PLANT DETAILS
Make: Merlin Gerlin Rated Voltage: 1000 V Tripping Voltage: N/A Closing Voltage: N/A
Model: Masterpact M32 H1 Nominal Current: 3200 A Mechanism: ✘ Spring Solenoid Hydraulic S/Pole
Serial Number: N/A Short Circuit Current: 75 kA Format: Live Tank Dead Tank ✘ Indoor Outdoor
Asset Number: N/A Short Circuit Time: 1 Sec Insulating Medium: Oil ✘ Air SF6 Vacuum
OPERATION TESTS
INJECTION TRIP TIME IN EXPECTED TIME IN STATUS
CURRENT SECONDS SECONDS
LONG TIME (2x) 180 mA 15.02 s 16.87 s PASSED
LONG TIME (3x) 268 mA 6.89 s 7.55 s PASSED
LONG TIME (6x) 488 mA 1.93 s 1.88 s PASSED
SHORT TIME 320 mA 0.07 s 0.00 s PASSED
INSTANTANEOUS 800 mA 0.08 s 0.00 s PASSED
GROUND FAULT 100 mA 0.52 s 0.40 s PASSED
COMMENTS:
Relay on the breaker was tested as per the configured settings and is found to be working satisfactory.