You are on page 1of 12

Geotextiles and Geomembranes 42 (2014) 599e610

Contents lists available at ScienceDirect

Geotextiles and Geomembranes


journal homepage: www.elsevier.com/locate/geotexmem

Behavior of strip footing on fiber-reinforced cemented sand adjacent


to sheet pile wall
Ahmed M. Nasr
Structural Engineering Department, Faculty of Engineering, Tanta University, Egypt

a r t i c l e i n f o a b s t r a c t

Article history: In urban areas, shallow foundations are often placed along the ground surface above a sheet pile wall. In
Received 3 June 2014 this research, the potential benefits of reinforcing the active zone behind a model sheet pile wall by using
Received in revised form polypropylene fiber and cement kiln dust have been investigated experimentally and numerically. Tests
16 September 2014
were conducted by varying parameters including fiber ratio (RF), cement kiln dust (CKD) ratio, thickness
Accepted 25 October 2014
of reinforced layer, footing location relative to the sheet pile wall and curing time of reinforced layer.
Available online 14 November 2014
Finite element computer code PLAXIS 2D foundation was used for numerical modeling. Close agreement
between the experimental and numerical results was observed (maximum difference 14%). Experimental
Keywords:
Geosynthetics
and numerical results clearly show that fiber insertion into the cemented soil causes an increase in
Sheet pile wall ultimate bearing capacity of footing and significant reduction in the lateral deflection of the sheet pile
Fiber-reinforced sand wall. At higher fiber ratios (RF  0.75%), the bearing capacity ratio (BCR) increased by about 42% and the
Cement kiln dust effect of CKD ratio on BCR is more pronounced. The addition of fibers changed the brittle behavior of
Strip footing cemented sand to a more ductile one. Critical values of reinforcing parameters for maximum reinforcing
Active zone effects are established.
© 2014 Elsevier Ltd. All rights reserved.

1. Introduction increase with increasing surcharge load and decreasing strip load
distance to the excavation.
Shallow foundations, such as the roadway or continuous wall Several stabilization techniques have been used to stabilize and
footings for buildings are often placed along the ground surface improve the properties of the sandy soil, but improvement with the
above a sheet pile wall. These foundations may impose significant addition of cement is the most generally and successfully used the
lateral pressure on the sheet pile wall (Ghanbari and Taheri, 2012). technique. Natural or artificial cementation of soil particles con-
In earth-retaining problems, the subject of reinforcing the active tributes to settlement reduction and bearing capacity increase
zone has attracted a great deal of attention (Santos and (Asghari et al., 2003), which are the two key design considerations
PalmeiraBathurst, 2013). Nasr and Nazir (2013) studied the in the field of geotechnical engineering. Shear strength behavior of
behavior of a sheet pile wall embedded in non-cohesive soil rein- cemented sands has been widely studied (Schnaid et al., 2001;
forced by geosynthetics in the active zone adjacent to the strip Consoli et al., 2012). Ismail (2005) used cemented in situ soil for
footing. The results indicate that the inclusion of geogrid rein- retaining walls. According to these studies, cementation of sand
forcement in the active zone leads to a reduction by about 48%e75% results in increased brittle behavior as peak shear strength in-
in the lateral deflection. Nasr (2009) showed that the provision of creases. However, the high cost of cement motivated the search for
discrete vertical reinforcement behind the sheet pile wall has a a suitable alternative stabilizing material with low or no cost, such
significant effect in increasing the stiffness of the soil and decreases as cement kiln dust (CKD) for the stabilization of sandy soil. The
the lateral deflection of the sheet pile wall produced by the lateral high alkalinity and fine particle size of the CKDs, in addition to their
stress of the strip load. Georgiadis and Anagnostopoulos (1998) cementitious properties, make these materials suitable for several
used a model sheet pile wall embedded in sand to investigate the applications: waste solidification (Conner et al., 1992; Mckay and
effect of surcharge strip loads on wall behavior. From the results, it Emery, 1992) and mineral fillers in asphalt paving and mine
was concluded that the bending moments along the sheet pile wall reclamation operations. According to Portland Cement Association
(PCA, 2007), more than half million metric tons of CKD were used
for soil stabilization and as a binder in soil stabilized base and sub-
base pavement applications.
E-mail address: amanasrg@hotmail.com.

http://dx.doi.org/10.1016/j.geotexmem.2014.10.004
0266-1144/© 2014 Elsevier Ltd. All rights reserved.
600 A.M. Nasr / Geotextiles and Geomembranes 42 (2014) 599e610

The behavior of fiber reinforced sand has been studied by a 2.1.2. Fiber
number of researchers (Park and Tan, 2005; Chauhan et al., 2008; Polypropylene fiber is the most widely used inclusion in the
Ahmad et al., 2010; Diambra et al., 2010; Lovisa et al., 2010; laboratory testing of soil reinforcement (Ple and Le, 2012; Tang
Falorca and Pinto, 2011; Tang et al., 2007). These studies showed et al., 2007). Therefore, white monofilament polypropylene fibers
that adding fiber to sandy soil results in greater peak shear strength with circular cross section were used throughout this investigation
and more ductile behavior. In particular, when applying cemented to reinforce the cemented sand. Short fiber was used in this present
soils at a shallow depth, the degree of brittle failure may be more study to be consistent with model tests. The fibers were 12 mm in
pronounced due to a low confining stress. A number of studies have length and 0.023 mm in diameter (consequently aspect ratio of
also reported on the influence of both cement and fiber on the 521), with a specific gravity of 0.91, tensile strength of 350 MPa, and
mechanical behavior of sandy soils. Maher and Ho (1993) con- elastic modulus of 6 GPa. Also, the fiber used is a hydrophobic and
ducted static and dynamic triaxial compression and extension tests chemically inert material which does not absorb or react with the
on cemented sand containing randomly distributed fibers and re- soil moisture.
ported more shear strength and energy absorption for soil con-
taining fiber. Consoli et al. (1998, 2004) conducted consolidated 2.1.3. Cement kiln dust (CKD)
drained triaxial tests on sand reinforced with fiber and cement. The chemical composition of CKD used in this study was
They found that the addition of fiber increased peak and residual determined by X-ray fluorescence and is given in Table 2. For
shear strength and reduced residual dilation. The addition of fiber comparative purposes, the chemical composition of ordinary
to cemented soil produces bonding and friction between the soil Portland cement (from the same company) is also included in
and the fibers. A fiber-reinforced cemented soil can sustain a load Table 2. Relative to cement compounds, CKD contains the main
even after failure of a cemented soil and thus, can effectively oxides in proportions that produce intrinsic cementitious proper-
improve the brittle behavior of the soil. ties as indicated by the calculated hydration modulus (Kamon and
From the above literature, only limited information has been Nontananandh, 1991). The beneficial properties of CKD and its cost
reported on the use of fiber-reinforced cemented sand in active effectiveness compared with other types of stabilizers have led to
zone behind the sheet pile wall. Therefore, the present work de- its use as a popular stabilization agent in recent times (Miller and
scribes a study of the behavior of the strip footing resting on fiber- Azad, 2000). Kamon and Nontananandh (1991) have suggested
reinforced cemented sand adjacent to the sheet pile wall. that in order that reactions take place, the hydration modulus must
be greater than 1.7.

