You are on page 1of 11

IET Generation, Transmission & Distribution

Research Article

ISSN 1751-8687
Advanced fuzzy power extraction control of Received on 25th June 2015
Revised on 25th October 2015
wind energy conversion system for power Accepted on 1st December 2015
doi: 10.1049/iet-gtd.2015.0769
quality improvement in a grid tied hybrid www.ietdl.org

generation system
Chayan Bhattacharjee ✉, Binoy Krishna Roy
Electrical Engineering Department, National Institute of Technology, Silchar, India
✉ E-mail: chayan_kol@yahoo.co.in

Abstract: This paper introduces an intelligent extraction of optimum power and its dispatch by using fuzzy logic from a
grid tied hybrid generation system comprising of a permanent magnet synchronous generator based wind turbine and
a low concentration photovoltaic generator. For photovoltaic generator, maximum power point tracking control is
implemented using fuzzy logic under varying solar irradiance. Power extracted from wind turbine is designed as a
fuzzy function of the dc link voltage error, its rate of change and error in the direct axis current of the inverter. This
reduces high frequency oscillations in the wind extracted power. Such an extraction is considered as a novelty of this
paper. A failure mode and effect analysis is done for power converters and possible mitigation schemes are suggested
for different faults. A 1:1 delta wye-grounded transformer is used at the inverter output to eliminate the triplet
harmonics. Further, dynamic performances of both fuzzy proportional-derivative and integral (PD+I) controller and
classical proportional integral (PI) controller, to control the inverter currents, are compared. The proposed method
results in an enhanced power dispatch and improvement in distortions and oscillations in the converter currents. This
also reduces the probability of failures in the converter switches and other passive components.

1 Introduction algorithm based on the knowledge of direct (d) axis current error
of the inverter (Δid), deviation in dc link voltage (ΔVdc) with
Increased penetrations of renewable energy sources into the power respect to its reference and its rate of change (δ (ΔVdc)). This
grid arouse several challenges in integration not only amongst technique performs well to stabilise dc link voltage and is devoid
themselves but also between such sources and the grid. Though of high frequency components. The crucial challenge is fast
the energy obtained from such sources is environment friendly but damping of oscillations in dc link voltage during rapid changes in
the power and voltage obtained from such sources varies randomly wind speed under wind turbulence and change in solar irradiance
with the variation of weather. Furthermore, non-linear power while dispatching the extracted power, at the PCC. Furthermore,
converters, used for conditioning the power outputs from such sag ride through of the inverter voltage would not be possible if
sources, distort the waveform and hence degrade the quality of the inverter reactive power compensation for load variation is
dispatched power thereby affecting sensitive loads connected to inappropriate [12]. The earlier papers cited do not focus keenly
the grid. Exhaustion of fossil fuels, their hazardous influence on into these aspects altogether. The BESS control aims to regulate
environment and an increasing power demand result in an the dc link voltage (Vdc) as for a grid connected system fast power
increased penetration of renewable energy sources into the utility transfer at the PCC is possible if Vdc remains constant under all
grid [1]. Since availability of renewable energies is variable and circumstances [13, 14]. Voltage oriented control (VOC) of a
unpredictable so energy storage device is essential at the dc link. two-level fully controlled inverter is done as the load system
This device maintains the power balance at the dc link which considered requires no neutral grounding and switching losses may
results in a smooth power dispatch. Li-ion batteries though costly be reduced unlike higher-level inverters [15]. The VOC is
have higher power density and can withstand higher charging/ designed to achieve an improved quality power to be fed at the
discharging cycles than that of lead-acid batteries while NiMH grid, apart from load reactive power compensation for power
batteries are costlier and have carcinogenic effect on the factor improvement and voltage stabilisation at the load bus [16].
atmosphere in spite of having higher power density than Li-ion Low pass filtered references for both active and reactive current
batteries [2, 3]. Low concentration photovoltaic (LCPV) generator components are used to reduce power distortions at the PCC. This
used in this work has a degree of concentration of 2.2X which do method along with the passive L-C-L filter at the inverter output
not require any extra tracking mechanism and cooling together improves both voltage and current THD. A failure mode
arrangements for their cells [4]. The use of such cells can increase and effect analysis (FMEA) of the power conditioning interface
solar power extraction efficiency to 20–25% [5] than flat plate between the generators and the grid is also discussed. Possible
collectors, with the use of simple mirror reflection with good mitigation methods for system protection for faults in different
optical efficiency. In the proposed system maximum power converters are shown. This analysis is of importance in such
extraction is essential from both LCPV generator and wind energy hybrid system as the continuous heating of the power switches;
conversion system (WECS) for increasing system efficiency [6, 7]. improper heat sink and ageing may result in either open or short
Fuzzy logic control has proved better than classical control for circuit faults in converters switches, failures in line inductors and
maximum power point tracking (MPPT) particularly under varying capacitors. This hampers power conversion process, degrades
inputs for renewable energy sources [8–10]. Tracking of maximum power quality and incurs economic losses.
operating power point is done using source side variations which The remaining part of this paper is organised as, Section 2 deals
results in high frequency components in the dc link voltage [11]. with the system component modelling and their dynamics, Section
In this work optimum power is extracted from WECS using fuzzy 3 discuss the FMEA of the power conditioning interface of the

