A SYSTEM PARAMETERS

Rated Operating voltage 415 v ac '+10-15%


Rated Frequency 50 HZ ' +6 -6 %
Ambient Temp. 50 deg. Cel.
Humidity ( RH) 100%
Altitude a.s.l. < 1000 mtr
Distribution System 3 P + Neutral
Fault Level 50 ka rms for 1 sec.
Swgr . Rated short time withstand current ( 1 sec.) 50 ka
System Earthing Solidly Earth
Panel Mounting Floor Mounting , free standing
Protection Degree ( PCC / MCC / PDB ) - indoor IP 42 as per IS 13947
Arrangement Single front , Fixed Type , suitable for extension on either side
Construction Modular & fully compartmentalized
Enclosure 2 mm CRCA , 75 mm base channel
Painting / Color powder painting / RAL 7035 ( Light Grey) - TEXTURED finish or approved shade
Control Voltage 220 vac
Auxiliary service AC voltage 220vac
Outgoing : cable Outlet Bottom , removable undrilled gland plate ( 3 mm thick) , Aluminium
Bus Bar Type Aluminum E91 Electrolytic Grade ,99.99% purity , conductivity more than 56 % IACS.
Dropper Bus Bars Aluminum E91 Electrolytic Grade ,99.99% purity , conductivity more than 56 % IACS.
Neutral Bus Bar Rating 50 % of main bus bars
Earth Bus should run in bottom throughout the panel , minimum 50 x 10 mm or 75 x 6 mm aluminum
Cable Alley Separate & Vertical
Cluster type LED indication ( on / off / trip) for Incomer ACB ( on / off/ trip / breaker on /
Indications for starter feeders
breaker off)
Overall Height max. up to 2400 mm keeping 75 mm base channel & 125 mm dummy throughout at base.

B Panel & Manufacturing Specification


ACB,s for INCOMING & outgoing feeders shall be 3 pole , with latest generation microprocessor based release ( LSIG Protection ) with current
1
measuring function .
2 All Incomer feeder doors color should be Blue
3 All CT , Bus Bars , Sleeves ,gaskets ,Insulators ,Polycarbonate sheets, Control wires , Hardware etc must be with there test certificates as per make:
4 CT & PT : make Precision / Kappa / AE cast resin with accuracy class 1 for metering & Class 5P10 protection.
5 Insulators : SMC with glass reinforced
6 Bus Bar Support : Powermat or reputed
7 Terminal Blocks : Elmex ,Phoenix , Wago , Connect well
8 Thimble or Lugs : Jainson / Dowell or reputed
9 Control & Power Wire :1100v grade FRLS make : Finolex , KEI , RR , Polycab only
10 Indication Lamp should be LED type & of reputed make .
11 Digital Multi function meter should be Conzerve make & with RS 485 port in ready state.
12 PU / Neoprene type gasket shall be provided inside the doors to keep panel dust & vermin proof.
13 Hardware : All Nut Bolts washers must be cadmium plated , high tensile , higher grades only.
14 CRCA Sheet : TATA , SAIL , Bhusion , JINDAL or reputed .
15 Equipments like PT,CTs etc. shall not be supported on bus bars.
16 All Bus bar live parts must be covered by Polycarbonate sheet of 100 % transparency , fitted throughout on exposed part wherever required.
17 There should be at least 10% margin between derated ratings and maximum demand for Bus Bar .
Execution Drawings : Legends & Notes , general arrangement , top view with foundation plan, SLD , BOM , Control Scheme which are submitted for
18
approval prior to manufacturing
19 Each panel must have Standard Identification Tags ( Title / Project name / Area Application / P.O. Detail / Manf. Date / Address Plate)
20 Drawing pockets & Manual keeping space to be allocate in each panel with identification.
21 if any doubt or any kind of clarification needed by the supplier must ask otherwise it will assume that every point is agreed by supplier
22 During commissioning of panel if any kind of technical problem occurs , supplier engineers must be on site with in two days whenever call by customer.
23 Packing of panels : polythene pack , wooden packing , rubber supports , scratch proof .
24 Space heater at bottom side of cable chember and ACB chember connected with PB mounted on front
25 DANGER 415 VAC STICKER on both TIE and incomer door
26 All BUS bar must be covered with RYB insulated Sleeve