Professional Documents
Culture Documents
XCell Troubleshooting Manual
XCell Troubleshooting Manual
VERSION 1.07
Troubleshooting M anual Version 1.07
email: info@microsol.com
web: www.microsol.com
Page ii
Troubleshooting Manual Version
1.06
Table of contents
1. INTRODUCTION .................................................................................................1
4. Diagnostic Facilities..........................................................................................7
Page iii
Troubleshooting M anual Version 1.07
Page iv
Troubleshooting Manual Version
1.06
1. INTRODUCTION
This document provides support knowledge for customers installing and operating XCell
hardware and software in the field.
The manual is subdivided into different sections corresponding to the major components of a
typical XCell system. This approach helps to focus on the specific area requiring attention,
thus allowing a more efficient isolation of the problem leading to clearer diagnosis and
resolution.
The problem solving sections contain a list of potential problems along with likely causes
and corrective actions.
Page 1
Troubleshooting M anual Version 1.07
Page 2
Troubleshooting Manual Version
1.06
Page 3
Troubleshooting M anual Version 1.07
Page 4
Troubleshooting Manual Version
1.06
AC Alternating Current
AI Analogue Input
AO Analogue Output
BRAM Battery Backed RAM
CPU module XCell processor module
CT/VT array Current Transformer / Voltage Transformer array
DDI Double Digital Input
DDE Dynamic Data Exchange
DI Digital Input
DO Digital Output
Dongle Software protection key on the PC parallel port
DSP Digital Signal Processing
EPROM Erasable Programmable Read Only Memory
FO Fibre Optic
FSD Field Service Diagnostics
IED Intelligent Electronic Device
IOA Information Object Address
LAN Local Area Network.
LED Light Emitting Diode
HMI Human Machine Interface
OLU On Line Unit
PC Personal Computer
PSU Power Supply Unit
RAM Random Access Memory
RMS Root Mean Square
RS-232 IEEE Serial communications standard
RS-485 IEEE Serial communications standard
RTU Remote Terminal Unit
SAV Save hardware configuration
SHC Show Hardware Configuration
SOE Sequence Of Events
Page 5
Troubleshooting M anual Version 1.07
Page 6
Troubleshooting Manual Version
1.06
4. Diagnostic Facilities
A range of diagnostic facilities is provided with the XCell product. These should be used
in conjunction with this manual to isolate and diagnose any problems. These facilities
include:
• Data quality information on each data point. This is generally available at the Master
Station / Control Centre display (providing the installed protocol supports it).
• XCell unit status and I/O module status which is available as digital status points at
the Master Station / Control Centre display.
• Local Front Panel diagnostics to assist fault finding. For further information refer to
the XCell User Manual and Appendix One of this manual.
• eXplore diagnostic software which runs on a PC and can assist fault finding. For
further information please refer to the eXplore User Manual.
• Vision diagnostic screens where the Vision HMI product is used.
Page 7
Troubleshooting M anual Version 1.07
Page 8
Troubleshooting Manual Version
1.06
5. Reference Documentation
Problem Involving Please Refer To
Operator Workstation Problems
PC problems. PC User Documentation
IED Problems
Relay address numbers Changing Manufacturer supplied IED User Documentation
Communication Problems Manufacturer supplied IED User Documentation
Communication Problems
Cables XCell User Manual
Connectors XCell User Manual
Network termination XCell User Manual
Configuration Problems
Setting parameters eXpert User Manual
Downloading Configurations eXpert User Manual
eXpress software eXpress User Manual
Page 9
Troubleshooting M anual Version 1.07
Page 10
Troubleshooting Manual Version
1.06
Message on booting the PC indicating that a “Non system disc is installed in the drive”. Page 21
Message displayed indicating that the Vision Tag Count is limited to a certain number. Page 23
No response from the field when attempting to carry out a routine action previously carried out Page 25
through Vision.
Plant status changes not being reported to the Event Log. Page 29
Incorrect analogue values displayed for long periods but correct themselves again for long Page 29
periods.
A single point is reported as a red box with three question marks ??? on the Vision HMI screen. Page 32
Vision displays one or more points as a red box with three question marks ???. Page 33
Page 11
Troubleshooting M anual Version 1.07
Each point is displayed on the Vision HMI screen as a red box with three question marks ???. Page 36
Data points are toggling between good values and values that are clearly in error i.e. points Page 42
toggle between normal Vision colours and red with three question marks ???.
No power to a single XCell processor module in a rack. Power LED is not illuminated. Page 49
XCell processor module does not cycle through its boot up sequence Page 50
XCell processor module does not cycle through its boot up sequence following a firmware Page 52
upgrade.
XCell processor module rebooting while running an eXpress logic sequences. Page 56
Page 12
Troubleshooting Manual Version
1.06
Online LED is not illuminated on the front panel of the XCell Processor module. Page 57
Accumulator values are not being produced by the source XCell processor module. Page 62
XCell Processed Digital Input (SDI, DDI etc) is not functioning in the XCell processor module. Page 71
XCell Raw Digital Input is not available in another XCell processor module. Page 72
XCell Processed Digital Input value (SDI, DDI etc) is not available in another XCell processor Page 72
module.
Processed Digital Input value (SDI, DDI etc) not received across a protocol interface. Page 73
Page 13
Troubleshooting M anual Version 1.07
Unable to drive a Digital Output from eXplore connected to another XCell processor module. Page 83
Multiple control outputs cannot be driven on the same XCell processor module. Page 84
Analogue Input values not changing in the source I/O unit – verified using eXplore. Page 88
Analogue Input values are not correct when viewed within the source XCell processor module Page 90
– verified with eXplore in the source XCell processor module; (Analogue Input values should be
displayed as a percentage of the configured range).
Analogue Input values not received across an XCell protocol interface Page 92
Analogue Input values are not correct when viewed in another XCell processor module – Page 92
verified with eXplore.
XCell not communicating, -RXD LED is flickering but TXD indicator LED not lighting. Page 98
Communications not working after the unit was powered OFF for some time. Page 98
XCell processor module cannot be seen by another XCell processor module. Page 103
Fibre Ring Monitoring module (OPB) displays ”CLS” on the Front Panel. Page 104
Page 14
Troubleshooting Manual Version
1.06
Communications lost while debugging XCell target on a regular basis Page 117
Failed to download to the XCell target XCell processor module. Page 124
Test function failed in the FieldNet Tab Dialogue from the Comms menu. Page 125
Page 15
Troubleshooting M anual Version 1.07
Error encountered when trying to configure Analogue or digital I/O modules. Page 127
Error encountered when trying to configure an XCell processor module too soon after Page 128
powering on.
Raw Digital Input is not displayed correctly in eXplore connected to another XCell processor Page 131
module.
Processed Input (SDI, DDI etc) is not displayed correctly in eXplore connected directly to the Page 131
input unit.
Processed Input (SDI, DDI etc) is not displayed correctly in eXplore connected to another XCell Page 132
processor module.
Page 16
Troubleshooting Manual Version
1.06
Page 17
Troubleshooting M anual Version 1.07
Page 18
Operator Workstation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 19
Troubleshooting M anual Version 1.07
Page 20
Operator Workstation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Message on booting • Floppy disc installed in the • Remove the floppy disc
the PC indicating that a Floppy Disc Drive during boot- from the Floppy Disc Drive
“Non system disc is up. and start again.
installed in the drive”.
Page 21
Troubleshooting M anual Version 1.07
Page 22
Operator Workstation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Printer not powered • The printer may not be • Ensure that the printer is
ON. switched ON. switched ON.
Printer not printing. • Printer not powered ON. • Check previous fault
description.
Page 23
Troubleshooting M anual Version 1.07
“Print Screen” software • No power to the printer. • Ensure that printers are
menu item in Vision is powered ON at all times.
not responding
• Printer not printing. • Refer to the actions for
“Printer not Printing”.
Page 23.
Page 24
Operator Workstation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 25
Troubleshooting M anual Version 1.07
Unable to retrieve • Stored data has been • Verify that the date of the
logged data. automatically deleted by required data does not
Vision archiving system. exceed the configured
archive period.
Page 26
Operator Workstation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 27
Troubleshooting M anual Version 1.07
Page 28
Operator Workstation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 29
Troubleshooting M anual Version 1.07
Page 30
Operator Workstation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 31
Troubleshooting M anual Version 1.07
Page 32
Operator Workstation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Vision displays one or • The appearance of a red box • Check the Alarm Log for
more points as a red with three question marks ??? any recent alarms that
box with three question indicates that the data is might identify the problem.
marks ???. unavailable to Vision.
• Check Vision diagnostic
screens to identify any
faulty modules, units or
communications links.
Page 33
Troubleshooting M anual Version 1.07
Page 34
Operator Workstation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 35
Troubleshooting M anual Version 1.07
Page 36
Operator Workstation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Multiple I/O Bad alarms • The associated XCell • Refer to the actions for
reported in the Alarm processor module is powered “XCell processor
Log. OFF or failed. module failure is
reported in the Alarm
Log”. Page 41.
• The associated XCell I/O • Refer to the actions for
module is removed or failed. “XCell I/O module failure
is reported in the Alarm
Log”. Page 40.
Page 37
Troubleshooting M anual Version 1.07
Unable to drive an XCell • Interlocking conditions prevent • Ensure that the plant
output from Vision. the command from being sent conditions are suitable for
to the XCell system. driving the required output.
Page 38
Operator Workstation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 39
Troubleshooting M anual Version 1.07
XCell I/O module failure • I/O module has been removed. • Replace the module and
is reported in the Alarm verify that it is no longer
Log. reported as failed.
Page 40
Operator Workstation Fault Finding Guide
Troubleshooting
Manual Version 1.06
XCell processor module • XCell processor module is • Switch on the unit using
failure is reported in the powered OFF or removed. the switch on the front of
Alarm Log. the XCell processor
module.
Page 41
Troubleshooting M anual Version 1.07
Vision system reports • Spurious field events can give • Check the plant device.
fleeting alarms. rise to alarms at the operator
Workstation. • Ensure that the XCell
processor modules
interfacing with the field
are configured properly.
XCell processor module • XCell processor module is • Refer to the actions for
is repeatedly reported constantly rebooting. “XCell processor module
OK and then Failed. rebooting continuously”.
Page 54.
• XCell FieldNet LAN fault. • Refer to the actions for
“XCell FieldNet LAN
fault”. Page 101.
Page 42
Operator Workstation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Data points are toggling • XCell processor module is • Refer to the actions for
between good values constantly rebooting. “XCell processor module
and values that are rebooting continuously”.
clearly in error i.e. Page 54.
points toggle between
normal Vision colours
and red with three
question marks ???.
• XCell LAN fault. • Refer to the actions for
“XCell FieldNet LAN
fault”. Page 101.
Page 43
Troubleshooting M anual Version 1.07
Page 44
XCell Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 45
Troubleshooting M anual Version 1.07
Page 46
XCell Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 47
Troubleshooting M anual Version 1.07
Page 48
XCell Fault Finding Guide
Troubleshooting
Manual Version 1.06
No power to a single • The XCell I/O unit is powered • Ensure that the XCell I/O unit
XCell processor OFF. is switched ON using the front
module in a rack. panel power switch.
Power LED is not
illuminated.
• XCell processor module is not • Re-insert the module correctly
secured properly in the rack and secure properly
and is not making proper
electrical contact with the
backplane.
Page 49
Troubleshooting M anual Version 1.07
• The RAM Clear link on the • Ensure that the RAM Clear
processor module is set to the link on the XCell processor
wrong position module is not set to the Clear
position.
Page 50
XCell Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 51
Troubleshooting M anual Version 1.07
Page 52
XCell Fault Finding Guide
Troubleshooting
Manual Version 1.06
• The RAM chips are installed • Ensure that the RAM chips are
incorrectly or in the wrong installed in the correct sockets
positions on the XCell on the XCell processor module
processor module board. circuit board and that the
orientation of the chips is
correct.