Cao; %
2. Experimental investigation Hydration modulus ¼  1:7 (1)
Sio2 ; % þ AL2 o3 ; % þ Fe2 o3 ; %

2.1. Material used for the testing Based on the values of each component in Table 2, the hydration
modulus (Eq. (1)) of CKD and Portland cement are found to be 2.30
2.1.1. Sand and 2.17, respectively. This indicates that CKD can be considered a
The experiments were carried out on clean, oven dried, soil stabilizer.
commercially available sand. Mineralogical analysis showed that
sand particles are predominantly quartz. According to the Unified 2.2. Test tank
Soil Classification System (ASTM, 2010), the soil is classified as
poorly graded sand with letter symbol (SP). The sand was placed in A series of laboratory model tests was executed in a test tank
a test tank at a unit weight of 15.57 ± 0.15 kN/m3, which corre- made of steel, having inside dimensions of 1.50 m long, 0.5 m wide,
sponds to relative density (Dr) of 50%. The friction angle of the sand and 0.9 m high. These tank dimensions were chosen to ensure that
(Ø) at 50% relative density, as determined from standard Uncon- the failure zone did not extend up to the walls (based on pre-
solidated Undrained (UU) triaxial compression tests on a dry sand liminary results of Plaxis 2D and other investigators such as Nasr
sample, was found to be 36 . Other physical properties of the sand and Nazir, 2013. To ensure the rigidity of the tank, the sides of
are summarized in Table 1. the tank were braced with vertical and horizontal stiffeners to
prevent any deflection during the loading process. Furthermore, to
achieve almost frictionless side faces, the inside fixed walls of the
Table 1 tank were polished smooth. Then, the longitudinal sides of the tank
Physical and mechanical properties of sand used in the model tests. were coated with lubricating oil in order to reduce the effect of side
Property Value
wall friction. A schematic diagram of the model test configuration is

Specific gravity, Gs 2.64


Grain size analysis Table 2
Effective grain size, D10 (mm) 0.10 Chemical composition of CKD and ordinary Portland cement.
Average grain size, D50 (mm) 0.30
Uniformity coefficient, Cu 3.80 Chemical composition Analysis method Composition (% by weight)
Coefficient of curvature, Cc 1.05
CKD OPC
Coarse to medium sand, % 30.0
Fine sand, % 68.5 SiO2 XRF 15.42 21.20
Fines (<0.075 mm) 1.50 Al2O3 XRF 3.92 4.95
Classification (USCS) SP Fe2O3 XRF 2.95 2.82
Maximum dry unit weight, gd max (kPa) 17.10 CaO XRF 51.23 62.81
Minimum dry unit weight, gd min (kPa) 14.30 MgO XRF 2.73 4.0
Maximum void ratio, emax 0.811 SO3 XRF 4.36 2.63
Minimum void ratio, emin 0.515 Na2O3 XRF 0.35 0.2
Compaction study K2O XRF 1.91 0.3
Optimum moisture content, Wc(%) 9.50 Loss on ignition (LOI) ASTM C575 19.82 1.72
Maximum dry density, (kPa) 16.90 Specific gravity, Gs ASTM D 854 2.78 3.13
A.M. Nasr / Geotextiles and Geomembranes 42 (2014) 599e610 601

Fig. 1. Schematic diagram of the model test configuration (not to scale).

shown in Fig. 1. A raining device consisting of an upper steel box 2.6. Preparation of reinforced-sand layer
(raining box) was designed and constructed in the loading frame to
obtain the desired density of sand. This section describes briefly the stages followed in preparation
of the reinforced e sand layer. The cement kiln dust ratio (RCKD) is
based on dry sand defined as follows:
2.3. Model footing
RCKD ¼ ðWCKD =WS Þ  100ð%Þ (2)
The footing was 499 mm in length, 100 mm width, B, and
25 mm in thickness. The length of the footing was made almost where WCKD is the weight of CKD and WS is the weight of dry sand.
equal to the width of the tank in order to maintain the plane strain The different values adopted in the present study for RCKD are 3, 6, 9,
conditions. All tests were performed with the footing resting on and 12%. The fiber ratio (RF) is based on the amount of the fiber used
the sand surface (Df ¼ 0.0) in the active zone. To overcome po- in each fiber inclusion layer. It is defined as follows:
tential error due to friction on the sides of the tank, the ends of the
footing box section were polished smooth to minimize the end RF ¼ WF =ðWS þ WCKD Þ  100ð%Þ (3)
friction effect. In order to simulate a valid, real condition, a rough
base condition was achieved by attaching sandpaper to the bottom where WF is the weight of fiber. The reinforced-sand layer was
of the footing. prepared at four fiber ratios, namely, 0.25, 0.5, 0.75, and 1.0%.
The fiber-reinforced cemented sand used in the experiments
was prepared by hand-mixing dry sand, CKD, polypropylene fibers
2.4. Sheet pile wall with optimum moisture content of 9.5% (as calculated from
compaction test). Proper care was taken to prepare homogenous
The sheet pile wall consisted of a flexible steel plate 750 mm mixtures at each stage of mixing.
in length, 499 mm width, and 3.3 mm in thickness. The sheet pile
was embedded 500 mm into the sand bed. The base of the sheet 2.7. Sand deposit preparation
pile wall was tapered to facilitate the penetration into the soil.
The sheet pile wall was polished smooth to minimize the end The inside walls of the tank were marked at every 100 mm.
friction effects and friction with the soil bed. The flexural stiff- Then, the sand was placed in 100 m layers of thickness using a
ness of the model sheet pile wall (EI) about the ZeZ axis was raining technique through the air. The height of fall to achieve the
0.629 kN m2/m. desired unit weight was determined a priori by performing a series
of trials with different heights of the fall. In each trial, the unit
weights were calculated by collecting samples in small cups of
2.5. Loading system
known volume placed at different locations in the test tank. In all
model tests, the average unit weight and relative density of the
A rigid loading frame was used in the experimental work. The
sand were kept as 15.57 ± 0.15 kN/m3 and 50%, respectively.
footing was loaded by a hand operated hydraulic jack of 50 kN
capacity. To push the footing slightly into the sand bed, load
applied through the jack was recorded with the help of a pre- 2.8. Test procedures
calibrated proving ring fitted to the piston of the jack. In order
to record the correct settlement of the footing after application of A sand bed, initially 600 m deep (100 mm for each layer), was
the load, two dial gauges with a measurement of at least prepared in the test tank using the sand raining technique as dis-
0.01 mm were used. Also, to measure the lateral deflection along cussed previously. The position of the sheet pile wall was marked
the sheet pile wall, four LVDT'S were placed in the center of the vertically for reference. Then, the model sheet pile wall was driven
sheet pile wall at different elevations in the passive zone as vertically into place. A supporting wooden box was made to guide
shown in Fig. 1. the sheet pile wall on one side of the wall (passive zone). The sand
602 A.M. Nasr / Geotextiles and Geomembranes 42 (2014) 599e610

Table 3
Details of parametric study.

