You are on page 1of 5

WATER APPLICATION VALUE ENGINE

WATER SOLUTIONS

WATER APPLICATION VALUE ENGINE


WATER SOLUTIONS
WAVE Program Version: 1.77.774

Calculation Engine Version: 01.11.12.00

Database Version: 19.0

Project Name: 100 TPD Design


Case Name: Case 1
Customer:

Prepared by: Wave Tango


Company: DuPont
Country:

Date Created: February 11, 2021


Project Notes:

Case #: 1 of: 1
Case Notes: Case 1

Keywords:

Information provided is offered in good faith, but without guarantees. Users of such information assume all risk and liability and expressly
release DuPont de Nemours Inc. and its subsidiaries, officers and agents from any and all liability. Because use conditions and applicable
laws may differ from one location to another and may change with time, users of information set forth herein or generated during use of
WAVE are responsible for determining suitability of the information. Neither DuPont nor its subsidiaries assume any liability for results
obtained or damages incurred from the use of information provided and TO THE FULLEST EXTENT PERMITTED BY LAW, EXPRESSLY
DISCLAIM ALL WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE. Users will not export or re-export any information or technology received from DuPont or its subsidiaries, or the
direct products or designs based upon such information or technology in violation of the export-control or customs laws or regulations of
any country, including those of the United States of America. DuPontŒDuPont Oval Logo, and all products denoted with ® or Œare
WUDGHPDUNVRUUHJLVWHUHGWUDGHPDUNVRI'X3RQWRULWVDIILOLDWHV࣯&RS\ULJKW‹'X3RQW'2:(;ŒDOWEX MONOSPHEREŒ
DOWEX MARATHONŒDOWEX UPCOREŒare a trademark of The Dow Chemical Company used under license by DuPont.

WAVE Version: 1.77.774


Project Name: 100 TPD Design Case: Case 1 Created: 02/11/2021 Page 1 of 5
WATER APPLICATION VALUE ENGINE
WATER SOLUTIONS

RO Detailed Report
RO System Flow Diagram

# Description Flow TDS Pressure


(m³/h) (mg/L) (bar)
1 Raw Feed to RO System 14.0 35,983 0.0
2 Net Feed to Pass 1 14.0 36,069 54.1
4 Total Concentrate from Pass 1 9.78 51,459 53.4
6 Net Product from RO System 4.20 128.9 0.0

RO System Overview
Total # of Trains 1 Online = 1 Standby = 0 RO Recovery 30.0 %
System Flow Rate (m³/h) Net Feed = 14.0 Net Product = 4.20

Pass Pass 1
Stream Name Seawater - Standard Reference
Water Type Sea Water (With conventional
pretreatment, SDI < 5)
Number of Elements 6
Total Active Area (m²) 245
Feed Flow per Pass (m³/h) 14.0
&ĞĞĚd^࣊ (mg/L) 36,069
Feed Pressure (bar) 54.1
Flow Factor 0.75
Permeate Flow per Pass (m³/h) 4.20
Pass Average flux (LMH) 17.1
WĞƌŵĞĂƚĞd^࣊ (mg/L) 128.9
Pass Recovery 30.0 %
Average NDP (bar) 22.5
Specific Energy (kWh/m³) 6.28
Temperature (°C) 25.0
pH 8.3 (After Adjustment)
Chemical Dose -
RO System Recovery 30.0 %
Net RO System Recovery 30.0%
Footnotes:
࣊dŽƚĂůŝƐƐŽůǀĞĚ^ŽůŝĚƐŝŶĐůƵĚĞƐŝŽŶƐ͕^ŝKЇand B(OH)Ј͘It does not include NHЈand COЇ

WAVE Version: 1.77.774


Project Name: 100 TPD Design Case: Case 1 Created: 02/11/2021 Page 2 of 5
WATER APPLICATION VALUE ENGINE
WATER SOLUTIONS

RO Flow Table (Stage Level) - Pass 1


Feed Concentrate Permeate
Stage Elements #PV #Els Feed Recirc Feed Boost Conc Conc Press Perm Avg Flux Perm Perm
per Flow Flow Press Press Flow Press Drop Flow Press TDS
PV
PV (m³/h) (m³/h) (bar) (bar) (m³/h) (bar) (bar) (m³/h) (LMH) (bar) (mg/L)
1 SW30HRLE-440 2 3 14.0 0.00 53.8 0.0 9.78 53.4 0.5 4.20 17.1 0.0 128.9

RO Solute Concentrations - Pass 1


Concentrations (mg/L as ion)
Concentrat Permeate
e
Feed Stage1 Stage1 Total

NHЉЀ 0.00 0.00 0.00 0.00


KЀ 408.5 583.9 1.94 1.94
NaЀ 11,034 15,777 45.15 45.15
MgЀ² 1,314 1,880 1.24 1.24
CaЀ² 421.7 603.6 0.39 0.39
SrЀ² 8.14 11.64 0.01 0.01
BaЀ² 0.00 0.00 0.00 0.00
COЈЁ² 23.07 34.24 0.00 0.00
HCOЈЁ 98.93 139.9 0.62 0.62
NOЈЁ 0.00 0.00 0.00 0.00
FЁ 1.33 1.90 0.01 0.01
ClЁ 19,802 28,318 74.39 74.39
BrЁ¹ 68.85 98.41 0.39 0.39
SOЉЁ² 2,775 3,973 1.05 1.05
POЉЁ³ 0.00 0.00 0.00 0.00
SiOЇ 1.00 1.42 0.01 0.01
Boron 4.58 6.29 0.64 0.64
COЇ 69.13 98.86 0.65 0.65
d^࣊ 35,983 51,459 128.9 128.9
pH 8.3 8.2 6.6 6.6
Footnotes:
࣊dŽƚĂůŝƐƐŽůǀĞĚ^ŽůŝĚƐŝŶĐůƵĚĞƐŝŽŶƐ͕^ŝKЇand B(OH)Ј͘It does not include NHЈand COЇ