• Some pins from the RAM or • Ensure that all the RAM and
EPROM chips are bent and not EPROM pins are correctly
inserted properly in their inserted into their respective
sockets. sockets.
Page 53
Troubleshooting M anual Version 1.07
Page 54
XCell Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 55
Troubleshooting M anual Version 1.07
Non-volatile memory • Memory links not configured • Ensure that the jumpers are
fault. properly for non-volatile set correctly on the XCell
retention. processor module to ensure
that the memory is retained
during power OFF.
Page 56
XCell Fault Finding Guide
Troubleshooting
Manual Version 1.06
Online LED is not • XCell processor module not • Refer to the actions for “XCell
illuminated on the booting properly. processor module does not
front panel of the cycle through its boot-up
XCell Processor sequence”. Page 50.
module.
• Front panel online LED faulty. • Verify the LED during the XCell
processor module boot up
sequence when all front panel
LEDs are exercised.
Page 57
Troubleshooting M anual Version 1.07
Page 58
Accumulator Fault Finding Guide
Troubleshooting Manual
Version 1.06
Page 59
Troubleshooting M anual Version 1.07
Page 60
Accumulator Fault Finding Guide
Troubleshooting Manual
Version 1.06
Page 61
Troubleshooting M anual Version 1.07
Page 62
Accumulator Fault Finding Guide
Troubleshooting Manual
Version 1.06
Accumulator values not • High Speed Counter module • Refer to the actions for “High
available in another is not being scanned (if HSC Speed Counter (HSC)
XCell processor being used). module is not being
module. scanned on the front panel
LED matrix”. Page 60.
Accumulator values are • Accumulator values are not • Refer to the actions for
not received through a being produced by the “Accumulator values not
communications source XCell processor being produced by the
interface. module. source XCell processor
module”. Page 62.
Page 63
Troubleshooting M anual Version 1.07
Page 64
AC Analogue Input Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 65
Troubleshooting M anual Version 1.07
Page 66
AC Analogue Input Fault Finding Guide
Troubleshooting
Manual Version 1.06
• ACI module is not seen by the • Ensure that all I/O modules
XCell processor module. are installed and visible using
the SHC menu option on the
front panel of the XCell
processor module.
Page 67
Troubleshooting M anual Version 1.07
Inaccurate AC • ACI module not calibrated. • Ensure that the ACI module
measurements has been calibrated with the
matching CTs and VTs.
• CTs and VTs not matched to • Ensure that the ACI module
the ACI module. has been calibrated with the
matching CTs and VTs.
Page 68
Digital Input Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 69
Troubleshooting M anual Version 1.07
• Digital Input module is not • Ensure that all I/O modules are
seen by the XCell processor installed and visible using the
module. SHC menu option on the XCell
processor module front panel.
Page 70
Digital Input Fault Finding Guide
Troubleshooting
Manual Version 1.06
XCell Processed • Raw digital point may not be • Using eXplore check the
Digital Input (SDI, functional. operation of the Raw Digital
DDI etc) is not points. If these are not
functioning in the operational refer to the actions
XCell processor for “Digital Input LED matrix
module. not reflecting the plant status“ .
Page 70.
Page 71
Troubleshooting M anual Version 1.07
XCell Raw Digital • XCell unit is powered OFF. • Ensure that both XCell units are
Input is not available switched ON using the front
in another XCell panel power switch.
processor module.
• Fault on the XCell I/O unit. . • Refer to the actions for “Digital
Input LED matrix is not
reflecting the plant status” .
Page 70.
XCell Processed • XCell processor module is • Ensure that both XCell processor
Digital Input value powered OFF. modules are switched ON using
(SDI, DDI etc) is not the front panel power switch.
available in another
XCell processor
module.
Page 72
Digital Input Fault Finding Guide
Troubleshooting
Manual Version 1.06
Processed Digital • XCell processed Digital Input • Refer to the actions for “XCell
Input value (SDI, DDI (SDI, DDI etc) is not processed Digital Input (SDI,
etc) not received functioning in the XCell DDI etc) is not functioning in
across a protocol processor module. the XCell processor module”.
interface. Page 71.
• I/O not transferred by the XCell • Refer to the actions for “I/O not
protocol Interface unit. transferred by the XCell
protocol Interface unit”. Page
74.
Raw Digital Input not • Digital Input is not read • Refer to the actions for “Digital
received across a correctly by the I/O processor Input LED matrix not reflecting
protocol interface. module. the plant status”. Page 70.
• I/O unit cannot be seen by the • Refer to the actions for “XCell
protocol XCell processor processor module cannot be
module. seen by another XCell
processor module”. Page 103.
Page 73
Troubleshooting M anual Version 1.07
• I/O not transferred by the XCell • Refer to the actions for “I/O not
protocol interface unit. . transferred by the XCell
protocol interface unit”. Page
74.
I/O not transferred by • The protocol interface XCell • Ensure that the protocol
the XCell protocol processor module is powered interface unit is switched ON
interface unit. OFF or failed. using the front panel power
switch.
Page 74
Analogue Output Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 75
Troubleshooting M anual Version 1.07
Page 76
Analogue Output Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 77
Troubleshooting M anual Version 1.07
Unable to drive an • Local XCell processor module • Ensure that the local XCell
Analogue Output is powered OFF. processor module is switched
from eXplore on ON using the front panel power
another XCell unit. switch.
Page 78
Analogue Output Fault Finding Guide
Troubleshooting
Manual Version 1.06
Unable to drive an • Fault on the XCell system. • Check if the output can be
Analogue Output driven from eXplore on the
through a protocol protocol interface module and
interface module. if not then refer to the actions
for “Unable to drive an
Analogue Output from
eXplore on another XCell
unit”. Page Error! Bookmark
not defined..
Page 79
Troubleshooting M anual Version 1.07
Page 80
Digital Output Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 81
Troubleshooting M anual Version 1.07
• Digital Output module is not • Ensure that all I/O modules are
seen by the XCell processor installed and vi sible using the
module. SHC menu option on the XCell
processor module front panel.
Page 82
Digital Output Fault Finding Guide
Troubleshooting
Manual Version 1.06
Unable to drive a • Local XCell processor module • Ensure that the local XCell
Digital Output from is powered OFF. processor module is switched ON
eXplore connected to using the front panel power
another XCell switch.
processor module.
Page 83
Troubleshooting M anual Version 1.07
• I/O unit cannot be seen by the • Refer to the actions for “XCell
XCell processor module to processor module cannot be
which eXplore is connected. seen by another XCell
processor module”. Page 103.
Unable to drive a • Fault on the XCell system. • Check if the output can be driven
Digital Output from eXplore on the protocol
through a protocol interface unit and if not then refer
interface to the actions for “Unable to
drive a Digital Output from
eXplore connected to another
XCell processor module”. Page
83.
• I/O not transferred by the XCell • Refer to the actions for “I/O not
protocol interface module. transferred by the XCell
protocol interface module”.
Page 74.
Multiple control • Jumper on Digital Output card • Ensure that the jumper is set for
outputs cannot be for 2-up inhibit is incorrectly 2-up inhibit if only one output at a
driven on the same set. time is required on the Digital
XCell processor Output module. If jumper
module. positions are changed on I/O
boards the configuration must be
saved using the SHC option on
the front panel menu.
Page 84
Analogue Input Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 85
Troubleshooting M anual Version 1.07
Page 86
Analogue Input Fault Finding Guide
Troubleshooting
Manual Version 1.06
• LED matrix displaying the • Ensure that the LED matrix is set-
wrong I/O channels. up to display the relevant I/O
indications. (Refer to the XCell User
Manual for further information.
• Faulty LED matrix element or • Verify the I/O status using the
LED matrix. eXplore diagnostic tool. If it displays
the inputs correctly then the LED /
LED matrix is faulty. Refer to the
XCell User Manual and the
eXplore User Manual for further
information.
Page 87
Troubleshooting M anual Version 1.07
Analogue Input • Module not scanning properly. • Refer to the actions for “Analogue
values not changing Input not scanning on the front
in the source I/O unit panel LED matrix”. Page 87.
– verified using
eXplore.
Page 88
Analogue Input Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 89
Troubleshooting M anual Version 1.07
• If no channel configuration is
required then ensure that the delta
value set via the front panel after
start-up is not set so high as to
prevent current changes being
reported.
Analogue Input • Incorrect module range. • Ensure that the range of the
values are not correct Analogue Input module is suitable
when viewed within for the inputs.
the source XCell
processor module –
verified with eXplore
in the source XCell
processor module;
(Analogue Input
values should be
displayed as a
percentage of the
configured range).
Page 90
Analogue Input Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 91
Troubleshooting M anual Version 1.07
Analogue Input • Analogue Input is not read • Refer to the actions for “Analogue
values not received correctly by the I/O processor Input not changing in the source
across an XCell module. I/O processor module – verified
protocol interface. using eXplore”. Page 88.
• I/O unit cannot be seen by the • Refer to the actions for “XCell
XCell protocol unit. processor module cannot be seen
by another XCell processor
module”. Page 104.
• I/O not transferred by the XCell • Refer to the actions for “I/O not
protocol interface unit. transferred by the XCell protocol
interface module”. Page 74.
Analogue Input • Analogue Input values are • Refer to the actions for “Analogue
values are not correct transmitted with incorrect Input values are not correct when
when viewed in values from the source XCell viewed within the source XCell
another XCell processor module. processor module - ”. Page 90.
processor module –
verified with eXplore.
• The unit is not communicating • Refer to the actions for “XCell
properly with the source XCell processor module cannot be seen
processor module. by another XCell processor
module”. Page 103.
Page 92
Serial Communications Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 93
Troubleshooting M anual Version 1.07
Page 94
Serial Communications Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 95
Troubleshooting M anual Version 1.07
Page 96
Serial Communications Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 97
Troubleshooting M anual Version 1.07
Communications not • Fault with non-volatile • Refer to the actions for “Non-
working after the unit memory. volatile memory fault”. Page 56.
was powered OFF for
some time.
XCell appears to have • Unit powered OFF and lost • Refer to the actions for “Non-
lost its configuration its memory, volatile memory fault”. Page 56.
data.
Page 98
XCell FieldNet LAN Fault Finding Guide
Troubleshooting
Manual Version 1.06
• Ensure that all XCell processor modules on the network are fitted
with the same version of BASE software.
• Use the front panel OLU display to verify that each XCell processor
module can see all other units on the network. If this is not the case,
then identify a dividing point in the network and check all connections
and modules at this point.
• Use the front panel PRI display to establish which network of the
redundant pair each unit is using for its communications, (all units
should be on the same network).
Page 99
Troubleshooting M anual Version 1.07
• Remove any fibre optic ring monitoring modules from the network to
simplify troubleshooting.
• Ensure fibre optic cables connect the transmitter on one card to the
receiver on another.
• Ensure that fibre optic cables do not exceed their maximum bend
radius.
Page 100
XCell FieldNet LAN Fault Finding Guide
Troubleshooting
Manual Version 1.06
• Incorrect fibre optic • Ensure that all fibre optic leads are
connections. connected to the correct points, i.e.
upstream to down-stream, on the
next node, down-stream to upstream
on the next node, LAN A to LAN A
and LAN B to LAN B.
Page 101
Troubleshooting M anual Version 1.07
• Fibre Optic module used in • Ensure that all Fibre Optic modules
the network is powered are powered ON and appear to be
OFF. functioning correctly.
• Fibre optic patch lead is • Ensure that no fibre optic cables are
bent severely and damaged bent to exceed their minimum bend
as a consequence. radius or it can be assumed that they
are permanently damaged.
Page 102
XCell FieldNet LAN Fault Finding Guide
Troubleshooting
Manual Version 1.06
XCell processor • XCell processor module is • Ensure that both XCell processor
module cannot be powered OFF. modules are switched ON using the
seen by another front panel power switch.
XCell processor
module.