Series Study on effect of Constant parameters Variable parameters

A Unreinforced active zone (no fiber) X/H ¼ 0.6, U/H ¼ 0.3, Time ¼ 0.0 RCKD (%) ¼ 3, 6, 9, 12
B Fiber ratio þ CKD ratio RCKD ¼ 3%, X/H ¼ 0.6, U/H ¼ 0.3, Time ¼ 0.0 RF (%) ¼ 0.25,0.5, 0.75, 1.0
RCKD ¼ 6%, X/H ¼ 0.6, U/H ¼ 0.3, Time ¼ 0.0 RF (%) ¼ 0.25,0.5, 0.75, 1.0
RCKD ¼ 9%, X/H ¼ 0.6, U/H ¼ 0.3, Time ¼ 0.0 RF (%) ¼ 0.25,0.5, 0.75, 1.0
RCKD ¼ 12%, X/H ¼ 0.6, U/H ¼ 0.3, Time ¼ 0.0 RF (%) ¼ 0.25,0.5, 0.75, 1.0
C Reinforced layer thickness RCKD ¼ 9%, X/H ¼ 0.6, Time ¼ 0.0, RF ¼ 0.50% U/H ¼ 0.1, 0.2, 0.3, 0.4, 0.5
RCKD ¼ 9%, X/H ¼ 0.6, Time ¼ 0.0, RF ¼ 0.75% U/H ¼ 0.1, 0.2, 0.3, 0.4, 0.5
RCKD ¼ 9%, X/H ¼ 0.6, Time ¼ 0.0, RF ¼ 1.00% U/H ¼ 0.1, 0.2, 0.3, 0.4, 0.5
D Footing location relative to SPW RCKD ¼ 9%, U/H ¼ 0.3, Time ¼ 0.0, RF ¼ 0.50% X/H ¼ 0.4, 0.6, 0.8, 1.0
RCKD ¼ 9%, U/H ¼ 0.3, Time ¼ 0.0, RF ¼ 0.75% X/H ¼ 0.4, 0.6, 0.8, 1.0
RCKD ¼ 9%, U/H ¼ 0.3, Time ¼ 0.0, RF ¼ 1.0% X/H ¼ 0.4, 0.6, 0.8, 1.0
E Curing time of reinforced layer RCKD ¼ 6%, U/H ¼ 0.3, RF ¼ 0.75%, X/H ¼ 0.6 Time ¼ 0.0, 7, 14, 21 days
RCKD ¼ 9%, U/H ¼ 0.3, RF ¼ 0.75%, X/H ¼ 0.6 Time ¼ 0.0, 7, 14, 21 days

raining process continued until the required height behind the represented by a non-dimensional parameter called the bearing
sheet pile wall (active zone) was achieved. The fiber-reinforced capacity ratio (BCR) and described as.
cemented sand was also prepared as explained previously. At a
maximum dry density (gd max ¼ 16.90 kN/m3, as calculated from
quðfiberÞ
BCR ¼ (4)
compaction test), the quantity of fiber-reinforced cemented sand quðnofiberÞ
for the required thickness layer was deposited in the active zone.
The reinforced layer was compacted to reach the required layer where qu (fiber) and qu (no fiber) ¼ ultimate bearing capacities of the
thickness by using a flat bottom hammer (0.1 m  0.1 m, weighting footing on fiber reinforced and unreinforced cemented active zone,
20 N). As shown in Fig. 1, after preparing the reinforced layer, the respectively.
surface was leveled, and the footing was placed in the desired Another factor to consider the settlement characteristics of the
position. The guiding wooden box remained in place (passive zone) system is the “deformability index” is proposed and defined to
until the model was fully prepared. Then, the supporting wooden describe the ductility of fiber-reinforced cemented sand layer as
box was removed. Two dial gauges were placed at equal distance follows:
from the edges of the hydraulic jack. Finally, after the wooden box
was removed, LVDT'S were placed to measure the lateral deflection SðfiberÞ
DI ¼ (5)
of the sheet pile wall (see Fig. 1). The footing was loaded statically SðnofiberÞ
using the hydraulic jack and the average vertical displacements
measured by gauges were taken. The lateral deflection of the sheet where S(fiber) and S(no-fiber) ¼ vertical surface settlement obtained at
pile wall at each load was recorded. the ultimate bearing capacity conditions for fiber reinforced and
unreinforced cemented sand in the active zone, respectively.

2.9. Test program


3.1. Effect of cement kiln dust inclusion on the behavior of strip
footing
A total of 47 tests were conducted to study the effect of fiber-
reinforced cemented sand in the active zone on the behavior of
Since the primary objective of the experimental investigation is
strip footing and sheet pile wall. First, the response of the model
to evaluate the effect of fiber-reinforced cemented sand in
footing constructed on the unreinforced active zone (without fiber
improving the load carrying capacity of the strip footing adjacent to
reinforcement) was studied at different CKD ratios to obtain the
necessary reference data for the purpose of comparing on (series A).
Then, four series of tests (from B to E) were performed to study the
effects of different parameters on the strip footing and the sheet
pile wall behavior. Each series was conducted to study the response
of one parameter while the other variables were remaining con-
stant. Table 3 shows the details of the parametric study.

3. Interpretation and discussion of results

The footing pressure-settlement curves were obtained from the


results of the experimental model strip footing tests on the active
zone of sheet pile wall. The ultimate bearing capacities for the
model footing were determined from the footing pressure-
settlement curves as the pronounced peaks and after which the
footing collapsed. In curves that did not exhibit a definite failure
point, the ultimate bearing capacity was taken as the point at which
the slope of the footing pressure-settlement curve first reaches zero
or reaches a steady minimum value (Vesic, 1973). In order to
evaluate the fiber reinforcement effects, the bearing capacity Fig. 2. Variation of footing stress q with settlement for different RCKD (unreinforced
improvement of footing on fiber-reinforced cemented sand is case).
A.M. Nasr / Geotextiles and Geomembranes 42 (2014) 599e610 603

Fig. 3. Variation of q with settlement for physical model strip footing with different RF (reinforced case).

a sheet pile wall; it is convenient to present the results of the sand layer had 3%, 6%, 9%, and 12% (by weight of dry soil) of CKD
footing on cemented sand without any reinforcement (unrein- ratio, having ultimate bearing capacities, qu, of 150, 191, 239, and
forced case). Initially the tests were conducted with strip footing 265 kPa, respectively. It is probably for the following reason: the
placed on the top of the unreinforced cemented sand layer pre- additional of cement kiln dust binds sand particles together and
pared at maximum dry density and optimum moisture content. The makes the matrix more compacted, and thus restricts the rear-
tests were carried out by keeping the footing distance from the rangement of particles and increases the effective contact area.
sheet pile wall X/H ¼ 0.6 and thickness of cemented layer U/H ¼ 0.3 Furthermore, the cement kiln dust provides tensile strength capa-
constants (series A). Typical footing stressesettlement curves for bility, which will increase cohesion values.
four different CKD ratios are presented in Fig. 2. It can be observed In all tests, general shear failures happened as expected in the
from Fig. 2 that the CKD ratio (RCKD) has a great effect on the ulti- compacted cemented sand layer and load dropped after failure.
mate bearing capacity of the strip footing. The ultimate bearing Vertical settlement values at failure (Sf) increased as CKD increased
capacity increases with an increase in CKD ratio. The cemented until 9%. At 12% CKD ratio, the vertical settlement at failure is
9.25 mm, which is smaller than that at 6% and 9% CKD ratios. Thus,
at 12% CKD ratio, the cemented sand layer exhibited a more brittle
Table 4 behavior.
Summary of the results for fiber-reinforced cemented sand in active zone tests
(Series B).