IET Gener. Transm. Distrib., pp. 1–11


& The Institution of Engineering and Technology 2016 1
system and the possible mitigation system, Section 4 deals with the respectively, while Tcnom is the nominal operating cell temperature
control algorithms and controller configurations, Section 5 deals at Tanom .
with simulated results with discussion and finally Section 6
concludes with the essence of the work.
2.2 Wind energy conversion system

A one mass drive train for PMSG-turbine shaft model is chosen in


2 System dynamics and modelling this work. While the generator rated speed is low, the speed
difference between the turbine and the generator is considered
In this paper a permanent magnet synchronous generator (PMSG) negligible [19] thus almost neglecting the contribution of viscous
based WECS-LCPV hybrid system with Li-ion battery storage is friction. The mechanical torque generated is given in (3), while the
considered. The proposed system is feeding power to a local load PMSG voltage and torque dynamics are represented in the
and the grid as shown in Fig. 1 where Cdc is the dc link capacitor. direct-quadrature (d–q) axes from rotor reference frame of the
The turbine coupling shaft is modelled as one mass drive system PMSG, follows from (4)–(8)
as the rated rotor speed is low with a high number of rotor poles
for the PMSG [17]. Such shaft dynamics with less torsional losses 1
and viscous friction has high increasing transmission efficiency Tm = {0.5rACp (l, b)v3w } (3)
vr
through the shaft.
The LCPV generator, WECS which includes wind turbine model
and PMSG with one-mass shaft dynamics, variable-linear load where ωr, ρ, A, Cp(l, β) and vw are rotor angular speed [rad/s],
system and their conditional switching scheme and the battery air-density [Kg/m3], swept area of the turbine blades [m2],
energy storage system (BESS), is modelled based on their performance coefficient of the turbine and wind speed [m/s],
dynamic equations. The choice of the dc link capacitor is respectively. Cp in turn is dependent on the tip-speed ratio (l) and
considered so as to manage dynamic power balance at the the blade pitch angle (β).
common dc link during its fast charging/discharging modes with  
minimum oscillations in Vdc. vd = rs + Ld p id − Ed (4)
 
vq = rs + Lq p iq − Eq (5)
2.1 LCPV system
Ed = vr Lq iq (6)
With the advancement in nanotechnology, LCPV generators are
emerging as better choice over flat plate photovoltaic generators
as the solar concentration can be enhanced to more than 6X with Eq = vr Ld id + vr wr (7)

3    
no tracking and extra cooling arrangement thus enabling power
extraction at a higher efficiency [18]. Basic one diode equivalent Te = P wr − Ld − Lq id iq (8)
circuit is used [16] in this work, where solar concentration of 2
2.2X is assumed to vary due to cloud intervention. The solar
irradiance is in per unit (pu), (Gpu) over its base value of 1 KW/ where vd, vq, id and iq are the respective voltage and current
m2. The ambient temperature, Ta [°C] and the cell temperature Tc components in d-q-axes while Ed and Eq are the d-q-axes
[°C] are dependent on Gpu as per (1) and (2), as both temperature back-emf components and Te is the electro-magnetic torque
and irradiance regulates the output extractable power from the experienced by the generator. Ld, Lq and rs are the stator leakage
LCPV collector. An increase in cell temperature decreases the reactances and winding resistance while jr and P is the constant
amount of possible power extraction unlike an increase in solar rotor flux and the number of pole-pair of the PMSG, respectively,
irradiance. whose rated power is 90 KW. The instantaneous disturbances in
the rotor torque and shaft speed which follows from wind speed
Ta = 22 + 0.05(Gpu − 1.2) (1) variations and shaft dynamics as in (9) are directly reflected in the
output voltage and power of the generator. The amount of ripples
in the dc side voltage after rectification of the PMSG ac voltage
G(Tcnom − Tanom ) decides the value of the dc bus line inductor which is responsible
Tc = Ta + (2)
Gnom for suppressing the ripples [20] as per (10).

where Tanom , G and Gnom are the nominal ambient temperature (20° dv
Tm = J + Bv + T e (9)
C), solar irradiance in KW/m2 and nominal irradiance of 0.8 KW/m2, dt