Page 103
Troubleshooting M anual Version 1.07
Fibre Ring Monitoring • Indicates that a fault was • Refer to the actions listed for “XCell
module (OPB) detected elsewhere in the FieldNet LAN Fault”. Page 101.
displays ”CLS” on the F.O. Ring and the Ring
Front Panel. monitor had to close to
compensate for the fault.
Page 104
Time Synchronisation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 105
Troubleshooting M anual Version 1.07
Page 106
Time Synchronisation Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 107
Troubleshooting M anual Version 1.07
Page 108
Sequence Of Events Fault Finding Guide
Troubleshooting Manual
Version 1.06
Page 109
Troubleshooting M anual Version 1.07
• The SOE may be empty at the • Ensure that some SOE points have
time of request. changed before uploading the file.
Page 110
IED Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 111
Troubleshooting M anual Version 1.07
• IED data not transferred by • Refer to the actions for “I/O not
XCell to the display system. transferred by the XCell
protocol Interface unit”. Page
74.
Page 112
IED Fault Finding Guide
Troubleshooting
Manual Version 1.06
IED device status is • IED failed or communications • Refer to the actions for "IED
"Failed". fault. failed or communications
fault". Page 113.
Page 113
Troubleshooting M anual Version 1.07
Page 114
eXpress Fault Finding Guide
Troubleshooting
Manual Version 1.06
Page 115
Troubleshooting M anual Version 1.07
Page 116
eXpress Fault Finding Guide
Troubleshooting
Manual Version 1.06
Communications lost • Parameters missing from • Check the .INI file against the set-
on a regular basis eXpress .INI file. up specified in the eXpress User
while debugging an Manual and Language
application on the Reference .
target XCell unit.
Page 117
Troubleshooting M anual Version 1.07
eXpress unit is • eXpress cycle time is too short • Ensure that the eXpress cycle
constantly rebooting. for the eXpress logic and all time allows sufficient time for the
other XCell activities. eXpress sequence and all other
XCell processing activities. No
eXpress logic sequence should
have a cycle time of zero.
eXpress application is • The application is not • Ensure that the correct compiler
not operating programmed correctly. options were selected prior to
verifying and downloading.
Page 118
eXpress Fault Finding Guide
Troubleshooting
Manual Version 1.06
eXpress application is • eXpress program not running. • Refer to the actions for “eXpress
not activating outputs. application is not operating”.
Page 118.
I/O connection error • Multiple eXpress tags were • Ensure each eXpress point has a
generated in eXpress generated with the same unit unique combination of unit and
compiler. and channel number. channel.
Page 119
Troubleshooting M anual Version 1.07
Page 120
eXpert Fault Finding Guide
Troubleshooting Manual
Version 1.06
Page 121
Troubleshooting M anual Version 1.07
• When using eXpert ensure that the unit number you are
trying to connect to is the same unit number set in the
eXpert dialog box.
Page 122
eXpert Fault Finding Guide
Troubleshooting Manual
Version 1.06
Page 123
Troubleshooting M anual Version 1.07
Newly entered value • Data entry not completed with • Ensure that all data entry is
not stored in the field. the “Enter” key. Possibly used completed with the “Enter”
the mouse to select another key.
field.
Page 124
eXpert Fault Finding Guide
Troubleshooting Manual
Version 1.06
Test function failed in • PC not connected to the XCell • Ensure that the interface cable
the FieldNet Tab FieldNet network. is connected to the correct
Dialogue from the serial port on the PC and to the
Comms menu. correct port on the XCell
processor module.
Page 125
Troubleshooting M anual Version 1.07
CFG- 027 message • Download failed because the • Wait for approximately one
returned on the PC. XCell processor module had minute to allow the previous
not terminated the previous download session to timeout in
configuration session. the XCell target and try to
download again.
Error message • eXpert requires more than 256 • Ensure the display is set in a
“Exception in Delete colours in its set-up graphics mode with more than
Object errno = 2” 256 colours.
Page 126
eXpert Fault Finding Guide
Troubleshooting Manual
Version 1.06
Error encountered • Attempting to configure non- • Check the front panel message
when trying to existent hardware. For generated on the target XCell
configure Analogue or example, trying to configure 64 processor module. Refer to the
digital I/O modules. channels when only one card appendix on “Front Panel
is installed. Diagnostic Messages” (page
132) for an interpretation of all
relevant front panel user
messages.
Page 127
Troubleshooting M anual Version 1.07
Page 128
eXplore Fault Finding Guide
Troubleshooting Manual
Version 1.06
Page 129
Troubleshooting M anual Version 1.07
Page 130
eXplore Fault Finding Guide
Troubleshooting Manual
Version 1.06
• Fault on the XCell I/O unit. • Refer to the actions for “Digital
Input LED matrix not reflecting
the plant status”. Page 70.
Raw Digital Input is • XCell I/O unit is powered OFF. • Ensure that the XCell I/O unit is
not displayed switched ON using the front panel
correctly in eXplore power switch. Wait one minute for
connected to another the unit to power ON fully. Exit
XCell processor eXplore and restart the package.
module.
• Fault on the XCell I/O • Refer to the actions for “Digital
processor module. Input LED matrix not reflecting
the plant status”. Page 70.
• I/O unit cannot be seen by the • Refer to the actions for “XCell
eXplore interface unit. processor module cannot be
seen by another XCell processor
module”. Page 103.
Processed Input • XCell Processed Digital Input • Refer to the actions for “XCell
(SDI, DDI etc) is not (SDI, DDI etc) is not Processed Digital Input (SDI, DDI
displayed correctly in functioning in the XCell etc) is not functioning in the
eXplore connected processor module. XCell processor module”. Page
directly to the input 71.
unit.
Page 131
Troubleshooting M anual Version 1.07
Analogue Input is not • XCell processor module is • Ensure that the associated XCell
displayed correctly in powered OFF. processor module is switched ON
eXplore. using the front panel power switch.
Wait one minute for the unit to
power ON fully. Exit eXplore and
restart the package.
• Fault on the XCell I/O unit. • Refer to the actions for “Analogue
Input not changing in the
source I/O unit – verified using
eXplore”. Page 88.
Page 132
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
Page 133
Troubleshooting M anual Version 1.07
8. APPENDIX ONE
This appendix lists diagnostic messages that may be encountered on the
front panel seven segment display of an XCell processor module. The
message display combines a three-character string followed by a three-digit
number.
Each message and any corrective actions are described in the following
tables.
Diagnostic messages are divided into two categories: 1) those that appear
during XCell system initialisation and 2) those that appear when the XCell is
actually running.
Page 134
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
Page 135
Troubleshooting M anual Version 1.07
Page 136
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
TABLE ONE
010 General XCell processor module Ensure all RAM chips correctly inserted on XCell processor
hardware failure. module. Ensure all jumpers on the XCell processor module
are in the correct positions. Refer to the XCell User
Manual for further information on jumper settings.
020 General XCell processor module Ensure all RAM chips correctly inserted on XCell processor
hardware failure. module. Ensure all jumpers on the XCell processor module
are in the correct positions. Refer to the XCell User
Manual for further information on jumper settings.
030 General XCell processor module Ensure the EEPROM chip is correctly inserted XCell
hardware failure. processor module. Ensure RAM chips correctly inserted on
the XCell processor module. Ensure all jumpers on the XCell
processor module card are in the correct positions. Refer to
the XCell User Manual for further information on jumper
settings.
040 General XCell processor module Ensure all RAM chips correctly inserted on the XCell
hardware failure. processor module. Ensure all jumpers on the XCell
processor module are in the correct positions. Refer to the
XCell User Manual for further information on jumper
settings.
050 General XCell processor module Ensure all RAM chips correctly inserted on XCell processor
hardware failure. module. Ensure all jumpers on XCell processor module are in
the correct positions. Refer to the XCell User Manual for
further information on jumper settings.
Page 137
Troubleshooting M anual Version 1.07
070 General XCell processor module Ensure the EEPROM chip is correctly inserted on the XCell
hardware failure. processor module. Ensure all jumpers on the XCell
processor module are in the correct positions. Refer to the
XCell User Manual for further information on jumper
settings.
080 General XCell processor module Ensure all RAM chips are correctly inserted on the XCell
hardware failure. processor module. Ensure all jumpers on the XCell
processor module are in the correct positions. Refer to the
XCell User Manual for further information on jumper
settings.
090 Invalid or conflicting Named Blocks Ensure that correct versions of PROMs are installed on the
found in memory. XCell processor module. Ensure all PROM chips are
correctly inserted on the XCell processor module and not
corrupted. Ensure that code and data sections of Named
Blocks in PROM do not overlap.
100 The XCell processor module is Check that RAM and PROM jumpers on the XCell processor
reporting data corruption. module are correctly set. Ensure all PROM chips correctly
inserted on the XCell processor module card and are not
corrupted. Refer to the XCell User Manual for further
information on jumper settings.
110 Data corruption or invalid Named Check that RAM and PROM jumpers on the XCell processor
Block. module are correctly set. Ensure that correct versions of
PROMs are installed on the XCell processor module. Ensure
all PROM chips are correctly inserted on the XCell processor
module card and are not corrupted. Refer to the XCell User
Manual for further information on jumper settings.
Page 138
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
130 General XCell processor module Ensure the hardware timer chip is correctly inserted on
hardware failure. XCell processor module card. Ensure that RAM chips are
correctly inserted on XCell processor module. Make sure all
jumpers on XCell processor module card are in the correct
positions. Refer to the XCell User Manual for further
information on jumper settings.
140 Invalid or corrupted PROM chips. Ensure correct versions of PROMs are installed on the XCell
processor module card. Ensure that all PROM chips are
correctly inserted on the XCell processor module and are
not corrupted. Ensure that all jumpers on the XCell
processor module card in the correct positions. Refer to the
XCell User Manual for further information on jumper
settings.
200 General XCell processor module Ensure all RAM chips are correctly inserted on the XCell
hardware failure. processor module Card. Ensure that all jumpers on the XCell
processor module are in the correct positions. Refer to the
XCell User Manual for further information on jumper
settings.
210 General XCell processor module Ensure the Hardware Timer Chip is correctly inserted on the
hardware failure. XCell processor module card
220 Data corruption or invalid Named Check that RAM and PROM jumpers on the XCell processor
Block. module card are correctly set. Ensure that correct versions
of PROMs are installed on the XCell processor module.
Ensure that all PROM chips are correctly inserted on the
XCell processor module card and not corrupted. Ensure that
Code and Data sections of Named Blocks in PROM do not
overlap. Refer to the XCell User Manual for further
information on jumper settings.
Page 139
Troubleshooting M anual Version 1.07
230 The XCell processor module is Check that RAM jumpers on the XCell processor module
reporting that it has insufficient card are correctly set. Ensure that correct versions of
memory. PROMs are installed on the XCell processor module card.
Refer to the XCell User Manual for further information on
jumper settings.
240 The XCell processor module is Check that RAM jumpers on the XCell processor module
reporting that it has insufficient card are correctly set. Ensure that correct versions of
memory. PROMs are installed on the XCell processor module. Refer to
the XCell User Manual for further information on jumper
settings.
250 General XCell processor module Check that RAM jumpers on the XCell processor module
hardware failure. card are correctly set. Ensure that correct versions of
PROMs are installed on the XCell processor module. Refer to
the XCell User Manual for further information on jumper
settings.
260 The XCell processor module is Check that RAM jumpers on the XCell processor module
reporting that it has insufficient card are correctly set. Ensure that correct versions of
memory. PROMs are installed on the XCell processor module. Refer to
the XCell User Manual for further information on jumper
settings.
270 The XCell processor module is Check that RAM jumpers on the XCell processor module
reporting that it has insufficient card are correctly set. Ensure that correct versions of
memory. PROMs are installed on the XCell processor module. Refer to
the XCell User Manual for further information on jumper
settings.