RCKD RF, qu, Settlement Max. Lateral deflection BCR DI 3.2. Effect of fiber ratio on the behavior of strip footing
(%) (%) (kPa) at Peak, (mm) at peak, (mm)

3 0.25 167 9.73 6.53 1.11 1.12 In this series of tests, the effect of fiber inclusion on cemented
0.50 198 10.40 4.50 1.32 1.20 sand was investigated. The tests were carried out using four
0.75 234 10.83 3.80 1.56 1.25 different percentages of fiber ratios 0.25%, 0.5%, 0.75%, and 1.0%
1.00 259 11.28 3.53 1.73 1.29 (series B). Fig. 3 shows the behavior of the strip footing on the top of
6 0.25 219 12.75 5.20 1.15 1.25
0.50 285 14.28 3.83 1.49 1.40
fiber-reinforced cemented sand and adjacent to the sheet pile wall.
0.75 323 15.96 3.17 1.69 1.56 A summary of the test results is given in Table 4. It is readily
1.00 349 16.55 2.97 1.83 1.62 observed that fiber reinforcement improves the footing-settlement
9 0.25 295 12.50 3.96 1.23 1.14 behavior. In other words, at any CKD content, footing supported on
0.50 391 14.00 3.26 1.64 1.27
fiber-reinforced cemented sand provided considerable higher ul-
0.75 471 15.35 2.83 1.97 1.40
1.00 520 16.93 2.59 2.17 1.54 timate loads than the corresponding cemented sand only without
12 0.25 342 11.17 3.35 1.29 1.21 fiber reinforcement. This can be attributed to both the internal
0.50 463 12.19 2.75 1.75 1.31 friction angle and cohesion intercept increase when fiber was
0.75 575 14.79 2.56 2.17 1.60 added (Amir and Mahdi, 2013). The addition of fiber to cemented
1.00 655 16.34 2.47 2.47 1.77
sand produces bonding and friction between the soil and the fibers.
604 A.M. Nasr / Geotextiles and Geomembranes 42 (2014) 599e610

Fig. 4. Variation of BCR and DI with fiber ratio for different CKD ratios.

Amir and Mahdi (2013) stated that, at 1.0% polypropylene fibers, the reinforcement benefit than that in cemented sand without fiber
internal friction angle of cemented sand increased from 39 to 41.5 reinforcement.
for 50% relative density. Furthermore, the failure of the fiber rein- The variations of bearing capacity ratio, BCR (Eq. (4)), and
forced cemented sand occurred due to slippage between the sand deformability index, DI (Eq. (5)), with fiber ratio are shown in Fig. 4
particles and the fibers. For cemented sand, the use of fiber seems for different CKD ratios. From Fig. 4-A, it is evident that at any CKD
to produce a strong frictional interaction between the fibers and ratio, the fiber ratio has a significant effect on BCR. The bearing
the sand particles. capacity ratio increases with increasing fiber ratio. It is clear that
Upon comparison with unreinforced cemented sand (RF ¼ 0.0%), the effect of the CKD ratio on BCR is minimized when the footing is
it can be seen that the inclusion of fibers within the cemented sand placed on reinforced sand with RF ¼ 0.25%. At RF ¼ 0.25%, the BCR
reduces the brittleness of the response. The vertical settlement at increased by about 16% when the CKD ratio increased from 3% to
failure increased with increasing in fiber ratio. It is clear that at 12%. On the contrary, at RF ¼ 1.0%, the BCR increased by about 42%
RCKD ¼ 3%, the footing stressesettlement curves at different fiber and the effect of the CKD ratio on BCR is more pronounced.
contents did not exhibit a peak point (failure point). This result Furthermore, Fig. 4-A shows that at any fiber ratio the BCR of a
indicates that the addition of fiber delay failure and mitigates the footing on a fiber-reinforced cemented sand is considerably higher
brittle behavior. The above results are in good agreement with the than that of a footing on an unreinforced cemented sand where BCR
findings of Consoli et al. (1998, 2004). In case of fiber-reinforced is greater than 1.0 (BCR > 1.0). Thus, reflecting the beneficial effect
cemented sand, RCKD ¼ 9% and 12%, the footing stress increases of fiber reinforcement in improving the bearing capacity of footing
with an increase in vertical settlement until the peak value is in active zone adjacent to the sheet pile wall.
reached, followed by reduction of post-peak stress gradually. Un- Fig. 4-B illustrates the variation of deformability index DI (Eq.
doubtedly, one of the main advantages of fiber reinforcement when (5)) with fiber ratio for different CKD ratios. The results clearly
applied to soil is the improvement in material ductility. The above- indicate that the DI increases with increasing the fiber ratio. The
mentioned behavior of fiber-reinforced cemented sand explains value of DI increases from 1.12 to 1.77, as the fiber ratio increases
why the fiber in cemented stabilized sand shows higher from 0.25% to 1.0%. However, at low levels of the fiber ratio
(RF  0.5%), DI was weakly influenced by the cement kiln dust ratio.
The deformability index can be applied to evaluate the ductility or
deformability of cemented sand that is reinforced by various fibers.
This index may indicate the degree of fiber extensibility in
cemented sand and aid in the selection of suitable fibers for a given
cementation. In the case of RCKD ¼ 3%, the variation of DI with fiber
ratios was minimal.
The main observation of the results of the experimental work
was the deformation of the sheet pile wall. From Table 4, the var-
iations of the maximum lateral deflection of the sheet pile wall at
ultimate bearing capacity with fiber ratio at four different CKD ra-
tios are presented. The results indicate that the fiber ratio, RF, has a
major influence on the maximum lateral deflection of the sheet pile
wall. Increasing the fiber ratio, RF, decreases the maximum lateral
deflection at peak stress. At cement kiln dust ratio, RCKD ¼ 9%, the
maximum lateral deflection decreased by about 51% and 55% at
fiber ratio of 0.75% and 1.0%, respectively. It can be concluded that
by using fiber ratio, RF ¼ 0.75%, polypropylene fiber reinforcement
provided a beneficial reduction in the lateral behavior of the sheet
pile wall adjacent strip footing. It is clear that the decrease in the
maximum lateral deflection values was reduced significantly when
the RF ratio was increased to 0.75%. At the same time, increasing the
CKD ratio decreases the maximum lateral deflection of the sheet
Fig. 5. Lateral deflection along the sheet pile wall at different fiber ratios. pile wall at peak stress. From the LVDT readings along the free
A.M. Nasr / Geotextiles and Geomembranes 42 (2014) 599e610 605

length of the sheet pile wall, Fig. 5 shows the lateral deflection
along the sheet pile wall at different fiber ratios. The CKD ratio was
kept constant at 9%. The figure demonstrates that increasing the
fiber ratio not only decreases the maximum lateral deflection at the
ground surface, but also decreases the lateral deflection along the
length of the sheet pile wall. At the end of a fiber-reinforced
cemented sand layer, the lateral deflection decreased by about
65% when the fiber ratio increased from 0.25% to 1.0%.

