor can be used. equipment can be reduced. ・The abnormal voltage can be suppressed at
・At the time of the single line-to-earth fault, the voltage to earth of other healthy phases ・The abnormal voltage can be controlled to some extent at the time of the ・A large earth fault current makes the the time of the single line-to-earth fault with the
increases. The dielectric strength of the equipment should be increased to a satisfactory single line-to-earth fault with the continuity of the power supplying identification of the earthed circuit continuity of the power supplying maintained.
extent. maintained. easy.
Characteristics ・The continuity of the power supplying
・A leased earthing transformer is required.
・The selective coordination is ensured at the time of the earth fault. is not maintained due to a large earth
fault current.
・ In the parallel running of the
generators, the excessive circulating
current may flow through the earthed
circuit, which must be considered in
the design of the generator.
Insulation coordination Theoretically, 7.5 times of the rated voltage is applied to this rate, however, if the The over-voltage is suppressed more than the neutral insulation while the The insulation coordination is The insulation coordination is suppressed to
by over-voltage capacitance and the internal impedance of the earthing over-voltage relay are higher cost is required than other earthing systems. suppressed to √3 times of the rated √3 times of the rated voltage.
considered, it will be about 5 times of the rated voltage at maximum. voltage.
・This system is normally applied to container vessels, for which a large amount of the This system is often applied to LNG vessels, for which the earthed circuit This system is rarely applied to the This system is rarely applied to commercial
Remarks power supply is not required. must be tripped shortly for protection of the vital auxiliaries as well as the commercial vessels and sometimes vessels and sometimes applied to offshore.
・In some cases, this system is applied to LNG vessels since it has a weak earth fault continuity of the power supplying to the healthy circuit should be applied to the offshore.
current. maintained.
11
3.5 Earth Fault Detecting System
An earth fault should be detected immediately with an alarm, opening the earthed circuit where
necessary.
Generally, the neutral insulation system places an emphasis on the continuity of the power supply
and only gives an alarm. On the other hand, the neutral earthing system opens the earthed circuit
immediately for protection of the equipment as well as prevention of a secondary disaster such as
fire in consideration of a strong earth fault current. The detection method of the earth fault is
closely related to the earthing system.
Bus bar
12
3.5.2 Earth detection by neutral earthing system
Figure 6 shows how the earthed circuit is identified and opens the circuit.
The high resistance earthing system detects the earth fault current by a zero-phase-sequence
current transformer since small current flows at the earth fault. The phase difference of the current
flowing between the earthed circuit and healthy circuit is at a phase difference angle of about 180
degrees. Therefore, the phase angle is estimated based on the zero phase voltage Vo by a
directional earth-fault relay, enabling the earthed circuit to be detected.
Bus bar
Circuit
breaker
CB1
CB2
Earth directional
relay
Zero-phase-
sequence
current DG1 DG2 DR
ZCT2
transformer V
ZCT1
OVG
Consumer 1 Consumer 2
The neutral direct earthing system and the neutral resistance earthing system, both of which are
included in the neutral earthing system, detect the earth fault current by an earth fault over-current
relay since a large earth fault current flows at the earth fault. Figure 7 shows the detection of the
earth fault current. This circuit should be provided with the current transformer in each phase. In
addition, a relay should be selected so that required detectivity can be obtained according to the
ratio of the current transformer decided by the full-load current.
Bus bar
Consumer
Figure 7: Earth fault over-current detection circuit
13
3.6 Consideration for Earthing System
3.6.1 Reasons for necessity of examining earthing system
For a high voltage power distribution system, examination of the earthing system is important for
the following reasons.
1) Suppression of the earthing over-voltage
2) Proper operation of the protective relay
3) Reduction of obstruction to the communication line
The suppression of the earthing over-voltage is the most important technological examination item
from the above.
Normally, the neutral insulation system is applied to the low voltage power distribution system. The
specification and the regulation require the insulation resistance test for low voltage equipment in
use under the neutral insulated condition. This enables a low voltage power distribution system to
have the abnormal voltage endurance at a single line-to-earth fault.
14
Table 5: Dielectric strength test
NK (2007) LR (July 2005)
Voltage applied in
the one-minute Maximum voltage Voltage applied in the one-minute
Dielectric strength Maximum voltage (r.m.s.) insulation resistance (r.m.s.) insulation resistance test with
test kV test with commercial commercial frequency (r.m.s.)
frequency (r.m.s.) kV kV
kV
15
3.8 Examples of Achievement of High Voltage System
An example of the achievement of high voltage system is shown in Table 6.