280 The XCell processor module is Check that RAM jumpers on the XCell processor module
reporting that it has insufficient card are correctly set. Ensure that correct versions of
memory. PROMs are installed on the XCell processor module. Refer to
the XCell User Manual for further information on jumper
settings.
Page 140
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
290 General XCell processor module Ensure all input/output boards are correctly inserted in the
hardware failure. rack. Ensure the correct versions of EPROMS are installed.
295 General XCell processor module Ensure all input/output boards are correctly inserted in the
hardware failure. rack. Ensure the correct versions of EPROMS are installed.
Make sure that each additional board in the rack is correctly
connected to the power supply.
300 General XCell processor module Ensure the EEPROM chip correctly inserted on the XCell
hardware failure. processor module card. Ensure all RAM chips are correctly
inserted on the XCell processor module card. Ensure all
jumpers on the XCell processor module are in the correct
positions. Refer to the XCell User Manual for further
information on jumper settings.
310 General XCell processor module Check that RAM jumpers on the XCell processor module
hardware failure. card are correctly set. Ensure that correct versions of
PROMs are installed on the XCell processor module. Refer to
the XCell User Manual for further information on jumper
settings.
320 An application running on the Ensure that the correct versions of PROMs are installed on
XCell processor module has the XCell processor module card.
caused an error.
330 An application running on the Ensure that the correct versions of PROMs are installed on
XCell processor module has the XCell processor module card.
caused an error.
335 General XCell processor module Check that RAM jumpers on the XCell processor module
hardware failure. card are correctly set. Ensure that correct versions of
PROMs are installed on the XCell processor module. Refer to
the XCell User Manual for further information on jumper
settings.
Page 141
Troubleshooting M anual Version 1.07
350 General XCell processor module Check that RAM jumpers on the XCell processor module
hardware failure. card are correctly set. Ensure that correct versions of
PROMs are installed on the XCell processor module. Refer to
the XCell User Manual for further information on jumper
settings.
Page 142
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
1) System Modules:
SYS System interface
bRA Battery Backed RAM driver
DB Runtime database
DD Distributed database manager
CFG Configurator
NET FieldNet network
2) I/O Server :
AIR Standard AI driver
AO Raw Analogue Output Point Type
AOI Standard AO driver
DI Standard DI driver
HAI High density AI driver
RAI Raw Analogue Input Point Type
RDI Raw Digital Input Point Type
RDO Raw Digital Output Point Type
RHS Raw HSC Point Type
SIO I/O Scheduler
Page 143
Troubleshooting M anual Version 1.07
System Modules
System Modules are software components managing system resources (i.e. memory,
database etc).
Problems sometimes arise in system modules due to erroneous actions taken by an
application attempting to access a system resource.
ACI - 001 to ACI - 099 inclusive are internal XCell system messages and are not
user-serviceable. When these messages are seen and the XCell does not recover, the
unit should be powered OFF then on again. If the message persists the user should
power OFF the XCell and clear BRAM then reconfigure the unit from eXpert. If the
difficulty remains, your equipment vendor should be notified.
ACI - 100 to ACI - 199 inclusive are XCell ACI configuration messages.
Most of these messages point to problems in the user’s eXpert configuration.
When these messages are seen the AC measurement configuration causing the
message is rejected and any previously valid AC measurement configuration running on
the XCell continues to run. (Other Point Types on the local unit are not affected).
Page 144
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
ACI-200 to ACI-229 inclusive are ACI card failure messages. These messages indicate a
problem with the ACI module. Indicating a DSP not performing within expected bounds
that may have ceased to update its heartbeat register leading the XCell to conclude the
DSP has failed. These messages are usually cleared by re-booting the XCell processor
module. If this action fails to resolve the problem the card may need to be replaced.
ACI-230 to ACI-250 inclusive are ACI card non-fatal warnings of no concern to the
customer.
NOTE: Messages not listed below should be communicated to your system supplier.
Page 145
Troubleshooting M anual Version 1.07
TABLE TWO.
ACI-101 ACI card is not present or has failed. Ensure that ACI cards are installed in the
correct slot positions. Refer to XCell User
Manual.
ACI-102 Attempting to configure more than eight AC Make sure the cards installed in the XCell
channels for AC RMS Phase measurement. processor module match the configuration
established in eXpert. Check configuration
tables.
ACI-103 Attempting to configure more than eight AC Ensure the eXpert configuration matches the
channels for AC frequency measurement. installed hardware. Check configuration
tables.
ACI-104 The DC Analogue channel is out of range. Compare the installed hardware list with the
eXpert configurations and correct as
appropriate. Check number of channels in the
ACM16 configuration table.
ACI-105 Attempted to configure an AC frequency Ensure the eXpert configuration matches the
over DC Analogue. installed hardware. Check frequency settings
in the ACM16 configuration table.
ACI-106 ACI Card number out of range. Compare the installed hardware list with the
eXpert configurations and correct as
appropriate. Check the card number in the
ACICARD configuration table; ensure card
number is within the allowed range.
ACI-107 Attempted to configure AC RMS Phase over Compare the installed hardware list with the
DC Analogue. eXpert configurations and correct as
appropriate. Check number of channels in the
ACM16 configuration table.
ACI-108 Type of AC Channel has different settings in Ensure the eXpert configuration matches the
different feeders. installed hardware. Check the feeder settings
in the ACIFDR configuration table.
Page 146
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
ACI-110 Maximum CT or VT input for a feeder is set to Ensure the eXpert configuration matches the
zero. installed hardware. Check the CT and VT
settings in the ACIFDR configuration table are
nonzero.
ACI-111 Attempt to configure DC Analogues on a non- Make sure the cards installed in the XCell
DC Analogue ACI card. processor module match the configuration
established in eXpert. Check the DC analogue
settings in the ACM16 configuration table.
ACI-112 Attempt to configure a 16-bit AC Compare the installed hardware list with the
measurement twice. eXpert configurations and correct as
appropriate. Check for AC measurement
conflicts in the ACM16 configuration table.
ACI-113 Attempt to configure a 32-bit AC Compare the installed hardware list with the
measurement twice. eXpert configurations and correct as
appropriate. Check for AC measurement
conflicts in the ACM32 configuration table.
ACI-114 Unable to configure one or more busy ACI Allow the busy ACI card to complete its time-
cards. critical task before attempting to download the
configuration.
ACI-115 Feeder out of range for derived power Ensure the eXpert configuration matches the
measurement. installed hardware. Check the feeder number
in the ACM16 configuration table. Ensure the
feeder number is within the allowed range.
ACI-116 Less than three current inputs defined for Ensure the eXpert configuration matches the
three-phase feeder. installed hardware. Ensure the correct three-
phase feeder settings in the ACICARD
configuration table.
Page 147
Troubleshooting M anual Version 1.07
ACI-118 Attempt to configure AC RMS Line voltage on Ensure the eXpert configuration matches the
a single-phase feeder. installed hardware. Ensure the correct single-
phase and three-phase feeder settings in the
ACM16 and ACICARD configuration tables.
ACI-119 Less than three voltage inputs defined for a Ensure the eXpert configuration matches the
three-phase feeder. installed hardware. Ensure the three-phase
feeders are configured with three current
inputs and three voltage inputs in the ACIFDR
configuration tables.
ACI-120 Attempting to access more than 16 AC Ensure the channel number settings in the
channels for AC RMS phase measurements. ACM16 table are correct for AC RMS phase
measurement; the maximum channel number is
fifteen.
ACI-125 ACI Card Numbers not configured in When configuring ACI cards in the ACICARD
ascending order. table.
Compare the installed hardware list with the
eXpert configurations and correct as
appropriate. Ensure ACI cards are configured
in ascending order in the ACICARD
configuration table.
Page 148
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
ACI-127 No feeders configured for at least one ACI Ensure the eXpert configuration matches the
card. installed hardware. Ensure each ACI card
have at least one associated feeder
configured in the ACIFDR table.
ACI-128 Feeder numbers for an ACI card do not start Ensure the eXpert configuration matches the
at zero. installed hardware. Ensure the first feeder
configured for each ACI card, in the ACIFDR
table is numbered zero.
ACI-129 Not enough configured feeders for AC RMS Compare the installed hardware list with the
Line Voltage. eXpert configurations and correct as
appropriate. Ensure there are sufficient
configured feeders for AC RMS line voltage
measurements in the ACM16 table.
ACI-130 Not enough configured feeders for derived Ensure the eXpert configuration matches the
power. installed hardware. Ensure there are sufficient
configured feeders for derived power AC
measurements in the ACM16 table.
ACI-131 AC channel in a feeder does not exist. Compare the installed hardware list with the
eXpert configurations and correct as
appropriate. Ensure the assigned channel
exists in the ACIFDR table; eight channel cards
support from zero to seven, sixteen channel
cards support from zero to fifteen.
ACI-132 Feeder numbers for an ACI card are not Ensure the eXpert configuration matches the
contiguous. installed hardware. Ensure the feeder
numbers in the ACIFRD table are configured in
ascending order with the first feeder being
zero.
Page 149
Troubleshooting M anual Version 1.07
ACI-134 Attempting to access more than sixteen AC Compare the installed hardware list with the
channels for AC frequency measurement. eXpert configurations and correct as
appropriate. Ensure that no channel is
configured beyond fifteen when configuring
an AC frequency measurement in the ACM16
table.
ACI-135 Not all ACI cards received a feeder Compare the installed hardware list with the
configuration. eXpert configurations and correct as
appropriate. Ensure all installed ACI cards
have at least one associated feeder
configured in the ACIFDR table.
ACI-136 Feeder configuration contains extraneous Check for inconsistencies between the eXpert
records. configuration and the installed hardware.
Ensure the ACIFDR table contains the correct
number of records. Ensure the correct number
of ACI cards are installed and functioning for
the intended configuration download.
ACI-137 Maximum system frequency is lower than the Ensure the eXpert configuration matches the
nominal system frequency. installed hardware. Ensure the maximum
system frequency is set greater than the
nominal system frequency in ACICARD table.
ACI-138 Reporting period is too short. Make sure the cards installed in the XCell
processor module match the configuration
established in eXpert. Ensure the AC
measurement reporting period is not less than
the reciprocal of the nominal system
frequency in the ACICARD table.
Page 150
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
ACI-140 An AC measurement has been configured for Check the feeder table; ensure the channel
a channel that is not in the feeder table. exists in the table. Download the configuration
again.
ACI-141 Current and voltage AC Channels are Check for inconsistencies between the eXpert
identical within a feeder. configuration and the installed hardware.
Ensure AC channels are not configured to
provide both current and voltage inputs in the
ACIFDR table.
ACI-142 Current and voltage phases differ within a Ensure the correct eXpert configuration is
feeder. downloaded. Check the ACIFDR table for
multiple instances of CTs VTs and
inconsistencies across feeders. Ensure
voltage and current channels have the same
phase in the ACIFDR table.
ACI-143 Not enough configured feeders for Ensure the correct eXpert configuration is
cumulative energy. downloaded. Ensure the three-phase feeder
number is properly specified when configuring
a cumulative energy AC measurement in the
ACM32 table.
ACI-144 Delta for sixteen-bit AC measurement Ensure the delta value does not exceed 100%
exceeds 100%. when configuring sixteen-bit AC
measurements in the ACM16 table.
ACI-145 Delta for thirty-t w o-bit AC measurement is Ensure the delta value does not exceed 100%
exceeds 100%. when configuring thirty-t w o-bit AC
measurements in the ACM16 table.
ACI-146 Attempt to configure sixteen-bit AC Check for inconsistencies between the eXpert
measurement on non-existent ACI card. configuration and the installed hardware.
Check for failed or missing sixteen-bit ACI
cards.
Page 151
Troubleshooting M anual Version 1.07
ACI-148 Attempt to configure a failed ACI card. Check for inconsistencies between the eXpert
configuration and the installed hardware.
Check for failed or missing ACI cards.