3.3. Effect of thickness of fiber-reinforced cemented sand layer

The variation of ultimate bearing capacity, qu, with the thickness


of the fiber-reinforced cemented sand layer, U/H, is shown in Fig. 6.
From the aforementioned figure, it is found that the value of qu
depends markedly on the thickness of the fiber-reinforced
cemented sand layer. It is clear that increasing the thickness of
the reinforced layer will increase the ultimate bearing capacity, qu.
For the three RF ratios used in this series of tests, most of the in-
crease in the qu takes place between U/H ratios of 0.1 and 0.4. After
that, for higher fiber ratios (RF  0.75%) and at U/H ¼ 0.5, the in-
crease in qu is not significant, and the effect of fiber reinforcement Fig. 7. Lateral deflection along the sheet pile wall at different U/H ratios.
on qu was diminished. This can be attributed to shearing resistance
and cohesion between sand particles (Amir and Mahdi, 2013)
caused by the fiber reinforcement in the upper cemented sand was the most affected zone by lateral deflection. In contrast, when
layer, which intersects the collapse mechanism (shear zone resis- the thickness of the fiber-reinforced layer increased to 0.4 and 0.5,
tance) of the soil under the footing. At the same time, by increasing the top lateral deflection decreased significantly. It is also of interest
U/H, the area of the fiber-reinforced cemented sand that has greater to note that the increase of the thickness of reinforcement layers to
shear strength increased under the footing. However, at RF ¼ 0.75% U/H ¼ 0.5 tends to cause a shift of the maximum lateral deflection
and 1.0%, it is clear that using fiber-reinforced cemented sand layer from the top of the sheet pile to a deeper depth along the sheet pile
with thickness U/H ¼ 0.4 is more effective than that at U/H < 0.4 in wall.
increasing the ultimate bearing capacity of the strip footing adja-
cent to the sheet pile wall. For example, at U/H ¼ 0.4 and fiber
3.4. Effect of footing location relative to the sheet pile wall
ratio ¼ 0.75%, the ultimate bearing capacity increased by about
121% than that at U/H ¼ 0.1.
A series of tests was performed to study the effect of strip
To investigate the effect of U/H on the lateral deflection along the
footing location behind and parallel with the cantilever sheet pile
sheet pile wall, the LVDT readings were recorded, as shown in Fig. 7.
wall. The variations of ultimate bearing capacity, qu, and maximum
The increase in the thickness of the fiber-reinforced cemented sand
lateral deflection at different footing locations are shown in Fig. 8A-
layer decreased the lateral deflection along the sheet pile wall.
B, respectively. From Fig. 8-A, the results clearly indicate that at any
Furthermore, the results in Fig. 7 clarify that the lateral deflection
fiber ratio, the ultimate bearing capacity, qu, of the strip footing
values and the lateral deflection shape along the sheet pile wall
adjacent to a sheet pile wall increases with increasing distance
strongly depend on the thickness of the reinforced layer. As the
between the footing and the sheet pile wall. This clearly indicates
lateral deflection is the main cause of failure of sheet pile walls
the adverse effect of sheet pile wall on footing behavior. Further-
(Georgiadis and Anagnostopoulos, 1998), using fiber reinforcement
more, at any X/H ratio, the qu increase considerably due to reflecting
can improve the overall behavior of a sheet pile wall. It was evident
the beneficial effect of fiber reinforcement in improving the
that in the case of U/H ¼ 0.1, 0.2, and 0.3, the top of the sheet pile
behavior of the strip footing adjacent to the sheet pile wall. Also, for
fiber ratios of 0.75% and 1.0%, most of the increase in the qu takes
place between X/H ratios of 0.4 and 0.8. After that, if X/H is more
than 0.8 there is no appreciable increase in the ultimate bearing
capacity of the footing (about 4.8%).
Strip footing supported by a uniform backfill soil and subjected
to a central vertical loading will undergo lateral displacement only
when their lateral supports are not equal on both sides. When a
footing is nearby a wall, the lateral support provided by the wall
may be smaller or greater than that on the other side depending on
the footing location and wall stiffness. The variation of maximum
lateral deflection of sheet pile wall with different X/H ratios is
presented in Fig. 8-B. From Fig. 8-B, the maximum lateral deflection
decreases with increasing X/H for any fiber ratio. Markedly, for
fiber-reinforced active zone and at X/H ¼ 0.8, the maximum lateral
deflection decreased relative to the case of X/H ¼ 0.4 by about 52%,
54%, and 47% for fiber ratios of 0.5%, 0.75%, and 1.0%, respectively.
However, the rate of decrease of maximum lateral deflection
decreased with increasing X/H ratio to 1.0. At X/H ¼ 1.0, the effect of
Fig. 6. Variation of ultimate bearing capacity qU with U/H at different fiber ratios. fiber ratio in reducing the maximum lateral deflection of the sheet
606 A.M. Nasr / Geotextiles and Geomembranes 42 (2014) 599e610

Fig. 8. Variation of ultimate bearing capacity and maximum lateral deflection with X/H at different fiber ratios.

pile wall can be neglected. The above results agree with the findings 4. Finite-element analysis
of Nasr and Nazir (2013).
A series of two-dimensional (2D) finite element analyses (FEAS)
on a model-scale strip footing and sheet pile wall system was
3.5. Effect of curing time on the behavior of strip footing performed to supplement the results of the model laboratory tests.
The dimensions of strip footing and sheet pile wall modeled in the
Obviously, when CKD-mixed with sand, the cemented sand will FEAS are similar to the dimensions used in the experimental model.
continue to improve with time (like concrete). Therefore, a series of Plane strain elasto-plastic FEAS were performed using the com-
tests were conducted to study the effect of curing time on the mercial program PLAXIS 7.2 (Bringkgreve and Vermeer, 1998). Note
bearing capacity of the strip footing resting on fiber-reinforced that the FE model was assumed to be constructed using the same
cemented sand layer. The fiber ratio was kept constant at 0.75% materials used in the laboratory tests. The dimensions of the mesh
and two different CKD ratios of 6% and 9% were used (series E). size were chosen large enough to ensure that the boundaries will
Ultimate bearing capacity, qu, is plotted against curing time in Fig. 9. have no effect on the calculated results (width of mesh ¼ 15B, and
The results clearly indicate that, for both CKD ratios, the ultimate height of mesh ¼ 8.5B). The analyzed strip footing, sheet pile ge-
bearing capacity increases with increasing curing time. This is ex- ometry, and generated mesh are shown in Fig. 10.
pected since fiber-reinforced cemented sand mixture requires time
to gain strength (Sulapha et al., 2008). Also, it can be seen that the
4.1. Finite element modeling
value of qu rapidly increased at the beginning of the curing time
(Tang et al., 2007). It is clear from the above figure that the greatest
A variety of soil models are built into the computer code chosen
rate of strength gain occurs within the first 14 days. For example, at
for this study. However, it was decided to use the non-linear
6% CKD ratio, the ultimate bearing capacity, qu, at 21 days is 1.46
MohreCoulomb criteria to model the sand for its simplicity, prac-
times the qu after 7 days of curing, and 1.07 times after 14 days of
tical importance and the availability of the parameters needed. The
curing. At 9% CKD ratio, the qu at 21 days is 1.36 times the qu after 7
MohreCoulomb soil model parameters used in the FEAs were
days of curing, and 1.1 times after 14 days of curing. This can be
derived from a series of laboratory tests as shown in the reduced
attributed to higher fineness and the surface area of CKD. The same
scale laboratory model. For pure sand, an internal friction angle (Ø)
results were obtained by Miller and Azad (2000). Therefore, sig-
of 36 and a dilatancy angle (j) of 6 were used, where j ¼ Ø  30 .
nificant increases in qu occurred with increases in the CKD ratio in
For fiber reinforced-cemented sand, the results of material tests
reinforced layer at different curing times.
which used in the FE analysis are reported in Table 5. The analyses
were carried out for draining condition without pore water pres-
sure and the FE calculations for soil elements were based on 15-
node triangular elements. From the Plaxis manual, to avoid com-
plications during a numerical process, enter at least a small value
for cohesion (c > 0.2 kPa), but its effect on the resulting collapse
load values is negligible (less than 0.1%). Therefore, the cohesion in
all calculation process was taken 1.0 kPa. Table 5 summarizes the
parameters used in the analysis.
The linear elastic behavior of the sheet pile wall and the footing
were modeled as plate elements. Plates in the 2D finite element
model are composed of beam elements with three degrees of
freedom per node. When 15-node soil elements are employed then
each beam element is defined by 5-nodes. The beam elements are
based on Mindlin's plate theory. This theory allows for beam de-
flections due to shearing as well as bending. For the modeling of
elastic plates, an axial stiffness, EA, and a flexural rigidity, EI, must
be specified as material properties (Table 5).
The interaction between the sheet pile wall, footing, and the
Fig. 9. Variation of ultimate bearing capacity qU with curing time for different CKD surrounding soil was simulated by interface elements located at the
ratios. contact between any two elements. The interface elements, which
A.M. Nasr / Geotextiles and Geomembranes 42 (2014) 599e610 607

