You are on page 1of 1

TECHNICAL DATA SHEET

Synchronous Alternators
Model: GTA 202 AS36 for P-110

Insulation class 180ºC (H) Excitation sistem: Brushless with auxiliary coil
Degree of protection IP21 Stator winding pitch 2/3
Leads 12 Stator winding layers 2
Air flow (m/s) 0.5 Number of poles 4
IEC frame 200 Pole type Saliente
Cooling IC01 Voltage regulator
Altitude (m) a.s.l. ≤ 1000m Accuracy (stability) To be defined

Speed (rpm) - 50Hz 1500 Rated current To be defined


GENERAL DATA

Speed (rpm) - 60Hz 1800 Analog input To be defined


Overspeed (rpm) 2250 Digital input To be defined
Power factor 0,8 a 1,0 Pick currient To be defined
Exciter stator winding resistance at 20ºC (Ohm) 10,6 Droop / CT To be defined

Stator winding resistance at 20ºC (Ohm) 0,06 Dynamical recovery (ms) To be defined
Rotor winding resistance (Ohm) 1,4 U/F To be defined
T.H.D. (Total Harmonic Distortion) (at no load) (%) <5% Internal voltage adjustment To be defined
Non-drive end bearing 6216-2RSC3 External voltage adjustment To be defined
Drive end bearing (B35T) 6320-2RSC3 Transient recovery time for ΔU=20% To be defined
Single bearing Double bearing
Alternator mass(kg)
355 B35: 375 B3: 361
Inertia WR² (kgm2) 0,63 0,57

50Hz 60Hz
Frequency and number of phases
Three-phase Single-phase Three-phase Single-phase

Y Connection 380 400,0 415,0 380,0 400,0 416,0 440,0 480


VOLTAGE (V)

YY Connection 190,0 200,0 207,5 190,0 200,0 208,0 220,0 240,0


Δ Connection 220,0 231,0 240,0 220,0 231,0 240,0 254,0 277,0
ΔΔ Connection 110,0 115,0 119,0 110,0 115,0 119,0 127,0 138,0
Single phase low zig-zag or single phase delta 190-200 220-240
OUTPUTS (kVA)

ΔT=125°C (ta=40°C) 100,0 100,0 100,0 57,5 111,0 112,5 112,5 113,0 113,0 65,0
ΔT=150°C (ta=40°C) 110,0 110,0 110,0 63,5 122,0 124,0 124,0 125,0 125,0 72,0
ΔT=163°C (ta=27°C) 115,0 115,0 115,0 66,0 127,0 129,5 129,5 130,0 150,0 75,0

Xd (%) - Direct axis synchronous reactance 223 187 161 291 333 299 272 234 176 305
X'd (%) - Direct axis transient reactance 11,7 10,3 9,4 15,2 16,2 14,7 13,5 12,0 9,7 15,6
X"d (%) - Direct axis subtransient reactance 9,3 8,2 7,5 12,1 12,9 11,7 10,8 9,5 7,7 12,4
ELECTRICAL DATA (FP=0,8 - Δt=125ºC - ta=40ºC)

Xq (%) - Quadrature axis sync. reactance 71,6 57,1 46,6 93,0 119,2 104,8 93,4 77,1 53,8 100,4
X"q (%) - Quadrature axis subtrans. reactance 11,9 10,6 9,6 15,5 16,4 15,0 13,7 12,2 9,9 15,8
X2 (%) - Negative sequence reactance 11,0 9,0 9,0 14,0 15,0 13,0 12,0 11,0 9,0 14,0
X0 (%) - Zero sequence reactance 2,0 1,0 1,0 2,0 2,0 2,0 2,0 2,0 1,0 2,0
T'd (ms) - Direct axis trans. short circ. time constant 44 44 44 44 45 45 45 44 44 44
T"d (ms) - Direct axis subtrans. short circ. time constant 0,9 0,8 0,7 0,9 1,1 1,0 1,0 0,9 0,8 0,9
T'do (ms) - Transient open circuit time constant 858 809 760 858 935 923 911 882 809 882
T''do (ms) - Subtrans. constant of opened circuit 1,3 1,3 1,3 1,3 1,3 1,3 1,3 1,3 1,3 1,3

Ta (ms) - Short circuit time const. of armature 8 7 7 8 8 8 8 8 7 8

uc (V) - Full load excitation voltage 36,3 37,2 38,5 35,3 32,9 32,6 32,3 32,4 33,5 31,3

ic (A) - Full load excitation current 3,0 3,1 3,2 2,9 2,7 2,7 2,7 2,7 2,8 2,6

ic (A) - No load excitation current 1,0 1,1 1,2 1,0 0,8 0,8 0,8 0,9 1,1 0,9

Icc (A) - Sustained short-circuit current 456 433 417 719 506 487 468 445 408 812

Short-circuit ratio (Kcc) 0,43 0,51 0,59 - 0,30 0,33 0,36 0,42 0,54 -

Power factor 0,8 1,0 0,8 1,0 0,8 1,0 0,8 1,0 0,8 1,0 0,8 1,0 0,8 1,0 0,8 1,0 0,8 1,0 0,8 1,0
EFFICIENCY (%)

25% of load 87,6 90,3 86,6 89,5 85,8 88,8 81,9 85,4 90,0 92,3 89,6 91,9 89,2 91,6 88,5 90,9 86,9 89,6 83,4 86,6

50% of load 90,6 92,9 90,2 92,6 89,8 92,2 86,8 89,7 91,8 93,8 91,8 93,8 91,7 93,8 91,5 93,6 90,9 93,0 88,2 90,8

75% of load 90,6 93,0 90,5 92,9 90,3 92,8 87,3 90,3 91,3 93,4 91,5 93,6 91,6 93,7 91,7 93,8 91,6 93,7 88,8 91,4

100% of load 89,8 92,5 90,0 92,7 90,0 92,6 86,7 89,9 90,2 92,5 90,6 92,8 90,9 93,1 91,2 93,4 91,4 93,6 88,4 91,1

125% of load 88,9 91,7 89,2 92,1 89,3 92,2 - - 88,9 91,5 89,5 91,9 89,9 92,3 90,4 92,8 90,8 93,3 - -

According to : IEC 60034 - NBR 5117 - NEMA MG1 - VDE530 - ISO8528 - CSA FDE 42372
The values indicated are typical values and subject to change without prior notice. Rev. 1
Satured reactances values abr-16