ACI-149 Attempting to access more than seven three- Check for inconsistencies between the eXpert
phase feeders on one ACI card. configuration and the installed hardware.
Ensure that no more than seven three-phase
feeders, numbered from zero to six, are
configured in the ACIFDR table; additional
feeders must be single-phase.
ACI-150 Single-phase feeders and three-phase Make sure the cards installed in the XCell
feeders are mixed on an ACI card. processor module match the configuration
established in eXpert. Ensure that all three-
phase feeders are configured before single-
phase feeders on the same card in the
ACIFDR table.
ACI-151 Max Current or Voltage input for an AC Check for inconsistencies between the eXpert
Channel is inconsistent across feeders. configuration and the installed hardware.
Ensure that all feeders are properly configured
in the ACIFDR table. Check maximum voltage
and current input settings.
ACI-152 Attempting to configure an incorrect number Check the software version number. Ensure
of feeders for the software installed. that the correct software is installed in the
XCell processor module for the intended
number of feeders. Some software versions
restrict feeder numbers.
ACI-154 Attempting to configure a feeder with no Check for inconsistencies between the eXpert
input AC channels. configuration and the installed hardware.
Ensure that all three-phase and single-phase
feeders are configured with voltage and
current inputs in the ACIFDR table.
Page 152
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
ACI-156 Attempting to configure more than one Make sure the cards installed in the XCell
voltage input on a single-phase feeder. processor module match the configuration
established in eXpert. Ensure that all single-
phase feeders are configured with no more
than one voltage input in the ACIFDR table.
ACI-157 Attempting to configure more than one Check for inconsistencies between the eXpert
current input on a single-phase feeder. configuration and the installed hardware.
Ensure that all single-phase feeders are
configured with no more than one current
input in the ACIFDR table.
ACI-158 No neutral current input for three-wire three- Check for inconsistencies between the eXpert
phase feeder has been defined. configuration and the installed hardware.
Ensure that all three-phase feeders are
configured with the correct neutral current
source settings in the ACIFDR table.
ACI-159 Three-phase derived power measurement Check for inconsistencies between the eXpert
configured on single-phase feeders. configuration and the installed hardware.
Ensure that when configuring a derived power
AC measurement all relevant settings are
correct in the ACM16 table.
ACI-160 Use of neutral current input inconsistent Ensure the correct eXpert configuration is
across feeders. downloaded. Ensure that neutral current input
settings are consistent with three-phase
feeder settings in the ACIFDR table.
ACI-161 There is a mismatch between the allowed Check the software version number. Ensure
number of feeders and the software version that the correct software is installed in the
installed. XCell processor module for the intended
number of feeders. Some software versions
restrict feeder numbers.
Page 153
Troubleshooting M anual Version 1.07
ACI-167 Attempting to configure an incorrect number Check the software version number. Ensure
of DC analogue measurements for the that the correct software is installed in the
software installed. XCell processor module for the intended DC
analogue measurements. Some software
versions do not support certain
measurements.
ACI-169 The phase of an AC Channel is inconsistent Check for inconsistencies between the eXpert
across feeders. configuration and the installed hardware.
Ensure there are no phase conflicts for AC
channels across feeders in the ACIFDR table.
ACI-170 Attempting direct memory access to a non- Make sure the cards installed in the XCell
existent ACI card. processor module match the configuration
established in eXpert. Ensure a working ACI
card is connected to the XCell processor
module.
ACI-171 Attempting direct memory write outside the Check for inconsistencies between the eXpert
ACI card's memory range. configuration and the installed hardware.
Ensure an installed protocol is not trying to
write to a non-existent memory location on the
ACI card.
ACI-172 Attempting direct memory read outside the Check for inconsistencies between the eXpert
ACI card's memory range. configuration and the installed hardware.
Ensure an installed protocol is not trying to
read from a non-existent memory location on
the ACI card.
Page 154
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
ACI-204 The ACI card has been removed or has Make sure the cards installed in the XCell
failed. processor module match the configuration
established in eXpert. Pow er-OFF the XCell
processor module Ensure an ACI card is
present and working with the XCell processor
module. If an ACI card is present and the
message persists the card may be faulty.
ACI-205 The ACI card has failed to enter its start-up Check for inconsistencies between the eXpert
sequence. configuration and the installed hardware.
Power the XCell OFF then ON again. Ensure an
ACI card is present and working with the XCell
processor module. If an ACI card is present
and the message persists the card may be
faulty and need to be replaced.
ACI-206 The ACI card heartbeat has failed to start, the Check for inconsistencies between the eXpert
XCell has set the card as failed. configuration and the installed hardware.
Power the XCell OFF then ON again, if
possible. Ensure an ACI card is present and
working with the XCell processor module. If an
ACI card is present and the message
persistent the card may be faulty and need
replacement.
ACI-207 ACI card hardware version is unsupported. At power ON there is a hardware version
mismatch between the XCell processor module
and the ACI card. Reboot the XCell processor
module and ensure it supports the particular
ACI hardware version installed.
Page 155
Troubleshooting M anual Version 1.07
ACI-209 ACI card failed to exit start-up sequence. At power ON, the DSP processor on an ACI
card failed to complete its start-up sequence.
ACI-209 may also appear at run-time if the
XCell processor module resets an ACI card
and the DSP fails to restart properly. The ACI
card is marked as failed, eXpert configurations
are rejected. Reboot the XCell, repeatedly if
required.
ACI-210 ACI card was unsuccessfully reset after The ACI card has failed to acknowledge
failing to accept a time update. receipt of current time from the XCell
processor module and did not restart when
the XCell reset it. The ACI card is marked as
failed, eXpert configurations are rejected.
Reboot the XCell, repeatedly as required and
check eXpert configuration tables.
ACI-230 Information message announcing that the ACI ACI card processor lost its heartbeat but the
card heartbeat has been restored. XCell processor module successfully reset the
card. This message is only of significance if it
recurs very frequently in which case a faulty
card may be in place.
ACI-231 ACI card has ignored XCell for more than 10 The ACI card is engaged in a critical operation,
minutes. for example, opening or closing a relay, and
cannot be interrupted by the XCell processor
module. No user action is required unless the
XCell displays ACI -231 every ten minutes in
which case the ACI card may have failed
while carrying out a critical operation.
Page 156
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
ACI-234 ACI card reset due to sixteen-bit AC The ACI card has reported a 16-bit AC
measurement out of range. measurement outside of the predetermined
range. The XCell processor module
automatically resets the ACI card when this
occurs and corrects the problem. The
message is of significance only if it occurs
very frequently. Check the eXpert
configuration.
ACI –235 ACI card reset due to 32-bit AC measurement The ACI card has reported a 32-bit AC
out of range. measurement outside of the predetermined
range. The XCell processor module
automatically resets the ACI card when this
occurs and corrects the problem. The
message is of significance only if it occurs
very frequently. Check the eXpert
configuration.
ACU - 002 Operating System error. Re-boot the XCell processor module. If the
message persists, carefully note the
conditions under which the message occurred
and consult your system supplier or equipment
vendor.
ACU - 003 There is an error in the configuration Examine the configuration carefully in eXpert,
downloaded to the XCell processor module. make changes as required, re-compile and
download the configuration again.
ACU - 004 There is an error in the configuration Examine the configuration carefully in eXpert,
downloaded to the XCell processor module. make changes as required, re-compile and
download the configuration again.
Page 157
Troubleshooting M anual Version 1.07
ACU - 013 Bad channel configured for an accumulator Ensure that the correct card type (HSC or DI)
(HSC) or Digital Input (DI) module. exists in the rack and that the channel number
selected in eXpert exists and is operational.
ACU - 019 The XCell unit has experienced an operating Note the operational conditions under which
system fault. the message occurs and contact your system
supplier or equipment vendor.
ACU - 020 There is an error in the configuration Examine the configuration carefully in eXpert,
downloaded to the XCell processor module. make changes as required, re-compile and
download the configuration again. If the
message persists, carefully note the
conditions under which the message occurred
and consult your system supplier or equipment
vendor.
ACU - 021 There is an error in the configuration Examine the configuration carefully in eXpert,
downloaded to the XCell processor module. make changes as required, re-compile and
download the configuration again. If the
message persists, carefully note the
conditions under which the message occurred
and consult your system supplier or equipment
vendor.
ACU - 026 Accumulator Channel already configured Check the channels configured for SDI’s and
DDI’s, as an overlap exists between these
records and the configured Accumulator
Records.
Page 158
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
AIP - 004 Invalid host Analogue Input configuration Ensure the host configuration for all Analogue
data. Input points is correct.
AIP - 006 Invalid host Analogue Input configuration Ensure that all Host Analogue Input Points are
data. configured with correct Analogue Input
channel numbers. Check using the Show
Hardware Configuration function on the front
panel menu that the correct I/O configuration is
displayed. Ensure all Analogue Input Cards are
correctly installed in the XCell processor
module. Ensure the XCell processor module
card is correctly installed in the backplane.
See The XCell User Manual for further
information.
AIP - 007 Invalid host Analogue Input configuration Ensure that all Host Analogue Input Points are
data. configured with correct Analogue Input
channel numbers. Check using the Show
Hardware Configuration function on the front
panel menu that the correct I/O configuration is
displayed. Ensure all Analogue Input Cards are
correctly installed in the XCell processor
module. Ensure the XCell processor module
card is correctly installed in the backplane.
See The XCell User Manual for further
information.
Page 159
Troubleshooting M anual Version 1.07
AO - 024 General Input / Output hardware failure. Ensure that all Host Analogue Output Points
are configured with correct Analogue Output
channel numbers. Check using the Show
Hardware Configuration function on the front
panel menu that the correct I/O configuration is
displayed. Ensure all Analogue Output Cards
are correctly installed in the XCell processor
module. Ensure the XCell processor module
card is correctly installed in the backplane.
See The XCell User Manual for further
information.
AO - 028 Invalid host output configuration data or Ensure that all Host Analogue Output Points
general Input / Output Hardware failure. are configured with correct Analogue Output
channel numbers. Check using the Show
Hardware Configuration function on the front
panel menu that the correct I/O configuration is
displayed. Ensure all Analogue Output Cards
are correctly installed in the XCell processor
module. Ensure the XCell processor module
card is correctly installed in the backplane.
See The XCell User Manual for further
information.
Page 160
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
AOI - 003 The XCell unit is reporting a general Input / Check that the Show Hardware Configuration
Output hardware failure. menu item, activated using the front panel
function button, displays the correct I/O
configuration. Ensure that all Analogue Output
Cards are correctly installed in the XCell
processor module. Ensure that the XCell
processor module card correctly installed in
the backplane.
AOI - 006 The XCell processor module reports an Ensure that all host Analogue Output Points
invalid host output configuration data or I/O are configured with correct Analogue Output
hardware failure. channel numbers. Check using the Show
Hardware Configuration function on the front
panel menu that the correct I/O configuration is
displayed. Ensure all Analogue Output Cards
are correctly installed in the XCell processor
module. Ensure the XCell processor module
card is correctly installed in the backplane.
See The XCell User Manual for further
information.
AOP - 004 The XCell processor module reports invalid Ensure host Configuration for all Analogue
host Analogue Output configuration data. Output Points is correct. Examine the
configuration carefully in eXpert, make
changes as required, re-compile and
download the configuration again.
AOP - 005 The XCell processor module reports invalid Ensure all host Analogue Output Points are
host Analogue Output configuration data. configured with valid conversion types.
