INSULATION TEST RESULT BEFORE ENERGISING THE MAIN FEEDER LINE

MARCH 13, 2014 FIRE INCEDENT


ADMIN PANEL @ BASEMENT
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE OF CONDUCTOR REMARKS
RATING L1G L2G L3G L1L2 L1L3 L2L3 L1 L2 L3
MCB ADMIN PANEL ENERGISED
150A 20MΩ 20MΩ 20MΩ 20MΩ 30MΩ 20MΩ 1\0 1\0 1\0 on March 18, 2014 at around
AWG AWG AWG 1300 hrs. CB-Normal Temp.
CB1 ADMIN PANEL ENERGISED
100Amps. 0.50MΩ 0.00MΩ 0.50MΩ 22.0mm 22.0mm on March 18, 2014 at around
2F 1300 hrs. CB-Normal Temp.
CB2 ADMIN PANEL ENERGISED
50Amps. 0.50MΩ 0.00MΩ 0.50MΩ 14MM 14MM on March 18, 2014 at around
3F 1300 hrs. CB-Normal Temp.
CB3 ADMIN PANEL ENERGISED
50Amps. 0.50MΩ 0.00MΩ 0.50MΩ 14MM 14MM on March 18, 2014 at around
4F 1300 hrs. CB-Normal Temp.
CB4 ADMIN PANEL ENERGISED
50Amps. 0.50MΩ 0.00MΩ 0.50MΩ 14MM 14MM on March 18, 2014 at around
5F 1300 hrs. CB-Normal Temp.
CB5 ADMIN PANEL ENERGISED
50A 0.50MΩ 0.00MΩ 0.50MΩ 14MM 14MM on March 18, 2014 at around
6F 1300 hrs. CB-Normal Temp.
CB-6
50A
SPARE

RP3010@BASEMENT
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE OF CONDUCTOR REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
CB AHU Basement was Energised
200 Amps. 400MΩ 500MΩ 350MΩ 1000MΩ 900MΩ 1000MΩ 2\0 2\0 2\0 on March 18, 2014 at around
RP3010 MCM MCM MCM 1045 hrs. CB-Normal Temp.

Fire Pump@BASEMENT
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE OF CONDUCTOR REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
BR4 Fire Pump energized
200 Amps. 500MΩ 500MΩ 500MΩ 1000MΩ 1000MΩ 1000MΩ 2\0 2\0 2\0 on March 18, 2014 at around
F. PUMP MCM MCM MCM 1045 hrs. CB-Normal Temp.

Sewage Pump@BASEMENT
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE OF CONDUCTOR REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
BR5 Sewage Pump energized
50A 160MΩ 180A 180A 140MΩ 150MΩ 140MΩ 8 8 8 on March 18, 2014 at around
Sew.Pump AWG AWG AWG 1145 hrs. CB-Normal Temp.

Sump Pump@BASEMENT
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE OF CONDUCTOR REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
BR6 Sump Pump energized
50A 160MΩ 180A 180A 140MΩ 150MΩ 140MΩ 8 8 8 on March 18, 2014 at around
SumpPump AWG AWG AWG 1300 hrs. CB-Normal Temp.
EPB at BASEMENT
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE OF CONDUCTOR REMARKS
RATING L1G L2G LL L L
CB The EDPB Panel was energized
50A 160MΩ 180A 140MΩ 10 10 on March21, 2014 1200 hrs.
MAIN AWG AWG CB-Normal Temp.
CB1 The EDPB Panel was energized
20A 300MΩ 300MΩ 300MΩ 12 12 on March21, 2014 1200 hrs.
LTS AWG AWG CB-Normal Temp.
CB2 The EDPB Panel was energized
20A 300MΩ 300MΩ 300MΩ 12 12 on March21, 2014 1200 hrs.
LTS AWG AWG CB-Normal Temp.
CB3 The EDPB Panel was energized
20A 300MΩ 300MΩ 300MΩ 12 12 on March21, 2014 1200 hrs.
LTS AWG AWG CB-Normal Temp.
CB4 The EDPB Panel was energized
20A 300MΩ 300MΩ 300MΩ 12 12 on March21, 2014 1200 hrs.
LTS AWG AWG CB-Normal Temp.
CB5 The EDPB Panel was energized
20A 300MΩ 300MΩ 300MΩ 12 12 on March21, 2014 1200 hrs.
LTS AWG AWG CB-Normal Temp.
CB6 The EDPB Panel was energized
20A 300MΩ 300MΩ 300MΩ 12 12 on March21, 2014 1200 hrs.
LTS AWG AWG CB-Normal Temp.
CB7 The EDPB Panel was energized
20A 300MΩ 300MΩ 300MΩ 12 12 on March21, 2014 1200 hrs.
LTS AWG AWG CB-Normal Temp.
CB8
20A
SPARE
TEST CERTIFIED BY:
BERNARDO M. TERROBIAS
PEE 2778 UNTIL 8/202015
PTR 2562669 ISSUED ON
1/13/2014 AT MANILA