Fig. 1 Layout of the system

IET Gener. Transm. Distrib., pp. 1–11


2 & The Institution of Engineering and Technology 2016
Table 1 Variable load switching schedule exponential voltage time constant [Ah], R is internal series
resistance [Ω], ih is battery transient current [A] and SOCi is initial
Load Value (P + jQ) Switching scheme
state of charge. The parameters of the Li-ion battery used in the
L1 P = 113 KW, Q = always remain connected
work are given in the Appendix.
0.5 KVAR
L2 P = 5 KW, Q = 0.5 from time = 2 s to time = 3 s
KVAR 2.4 Variable load system
L3 P = 15 KW, Q = from time = 3.5 s to time = 4 s.
0.75 KVAR The load comprises of a constant inductive load (L1) and three
L4 P = 7 KW, Q = 0.3 from time = 0 s to time = 1.5 s and from time separate inductive loads L2, L3 and L4 whose switching follows a
KVAR = 3.5 s to time = 4 s
particular time sequence. All the loads and their switching
schemes are given in Table 1, where KW and KVAR are
respective units of active and reactive powers.
J and B being inertia and viscous friction coefficient of the
turbine-generator system, respectively.
3 FMEA of the hybrid system and possible
di methods of fault mitigation
Vc = Vcc − L r (10)
dt
FMEA is done on the system to find the chance or probability of
where Vc, Vcc and ir are the boost converter’s input voltage, failure of different system components. This is a reliability
uncontrolled rectifier’s output voltage and ripple current, analysis of the system which depends on the regular inspection,
respectively, at the dc side of the WECS. Turbine and generator monitoring and expert knowledge of the system components
parameters are as given in the Appendix. which are prone to failures and may affect the performance of the
system severely. FMEA is used to structure mitigation for risk
reduction based on either failure effect severity reduction or on
2.3 Battery energy storage system lowering the probability of failure or both [22, 23]. Particularly the
power converters in the proposed system may be prone to open
Lithium-ion battery is used for transient power support at the dc link
circuit or short-circuit faults due to excessive heating of the
for stabilisation of Vdc, because of high power density and capability
devices. The temperature of the components depends upon the
of undergoing higher charging/discharging states without
magnitude of the active current it handles and instantaneous
degradation of its life unlike cheaper lead-acid batteries. Due to
voltage build up across switches [24, 25]. Apart from the
such properties in spite of its high cost these batteries are suited
converters the line inductors and the shunt capacitors may fail due
for wind based hybrid power systems and electric vehicles. The
to very high increase in the rate of current and voltage experienced
battery terminal voltage is a combination of constant, polarisation
by the device, respectively. The root cause behind these failures is
and exponential components as given in (11) [16, 21] and can be
not only the continuous heating effect but also the rate of rise in
modelled based on its charging/discharging dynamics. The
temperature and development of hot spots due to inefficient
instantaneous battery charge is shown in (12).
distribution of heat and also improper cooling of the converters.
Further with an increase in power densities of converters, available
Cq
Vb = Vc − Ap − Rib + Ke−lq (11) surface area for heat dissipation decreases. For this reason the
C−q converters are generally derated under normal operation which
 increases reliability but does not increase component cost
  significantly. Different failure modes in the power converters of
q = 1 − SOCi C + ib dt (12)
the proposed system are given in Fig. 2 along with their possible
mitigation methods.
where Vb is the terminal voltage of the battery, Vc is constant As all the converters are connected directly to the dc link capacitor,
component voltage [V], Ap is polarisation constant [V/Ah], C is a fault in any of the switches alters the dc link voltage and affects
total capacity of battery [Ah], q is instantaneous battery charge smooth power transmission. In case of short circuit fault across any
[Ah], K is the amplitude of exponential component [V], 1/L is the switch, the dc link capacitor tends to discharge immediately

Fig. 2 Faults in converter switches and their possible mitigation

IET Gener. Transm. Distrib., pp. 1–11


& The Institution of Engineering and Technology 2016 3
delivering high fault current which may damage other switches in the current and when it equals fault current level urges opening of the
converter leg or line inductors connected for ripple reduction. Hence faulty dc converter/rectifier connecting it to the dc link or cease of
immediate disconnection of the faulty converter from the remaining gate drive signal for the inverter. The suggested control for
system is to be done after detection of high rate of increase in disconnection is shown in Fig. 3a for the LCPV generator and the
current and equals to fault current level. Under open circuit fault battery, where the isolator Sw1 is normally closed (NC) but is
for the dc–dc converters of WECS, LCPV generator and BESS, opened when the time rate of rise of the inductor current (di/dt)
MPPT from the renewable sources fails, and the dc link voltage exceeds its maximum limit ‘k’. Soft isolation of the PMSG
will exactly follow the variations of wind speed and solar generator isolates the WECS for a short circuit in either the boost
irradiance. It results in lowering of system efficiency, voltage stress chopper or the uncontrolled rectifier is shown in Fig. 3b. The
on buck-boost converter for BESS and degradation in active power switches for the phase isolators are NC type and opened
dispatch across the inverter. Retuning of integral gain of BESS simultaneously at times Ti, Ti+1, and Ti+2 for phases in the phase
voltage regulator may improve the dc link voltage stabilisation. sequence of the PMSG, where ‘i’ stands for 1, 2 and 3 for the
This alters the battery current reference within its permissible bias. respective phases. This process detects the magnitude of
This performance may be improved with a fuzzy voltage control. instantaneous voltage deviation of the three phase voltages of the
Open circuit fault of the BESS converter results in unidirectional PMSG from its average value, which is zero, over one cycle. The
and uncontrolled power compensation in the dc link. With open switch of the phase with minimum voltage deviation (i) is opened
circuit fault in the uncontrolled rectifier of WECS, voltage first followed by the other two in the phase sequence of voltage
imbalance will result at the ac side due to unidirectional power generation with a time delay corresponding to their instantaneous
flow through the freewheeling diodes. For this rectifier the whole phase, for minimum voltage build up across the isolators.
dc link voltage is experienced by a single diode of the converter
leg and may fail. Therefore prolonged operation is not suggested
after detection of open circuit faults. Though under sinusoidal
PWM inverter drive system both voltage and current will remain 4 System control methodologies
balanced but it will result in dc offset current through the switches
which degrades the output current quality [26]. Therefore the PI 4.1 Fuzzy control for optimal power point (OPPT)
regulators for the d-q axes current may be retuned to improve tracking from WECS
output current quality. Prolong operation with open circuit may
cause over-current in the healthy switch of the same leg when In this work intelligent fuzzy control algorithm is used to extract the
turned on and will experience the full dc link voltage when turned optimum power from WECS, which stabilises the dc link voltage in
off. Therefore isolation of the inverter from the dc link or ceasing spite of high frequencies in the power injected by the PMSG
its gate drive signals for all six switches may be required. generator. The inputs to the controller, ΔVdc, δ (ΔVdc), and Δid,
varies continually and does not obey any defined mathematical
model but depend on switching dynamics of the power
3.1 Possible design control for fault protection based on conditioning interface and load variation. Thus the objective of the
FMEA boost converter for WECS is to track optimum power based on
supply–demand relationship, which operates on linguistic fuzzy
As FMEA includes reducing the probability of failures which variables [27]. Mamdani type fuzzy controller with five triangular
primarily depends upon the temperature rise of a device and in membership functions is chosen for three inputs and the output,
turn active current of the device, it is shown in the outputs that which is the change in duty cycle of the converter (ΔD). Optimum
fuzzy control can reduce the oscillations in battery and inverter choice of prefix scale factors for the three inputs reduces high
currents and therefore reduces the average heating effect of these frequency components in the extracted wind power and therefore
devices (Fig. 7). Other suggested control methods upon short the overall power quality. Duty cycle (D) controls the charging/
circuit of converter switches are: discharging of dc link capacitor as it extracts the optimum power
with variations in natural energy sources. The linguistics for the
† Soft isolation of the PMSG from rectifier. membership functions used for all fuzzy controllers in this paper
† Isolation of the LCPV generator from the dc link. are PB, PS, Z, NS, NB which stands for positive big, positive
† Isolation of battery with fault current detection. small, zero, negative small and negative big, respectively. The rule
† Isolation of the inverter from the dc link. matrices for different values of ΔId controlling ΔD for fuzzy wind
power controller is shown in Table 2. For case I and case II,
As short circuit failures are more frequent in occurrence in respectively, when load demand is high and moderate, focus of the
converters, detection of sudden high rate of rise in the device control scheme is lessening the grid burden and hence power