Page 161
Troubleshooting M anual Version 1.07
bCD - 003 Invalid software installed. Contact your system supplier or equipment
vendor.
bCD - 004 The XCell processor unit reports insufficient Ensure that the processor module has
memory available for the task being sufficient RAM installed to carry out the
performed. required tasks. Install additional RAM if
required.
bCD - 015 The XCell processor unit reports an internal Re-boot the XCell unit, if the message persists,
software error. note the operational conditions under which
the message occurs and contact your system
supplier or equipment vendor.
bCD - 020 The XCell processor module reports an Note the operational conditions under which
internal database error. the message occurs and contact your system
supplier or equipment vendor.
bCD - 023 The XCell processor unit reports an internal Note the operational conditions under which
database error. the message occurs and contact your system
supplier or equipment vendor.
bCD - 034 There is insufficient memory installed on the Ensure that the processor module has
XCell processor unit. sufficient RAM installed to carry out the
required tasks. Install additional RAM if
required. Note the operational conditions under
which the message occurs and contact your
system supplier or equipment vendor.
bCD - 042 General Input / Output hardware error. Check all Input or Output modules installed
adjacent to the XCell unit; also check the
eXpert configuration.
bCD - 046 Invalid eXpert configuration downloaded to Check the locations of all boards adjacent to
the XCell processor module. the XCell unit against the intended eXpert
configuration.
Page 162
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
bCD - 071 The Digital Input module channel numbers do Ensure that the hardware configuration has
not match the eXpert configuration been saved, ensure that the eXpert
downloaded to the XCell processor module. configuration matches the installed hardware.
bCD - 074 An eXpert configuration was not Download the eXpert configuration again.
downloaded properly.
bCD - 078 Internal database problem. Note the operational conditions under which
the message occurs and contact your system
supplier or equipment vendor.
bCD - 081 Invalid configuration. Ensure that the hardware configuration has
been saved, ensure that the eXpert
configuration matches the installed hardware.
bCD - 082 Error in downloaded configuration. Verify the eXpert configuration and download
it again.
bRA - 001 Insufficient memory or memory corruption. Ensure that all RAM jumpers on XCell
processor module card are correctly set.
Ensure all RAM chips are correctly installed on
the XCell processor module. Refer to the
XCell User Manual for more information on
jumper settings.
bRA - 002 Insufficient BRAM memory or invalid Ensure that all RAM jumpers on XCell
allocation size specified by an application. processor module card are correctly set.
Ensure all RAM chips are correctly installed on
the XCell processor module. Refer to the
XCell User Manual for more information on
jumper settings.
CFG - 002 An operation has been attempted for an I/O Check that the target I/O card is recognised
channel not defined in a configuration, or the and is saved in the hardware configuration.
configuration has not been saved.
Page 163
Troubleshooting M anual Version 1.07
CFG - 007 The XCell processor module reports a Check the communications link. Reset the XCell
communications failure, the previous processor module and redo the eXpert
configuration did not terminate properly. configuration download.
CFG - 008 Configuration download in progress from Ensure no other host systems are
another host system. downloading.
CFG - 009 The XCell processor module has detected a Ensure that the version of the eXpert database
mismatch between the eXpert database field is compatible with the version of software
size and the XCell field size. running on the XCell unit.
CFG - 014 Database access is denied, database ‘in Reset the database lock. Wait approximately
use’ lock is set. Probably due to failure of a one minute for the previous download to
previous configuration download. session to time-out on the target XCell
processor module then download the
configuration again. If the problem recurs,
reset the XCell processor module.
CFG - 019 Unable to allocate memory. Verify that the downloaded configuration is as
expected.
Check RAM jumpers on XCell processor
module card correctly set. Ensure RAM chips
correctly installed. Possible network instability,
refer to the section on network
troubleshooting in this document.
CFG - 020 General configuration information message. Explanation depends upon the specific
configuration being attempted. Check the
configuration in eXpert.
CFG - 027 Unable to run software in EPROM. Check that Named Block is in memory. Ensure
download failed because the XCell processor it makes cold, warm and hot initialisations. Wait
module had not terminated the previous for approximately one minute to allow the
configuration session. previous download session to timeout on the
target XCell processor module and try to
download the configuration again.
Page 164
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
CGC – 111 An inconsistency was discovered with some Clear BRAM and redownload configuration.
configuration data and any outputs in this unit
will be disabled..
CGC – 112 The number of configuration tables (Static Contact Microsol.
Groups) has exceeded the allowed maximum
COU - 042 A bad frame was received from a KBUS Check if the KBUS device is functioning
device. The data will be re-requested. correctly and is correctly connected on the
communications line. Check the terminating
resistors and the cable shielding.
COU – 045 The wrong conversion function is defined in Review the conversion functions against the
the KBUS Map Table for a piece of data just data being polled. Verify the data type of each
received from a device. cell returned from the specific KBUS devices.
COU – 100 A KBUS device has been marked Offline. Check if the KBUS device is functioning
correctly and is correctly connected on the
communications line. Check the terminating
resistors and the cable shielding.
DB - 016 Time-out during access to a particular group Decrease the load on the XCell unit by
in the database by multiple applications. spreading the points over large scan periods
or by reducing the number of points
processed. Increase the applications time-outs
for database access.
DD - 011 A general message indicating that the Of itself this message is not indicative of a
processor has difficulty processing a specific problem. However, the message
received message. immediately before or after this message
should be noted and normally provides the
exact explanation.
DD - 015 The XCell processor module reports Check that all RAM jumpers on the XCell
insufficient memory. processor module card are correctly set.
Ensure all RAM chips are correctly installed.
Refer to the XCell User Manual for further
information on jumper settings.
DD - 030 Database locking during configuration. Reduce the number of points configured in a
single download.
Page 165
Troubleshooting M anual Version 1.07
DDI - 028 A digital input channel or channels, used in Ensure the channel numbers used in the DDI
the Double Digital Input point type configuration are correct. Check that the digital
configuration, does not exist. input card is recognised and is saved in the
hardware configuration.
DDI - 041 The channel or record specified in the Check the eXpert configuration against the
configuration does not exist. installed hardware; replace any removed or
failed card.
DI - 007 General Input / Output hardware failure. Check that the Show Hardware Configuration
menu item, activated using the front panel
function button, displays the correct I/O
configuration. Ensure that all Digital Input Cards
are correctly installed in the XCell processor
module. Ensure that the XCell processor
module card correctly installed in the
backplane.
DI – 018 General Input / Output hardware failure. Check that the Show Hardware Configuration
menu item, activated using the front panel
function button, displays the correct I/O
configuration. Ensure that all High Density
Digital Input Cards are correctly installed in the
XCell processor module. Ensure that the XCell
processor module card correctly installed in
the backplane.
DIP – 004 The XCell processor module reports an Ensure the host eXpert configuration is correct
invalid host Digital Input configuration. for all Digital Input points. Ensure that all host
Digital Input points are configured with correct
Digital Input channel numbers.
Page 166
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
DIP – 007 The XCell processor module reports an Ensure the host eXpert configuration is correct
invalid host Digital Input configuration. for all Digital Input points. Ensure that all host
Digital Input points are configured with
different Digital Input channel numbers.
DIP – 009 The XCell processor module reports an Ensure the host eXpert configuration is correct
invalid host Digital Input configuration. for all Digital Input points. Ensure that all host
Digital Input points are configured with correct
Digital Input channel numbers.
DIP – 010 The XCell processor module reports an Ensure the host eXpert configuration is correct
invalid host Digital Input configuration. for all Digital Input points. Ensure that all host
Digital Input points are configured with correct
Digital Input channel numbers.
DNT – 064 The XCell processor module is reporting a This message is normally seen soon after a
transitional network message. unit has been powered ON / OFF and can
usually be ignored. Allow the network to
stabilise for one minute after adding or
removing a unit.
DNT – 068 The XCell processor module is reporting a This message is normally seen soon after a
transitional network message. unit has been powered ON / OFF and can
usually be ignored. Allow the network to
stabilise for one minute after adding or
removing a unit.
Page 167
Troubleshooting M anual Version 1.07
DOP – 004 Invalid host Digital Output configuration data. Ensure that the host eXpert configuration for
all Digital Output points is correct.
HAI – 002 General Input / Output hardware failure. Check that the Show Hardware Configuration
menu item, activated using the front panel
function button, displays the correct I/O
configuration. Ensure that all Digital Input Cards
are correctly installed in the XCell processor
module. Ensure that the XCell processor
module card correctly installed in the
backplane.
HAI – 007 General Input / Output hardware failure. Check that the Show Hardware Configuration
menu item, activated using the front panel
function button, displays the correct I/O
configuration. Ensure that all Digital Input Cards
are correctly installed in the XCell processor
module. Ensure that the XCell processor
module card correctly installed in the
backplane.
HAI – 009 General Input / Output hardware failure. Check that the Show Hardware Configuration
menu item, activated using the front panel
function button, displays the correct I/O
configuration. Ensure that all Digital Input Cards
are correctly installed in the XCell processor
module. Ensure that the XCell processor
module card correctly installed in the
backplane.
Page 168
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
HDO – 002 The XCell processor module reports that it is Ensure that the Digital Output (HDO) card is
unable to power a Digital Output channel. correctly powered ON.
HDO – 005 The XCell unit is attempting to drive more than Ensure that the 2-up inhibit jumper on the
one Digital Output at the same time. Digital Output (HDO) card is set.
HDO – 070 The XCell is trying to send a zero value pulse Check the eXpert configuration is correct for
command i.e. trying to switch off a pulsed Digital Outputs; this message is usually just a
Digital Output. warning.
HDO – 073 The outputs have been disabled on this XCell Clear BRAM and redownload configuration.
because the periodic configuration validation
detected an inconsistency with some
configuration data..
IDI – 015 HDI card has failed. Replace or check the HDI module.
IDI – 025 The number of Digital Input signals received Do not connect or disconnect a SIM test box to
exceeds the capacity of the interrupt buffer. or from a live card.
This message can occur if a Microsol SIM Should this message occur in other
test box is disconnected and reconnected to circumstances please note the operational
a live card, generating spurious signals. conditions and contact your system supplier or
equipment vendor.
IE2 – 001 The XCell reports a difficulty in writing to its Check that the correct serial cable is being
serial port. used. Ensure that all relevant jumpers are set
correctly. Ensure that the correct serial port
settings have been included in the
downloaded eXpert configuration.
Page 169
Troubleshooting M anual Version 1.07
IEC – 001 Hardware failure or insufficient memory. Ensure that all RAM chips correctly inserted.
Check that the memory expansion card is
correctly installed. Ensure that a correct
version of IEC firmware is installed..
IEC – 002 Hardware failure or port configuration Ensure RAM chips correctly inserted. Ensure
problem. port is not being used by another protocol.
IEC – 010 Incorrect firmware installed on the XCell Ensure correct versions of IEC and BASE are
processor module board. installed.
IEC – 011 Incorrect firmware installed on the XCell Ensure correct versions of IEC and BASE are
processor module board. Incorrect version of installed. Ensure correct version of eXpert.
eXpert.
IEC – 020 Incorrect firmware installed on the XCell Ensure correct versions of IEC and BASE are
processor module board. installed.
IEC – 030 Incorrect firmware installed on the XCell Ensure correct versions of IEC and BASE are
processor module board. installed.
IEC – 040 Hardware failure or insufficient memory. Ensure that all RAM chips correctly inserted.
Check that the memory expansion card is
correctly installed. Ensure that a correct
version of IEC and BASE firmware is installed.
IEC – 041 Unrecognised message type received from Ensure correct versions of IEC and BASE are
the Master Station. installed in the XCell processor module. Check
the IEC message type byte in the frame sent
by IEC.
Page 170
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
IEC – 043 Error on reading from the internal time buffer, Ensure that correct versions of IEC and BASE
or general hardware failure. firmware are installed on the XCell processor
module card. Ensure that the memory
expansion card is installed.
IEC - 044 Error while processing internal IEC 870-5 Ensure correct versions of IEC and BASE are
protocol messages. Possible configuration installed on the XCell processor module board.
problem with the downloaded MAP table. Ensure a memory expansion card is installed.
Ensure that a correct configuration is
downloaded from eXpert.
IEC - 045 Error while accessing XCell database. Ensure correct versions of IEC and BASE are
Possible configuration problem with the installed. Ensure memory expansion card is
downloaded MAP table. installed. Ensure correct configuration is
downloaded from eXpert.
IEC - 046 Internal software problem. One of the This is a valid operational situation. Ensure that
following buffers has overflowed; Class 1 the host does not issue multiple simultaneous
buffer, Class 2 buffer or Command Response commands. Ensure a memory expansion card
buffer. is installed.
IEC – 047 Invalid protocol MAP table configuration. Ensure a valid eXpert protocol configuration
Attempt to access a non-existing IOA. was downloaded to the XCell unit. Ensure that
a memory expansion card is installed. In the
case of a General Interrogation or Counter
Interrogation command, ensure that the IOA is
zero.
IEC – 048 Attempt to perform a Single command failed. Ensure a valid protocol configuration was
downloaded to the XCell. Verify the host
database.
IEC – 049 The requested operation is neither a SELECT, Ensure a correct version of IEC firmware is
EXECUTE or BREAK. installed. Check the single command sent from
the master station.
Page 171
Troubleshooting M anual Version 1.07
IEC – 051 The requested operation is neither a SELECT, Ensure a valid eXpert protocol configuration
EXECUTE or BREAK. was downloaded to the XCell processor unit.
Verify that the XCell containing the outputs has
been configured correctly. Ensure a correct
version of IEC firmware is installed. Check the
double command sent from the master station.
IEC – 052 Attempt to perform a Double command failed. Ensure a valid eXpert protocol configuration
was downloaded to the XCell processor unit.
Verify that the XCell containing the outputs has
been configured correctly. Ensure a correct
version of IEC firmware is installed. Check the
double command sent from the master station.
IEC – 053 Attempt to perform a regulating step Ensure a valid eXpert protocol configuration
command failed. was downloaded to the XCell processor unit.
Verify that the XCell containing the outputs has
been configured correctly. Ensure a correct
version of IEC firmware is installed. Check the
regulating step command sent from the master
station.
IEC – 054 Attempt to perform a regulating step Ensure a valid eXpert protocol configuration
command failed. was downloaded to the XCell processor unit.
Verify that the XCell containing the outputs has
been configured correctly. Ensure a correct
version of IEC firmware is installed. Check the
regulating step command sent from the master
station.
Page 172
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
IEC – 056 Failure when constructing a reply to a Ensure that correct versions of IEC and BASE
command message. Insufficient memory for a firmware are installed in the XCell. Ensure a
reply. memory expansion card is installed.
IEC – 057 Problem encountered when processing Ensure a valid protocol configuration was
Counter Request. Either the COT or the VSQ downloaded to the cell. Check the interrogation
in the received frame is incorrect (i.e. not in command issued by the master station.
accordance with the IEC specifications).
IEC – 058 Error encountered when processing the QOI Ensure a valid protocol configuration was
parameter in a received message. downloaded to the cell. Check the interrogation
command issued by the master station.
IEC – 059 Error encountered when processing the Ensure a valid protocol configuration was
Parameter Loading command. downloaded to the cell. Check the measured
value issued by the master station.
IEC – 060 Error encountered when accessing Ensure a valid protocol configuration was
database. downloaded to the cell. Ensure a correct
version of IEC is installed in the XCell unit.
IEC – 061 Error encountered when processing time Ensure a valid protocol configuration was
functions within the IEC protocol. downloaded to the cell. Ensure correct
versions of IEC 870-5 protocol firmware is
installed in the XCell unit.
IEC – 062 Change message received is not a FULL- Ensure a valid protocol configuration was
UPDATE or a Normal Change message. downloaded to the XCell. Ensure correct
versions of IEC 870-5 protocol firmware is
installed in the XCell unit.
Page 173
Troubleshooting M anual Version 1.07
IEC – 064 Error encountered when processing protocol Ensure a valid protocol configuration was
database, following a cell failure on the local downloaded to the cell. Ensure correct
network. IEC cannot pack unit status events. versions of IEC 870-5 protocol firmware.
Check the unit operational status. Check
network.
IEC – 065 Error encountered when constructing a 7- Ensure a correct version of IEC firmware is
byte time-stamp. installed. Ensure that a memory expansion
card is installed.
IEC – 066 Error encountered processing SELECT Ensure a valid protocol configuration was
operation for a Set Point command. downloaded to the cell. Ensure correct
versions of IEC 870-5 protocol firmware are
installed in the XCell processor unit.
IEC – 067 Error encountered processing EXECUTE Ensure a valid protocol configuration was
operation for a Set Point command. possible downloaded to the cell. Ensure correct
error in the eXpert configuration. versions of IEC 870-5 protocol firmware.
IEC – 068 Error encountered processing BREAK Ensure a valid protocol configuration was
operation for a Set Point command. downloaded to the cell. Ensure correct
versions of IEC 870-5 protocol firmware.
IEC – 069 Error encountered trying to select a single Ensure a valid protocol configuration was
t w o-stage output when another two-stage downloaded to the cell (only one active two /
output on the same card is already active. three-stage output may be selected per card.
This message is also encountered when A select should not be sent to a single-stage
trying to select a single two-stage output command. Enter the commands in the correct
when that output is already selected. sequence).
Also occurs if a select is sent to a single Ensure correct versions of IEC 870-5 protocol
stage output. firmware.
IEC – 070 An XCell unit containing a Digital Output card Ensure the target XCell unit is on-line.
has gone off-line.
IEC – 071 Error encountered processing BREAK Ensure a valid protocol configuration was
operation for a Single command. downloaded to the cell. Ensure correct
versions of IEC 870-5 protocol firmware.
Page 174
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
IEC – 073 Error encountered processing EXECUTE Ensure a valid protocol configuration was
operation for a Double command. downloaded to the cell. Ensure a correct
version of IEC 870-5 protocol firmware is
installed in the XCell processor unit.
IEC – 074 Error encountered processing BREAK Ensure a valid protocol configuration was
operation for a Double command. downloaded to the cell. Ensure a correct
version of IEC 870-5 protocol firmware is
installed in the XCell.
IEC – 075 Error encountered when processing Counter Ensure a valid protocol configuration was
Interrogation command. downloaded to the cell. Ensure a correct
version of IEC 870-5 protocol firmware is
installed in the XCell processor module.
IEC – 076 Bad internal data type. Contact your system supplier or equipment
vendor.
IEC – 077 The XCell unit is reporting an internal data Note the operational conditions under which
type error. the message was displayed and contact your
system supplier or equipment vendor.
IEC – 080 Error encountered when formatting Ensure correct versions of IEC 870-5 protocol
messages for transmission to host. firmware. Check for Hardware failure. Ensure
the memory expansion card is correctly
installed.
IEC – 084 Invalid regulation step command. Check input message parameters.
IEC – 100 Error encountered when attempting to Ensure correct versions of IEC 870-5 protocol
allocate memory. firmware. Check for Hardware failure. Ensure
memory expansion card is correctly installed.
Page 175
Troubleshooting M anual Version 1.07
IEC – 102 The XCell processor module is reporting a Check that the IEC Map table in the eXpert
Point Type problem during a general configuration has been completed properly.
integration.
IEC – 103 An error has been encountered when Note the operational conditions under which
packing events. the message was displayed and contact your
system supplier or equipment vendor.
IEC – 104 A bad event buffer class was encountered Note the operational conditions under which
in the IEC firmware. the message was displayed and contact your
system supplier or equipment vendor.
IEC – 105 Error encountered when a large number of The RTU should be polled to empty the buffers
events are generated and polling of the RTU
has not taken place. If more events are
generated without polling the oldest events
are deleted one by one to make room for the
newest events. A background scan will
occur after polling is resumed to restore the
correct status of all deleted events.
IEC – 110 The IEC clock has drifted since the last time Check IECGEN table in the eXpert configuration
synchronisation. Host did not send Time Sync for expected time period. Send a time
message within expected time period. synchronisation command to the unit.
IEC – 199 Error encountered when continuous In order for more commands to be accepted by
commands sent to the RTU and no polling for the RTU polling of the RTU needs to occur
responses takes place. The command continuously. This polling will retrieve previous
response buffer has overfilled. command responses and keep the buffer from
getting filled.
IEC – 200 High-priority output message buffer RTU polling should occur more frequently to
overflow. Ususlly occurs when multiple retrieve previous command responses and
digital output drives are sent but the RTU is keep the buffer from getting filled.
not polled for responses
Page 176
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
IEC – 219 Sequencing error during an IEC file transfer. Usually no action required. The transfer
mechanism recovers. If the problem persists,
note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor
IEC – 221 File transmission error, or incorrect Check connections and try again. Check and,
configuration file or file number generated. if necessary, change the configuration file
number in IECFIL.
IEC – 223 Unable to overwrite a file because the file is Information message.
ready for upload.
IEC – 225 Bad redundancy, Configuration Unit Number. Check unit number in the eXpert configuration.
Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
IEC – 227 Error encountered when returning time Note the operational conditions under which
buffer. the message was displayed and contact your
system supplier or equipment vendor.
IEC – 235 Error getting Sequence Of Events (SOE) time Upload the Sequence Of Events (SOE) file;
buffer, i.e there is no partition space left to though the contents may be lost. Note the
make a Sequence Of Events (SOE) time operational conditions under which the
entry. message was displayed and contact your
system supplier or equipment vendor.
IEC – 247 Error in version number for PMR in IEC. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
IEI – 132 Received an IOA that is not in the Master Map Check the Master and Slave IEC Map Tables.
Table and therefore cannot be processed.
Page 177
Troubleshooting M anual Version 1.07
NET – 021 Internal software problem. Bad pointer to Check that all RAM jumpers on the XCell
data area or corrupt local data storage. processor module card are correctly set.
Ensure all RAM chips are correctly installed.
Ensure that correct versions of PROMs are
installed.
NET – 039 Internal software error. There are no more Possible network instability. Refer to the
Net-PB buffers available in the NPBP partition. section on network troubleshooting in this
This is a fatal error. A system limit has been document.
reached or there is incorrect operation of the
network, leading to a bottleneck.
NET- 085 Internal memory allocation problem Check that all RAM jumpers on XCell processor
module card are correctly set. Ensure that all
RAM chips correctly installed on the circuit
board. Ensure an expanded memory board is
installed on the XCell processor card.
NET- 087 Internal software error. The network layer is Ensure all expected XCell processor modules
attempting to transmit a message with either are online and operational. Check for possible
of the following conditions present: network instabilities.
• The address of the destination unit is the
local unit.
• The destination unit does not exist in the
Route Table.
Page 178
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
NET – 095 The XCell processor reports insufficient Check that all RAM jumpers on XCell processor
internal memory. module card are correctly set. Ensure that all
RAM chips correctly installed on the circuit
board. Ensure an expanded memory board is
installed on the XCell processor card.
NET – 096 The XCell processor reports insufficient Check that all RAM jumpers on XCell processor
internal memory. module card are correctly set. Ensure that all
RAM chips correctly installed on the circuit
board. Ensure an expanded memory board is
installed on the XCell processor card.
NET – 149 The XCell processor reports insufficient Check that all RAM jumpers on XCell processor
internal memory. module card are correctly set. Ensure that all
RAM chips correctly installed on the circuit
board. Ensure an expanded memory board is
installed on the XCell processor card.
NET – 152 Internal memory allocation problem. Check that all RAM jumpers on XCell processor
module card are correctly set. Ensure that all
RAM chips correctly installed on the circuit
board. Ensure an expanded memory board is
installed on the XCell processor card.
NET - 184 Detected the loss of a number of messages Check the network connections and
on FieldNet network and initiating message terminations and unit addressing conflicts.
recovery Check the online LED and list of Online Units
(OLU) on the frfont panel.
Page 179
Troubleshooting M anual Version 1.07
NET – 189 Internal XCell software problem. Datalink Check that all RAM jumpers on XCell processor
transmit task failed some initialisation. module card are correctly set. Ensure that all
RAM chips correctly installed on the circuit
board. Possible network instability, refer to the
section on network troubleshooting in this
document.
NET – 201 Excessive system load. Decrease the load on the XCell processor unit
by spreading points over large scan periods or
by reducing the number of points processed.
Possible network instability, refer to the
section on network troubleshooting in this
document.
NET – 225 Excessive system load. Decrease the load on the XCell processor unit
by spreading points over large scan periods or
by reducing the number of points processed.
Possible network instability, refer to the
section on network troubleshooting in this
document.
NET – 255 Message reserved for reporting errors in Debug code operating in the system software.
debug code. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
PTE – 010 Invalid Host Output configuration data. Ensure that instrument limits for all host
Analogue Points using square root conversion
are correctly configured.
RAI – 003 Unsupported operation on analogue inputs. Check all I/O mapping in the RTU’s protocol
This may be due to an attempt to drive an interfaces to the MMI for analogue inputs
analogue input mapped as outputs.
.
Page 180
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
RAI – 013 The XCell processor module is reporting a Check that the Show Hardware Configuration
general Input / Output hardware failure. function on the front panel menu displays the
correct Input / Output configuration. Ensure
that all Input / Output Cards are correctly
installed in the rack adjacent to the XCell
processor module. Refer to the XCell User
Manual for further information.
RDI – 007 The XCell processor module is reporting a Check that the Show Hardware Configuration
general Input / Output hardware failure. function on the front panel menu displays the
correct Input / Output configuration. Ensure
that all Input / Output Cards are correctly
installed in the rack adjacent to the XCell
processor module. Refer to the XCell User
Manual for further information.
RDI – 011 The XCell processor module is reporting a Check that the Show Hardware Configuration
general Input / Output hardware failure. function on the front panel menu displays the
correct Input / Output configuration. Ensure
that all Input / Output Cards are correctly
installed in the rack adjacent to the XCell
processor module. Refer to the XCell User
Manual for further information.
RDI – 024 Internal XCell software problem; bad GSR Illegal action performed on an input; check the
call. eXpert configuration for inconsistencies.
RDI – 039 Digital input transitions have occurred which This is a valid operational condition but it is
are less than the debounce time. notified to the operator in case there is some
underlying problem with the input that needs to
be addressed.
Page 181
Troubleshooting M anual Version 1.07
RDO – 020 Attempting to drive the channel incorrectly. A Check configuration to see if a channel is
bad response to the ACTIVATE command configured as 3 stage. Check that Show
was received. Hardware Configuration function on the front
panel menu displays the correct Input / Output
configuration. Ensure that all Digital Output
Cards are correctly installed in the rack
adjacent to the XCell processor module.
RDO – 021 Attempting to drive the channel incorrectly. A Check configuration to see if channel is
bad response to the REQUEST command configured as 3 stage. Check that Show
was received. Hardware Configuration function on the front
panel menu displays the correct Input / Output
configuration. Ensure that all Digital Output
Cards are correctly installed in the rack
adjacent to the XCell processor module.
RDO – 022 Attempting to drive a three-stage output with Check the DOT configuration to see if the
a single stage command channel configuration matches the issued
Or drive command.
A problem driving an output with a pulse
command
RDO – 027 Attempting to drive a channel for which there Check the DOT configuration and determine if
is no DOT configuration. the channel is configured, if not, configure the
channel.
RDO – 034 Attempting to drive a second 3-stage output Wait until the first output pulses OFF (if it is
when a 3-stage output is already activated in configured as pulse) or drive it OFF (if it is
the XCell processor unit. configured as steady) before driving the
second output ON.
Page 182
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
RDO – 052 If the Enable signal is not in the correct state, Check that the Enable signal is in the correct
this error will occur when trying to drive the state before driving the corresponding output.
corresponding output.
RDO – 053 Attempting to drive an output as a single Ensure output is configured to the mode in
stage output when the output is configured which it will be driven. Check the DOT
as a three-stage output. configuration to determine if the channel is
configured as a 3 stage. If so, configure it as a
single stage channel.
RHS – 001 Invalid Configuration for HSC Point Type. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
RHS – 002 Invalid Configuration for HSC Point Type. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
RHS – 003 Incorrect software versions. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
RHS – 004 Hardware I/O error. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
RHS – 005 Hardware I/O error or memory failure. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
RHS – 006 Insufficient memory. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
Page 183
Troubleshooting M anual Version 1.07
RHS – 008 System limit reached. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
RHS – 009 System limit reached. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
RHS – 010 General Input / Output hardware fault, failure Check that Show Hardware Configuration
to read a channel count. function on the front panel menu shows that a
HSC card is present. Ensure that all jumpers
are set for the correct slot position and that
the XCell processor module card is correctly
installed in the backplane.
RHS – 013 Internal software problem. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
RHS– 014 Internal software problem. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
RHS – 015 Internal software problem. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
RHS – 016 Internal software problem. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
RHS – 017 Internal software problem. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
Page 184
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
RP5 – 001 Error encountered while trying to free Ensure that PROMS containing the correct
memory. version of RP570 protocol software are
installed. Check for general hardware failure.
If present, ensure that the memory expansion
card is fitted correctly.
RP5 – 008 Error encountered while trying to free Ensure that PROMS containing the correct
memory. version of RP570 protocol software are
installed. Check for general hardware failure.
If present, ensure that the memory expansion
card is fitted correctly.
RP5 – 009 Invalid protocol map table configuration table. Ensure that a valid eXpert protocol
Attempting to access a non existing object configuration was downloaded to the XCell
number. processor module. If present, ensure that the
memory expansion card is fitted correctly.
RP5 – 011 Invalid protocol map table configuration table. Ensure that a valid eXpert protocol
Attempting to access a non-existing or invalid configuration was downloaded to the XCell
UGFR. processor module. If present, ensure that the
memory expansion card is fitted correctly.
RP5 – 012 Internal Software problem. Contact the system supplier or equipment
vendor.
RP5 – 013 Error encountered while trying to send a 1- If the selected output is not on a local XCell
stage drive command. unit, make sure the XCell unit with the selected
output Is powered ON and on-line. Otherwise
contact the system supplier or equipment
vendor.
RP5 – 015 Internal Software problem. Contact the system supplier or equipment
vendor.
RP5 – 016 Error encountered while processing a host Check that the frame sent by the host us a
command. valid RP570
Page 185
Troubleshooting M anual Version 1.07
RP5 – 021 Error encountered while accessing the XCell Ensure that correct versions of firmware are
database. installed. Ensure that a valid eXpert protocol
configuration was downloaded to the XCell
processor module. If present, ensure that the
memory expansion card is fitted correctly.
RP5 – 022 Internal software problem. Contact the system supplier or equipment
vendor.
RP5 – 023 Device read error. Ensure that the communication parameters in
the general protocol configuration table and
the master/Host are the same, e.g. parity, baud
rate, stop and start bits etc.
RP5 – 024 Invalid protocol general configuration. Ensure that a valid eXpert protocol
configuration was downloaded to the XCell
processor module. If correct, contact the
system supplier or equipment vendor.
RP5 – 028 Internal software problem. Contact the system supplier or equipment
vendor.
RP5 – 030 An incorrect range may be specified for a Check the range specified for each data type
data-type in the protocol map table or an in the protocol map table.
invalid protocol map table exists.
RP5 – 035 Invalid protocol map table for counters. Ensure that a valid eXpert protocol
configuration for counters is downloaded to
the XCell processor module.
RP5 – 036 Invalid protocol map table for digital data Ensure that a valid eXpert protocol
types. configuration for digital data types is
downloaded to the XCell processor module.
Page 186
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
RP5 – 039 Internal software problem. Contact the system supplier or equipment
vendor.
RP5 – 040 Internal software problem. Contact the system supplier or equipment
vendor.
RP5 – 041 Internal software problem. Contact the system supplier or equipment
vendor.
SDI – 042 The message indicates that a channel record 1. A configuration for an SDI has been
is missing. This can be triggered by many downloaded but the corresponding
conditions. These are some of them: channel is faulty or the card is missing.
RHS – 019 Internal software problem. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
SIO – 011 Insufficient memory. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
Page 187
Troubleshooting M anual Version 1.07
SPT – 028 Insufficient memory. Check that the RAM jumpers on the XCell
processor module card are correctly set.
Ensure RAM chips are correctly installed.
SPT – 034 Excessive system load. Decrease the load on the XCell unit by
spreading points over large scan periods or by
reducing the number of points being
processed. Decrease amount of I/O in the unit.
If the problem persists note the operational
conditions under which the message was
displayed and contact your system supplier or
equipment vendor.
SYS – 036 Insufficient memory. Check that the RAM jumpers on the XCell
processor module card are correctly set.
Ensure RAM chips are correctly installed.
SYS – 064 Insufficient memory. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
SYS – 065 Attempting to release unallocated memory. Note the operational conditions under which
the message was displayed and contact your
system supplier or equipment vendor.
TCP – 022 The IPE-101 card is not present or not Restart the unit ensuring that the IPE 010 is
powered on. powered up at the same time or before the
XCel processor module.
TCP – 039 Unable to obtain semaphore within the time When this occurs the system already has a
period allocated, problem in the driver; the code is not
functioning correctly.
Page 188
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
TCP – 041 It is not possible top bind an address to a System should self-recover from this error.
socket which has been created. Otherwise reboot the system.
TCP – 042 No space available to create a new socket This system only allows the user to open a
parameter block. certain number of sockets. If this number is
exceeded this message is given. To avoid this
problem, close some of the opened sockets.
TCP – 043 No space available for socket transmit and This error causes the system to reboot since
receive buffers the system cannot find any available space to
copy messages through the stack layers. This
may be due to incorrect closing of a previously
opened socket.
TCP – 044 Initialisation of pNA+ has failed Internal pSOS problem. Will only occur on start
up.
Reboot the system, if problem persists note
the operational conditions under which the
message was displayed and contact your
system supplier or equipment vendor.
TCP – 047 Unable to create Read Ahead Buffer for use There is no space available in the HEAP or it is
w ith a newly created socket. too fragmented to create a RAB. Install more
RAM on the XCell processor module; a
temporary solution is to restart the system.
TCP – 048 Unable to create mirror buffer for Ethernet There is no space available in the HEAP or the
card. HEAP is too fragmented to create an RAB.
Install more RAM on the XCell processor
module temporary solution is to restart the
system.
Page 189
Troubleshooting M anual Version 1.07
TCP – 050 Connection of host and local socket has Perhaps the host has abandoned the
failed. connection. The system should resolve this
problem.
TCP – 051 Cannot read characters from socket receive Memory allocation problems. May need to
buffer reboot system if the problem is not resolved
internally.
TCP – 052 Incorrect system start up or power was Reset the IPE - 010 card by switching power
removed from IPE - 010 temporarily supply off and on before restarting the
system.
TCP – 053 Cannot return memory to Heap after closing This will eventually cause problems with
socket. memory leakage.
Restart the system at the first available
opportunity.
TCP – 054 Non recoverable error in system In this situation the unit reboots due to memory
allocation problems within the system.
UIP – 016 XCell message timed out. An XCell processor Check that eXpert or eXplore are still running.
module timed out while waiting for a Ensure that the communications link between
response from eXpert or eXplore. the PC running eXpert and the XCell processor
module is secure and functioning.
UIP – 017 Destination XCell not responding. eXpert or Ensure the destination XCell’s unit address is
eXplore is attempting communication from one correctly configured in eXpert.
XCell processor module to another XCell
processor module which is not responding.
UIP – 018 Destination XCell is not found. eXpert or Ensure the destination XCell is on the network
eXplore is attempting communication from one and is powered ON and functioning.
XCell processor module to another XCell
processor module which cannot be seen on
the network.
Page 190
Front Panel Diagnostic Messages
Troubleshooting Manual
Version 1.06
Page 191
Document Number 404001-104
Issue Date: 25 August 2000