Sujana Power (Tuticorin) Limited Sujana Power (Gangikondan) Limited
Sujana Power (Tuticorin) Limited Sujana Power (Gangikondan) Limited
Project :
Combined Cycle Power Plant, Tuticorin
Title:
VOLTAGE DROP STUDY FOR AUXILIARY POWER SUPPLY SYSTEM
Name Signature Date
-sd-
Prepared G.Subramanian 05.02.2000
-sd-
Reviewed S.C.Saha 07.02.2000
-sd-
Approved M.R.Rao 08.02.2000 Sheet 1 of 21
Contract No.: CGL Doc. No.: Rev. No.:
S9901/S9902 CAL-E-0105 B
CROMPTON GREAVES LIMITED
POWER PROJECTS DIVISION, CHENNAI
CONTENTS
1.0 Introduction 3
2.0 Description 3
3.0 Calculation 4
4.0 Conclusion 23
1.0 Introduction
The auxiliary power supply system consist of 2 nos. unit auxiliary transformers , 8 nos. LT
auxiliary transformers to feed various loads at 6.6 kV & 415 V system. To ensure the
availability of voltage at motor terminals during steady state and running condition, with in
permissible limits, voltage drop (load flow) study has been carried out as summarised below.
2.0 Description
Key Single line diagram of auxiliary power supply distribution showing 11 kV, 6.6 kV and
415 V system is enclosed .
Under steady state operation voltage drop in the system shall be limited to 5%. That is with
availability of 1 p.u voltage at 11 kV system, voltage at motor terminals shall be not less than
0.95 p.u. and with availability of 0.95 p.u voltage at 11 kV system, voltage at motor terminals
shall be not less than 0.9 p.u.
During starting of largest 6.6kV/415 V motor, voltage drop in the system shall be limited to
20%. That is with availability of 1 p.u or 0.95 p.u voltage at 11 kV system, voltage at motor
terminals shall be not less than 0.8 p.u
Voltage drop study has been carried out for the following variations:
During steady state operation.
During starting of largest 6.6 kV motor
During starting of largest 415V motor
System parameters, Transformer rating , impedance values and Cable particulars considered
are based on the following document.
Short circuit study for Power supply system. (Doc.no.SPL-C-CAL-E-0104)
Sizing calculation –11 kV,6.6kV,415V Cables (Doc.no.SPL-C-CAL-E-0006)
During steady state operation voltage availability at 6.6 kV motor terminals , at largest LT
motor , fuel handling motor (which is located farthest from transformer) and sea water intake
system has been calculated.
During starting of largest 6.6 kV/LT motor, voltage availability at 6.6 kV motor terminals/ at
largest LT motor and fuel handling motor (which is located farthest from transformer ) has
Title: CGL Doc. No.: CAL-E-0105 Rev. No.:
VOLTAGE DROP STUDY FOR AUXILIARY Sheet. 3 of 21 B
POWER SUPPLY SYSTEM
File: GSM//conversion/tmp/activity_task_scratch/536171648.doc
CROMPTON GREAVES LIMITED
POWER PROJECTS DIVISION, CHENNAI
been calculated. Further during starting, momentary voltage dip experienced by various bus
also has been calculated.
3.0 Calculation
3.1 Voltage drop calculation during steady state operation
Cable size ( from UAT to 6.6 kV switchgear) 1cx800 1cx800 1cx800 1cx800
No.of runs/ phase(n) 2 2 2 2
No.of UAT in service , N 1 2 1 2
Cable resistance/km , Rc (ohms) 0.0523 0.0523 0.0523 0.0523
Cable reactance/km Xc, (ohms) 0.0893 0.0893 0.0893 0.0893
Cable distance , L (Metre) 150.000 150.000 150.000 150.000
Cable resistance Rc1=Lx Rc/n , (ohm) 0.004 0.004 0.004 0.004
Cable reactance Xc1= Lx Xc/n , (ohm) 0.007 0.007 0.007 0.007
Max.load on UAT considering 0.9 service factor and 8362.5 8362.5 8362.5 8362.5
0.85 power factor = 12500 x 0.9 x 0.85, (kW) - starting
motor rating
Nominal system voltage , kV 6.8 6.8 6.46 6.46
Running PF (CosQ1) 0.85 0.85 0.85 0.85
Running SinQ1 0.5268 0.5268 0.5268 0.5268
Rated current I1 =Max load/ (sqrt(3) x V60 xCosQ1 835.31 417.65 879.27 439.64
xN) , Amps
Starting current (largest starting motor from B3) , I2 994 994 994 994
,Amps
Starting PF (CosQ2) 0.3 0.3 0.3 0.3
Starting SinQ2 0.9539 0.9539 0.9539 0.9539
I cosQ= I1cosQ1+I2cosQ2 1008.213 653.207 1045.583 671.891
IsinQ = I1sinQ1 + I2 sinQ2 1388.24 1168.23 1411.40 1179.81
Voltage drop is 1.732 x( I CosQ x (Rc1+Ru) + 879.27 730.59 809.95 668.20
(ISinQ x (Xc1+Xu)) , V
Voltage at Switchgear V61= V60-Voltage drop, V 5920.7 6069.4 5650.0 5791.8
% voltage of V61 89.71 91.96 85.61 87.75
xN) , Amps
I cosQ= I1 x cosQ1 1137.055 2218.402 1191.529 2324.733
IsinQ = I1 x sinQ1 704.683 1374.842 738.444 1440.740
Voltage drop is 1.732 x( I CosQ x (Rc1+Ra+Rb1) + 9.82 19.99 9.51 19.35
(ISinQ x (Xc1+Xa+Xb1)) , V
Voltage at PCC V51= V50-Voltage drop, V 378.61 378.20 361.16 360.63
% voltage of V51 91.23 91.13 87.03 86.90
B9 At 415 V Fuel unloading MCC
Connected load in kW 75 75 75 75
No.of feeders, N 2 2 2 2
Running PF (CosQ1) 0.85 0.85 0.85 0.85
Running SinQ1 0.5268 0.5268 0.5268 0.5268
System voltage available , V51, Volts 378.61 378.20 361.16 360.63
Rated current I1 =Max load/ (sqrt(3) x V51xCosQ1x 67.3 67.3 70.5 70.6
N) , Amps
Cable size (from PCC to FO MCC ) 3.5cx300 3.5cx300 3.5cx300 3.5cx300
No.of cables 1 1 1 1
Cable resistance/km , Rc (ohms) 0.1300 0.1300 0.1300 0.1300
Cable reactance/km Xc, (ohms) 0.0705 0.0705 0.0705 0.0705
Cable distance , L (Metre) 400 400 400 400
Cable resistance Rc1=Lx Rc , (ohm) 0.052 0.052 0.052 0.052
Cable reactance Xc1= Lx Xc , (ohm) 0.0282 0.0282 0.0282 0.0282
I cosQ= I1cosQ1 57.1841 57.2468 59.9467 60.0358
IsinQ = I1sinQ1 35.4395 35.4784 37.1516 37.2069
Voltage drop is 1.732 xICosQx(Rc1) + 6.88 6.89 7.21 7.22
ISinQx(Xc1)) , V
Voltage at MCC V52= V51-Voltage drop, V 371.73 371.31 353.95 353.40
% voltage of V52 89.57 89.47 85.29 85.16
B10 Voltage at FO motor
Rated load (kW) 30 30 30 30
Voltage at MCC , V52, Volts 371.73 371.31 353.95 353.40
Running PF (CosQ1) 0.92 0.92 0.92 0.92
Running SinQ1 0.3919 0.3919 0.3919 0.3919
Efficiency 0.95 0.95 0.95 0.95
Full load current, I1, Amps 53.3 53.4 56.0 56.1
Cable size (MCC to motor) 3cx35 3cx35 3cx35 3cx35
No.of runs/ phase 1 1 1 1
Cable resistance/km , Rc (ohms) 1.1100 1.1100 1.1100 1.1100
Cable reactance/km Xc, (ohms) 0.0783 0.0783 0.0783 0.0783
Cable distance , L (Metre) 25 25 25 25
Cable resistance Rc1=Lx Rc , (ohm) 0.02775 0.02775 0.02775 0.02775
Cable reactance Xc1= Lx Xc , (ohm) 0.00196 0.00196 0.00196 0.00196
Voltage drop is 1.732 xI1 (CosQ1x(Rc1) + 2.43 2.43 2.55 2.55
SinQ1x(Xc1)) , V
Voltage at motor V53= V52-Voltage drop, V 369.30 368.88 351.40 350.85
% voltage of V53 88.99 88.89 84.67 84.54
Cable size ( from UAT to 6.6 kV switchgear) 1cx800 1cx800 1cx800 1cx800
No.of cables (n) 2 2 2 2
No.of UAT in service , N 1 2 1 2
Cable resistance/km , Rc (ohms) 0.0523 0.0523 0.0523 0.0523
Cable reactance/km Xc, (ohms) 0.0893 0.0893 0.0893 0.0893
Cable distance , L (Metre) 150 150 150 150
Cable resistance Rc1=Lx Rc/n , (ohm) 0.00392 0.00392 0.00392 0.00392
Cable reactance Xc1= Lx Xc/n , (ohm) 0.00670 0.00670 0.00670 0.00670
Max.load on UAT considering 0.9 service factor and 9402.5 9402.5 9402.5 9402.5
0.85 power factor = 12500 x 0.9 x 0.85, (kW) - starting
motor rating
Nominal system voltage , kV 6.8 6.8 6.46 6.46
Running PF (CosQ1) 0.85 0.85 0.85 0.85
Running SinQ1 0.5268 0.5268 0.5268 0.5268
Rated current I1 =Max load/ (sqrt(3) x V60 xCosQ1 939.19 469.60 988.62 494.31
xN) , Amps
Starting current (largest starting motor ) , I2 ,Amps 120.2559 120.255 120.255 120.255
(LT motor starting current (from C7) x0.433/6.6) 1 9 9 9
Starting PF (CosQ2) 0.3 0.3 0.3 0.3
Starting SinQ2 0.9539 0.9539 0.9539 0.9539
I cosQ= I1cosQ1+I2cosQ2 834.3909 435.233 876.407 456.242
8 4 1
IsinQ = I1sinQ1 + I2 sinQ2 609.4675 362.092 635.507 375.111
1 0 9
Voltage drop is 1.732 x( I CosQ x (Rc1+Ru) + 404.74 237.57 382.46 223.08
(ISinQ x (Xc1+Xu)) , V
Voltage at Switchgear V61= V60-Voltage drop, V 6395.3 6562.4 6077.5 6236.9
% voltage of V61 96.90 99.43 92.08 94.50
Transformer impedence with +ve tolerance, Za (%) 8.8 8.8 8.8 8.8
Transformer impedance in ohms ( Za xV40xV40/Pa) 0.0062 0.0065 0.0056 0.0059
Copper loss (kW) 30 30 30 30
Transformer resistance Ra = (copper loss ) x V40 x 0.0008 0.0009 0.0008 0.0008
V40 /Pa/Pa /1000 , (ohms)
Transformer reactance , Xa = sqrt (ZxZ-RxR) , (ohms) 0.0061 0.0065 0.0055 0.0058
3 3 3
Busduct reactance/m Xb, (ohms) 0.000080 0.00008 0.00008 0.00008
0 0 0
Busduct distance , L (Metre) 12 12 12 12
Busduct resistance Rb1=Lx Rb , (ohm) 0.00016 0.00016 0.00016 0.00016
Busduct reactance Xb1= Lx Xb , (ohm) 0.00096 0.00096 0.00096 0.00096
Max.load on LT auxiliary transformer considering 0.9 1500 1500 1500 1500
service factor and 0.85 power factor = 2000 x 0.9 x
0.85 - 30 (rating of starting motor from C10), (kW)
No.of LT transformer in service , N 2 1 2 1
Nominal system voltage , kV 0.4196 0.4305 0.3987 0.4092
Running PF (CosQ1) 0.85 0.85 0.85 0.85
Running SinQ1 0.5268 0.5268 0.5268 0.5268
Rated current I1 =Max load/ (sqrt(3) x V50xCosQ1 1214.2 2366.5 1277.6 2490.0
xN) , Amps
Starting current (largest starting motor from C10) , 343 343 343 343
I2 ,Amps
Starting PF (CosQ2) 0.3 0.3 0.3 0.3
Starting SinQ2 0.9539 0.9539 0.9539 0.9539
I cosQ= I1cosQ1+I2cosQ2 1134.945 2114.40 1188.89 2219.39
9 8 0
IsinQ = I1sinQ1 + I2 sinQ2 966.805 1573.82 1000.24 1638.88
3 2 4
Voltage drop is 1.732 x( I CosQ x (Rc1+Ra+Rb1) + 14.46 25.22 13.73 24.08
(ISinQ x (Xc1+Xa+Xb1)) , V
Voltage at PCC V51= V50-Voltage drop, V 405.11 405.31 384.99 385.10
4.0 Conclusion
With the selected impedance values of transformers and selected cable sizes, voltage drop is with in the
permissible limits. Calculation results are given below:
Description At 1.pu on 11 kV At 0.95 p.u on 11 kV
1UAT 1LT 1UAT 1LT
failure transformer failure transformer
failure failure
Steady state running condition
Voltage at BFP (%) 97.8 100.4 92.9 95.4
Voltage at CWP(%) 97.58 100.16 92.65 95.12
Voltage at RO motor(%) 98.1 97.82 93.4 92.75
Voltage at FO motor (%) 97.17 97.24 92.01 92.05
Voltage at PCC of sea water system 100 100.48 94.96 95.41
(%)
During starting of 6.6 kV CW motor, 88.37 90.63 84.27 86.42
Voltage at CWP (%)
During starting of LT RO motor 87.05 86.75 82.55 82.26
Voltage at RO motor (%)
During starting of LT FO motor 89.14 89.19 84.24 84.27
Voltage at FO Motor(%)