MASTERPACT CIRCUIT BREAKER RESULT FORM

LOCATION Marandoo SUBSTATION MC02 CLIENT REF 84722456


MC02CB02
EQUIPMENT ID BAY/ PANEL OF-2 CUSTOMER RTIO
INCOMER 2

PLANT DETAILS
Make: Merlin Gerlin Rated Voltage: 1000 V Tripping Voltage: N/A Closing Voltage: N/A

Model: Masterpact M32 H1 Nominal Current: 3200 A Mechanism: ✘ Spring Solenoid Hydraulic S/Pole

Serial Number: N/A Short Circuit Current: 75 kA Format: Live Tank Dead Tank ✘ Indoor Outdoor

Asset Number: N/A Short Circuit Time: 1 Sec Insulating Medium: Oil ✘ Air SF6 Vacuum

TESTED WITH STR TEST UNIT


Relay Type STR 58 U Setting Scale Condition and Unit
Rated Current
With 3200 A 1.0 x In
(Io)
With Current Setting (Ir) 0.9 x Io
Long Time delay Trip (LT) Time Setting (tr) 30 sec
Time Multiplier Setting 1.5 x Ir
Hot /Cold Selected N/A Cold
Current Setting (Im) 3 x Ir
Short time delay trip (ST)
Time Setting (tm) 0 sec

I²t Select Switch OFF


Instantaneous Trip
Current Setting (Ii) 8 x In
(INST)
Current Setting (Ih) 1000 A

Ground Fault (G) Time Setting (th) 0.4 Sec

I²t Select Switch ON

OPERATION TESTS
INJECTION TRIP TIME IN EXPECTED TIME IN STATUS
CURRENT SECONDS SECONDS
LONG TIME (2x) 180 mA 15.02 s 16.87 s PASSED
LONG TIME (3x) 268 mA 6.89 s 7.55 s PASSED
LONG TIME (6x) 488 mA 1.93 s 1.88 s PASSED
SHORT TIME 320 mA 0.07 s 0.00 s PASSED
INSTANTANEOUS 800 mA 0.08 s 0.00 s PASSED
GROUND FAULT 100 mA 0.52 s 0.40 s PASSED

COMMENTS:
Relay on the breaker was tested as per the configured settings and is found to be working satisfactory.

DATE: TESTED BY: WITNESS: APPROVED BY:

08/03/2020 D. Deshmukh G. Morrow

ANY PRINTED COPY OF THIS DOCUMENT IS NOT CONTROLLED Page 1 of 1