Fig. 3 Isolation of different converters from the dc link


a Isolation of the LCPV and BESS
b Soft isolation of the PMSG

IET Gener. Transm. Distrib., pp. 1–11


4 & The Institution of Engineering and Technology 2016
Table 2 Rule matrices for fuzzy-OPPT Table 3 Rule matrix for fuzzy-MPPT
δ (ΔVdc), ΔVdc NB NS Z PS PB ΔVdc ΔPw NB NS Z PS PB

Case I: When Δid is negative (N) NB PS PS PB NS NS


NB PB PB PB Z Z NS PB PB PS NB NB
NS PB PB PB Z NS Z PB PB Z Z Z
Z PB PB PS NS NB PS NB NB NS PB PB
PS PS PS Z NB NB PB NS NS NB PS PS
PB Z Z NS NB NB
Case II: When Δid is Z
NB PB PB PS Z Z
NS PB PB PS Z Z
Z PS PS Z NS NS which is an uncontrolled ac–dc rectifier along with a boost
PS Z Z NS NB NB chopper. Quantities at the dc side are only utilised for MPPT as
PB Z Z NB NB NB per (13) instead of measuring instantaneous rotor speed as in tip
Case III: When Δid is positive (P)
NB PB PB PS Z Z
speed ratio control.
NS PB PB Z Z Z
Z PB PS Z NS NB dPw dPw dVdc
PS Z Z Z NS NB = × (13)
PB Z Z NS NB NB dwr dVdc dwr

where,
extraction will be close to MPPT. For case III, when load demand is
low focus is given in lessening ΔVdc and power extraction is adjusted Vdc = f (wr ) (14)
accordingly.
The fuzzy OPPT control is modelled as shown in Fig. 4a where
FLC is the fuzzy logic controller and pulses are generated using Table 4 Rule matrix for fuzzy-MPPT control of SEGS
sinusoidal pulse width modulation.
CE E NB NS Z PS PB

4.2 Fuzzy control for MPPT from WECS NB Z Z PB PB PB


NS Z Z PS PS PS
Power extraction from the wind generator utilises electrical power Z PS Z Z Z NS
PS NS NS NS Z Z
versus Vdc trajectory at the dc side of the WECS converter to alter PB NB NB NB Z Z
its duty cycle. The WECS converter is a switched mode rectifier

Fig. 4 Different control schemes implemented for the WECS, battery and the inverter
a Fuzzy OPPT control
b Blade pitch angle control
c BESS bidirectional power control
d VOC of the inverter

IET Gener. Transm. Distrib., pp. 1–11


& The Institution of Engineering and Technology 2016 5
Table 5 Rule matrix for fuzzy PD+I VOC control of inverter current is a proportional function. Pw and wr are the electrical power
delivered and instantaneous rotor speed, respectively. It is implied
CE E NB NS Z PS PB
according to (13) that when dPw/dwr = 0 for maximum power then
NB NB NB NB NS Z
dPw/dVdc = 0, as dVdc/dωr≠0. The fuzzy rule matrix for the MPPT
NS NB NB NS Z PS control is shown in Table 3. The inputs to the controller are the
Z NB NS Z PS PB perturbation in the electrical power output (ΔPw) and perturbation
PS NS Z PS PB PB in the dc link voltage (ΔVdc) while the output is the perturbation in
PB Z PS PB PB PB
the chopper duty cycle. The switching scheme is the same as for
OPPT, shown in Fig. 4a.

Fig. 5 Fuzzy PD+I controller

Fig. 6 Input and output characteristics of wind turbine and LCPV generator
a Wind speed
b Rotor speed
c Solar irradiance for LCPV
d Solar power generated

IET Gener. Transm. Distrib., pp. 1–11


6 & The Institution of Engineering and Technology 2016
Fig. 7 Power management and error tracking for different modes of operation
a Inverter active power dispatched
b Battery power
c Inverter d-axis current error
d Inverter q-axis current error

4.3 Pitch angle control for wind turbine where d, IL and (Rs, Ls) are the duty cycle of the chopper, solar
generator load current and parameters of the boost converter,
As per IEC 61400-2, blade pitch control for limiting extraction of respectively. A basic hill-climb approach is used for tracking
power from wind turbine is essential when the generated power maximum power operating point where the control inputs
exceeds the rated power of the turbine to avoid its overloading considered are dPpv/dVpv and its rate of change [29] and change in
[28]. The required pitch angle, β is generated from the power duty-cycle as the output. Mamdani type fuzzy control with five
difference of turbine rated power and actual power. Fig. 4b shows triangular membership functions for the two inputs error (E) and
the blade pitch angle control where the power error, ΔP, is sent to change in error (CE) and the output which is perturbation in d are
a PI regulator that generates the reference pitch angle. When ΔP < considered with its rule matrix given in Table 4. Input
0, the limiter restricts the pitch angle reference to zero but when membership functions are considered tilted towards centre as
ΔP > 0, the pitch actuator actuates the necessary pitch angle maximum occurrences of errors are around the ‘0’ crisp value.
change of the blades to limit the extracted power. The dynamics of
the pitch angle actuator is non-linear and depends upon saturation
limits on pitch angle and pitch rate. 4.5 Bidirectional power flow control for BESS

With a transient power mismatch between the generated and the


consumed, ΔVdc deviates from its reference value, zero, which
4.4 Fuzzy control for MPPT of LCPV generator
hampers smooth power transfer at the inverter output, de-stabilising
The power transfer efficiency of a LCPV is about 25%, hence focus the output frequency from its nominal value [17, 30]. BESS
should be given on maximum extraction from such generator controls the power flow at the common dc link stabilising Vdc at its
ref
unconditionally in a grid connected system as any surplus power reference value Vdc . A dc buck-boost converter with IGBT
dispatched by the inverter will get consumed at the grid which switching is used for the model. The dynamics of the common dc
behaves as a virtual load. Deviations of Vdc are corrected by link capacitor which controls battery current are given in (16) and (17)
optimum power extracted from WECS and the control of the
BESS. The boost voltage fed at the common dc bus by the LCPV dVdc 1  
generator is as per (15). = iRL − iLoad + ibatt (16)
dt Cdc

1 dVpv
Vboost = {V − IL (Rs + Ls )} (15) ipvL = ipv − Cpv (17)
1 − d pv dt

IET Gener. Transm. Distrib., pp. 1–11


& The Institution of Engineering and Technology 2016 7
Fig. 8 THD of inverter voltage and current for MPPT and OPPT-fuzzy modes of operation
a Voltage THD for MPPT mode
b Voltage THD for OPPT-fuzzy mode
c Current THD for MPPT mode
d Current THD for OPPT-fuzzy mode

where iRL, iLoad and ibatt are current delivered from both renewable 3
sources, inverter input current and battery current, respectively, at the Q∗ = (vin iin − vin in
q id ) (20)
2 d q
common dc link. Cpv is the output capacitor of the LCPV generator
while Cdc is the dc link capacitor. The control action comprise of an
inner current control loop and outer voltage control loop as shown in where P*, the inverter active power reference is the sum of extracted
ref
Fig. 4c [31]. Ibatt is the battery reference current generated by the power from the renewable sources while Q* is the load reactive
voltage regulator for a ΔVdc. Vcom, battery voltage Vbatt and Vdc power demand. The component of net active current reference
controls the duty ratio, dbatt of the converter [32] as per (18) which derived from (19) by neglecting vq is id1* while the other
in turn controls the battery charge. Battery charge control is component Id2* is obtained from instantaneous ΔVdc as shown in
constrained by the two current limits of +Isat and –Isat for Fig. 4d. Here id2* is added with id1* so as to increase the current
respective discharge and charge operations, while limits on Vcom reference when ΔVdc > 0 and decrease the same when ΔVdc < 0.
are imposed assuming maximum Vbatt and desired Vdc. The net reactive current reference, id* is obtained from (20). The
inverter voltage quality is fully controlled by the series arm
Vcom + Vbatt impedance of the L-C-L filter while the current quality may be
dbatt = (18) improved according to IEEE 519 using an additional active shunt
Vdc
compensator. The PI regulators for both id and iq are first tuned
classically for optimum performances. These values are then
4.6 VOC of the inverter utilised in fuzzy proportional-derivative and integral (PD+I)
controllers and performances compared with optimal classical
The inverter control is aimed at – (i) maximising the power dispatch, controllers. The rule array for the fuzzy PD+I control is given in
(ii) stabilising Vdc, (iii) maintaining synchronism with the grid Table 5. The system’s sampling frequency is set at 1.25 KHz to
operating conditions and (iv) improving THD of the power improve the precision of fuzzy control output.
delivered at the PCC [33, 34]. Decoupled vector control approach The linguistics for the abbreviation of membership functions used
of inverter direct-axis (d-axis) and quadrature-axis (q-axis) currents in the rule matrix given in Table 5 are the same as used before. ‘PS’
is implemented on a synchronously reference rotating frame in
phase with the grid voltage by using phase locked loop control,
where the d-axis voltage is considered aligned with the grid Table 6 Inverter voltage and current quality in terms of THD
voltage. Dynamics of the inverter power dispatched are given in THD in inverter Modes of operation
(19) and (20) where vin in in in
d , id and vq , iq are the respective d-axis
and q-axis voltage and current components of the inverter. MPPT OPPT OPPT-fuzzy

3 voltage 0.09 0.63 0.87


P∗ = (vin iin + vin in
q iq ) (19) current 21.38 16.74 13.74
2 d d

IET Gener. Transm. Distrib., pp. 1–11


8 & The Institution of Engineering and Technology 2016
and ‘NS’ membership functions for both inputs are considered tilted 5 Simulated results and discussions
towards the central membership ‘Z’ as the maximum tendency of the
crisp values are to lie around ‘Z’ thus to provide maximum areal With the considered input source variations, fuzzy controllers help to
coverage offered for defuzzification to improve accuracy. Instead track the correct instantaneous operating points for all controllers.
of MIN-MAX, the PROD-MAX inference method was used for Furthermore, performances of the two inverter current control
defuzzification to minimise transient oscillations in the output [35]. techniques have proven that the fuzzy PD+I control provide better
time domain response than the classical PI control. The wind
speed profile considered here is given in Fig. 6a. The turbine rotor
speed, given in Fig. 6b which controls the generated frequency of
4.6.1 Fuzzy PD+I controller configuration for inverter the PMSG voltage. The variation in solar irradiance for LCPV is
control: High frequency transient variations in the d-q-axes shown in Fig. 6c due to intervention of clouds which results in the
currents of the inverter are minimised by the use of fuzzy PD+I maximum extracted power given in Fig. 6d. The rated power of
control where specifically the rate of variations are minimised. the generator is delivered at the maximum solar concentration of
Both transient and steady state time responses are improved. Five 2.2X.
triangular membership functions for both the inputs and the output A comparison of performances in power extraction and transient
are used with the rule matrix given in Table 5. The controller is responses among three different modes of operation, namely (i)
shown in Fig. 5, in which the controller gain constants namely MPPT (ii) OPPT and (iii) OPPT with fuzzy PD+I control of
GE, GCE, GIE and GU are calculated according to (21)–(24). inverter current (OPPT-fuzzy) is done. The first two modes of
operation use classical PI control for their inverter current control.
GE = 1/M (21) Figs. 7a and b show the inverter active power output and the
battery delivered power for the three operational modes,
GCE = GE × (Kd /Kp ) (22) respectively. Fig. 7a reveals that OPPT-fuzzy method dispatches
more power than OPPT but less than MPPT for a simulation time
GIE = GE × (Ki /Kp ) (23) of 2 s, while Fig. 7b shows that OPPT-fuzzy consumes lesser
average power from the battery. Figs. 7c and d show oscillations
GU = Kp /GE (24) in inverter d-axis and q-axis current, respectively, for all the three
modes. Out of the three modes, control by mode1 results in
Kp, Kd, Ki and M are the proportional, derivative and integral gains of injection of very high frequency current components into the PCC
the controller and M is the maximum magnitude of the error, than mode 2 and mode 3. A study of the distortions in voltage and
respectively. current at the output of the inverter-filter combination also reveals

Fig. 9 Active power management by OPPT-fuzzy and MPPT modes


a Active powers at the PCC by OPPT-fuzzy mode
b Active powers at the PCC by MPPT mode
c Extracted power from WECS
d DC link voltage stabilisation

IET Gener. Transm. Distrib., pp. 1–11


& The Institution of Engineering and Technology 2016 9
Fig. 10 Inverter reactive power management and its load compensation at the PCC
a By OPPT-fuzzy mode
b By MPPT mode
c Inverter reactive power compensation by mode 1 and mode 3 of operation

that OPPT-fuzzy is the best amongst the three modes for voltage droop at the inverter output. Fig. 10 shows the
improvement of power quality at the PCC as shown in Fig. 8. compensation done by mode 3 tracks the load requirement much
Figs. 8a and b shows that although the voltage THD is the best in closely with lesser oscillations than that mode 1. Figs. 10a and b
MPPT method but a voltage THD of 0.87 is quite acceptable as show the difference in the two modes in reactive power
obtained in OPPT-fuzzy as per standard IEEE-519. However compensation at the PCC. While Fig. 10a shows a much improved
Figs. 8c and d show a good improvement in the THD of the stability for the compensation by mode 3 resulting in average grid
inverter current for OPPT-fuzzy over that obtained in MPPT. A reactive power requirement to zero, Fig. 10b gives a picture of
summary of the results of THD in inverter voltage and current is poor stability by mode 1 with much higher oscillations. A
shown in Table 6 for all three modes of operations. comparison of load reactive power compensation as shown in
Therefore, OPPT-fuzzy proves to be the best method out of the Fig. 10c gives precise difference in the stability performances of
three in terms of power maximisation, reducing oscillations in the two modes.
system responses and reducing distortions in the inverter
dispatched power. Third harmonic and higher order triplets (3rd
order harmonics) are negated at source by the use of 1:1 delta-star 6 Conclusion
transformer (Fig. 1) which completely blocks the flow of triplets at
the PCC. This work emphasises to extract maximum power from the 2.2X
Operation by mode 2 although produces almost similar concentration LCPV solar generator and optimum power from a
oscillations in system responses but yields lesser power at the PMSG based direct driven wind power generator to provide
inverter output so onwards responses with this method is not necessary power to the local load and the grid. The power
shown. The active power management at the inverter output and extractions are done intelligently using fuzzy logic control but
dc power extracted from the wind generator for mode 1 and mode wind power being the dominant contributor amongst the two,
3, respectively, are shown in Figs. 9a and b. Fig. 9a shows active inject high frequency oscillations in the dc link power. Therefore
power dispatched by mode 3 is higher particularly after 2.5 s as extraction of power from this generator by the proposed method
compared with Fig. 9b for mode 1. Thus grid support is also focuses to stabilise the dc link voltage and reduce active power
higher in mode 3 reducing its active power burden of the local mismatch at the inverter output. This method utilises intelligently
load. Power extraction from WECS again is also higher by mode 3 the knowledge of transient power imbalance at the dc link and the
as shown in Fig. 9c particularly after 2.5 s. The dc link voltage variation of load current to extract and dispatch maximum possible
shown in Fig. 9d indicates mode 3 has lesser undershoot and power with an improved quality at the inverter output. The system
oscillations of the dc link voltage about its reference value functions in grid supporting mode by dispatching the active power
compared with mode 1. generated and reactive power compensation of the load wholly.
The grid inverter is supposed to compensate for the instantaneous Frequency and magnitude of the inverter output voltage is
load reactive power to improve load power factor and to control maintained at its desired nominal value without any voltage sags/