Fig. 10. Mesh used in the finite-element analysis.

Table 5
Material parameters used in the finite element analysis.

Parameter Pure sand Fiber-R.C. sand Footing Sheet pile

Material model MohreCoulomb model MohreCoulomb model Linear elastic Linear elastic
Type of material behavior Drained Drained Non-porous Non-porous
ref
Primary loading stiffness, E50 (kPa) 30,000 35,000 21  107 21  107
Poisson's ratio, n 0.30 0.30 0.20 0.2
Cohesion, c (kPa ) 1.00 (45, 66, 92, 145, 203)* e e
Friction angle, Ø ( ) 36 (39, 41, 42.5, 44.6, 45)* e e
Dilatancy angle, j ( ) 6 (9, 11, 12.5, 14.6, 15) e e
Interface reduction factor, Rint 0.75 0.75 e e
Failure ratio, Rf 0.90 0.90 e e
Axial stiffness, EA (kN/m) e e 420,000 2.1  106
Flexural stiffness, EI (kPa/m) e e 14 0.629

( )*Results from triaxial tests at RCKD ¼ 9% and RF varied from 0.0 to 1.0%.
( )*Tests were conducted at max. dry density and optimum moisture content.

have zero physical thickness, were connected to soil elements by that the difference in the ultimate bearing capacity calculated from
five pairs of nodes. The stiffness matrix of interface elements was finite element method and that calculated from experimental tests
obtained using Newton-Cotes integration points. The interface was about 5% and 14% at fiber ratio 0.75% and 0.25%, respectively. It
parameters were simulated in PLAXIS by assigning a suitable value is also clear that by increasing the fiber ratio, the behavior of the
(as stated in program manual) for the strength reduction factor in strip footing at failure was more ductile. For practical purposes, the
the interface compared with the corresponding soil strengths.
The modeled boundary conditions were assumed to fix parts of
the model in the directions of X and Y. All the boundary conditions
assumed in the physical model were simulated in the FE model.
Therefore, the vertical geometry lines of the model were con-
strained horizontally (ux ¼ 0.0), and the horizontal bottom line was
constrained in both the horizontal and vertical directions
(ux ¼ uy ¼ 0.0). The load was applied uniformly on the footing
(beam element) by using the distributed load option.

4.2. Results of finite-element analysis

The results of the finite-element analyses are shown in


Figs. 11e14. In these series, all the tests were performed on the
footing placed at U/H ¼ 0.3 and a CKD ratio of 9%, while the fiber
ratio, RF, and footing distance from the sheet pile wall, X/H, were
varied. Fig. 11 shows the variations of footing stress with a footing
settlement for different fiber ratios. The figure clearly shows that by
increasing the fiber ratio, much has improved for both the initial
stiffness (initial slope of the load-settlement curve) and the ulti-
mate bearing capacity of the footing. The above results agree with Fig. 11. Variation of q with settlement for FE model sheet pile wall with different fiber
the experimental results in terms of the fiber ratio. It was evident ratios.
608 A.M. Nasr / Geotextiles and Geomembranes 42 (2014) 599e610

Fig. 12. Comparison of BCR and DI with various fiber ratios as obtained from the physical model and FEAs.

optimum value of fiber ratio, was RF ¼ 0.75%, whereas the increase numerical analyses such as modulus of elasticity and the method
in the ultimate bearing capacity between RF ¼ 0.75 and RF ¼ 1.0 did used to model the soil in the analysis. The maximum difference in
not exceed 10%. qu between experimental and numerical results was about 10% at X/
The BCRS with different RF were calculated by using the FEAS H ¼ 1.0. Based on the results of the FEAS, the distribution of
(model scale) and compared with the results obtained from model displacement vectors and contours of the deformation in the active
experimental tests as shown in Fig. 12-A. The finite element results zone under the footing and behind the sheet pile wall is shown in
provide a reasonable fit with the experimental data (BCR obtained Fig. 14 at different X/H ratios. At X/H  0.6, it is clear from Fig. 14 that
from the FEA was defined in the same way as defined in the model the displacement vectors under the footing moved horizontally in
tests). The BCR increases with the increase of the fiber ratio, RF, for the direction of the sheet pile wall. The maximum lateral deflection
both experimental and numerical results. Although, the BCR ob- occurred at the top of the sheet pile and vanished at about 80% of
tained from the FEA appears to be smaller than that for model scale the sheet pile length. When the footings are not far behind the
footing, the maximum difference in BCR between experimental sheet pile walls, the lateral supports under the footing are not equal
results and FEAS was about 14% at RF ¼ 1.0. Fig. 12-B shows the on both sides. Furthermore, the footings and the sheet pile walls
variation of DI with various RF obtained from model tests and FEAS. may interact resulting in an adverse effect on the stability of the
This figure demonstrated that the results obtained from the footings and the walls. When the footing is located farther away at
experimental tests are in close agreement with those from the X/H  0.8 behind the wall, the displacement vectors shown in
finite-element method. It is clear also that at RF ¼ 1.0%, the Fig. 14 also skew toward the sheet pile wall, but the most of
maximum difference in DI between experimental results and FEA displacement vectors do not reach the wall. At different X/H ratios,
was 11.6%. However, the finite element analyses showed that the the difference in the lateral movement of the sheet pile wall be-
rate of the increase in DI reduces with increasing the RF to 1.0. comes more evident in the vector plots which decrease as X/H in-
Comparison between experimental and numerical results for crease. Furthermore, Fig. 14 shows that the shape of the contours of
ultimate bearing capacity, qu, at different X/H ratios can be seen in the deformation along the sheet pile wall and under the footing is
Fig. 13. Finite element results also indicate that the ultimate bearing changed relative to the footing location. At X/H  0.8, the de-
capacity of the strip footing increases with increasing distance formations are concentrated under the footing and approximately
between footing and sheet pile wall, X/H. As can be seen, the results distributed equally on both sides. This helps to explain that, when
are similar to experimental values. It is observed that the experi- X/H  0.8, there is no appreciable increase in the ultimate bearing
mental results curve is above the curve from the numerical capacity of the footing.
modeling. This can be attributed to the soil parameters used in the