Different systems are applied according to vessel type, such as a high voltage power distribution
system applied to LNG vessels and container vessels, and an extensive high voltage power
distribution system to cruise ships, deep-sea drilling vessels and the FPSO. The partial high
voltage system is applied to commercial vessels to supply the power to the high-capacity bow
thruster. Table 6 takes up only one example of the partial high voltage system for commercial
vessels from many other achievements. The capacities of the motors for which the partial high
voltage system is adopted cannot be specified. The adoption of the partial high voltage system will
be determined by comparing the cost reduction in wiring and the advantage from the smaller
wiring space with the increased cost for high voltage equipment. Generally, about 1000 kW is an
indication of the application of the partial high voltage system.
3.3 kV of the system voltage was applied to a high voltage power distribution system while 6.6 kV
was applied extensively to high voltage power distribution systems in the past.
Currently, the capacity of the inboard generator has become much greater than before, therefore
6.6 kV is applied to commercial vessels such as container vessels and LNG vessels instead of 3.3
kV which does not meet the breaking capacity. 11 kV is mainly applied extensively to high voltage
power distribution systems.
The tree-like distribution system is the mainstream of the power distribution system while cruise
ships adopt the ring net power distribution system.
The resistance earthing system by the earthing transformer is the mainstream of the earthing
system. This system allows only the current for operation of the earthing protection relay to flow
and the abnormal voltage to be suppressed with the advantage of cost reduction.
The earth fault protection for container vessels only activates the alarm giving priority on the
continuity of power supply, for LNG vessels which carry dangerous goods on the other hand; the
circuit is opened by the earthing protection relay.
16
Table 6: Example of achievement of high voltage power distribution system
Deep-sea drilling
Cruise ship Container vessel LNG vessel FPSO Commercial vessel
vessel
Power distribution Ring net power Tree-like distribution Tree-like distribution Ring net power Tree-like distribution Tree-like distribution
system distribution system system system distribution system system system
System voltage AC11kV - 3φ - 60Hz AC6.6kV - 3φ - 60Hz AC6.6kV - 3φ - 60Hz AC6.6kV - 3φ - 60Hz AC11kV - 3φ - 60Hz AC3.3kV - 3φ - 60Hz
Electric propulsion
Bow thruster
system Cargo pump Thruster
Main load Refrigerated container Under investigation Bow thruster
Thruster Air Relique faction plant Drilling device
facility
conditioning equipment
Short circuit breaking
30 kA 15 kA 17 kA 36.5 kA 19 kA
capacity
3200 kW x 4
GTG: 2500 kW x 1
Total capacity of the 1500 kW x 1 5000 kW x 3 pcs
DG: 8150 kW x 2 3360 kW x 5 pcs 6300 kW x 5
generator Shore power 2500 kW x 1 pc
DG: 9150 kW x 2
supplying
Generator neutral point High resistance High resistance High resistance High resistance
Neutral insulation
Earthing system High resistance earthing system by the earthing system by the earthing system by the earthing system by the
system
earthing system earthing transformer earthing transformer earthing transformer earthing transformer
The earth fault The earth fault The earth fault
Earth fault protective
protective relay is protective relay is protective relay is
Earth fault protection Alarm relay is provided Alarm
provided. provided. provided.
(Trip)
(Trip) (Trip) (Trip)
This system is applied to
the motors with over
Remarks 1000 kW depending on
the length of the cables.
17
4. Additional Information
(Surge voltage, short circuit, arc discharge and earth fault)
Current chopping surge at small current breaking and multiple recurrent arc surge at larger current
breaking is generated when opening and closing VCB.
Over-voltage is caused in line with a drastic current change, called surge voltage. The surge
voltage is transmitted from the VCB to the loading apparatus through the cable and the surge
voltage is applied on the loading apparatus.
Voltage
Vr Surge voltage
18
4.2 Short Circuit
On the electric power system, a large current, well over the rated value, flows in the cable way due
to short circuit caused by the deterioration or breakage of the cover of the distribution line, or
damage of the electric power equipment such as the transformer.
19
4.4 Earth Fault
The earth fault is the situation shown as {b}
in the figure. Electrically, it refers to the
insulation between the cable way and the
earth becoming extremely low.
When the earth fault occurs, in some cases,
a dangerous impulse voltage occurs outside
of the cable way or the equipment, or dangerous
current flows which is called “earth fault”.
When the earth fault occurs, a large earth fault current may flow on the transmission and
distribution cable way depending on the capacitance of the cable way to earth and the types of the
earthing system. That may cause an intermittent arcing earth fault or occurrence of abnormal
voltage which may lead to a huge accident.
5. Trailer
Recently, high voltage power distribution systems have been applied to commercial vessels such
as container vessels and LNG vessels, and the number of vessels with high voltage power
distribution systems will increase in the future.
In this article, the elementary items of a high voltage power distribution system are organized. We
hope this will be of help to you in understanding a high voltage power distribution system.
20