IET Gener. Transm. Distrib., pp. 1–11


10 & The Institution of Engineering and Technology 2016
swells as load changes. Fuzzy PD+I control of the inverter proves to 21 Wang, B., Rogers, C., Peng, F., et al.: ‘Energy storage system based power control
be the best amongst the three modes of operation discussed in for grid-connected wind farm’, IJEPES, 2013, 44, pp. 115–122
22 Ribeiro, E., Cardoso, A., Boccaletti, C.: ‘Open circuit fault diagnosis in interleaved
stabilising dc link voltage, battery power control, improved grid DC–DC converters’, IEEE Trans. Power Electron., 2014, 29, (6), pp. 3091–3102
support and improving THD of the inverter output voltage and 23 Kahrobaee, S., Asgarpoor, S.: ‘Risk-based failure mode and effect analysis for
current. FMEA of the power conditioning system is done and wind turbines (RB-FMEA)’. NAPS, 2011
possible mitigational methods are suggested for a ride-through of 24 Sheng, H., Wang, F., Tipton IV, C.W., et al.: ‘A fault detection and protection
scheme for three-level DC–DC converters based on monitoring flying capacitor
the system in the event of faults. The proposed control method voltage’, IEEE Trans. Power Electron., 2012, 27, (2), pp. 685–697
under steady natural resources may produce marginal improvement 25 Jlassi, I., Estima, J. D., Khil, S. KEI., et al.: ‘Multiple open-circuit fault diagnosis in
as compared with the performances of the classical control. back-to-back converters of PMSG drives for wind turbine systems’, IEEE Trans.
Power Electron., 2015, 30, (5), pp. 2689–2702
26 Kastha, D., Bose, B.: ‘Investigation of fault modes of voltage-fed inverter system
for induction motor drives’, IEEE Trans. Ind. Appl., 1994, 30, (4), pp. 1028–1038
7 References 27 Hajizadeh, A., Golkar, M.: ‘Intelligent power management strategy of hybrid
distributed generation system’, IJEPES, 2007, 29, (10), pp. 783–795
1 Saedi, W., Lachowiz, S., Haibi, D., et al.: ‘Power flow control in grid connected 28 Kurahane, K., Senjyu, T.A., Yong, A., et al.: ‘A hybrid smart AC/DC power
microgrid operation using particle swarm optimization using variable loads’, system’, IEEE Trans Smart Grid, 2010, 1, (2), pp. 199–204
IJEPES, 2013, 49, pp. 76–85 29 Larbes, C., Cheik, S., Obeidi, T., et al.: ‘Genetic algorithms optimized fuzzy logic
2 Pistoia, G.: ‘Lithium-ion batteries- advances and applications’ (Elsevier, 2013, 1st control for maximum power point tracking in photovoltaic system’, J. Renew.
edn.) Energy, 2009, 34, pp. 2093–2100
3 Zhu, D., Glanzmann, G.: ‘Real-time control of energy storage devices in future 30 Chen, Y., Chen, C., Wu, H.: ‘Grid-connected hybrid PV/wind power generation
electric power systems’ (IEEE Trondheim Powertech, Norway, 2011) system with improved dc bus voltage regulation strategy’. Power and Electronic
4 Sonneveld, P., Swinkles, G., Tuijl, B., et al.: ‘Performance of a concentrated Conf., APEC, 2006
photovoltaic energy system with static linear fresnel lenses’, J. Solar Energy, 31 Kim, S., Jeon, J., Cho, C., et al.: ‘Dynamic modeling and control of a
2011, 85, (3), pp. 432–442 grid-connected hybrid generation system with versatile power transfer’, IEEE
5 Brognen, M.: ‘Optical efficiency of low cconcentrating solar energy systems with Trans. Ind. Electron., 2008, 55, (4), pp. 1677–1688
parabolic reflectors’. Dissertation of Faculty of Science and Technology, Uppasala 32 Nguyen, T., Lee, D.: ‘Advanced fault ride through technique for PMSG wind
University, 2004 turbine systems using line-side converter as STATCOM’, IEEE Trans. Ind.
6 Wang, Q., Chang, L.: ‘An intelligent maximum power extraction algorithm for Electron., 2013, 60, (7), pp. 2842–2850
inverter-based variable speed wind turbine systems’, IEEE Tran. Power Electr., 33 Bahrani, B., Karimi, A., Rey, B., et al.: ‘Decoupled dq-current control of grid-tied
2004, 19, (5), pp. 1242–1249 voltage source converters using non-parametric models’, IEEE Trans. Ind.
7 Kadri, R., Gaubert, J., Champenoies, G.: ‘An improved maximum power point Electron., 2013, 60, (4), pp. 1356–1366
tracking for photo-voltaic grid-connected inverter based on voltage-oriented 34 Kadri, R., Gaubert, J., Champenois, G.: ‘An Improved maximum power point
control’, IEEE Trans. Ind. Electr., 2011, 58, (1), pp. 66–75 tracking for photovoltaic grid-connected inverter based on voltage-oriented
8 Patcharaprakiti, N., Premrudeepreechacharan, S., Sriuthaisiriwong, Y.: ‘Maximum control’, IEEE Trans. Ind. Electron., 2011, 58, (1), pp. 66–75
power point tracking using adaptive fuzzy logic control for grid-connected 35 Pivonka, P.: ‘Compariritive analysis of fuzzy PI/PD/PID controller based on
photo-voltaic system’, J. Renew. Energy, 2005, 30, pp. 1771–1788 classical PID approach’. Proc. Int. Conf. FUZZ-IEEE 02, 1
9 Kamal, E., Koutb, M., Sobaih, A., et al.: ‘An intelligent maximum power
extraction algorithm for hybrid wind-diesel storage system’, IJEPES, 2010, 32,
(3), pp. 170–177
10 Gouden, N., Peter, S., Nallandula, H., et al.: ‘Fuzzy logic controller with MPPT
using line-commutated inverter for three-phase grid-connected photo-voltaic
8 Appendix: Parametric specifications of system
systems’, J. Renew. Energy, 2009, 34, pp. 909–915 components
11 Molina, M., Mercado, P.: ‘A new control strategy of variable speed wind turbine
generator for three-phase grid-connected applications’. Transmission and
Distribution Conf., IEEE, PES, 2008
12 Amin, M., Mohammed, O. ‘Vector oriented control of voltage souce PWM inverter
as a dynamic VAR compensator for wind energy’, APEC, 2010 LCPV rated power 18 KW
13 Yuan, X., Wang, F., Boroyeivich, D., et al.: ‘DC-link voltage control of a full panel voltage at Pmax 121 V
power converter for wind generator operating in weak-grid systems’, IEEE panel current at Pmax 146 A
Trans. Power Electron., 2009, 24, (9), pp. 2178–2192 panel open circuit voltage (Voc) 123 V
14 Li, X., Hui, D., Lai, X.: ‘Battery energy storage station (BESS) – based smoothing panel short circuit current (Isc) 153 A
control of photo-voltaic (PV) and wind power generation fluctuations’, IEEE number of cells in each series string 36
Trans. Sust. Energy, 2013, 4, (2), pp. 464–473 number of parallel strings 2
15 Kim, T., Kang, D., Lee, Y., et al.: ‘The analysis of conduction and switching losses turbine P (rated) 90 KW
in multi-level inverter system’. IEEE PESC, 2001 moment of Inertia 120 Kg/m2
16 Hajizadeh, A., Tesfahunegn, S., Undeland, T.: ‘Intelligent control of hybrid shaft stiffness coefficient 0.01
photo-voltaic/fuell cell/ energy storage generation system’, J. Renew. Sust. PMSG resistance/phase (Ω) 0.005
Energy-AIP, 2011, 3, (4), pp. 1–17 Ld, Lq 11 mH (each)
17 Uehara, A., Pratap, A., Goya, T., et al.: ‘A coordinated control method to smooth flux-linkage 1.2 V.s
wind power fluctuations of a PMSG-based WECS’, IEEE Trans Energy Convers., pole-pairs 40
2011, 26, (2), pp. 550–558 rated voltage-line 130 V
18 Reis, F., Brito, M., Corregidor, V., et al.: ‘Modelling the performance of low battery nominal voltage 210 V
concentration photovoltaic systems’, J. Sol. Energy Mater. Sol. Cells, 2010, 94, rated capacity 150 Ah
(7), pp. 1222–1226 nominal discharge current 110 A
19 Orlando, N., Lissere, M., Mastromauro, R., et al.: ‘A survey of control issues in internal resistance 0.007 Ω
PMSG-based small wind turbine systems’, IEEE Trans. Ind. Inf., 2013, 9, (3), exponential voltage 226.5 V
pp. 1211–1221 exponential capacity 14.8 Ah
20 Hasaneen, B., Mohammed, A.: ‘Design and simulation of dc/dc boost converter’, LC filter L, C 2.5 mH, 5 μF
MEPCON 2008, MiddleEast, pp. 335–340

IET Gener. Transm. Distrib., pp. 1–11


& The Institution of Engineering and Technology 2016 11

You might also like