RO Design Warnings

None

Special Comments
None

RO Flow Table (Element Level) - Pass 1


Stage Element Element Name Recovery Feed Flow Feed Press Feed TDS Conc Flow Perm Flow Perm Flux Perm TDS
(%) (m³/h) (bar) (mg/L) (m³/h) (m³/h) (LMH) (mg/L)
1 1 SW30HRLE-440 12.2 6.98 53.8 36,065 6.15 0.85 20.9 95.47
1 2 SW30HRLE-440 11.4 6.13 53.6 41,050 5.46 0.70 17.1 129.4
1 3 SW30HRLE-440 10.1 5.44 53.5 46,288 4.90 0.55 13.4 179.6

WAVE Version: 1.77.774


Project Name: 100 TPD Design Case: Case 1 Created: 02/11/2021 Page 3 of 5
WATER APPLICATION VALUE ENGINE
WATER SOLUTIONS

Footnotes:
࣊dŽƚĂůŝƐƐŽůǀĞĚ^ŽůŝĚƐŝŶĐůƵĚĞƐŝŽŶƐ͕^ŝKЇand B(OH)Ј͘It does not include NHЈand COЇ

RO Solubility Warnings
Warning Pass No
Stiff & Davis Stability Index > 0 1
Anti-scalants may be required. Consult your anti-scalant manufacturer for dosing and maximum allowable system recovery. 1

RO Chemical Adjustments
Pass 1 ZKϭ॰ࣞ
Feed Pass Conc

pH 8.3 8.2
Langelier Saturation Index 1.2 1.41
Stiff & Davis Stability Index 0.18 0.30
d^࣊;ŵŐͬůͿ 35,983 51,459
Ionic Strength (molal) 0.74 1.08
HCOЈЁ(mg/L) 98.93 139.9
COЇ(mg/l) 0.28 0.45
COЈЁ² (mg/L) 23.07 34.24
CaSOЉ;йsaturation) 22.3 34.4
BaSOЉ;йsaturation) 0.00 0.00
SrSOЉ;йsaturation) 15.5 24.9
CaFЇ;йsaturation) 17.1 45.2
SiOЇ;йsaturation) 0.65 0.95
Mg(OH)Ї;йsaturation) 4.6 4.6

Footnotes:
࣊dŽƚĂůŝƐƐŽůǀĞĚ^ŽůŝĚƐŝŶĐůƵĚĞƐŝŽŶƐ͕^ŝKЇand B(OH)Ј͘It does not include NHЈand COЇ

RO Utility and Chemical Costs


Service Water
Flow Rate Unit Cost Hourly Cost Daily Cost
(m³/h) ($/m³) ($/h) ($/d)
Non-Product Feed Water
Pass 1 9.8 0.1400 1.37 32.85
Total Non-product Feed Water 9.8 1.37 32.85
Cost
Waste Water Disposal
Pass 1 9.8 0.6900 6.75 161.92
Total Waste Water Disposal 9.8 6.75 161.92
Total Service Water Cost 194.77

Electricity
Peak Power (kW) 26.4
Energy (kWh/d) 632.9
Electricity Unit Cost ($/kWh) 0.0900
Electricity Cost ($/d) 57.0
Specific Energy (kWh/m³) 6.28

WAVE Version: 1.77.774


Project Name: 100 TPD Design Case: Case 1 Created: 02/11/2021 Page 4 of 5
WATER APPLICATION VALUE ENGINE
WATER SOLUTIONS

Pump Flow Rate Power Energy Cost


(m³/h) (kW) (kWh/d) ($/d)
Pass 1
Feed 13.97 26.37 632.92 56.96
Pass 1 Total Electrical Cost 26.37 632.92 56.96

Chemical
Chemical Unit Cost Dose Volume Cost
($/kg) (mg/L) (L/d) ($/d)
Total Chemical Cost 0.0

Utility and Chemical Cost ($/d) 251.8


Specific Water Cost ($/m³) 2.498
Information provided is offered in good faith, but without guarantees. Users of such information assume all risk and liability and expressly release
DuPont de Nemours Inc. and its subsidiaries, officers and agents from any and all liability. Because use conditions and applicable laws may differ from
one location to another and may change with time, users of information set forth herein or generated during use of WAVE are responsible for
determining suitability of the information. Neither DuPont nor its subsidiaries assume any liability for results obtained or damages incurred from the use
of information provided and TO THE FULLEST EXTENT PERMITTED BY LAW, EXPRESSLY DISCLAIM ALL WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Users will not export or re-export any information or technology
received from DuPont or its subsidiaries, or the direct products or designs based upon such information or technology in violation of the export-control or
customs laws or regulations of any country, including those of the United States of America. DuPontΡ͕DuPont Oval Logo, and all products denoted with
® or ΡĂƌĞƚƌĂĚĞŵĂƌŬƐŽƌƌĞŐŝƐƚĞƌĞĚƚƌĂĚĞŵĂƌŬƐŽĨƵWŽŶƚŽƌŝƚƐĂĨĨŝůŝĂƚĞƐ͘෴ŽƉLJƌŝŐŚƚΞϮϬϭϵƵWŽŶƚ͘KtyΡ͕DOWEX MONOSPHEREΡ͕DOWEX
MARATHONΡ͕DOWEX UPCOREΡare a trademark of The Dow Chemical Company used under license by DuPont.

WAVE Version: 1.77.774


Project Name: 100 TPD Design Case: Case 1 Created: 02/11/2021 Page 5 of 5