Prepared by: Verrified/Checked and Approved by:

______________________ Engr. BERNARDO M. TERROBIAS, PME


INSULATION TEST RESULT BEFORE ENERGISING THE MAIN FEEDER LINE
MARCH 13, 2014 FIRE INCEDENT
LP2-B PAGE: 01
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE OF CONDUCTOR REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
MCB This Main Feeder was already
100Amp. 350MΩ 350MΩ 500MΩ 22.0mm 22.0mm energised and in a functional
condition.
CB-1 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-2 This Branch Circuit Homerun was
20Amps. 700MΩ 700MΩ 1000MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
CB-3 This Branch Circuit Homerun was
20Amps. 10MΩ 400MΩ 500MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
CB-4 This Branch Circuit Homerun was
20Amps. 8MΩ 8MΩ 0.00MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
CB-5 This Branch Circuit Homerun was
30Amps. 400MΩ 400MΩ 1000MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
CB-6 This Branch Circuit Homerun was
30Amps. 20MΩ 20MΩ 0.00MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
CB-7 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
Prepared by: Verrified/Checked and Approved by:

______________________ Engr. BERNARDO M. TERROBIAS, PME

INSULATION TEST RESULT BEFORE ENERGISING THE MAIN FEEDER LINE


MARCH 13, 2014 FIRE INCEDENT
LP2-B PAGE: 02
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE OF CONDUCTOR REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
CB-8 This Branch Circuit Homerun was
20Amps. 500MΩ 500MΩ 2000MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
CB-9 This Branch Circuit Homerun was
20Amps. 10MΩ 400MΩ 400MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.

Prepared by: Verrified/Checked and Approved by:

______________________ Engr. BERNARDO M. TERROBIAS, PME


INSULATION TEST RESULT BEFORE ENERGISING THE MAIN FEEDER LINE
MARCH 13, 2014 FIRE INCEDENT
LP2-C PAGE: 01
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE OF CONDUCTOR REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
MCB This Main Feeder was already
100Amp. 500MΩ 500MΩ 600MΩ 22.0mm 22.0mm energised and in a functional
condition.
CB-1 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-2 This Branch Circuit Homerun was
30Amps. 200MΩ 500MΩ 550MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
CB-3 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-4 This Main Service Feeder was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-5 This Branch Circuit Homerun was
20Amps. 1000MΩ 1000MΩ 2000MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
CB-6 This Branch Circuit Homerun was
20Amps. 500MΩ 500MΩ 1000MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
CB-7 This Branch Circuit Homerun was
20Amps. 500MΩ 600MΩ 1000MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
Prepared by: Verrified/Checked and Approved by:

______________________ Engr. BERNARDO M. TERROBIAS, PME

INSULATION TEST RESULT BEFORE ENERGISING THE MAIN FEEDER LINE


MARCH 13, 2014 FIRE INCEDENT
LP2-C PAGE: 02
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE OF CONDUCTOR REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
CB-8 This Branch Circuit Homerun was
20Amps. 400MΩ 400MΩ 1000MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.

Prepared by: Verrified/Checked and Approved by:

______________________ Engr. BERNARDO M. TERROBIAS, PME


INSULATION TEST RESULT BEFORE ENERGISING THE MAIN FEEDER LINE
MARCH 13, 2014 FIRE INCEDENT
LP2-D PAGE: 01
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE OF CONDUCTOR REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
MCD This Main Feeder was not yet
100Amp. 110MΩ 110MΩ 0.00MΩ 22.0mm 22.0mm ENERGISED since it will not in used.

CB-1 This branch Homerun Circuit was


30Amps. 1000MΩ 800MΩ 1000MΩ 3.5mm 3.5mm not Energised since it is not in used.

CB-2 This branch Homerun Circuit was


30Amps. 700MΩ 700MΩ 1000MΩ 3.5mm 3.5mm not Energised since it is not in used.

CB-3 This Branch Circuit Homerun was


20Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-4 This branch Homerun Circuit was
20Amps. 340MΩ 300MΩ 90MΩ 3.5mm 3.5mm not Energised since it is not in used.

CB-5 This branch Homerun Circuit was


30Amps. 300MΩ 700M 1000MΩ 3.5mm 3.5mm not Energised since it is not in used.

CB-6 This branch Homerun Circuit was


30Amps. 500MΩ 20MΩ 2000MΩ 3.5mm 3.5mm not Energised since it is not in used.

CB-7 This branch Homerun Circuit was


20Amps. 1000MΩ 1000MΩ 1000MΩ 3.5mm 3.5mm not Energised since it is not in used.