5. Scale effects and limitations

Physical models have been commonly used to study bearing


capacity and settlement behavior of foundations because of the
difficulties associated with loading full-scale prototypes to failure.
However, as in all reduced-scale physical model tests, scaling ef-
fects must be minimized to ensure that the behavior observed on a
reduced scale can be extrapolated to prototype behavior (Muir
Wood, 2004). For reduced-scale models, the particle size and
density of sand, construction techniques, boundary conditions,
reinforcement stiffness, and dilatancy at low stress are the impor-
tant factors to be considered.
Considering the model footing size and the scale factor effect,
relatively fine-grained sand (D50 ¼ 0.3 mm) was used for tests.
Habib (1974) stated that the particle size effect has a negligible
effect on bearing capacity at B/D50 ratio less than 200, and no effect
at B/D50 values greater than 200. Kusakabe (1995) summarized test
Fig. 13. Comparing Plaxis and laboratory test results of ultimate bearing capacity at data and indicated that the particle size effect on the test results
various X/H ratios. becomes less marked for a D50/B ratio smaller than 0.01. In this
A.M. Nasr / Geotextiles and Geomembranes 42 (2014) 599e610 609

Fig. 14. Displacement vectors and contours of the deformation at various X/H ratios.

study, the effect of the particle size should be smaller, as the D50/B scale and centrifugal tests must be conducted to increase under-
ratio used in the model was 0.003. Furthermore, according to Amy standing of the real behavior and accurate design in the application
and Alan (2007), the model-scale test must be performed on sand of fiber reinforced sand.
that is looser than the sand underneath a full-scale test. Therefore,
all model tests were conducted on sand with relative density 50%. 6. Conclusions
To satisfy the plane strain conditions (Ko and Davidson, 1973),
first, the friction between soil and the front and back internal sur- The interaction behavior between strip footing resting on fiber-
faces of the tank should be zero. Balachandran (1996) stated that reinforced cemented sand in the active zone and the cantilever
the peak friction angle between sand and treated surfaces de- sheet pile wall was investigated through physical model tests and
creases by about 65% relative to the case of untreated surfaces. two-dimensional non-linear FE analyses. The results obtained from
Therefore, the inside walls were polished smooth and coated with model test studies and numerical analyses were compared. Based
lubricating oil in order to reduce friction as much as possible. on the investigations the following main conclusions can be drawn:
Second, deformation in longitudinal direction should be zero. This
implies that plane strain models should have rigid front and back 1 The addition of cement kiln dust, CKD, improves greatly the
planes. Therefore, the deformations of the test tank in longitudinal ultimate bearing capacity of the strip footing resting on fiber-
direction were reduced, whereas the vertical sides were strength- reinforced and unreinforced sand in the active zone. The rate
ened by using steel angles in the middle and the top of the sides. In of ultimate bearing capacity gain, increased with the increase in
all reduced-scale model tests, relatively wide tanks are used. The the fiber ratio, RF, of the reinforced cemented sand for the whole
length of the tank was about 15 times the footing width, and the range of cement kiln dust studied.
soil layer thickness under the footing was more than 8 times the 2 In physical model results and FE analyses, the addition of poly-
footing width. According to the tank dimensions, it may be seen propylene fibers to the cemented sand increases the deform-
there is sufficient space for the development of active and passive ability index, DI, which represents the ductility. At the lowest
wedges as established from the series of FE analyses. Therefore, the level of the fiber ratio (RF  0.5%), DI was weakly influenced by
boundary conditions do not have any significant effect on the re- the cement kiln dust ratio.
sults (Bransby and Smith, 1975). 3 The fiber insertion in the cemented sand behind the sheet pile
To simulate the fiber reinforcement in the model tests, proto- wall has a significant effect in decreasing the lateral deflection
type short fiber with small diameter was preferred for use. There- along the sheet pile wall. At cement kiln dust ratio, RCKD ¼ 9%,
fore, the results from the reduced-scale model may be not the maximum lateral deflection decreased by about 51% at fiber
influenced. The difference in the stress level between the model ratio of 0.75%.
tests and the field tests was the imperative factor invalidating the 4 The ultimate bearing capacity of the strip footing on fiber-
use of small-scale models, which have been constructed in sand reinforced cemented sand in the active zone increases with an
and tested at 1-g, for the accurate determination of deformation increase in the thickness of reinforced sand layer. However, for
behavior. The stress level under the footing in a small-scale model higher fiber ratios (RF  0.75%), at a thickness of fiber-reinforced
is much smaller than that under the footing in the field. This low cemented sand layer greater than U/H ¼ 0.4, the increase in
stress in granular soil corresponds to a greater angle of internal ultimate bearing capacity is not significant.
friction than that at higher stress level. In consequence, the results 5 Increasing the distance between the strip footing and the sheet
of reduced-scale models should be used with extreme caution. pile wall, X/H, leads to a significant increase in the ultimate
Some components of the physical model verified in this study bearing capacity of the footing and a decrease in the maximum
are reduced to a certain scale and therefore, does not relate to lateral deflection of the sheet pile wall. This clearly indicates the
prototype footing-sheet pile wall systems faced in the field. adverse effect of the interaction between footing and sheet pile
Nevertheless, the goals of this study are to expose the reflection of wall. However, the experimental and numerical results at a
using fiber reinforcement in the active zone behind the sheet pile higher fiber ratio (RF  0.75%) showed that if X/H is more than
wall. The study indicated the benefits for the overall behavior of 0.8 there is no appreciable increase in the ultimate bearing ca-
strip footing and sheet pile wall that can be achieved when using pacity of the footing (about 4.8%). The above result allows a
fiber reinforcement in the active zone. However, it is important to guideline to be formulated for designers to inform them when
make clear that the results observed herein are relevant for the soil, they need to consider wallefoundation interaction.
CKD, and fiber type used in the present research and that further 6 There is close agreement between the experimental and nu-
studies are necessary to generalize such findings. Furthermore, full- merical results in term of the fiber ratio. However, the numerical
610 A.M. Nasr / Geotextiles and Geomembranes 42 (2014) 599e610

results show that the BCR has a significant decrease (about 14%) Falorca, I.M.C.F.G., Pinto, M.I.M., 2011. Effect of short randomly distributed poly-
propylene microfibers on shear strength behavior of soils. J. Geosynth. Int. 18
compared with the experimental model results.
(1), 2e11.
Georgiadis, M., Anagnostopoulos, C., 1998. Lateral pressure on sheet pile walls due
It should be noted that the results presented in this study are to strip load. J. Geotech. Geoenviron. Eng. 124 (1), 95e98.
related to model-scale footings on fiber-reinforced sand and are Ghanbari, A., Taheri, M., 2012. An analytical method for calculating active earth
pressure in reinforced retaining walls subject to a line surcharge. J. Geotext.
limited to these conditions. Caution should be used when applying Geomembr. 34, 1e10.
model-scale footing test results in the behavior of full-scale foun- Habib, P.A., 1974. Scale effect for shallow footings on dense sand. J. Geotech. Eng.
dations. Therefore, further tests using full-scale or a large models 100 (GT1), 95e99.
Ismail, M.A., 2005. Performance of cement-stabilized retaining walls. Can. Geotech.
are recommended. Furthermore, the effect of some other parame- J. 39, 876e891.
ters such as scale effect, backfill soil type, rigidity of the sheet pile Kamon, M., Nontananandh, S., 1991. Combining industrial wastes with lime for soil
wall, type of reinforcement, loading conditions, etc. have not been stabilization. J. Geotech. Eng. 117 (1), 1e17.
Ko, H., Davidson, W., 1973. Bearing capacity of footings in plane strain. J. Soil Mech.
investigated. Found. Div. ASCE 99 (1), 1e23.
Kusakabe, O., 1995. Foundations. In: Taylor, R.N. (Ed.), Geotechnical Centrifuge
References Technology. Blackie Academic and Professional, London.
Lovisa, J., Shukla, S.K., Sivakugan, N., 2010. Shear strength of randomly distributed
moist fibre-reinforced sand. J. Geosynth. Int. 17 (2), 100e106.
Ahmad, F., Bateni, F., Azmi, M., 2010. Performance evaluation of silty sand reinforced
Maher, M.H., Ho, Y.C., 1993. Behavior of fiber-reinforced cemented sand under static
with fibers. J. Geotext. Geomembr. 28 (1), 93e99.
and cyclic loads. Geotech. Test. J. 16 (3), 330e338.
Amir, H., Mahdi, H., 2013. Effect of fiber reinforcement on triaxial shear behavior of
Mckay, M., Emery, J., 1992. Stabilization/solidification of contaminated soils and
cement treated sand. J. Geotext. Geomembr. 36, 1e9.
sludges using cementitious systems. In: Proceedings of the Cement Industry
Amy, B., Alan, J., 2007. Scale effects of shallow foundation bearing capacity on
Solutions to Waste Management, 7e9 October. Calgary, Alberta, Canada,
granular material. J. Geotech. Geoenviron. Eng. 133 (10), 1192e1202.
pp. 135e151.
Asghari, E., Toll, D.G., Haeri, S.M., 2003. Triaxial behavior of a cemented gravely
Miller, G.A., Azad, M., 2000. Field and Laboratory Evaluation of Cement Kiln Dust as
sand, Tehran alluvium. Geotech. Geol. Eng. 21, 1e28.
a Soil Stabilizer, vol. 1714. Transportation Research Board, Washington, DC.
ASTM., 2010. Standard Practice for Classification of Soils for Engineering Purposes
Muir Wood, D., 2004. Geotechnical Modeling. Spon Press, London.
(Unified Soil Classification System). ASTM standard D2487. American Society for
Nasr, A.M., 2009. Use of discrete vertical reinforcement in active zone to improve
Testing and Materials, West Conshohocken, Pa.
the lateral response of the sheet pile wall. Alex. Eng. J. 48 (6), 743e759.
Balachandran, S.B., 1996. Modeling of Geosynthetic Reinforced Soil Walls. Ph.D.
Nasr, A.M., Nazir, A.K., 2013. Effect of geosynthetic reinforcement in active zone on
thesis. University of Cambridge, Cambridge, England.
the behavior of sheet pile walls. Geotech. Test. J. 36 (3), 331e344.
Bransby, P.L., Smith, I.A., 1975. Side friction in model retaining wall experiments.
Park, T., Tan, S.A., 2005. Enhanced performance of reinforced soil walls by the in-
J. Geotech. Eng. GT7, 615e632.
clusion of short fiber. J. Geotext. Geomembr. 23 (4), 348e361.
Bringkgreve, R., Vermeer, P., 1998. PLAXISdFinite Element Code for Soil and Rock
PCA, 2007. Report on Sustainable Manufacturing. Portland Cement Association,
Analysis, Version 7. Plaxis B. V., Netherlands.
Skokie, IL.
Chauhan, M.S., Mittal, S., Mohanty, B., 2008. Performance evaluation of silty sand
Ple, O., Le, T.N., 2012. Effect of polypropylene fiber-reinforcement on the mechanical
subgrade reinforced with fly ash and fiber. J. Geotext. Geomembr. 26 (5),
behavior of silty clay. J. Geotext. Geomembr. 32 (3), 111e116.
429e435.
Santos, E.C., Palmeira, E.M., Bathurst, R., 2013. Behavior of a geogrid reinforced wall
Conner, J.R., Cotton, S., Lear, P.R., 1992. Chemical stabilization of contaminated soils
built with recycled construction and demolition waste backfill on a collapsible
and sludges using cement and cement by products. In: Proceedings of the
foundation. J. Geotext. Geomembr. 39, 9e19.
Cement Industry Solutions to Waste Management, 7e9 October. Calgary,
Schnaid, F., Prietto, P.D.M., Consoli, N.C., 2001. Characterization of cemented sand in
Alberta, Canada, pp. 73e97.
triaxial compression. J. Geotech. Geoenviron. Eng. 127 (10), 857e867.
Consoli, N.C., Cruz, R.C., da Fonsea, A.V., Coop, M.R., 2012. Influence of cement-voids
Sulapha, P., Jan, O., Janet, L., 2008. Influence of chemical and physical characteristics
ratio on stress-dilatancy behavior of artificially cemented sand. J. Geosynth. Int.
of cement kiln dusts (CKDs) on their hydration behavior and potential suit-
138 (1), 100e109.
ability for soil stabilization. Cem. Concr. Res. J. 38, 803e815.
Consoli, N.C., Montardo, J.P., Donato, M., Prietto, D.M., 2004. Effect of material
Tang, C., Shi, B., Gao, W., Chen, W., Cai, Y., 2007. Strength and mechanical behavior of
properties on the behavior of sand-cement-fiber composites. Ground Improv. J.
short polypropylene fiber reinforced and cement stabilized clayey soil.
8 (2), 77e90.
J. Geotext. Geomembr. 25 (3), 194e202.
Consoli, N.C., Prietto, P.D.M., Ulbrich, L.A., 1998. Influence of fiber and cement
Vesic, A.S., 1973. Analysis of ultimate loads of shallow foundations. J. Soil Mech.
addition on behavior of sandy soil. J. Geotech. Geoenviron. Eng. 124 (12),
Found. Div. 94 (SM3), 661e688.
1211e1214.
Diambra, A., Ibraim, E., Muir Wood, D., Russell, A.R., 2010. Fiber reinforced sands:
experiments and modeling. J. Geotext. Geomembr. 28 (3), 238e250.

You might also like