Prepared by: Verrified/Checked and Approved by:

______________________ Engr. BERNARDO M. TERROBIAS, PME

INSULATION TEST RESULT BEFORE ENERGISING THE MAIN FEEDER LINE


MARCH 13, 2014 FIRE INCEDENT
LP2-E PAGE: 01
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE OF CONDUCTOR REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
MCB This Main Feeder was already
100Amp. 200MΩ 200MΩ 275MΩ 22.0mm 22.0mm energised and in a functional
condition.
CB-1 This Branch Circuit Homerun was
30Amps. 100MΩ 100MΩ 400MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
CB-2 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-3 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-4 This Branch Circuit Homerun was
20Amps. 15MΩ 15MΩ 0.00MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
CB-5 This Branch Circuit Homerun was
20Amps. 1MΩ 2MΩ 0.00MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
CB-6 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-7 This Branch Circuit Homerun was
30Amps. 4MΩ 350MΩ 500MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
Prepared by: Verrified/Checked and Approved by:

______________________ Engr. BERNARDO M. TERROBIAS, PME


INSULATION TEST RESULT BEFORE ENERGISING THE MAIN FEEDER LINE
MARCH 13, 2014 FIRE INCEDENT
LP2-E PAGE: 02
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE 3.5mm REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
CB-8 This Branch Circuit Homerun was
20Amps. 40MΩ 40MΩ 90MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.
CB-9 This Branch Circuit Homerun was
20Amps. 2MΩ 2MΩ 0.50MΩ 3.5mm 3.5mm already energised and functional
in a NORMAL CONDITION.

Prepared by: Verrified/Checked and Approved by:

______________________ Engr. BERNARDO M. TERROBIAS, PME

INSULATION TEST RESULT BEFORE ENERGISING THE MAIN FEEDER LINE


MARCH 13, 2014 FIRE INCEDENT
LP2-F PAGE: 01
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE 3.5mm REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
MCB This Main Service Feeder was not
100Amp. 300MΩ 300MΩ 700MΩ 22.0mm 22.0mm yet energised due to majority of
branch circuit was failed on meger.
CB1 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-2 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-3 This Branch Circuit Homerun was
20Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-4 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-5 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-6 This Branch Circuit Homerun was
20Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-7 This Branch Circuit Homerun was
20Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
Prepared by: Verrified/Checked and Approved by:

______________________ Engr. BERNARDO M. TERROBIAS, PME


INSULATION TEST RESULT BEFORE ENERGISING THE MAIN FEEDER LINE
MARCH 13, 2014 FIRE INCEDENT
LP2-G PAGE: 01
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE 3.5mm REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
MCB This Main Service Feeder was not
100Amp. 500MΩ 500MΩ 1000MΩ 22.0mm 22.0mm yet energised due to majority of
branch circuit was failed on meger.
CB-1 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-2 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-3 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-4 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-5
20Amps. SPHARE-NO LOAD

CB-6 This Branch Homerun Circuit was


20Amps. 500MΩ 500MΩ 500MΩ 3.5mm 3.5mm not yet energised due to not so
much in used this time.
CB-7 This Branch Homerun Circuit was
20Amps. 700MΩ 700MΩ 1000MΩ 3.5mm 3.5mm not yet energised due to not so
much in used this time.
Prepared by: Verrified/Checked and Approved by:

______________________ Engr. BERNARDO M. TERROBIAS, PME

INSULATION TEST RESULT BEFORE ENERGISING THE MAIN FEEDER LINE


MARCH 13, 2014 FIRE INCEDENT
LP2-G PAGE: 02
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE 3.5mm REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
CB-8
20Amps. SPHARE-NO LOAD

CB-9 This Branch Homerun Circuit was


20Amps. 200MΩ 200MΩ 200MΩ 3.5mm 3.5mm not yet energised due to not so
much in used this time.
CB-10 This Branch Circuit Homerun was
20Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-11 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-12 This Branch Circuit Homerun was
30Amps. 0.00MΩ 0.00MΩ 0.00MΩ 3.5mm 3.5mm disconnected and sealed due to
INSULATION TEST RESULT FAILED.
CB-13
20Amps. SPHARE-NO LOAD

CB-14 This Branch Homerun Circuit was


20Amps. 500MΩ 500MΩ 500MΩ 3.5mm 3.5mm not yet energised due to not so
much in used this time.
CB-15 This Branch Homerun Circuit was
20Amps. 500MΩ 500MΩ 500MΩ 3.5mm 3.5mm not yet energised due to not so
much in used this time.
Prepared by: Verrified/Checked and Approved by:

______________________ Engr. BERNARDO M. TERROBIAS, PME


INSULATION TEST RESULT BEFORE ENERGISING THE MAIN FEEDER LINE
MARCH 13, 2014 FIRE INCEDENT
LP2-G PAGE: 03
CIRCUIT INSTRUMENT USED: SANWA MODEL: 1008S, INSULATION TESTER SIZE
BREAKER LINE TO GROUND LINE TO LINE 3.5mm REMARKS
RATING L1 L2 L3 L1-L2 L1-L3 L2-L3 L1 L2 L3
CB-16
20Amps. SPHARE-NO LOAD

Prepared by: Verrified/Checked and Approved by: