You are on page 1of 4

PT.

INSPIRA ENERGI SEKAWAN


ENGINEERING - PROCUREMENT - CONTRACTOR

LOW VOLTAGE CIRCUIT BREAKER TEST REPORT


Testing Company: Customer:
Address: Address:

Phone
Phone: :
Name of Panel: INCOMING GEN 1 Contact Name:
Job/Contract #: Equipment Type: -
Date: 15/07/2022

BREAKER NAME PLATE DATA


Family Breaker
Mfg: : EASYPACT Type: MT08
Seria
Standard: IEC Interrupt Rating: N1 l #:

TRIP UNIT DATA


MICROLOGI Seria
Family: C Type: 2.0 A l #:

TRIP UNIT BASIC PROTECTION SETTINGS


As As
Foun As Teste
Parameter d Left d I2t Current Level
Sensor Rating (In) 800 A 800 A
LT Switch Setting (Io) x In A
Long Time Pickup (Ir) 1 x In 800 A
Long Time Delay (tr) 8 Sec
Inverse Definite Min.Time
Lag (Idmtl) OFF
Short Time Pickup (Isd, Im) 10 x Ir ### A
Short Time Delay (tsd) 0 Sec Off
Instantaneous Pickup (Ii) OFF x In Off A
Ground Fault Pickup (Ig) x In 0 A
Ground Fault Delay (tg) Sec
Ground Fault Push to Trip
Button

FFTK File Name: LVMDP-2 Automatic Test Results


Trip Statu
Parameter Test Current Level Time s
6,14 Se
Long Time Pickup (Ir) 5600 A 7 x Ir 8 c Pass
0,06 Se
Short Time Pickup (Isd, Im) 10000 A 10 x Ir 2 c Pass
Instantaneous Pickup (Ii) 0 0 x In 0
Ground Fault Pickup (Ig) 0 0 x In 0

Comments

PT. INSPIRA ENERGI


PT. INSPIRA ENERGI SEKAWAN
ENGINEERING - PROCUREMENT - CONTRACTOR

LOW VOLTAGE CIRCUIT BREAKER TEST REPORT


Testing
Company: Customer:
Address: Address:

Phone: Phone:
Name of Panel: INCOMING GEN 2 Contact Name:
Job/Contract #: Equipment Type: -
Date: 15/07/2022

BREAKER NAME PLATE DATA


Mfg: Family: EASYPACT Breaker Type: MT08
Standard: IEC Interrupt Rating: N1 Serial #:

TRIP UNIT DATA


Family: MICROLOGIC Type: 2.0 A Serial #:

TRIP UNIT BASIC PROTECTION SETTINGS


Parameter As Found As Left As Tested I2t Current Level
Sensor Rating (In) 800 A 800 A
LT Switch Setting (Io) x In A
Long Time Pickup (Ir) 1 x In 800 A
Long Time Delay (tr) 8 Sec
Inverse Definite Min.Time Lag
(Idmtl) OFF
Short Time Pickup (Isd, Im) 10 x Ir 10000 A
Short Time Delay (tsd) 0 Sec Off
Instantaneous Pickup (Ii) OFF x In Off A
Ground Fault Pickup (Ig) x In 0 A
Ground Fault Delay (tg) Sec
Ground Fault Push to Trip Button

FFTK File Name: LVMDP-2 Automatic Test Results


Parameter Test Current Level Trip Time Status
Long Time Pickup (Ir) 5600 A 7 x Ir 6,156 Sec Pass
Short Time Pickup (Isd, Im) 10000 A 10 x Ir 0,061 Sec Pass
Instantaneous Pickup (Ii) 0 0 x In 0
Ground Fault Pickup (Ig) 0 0 x In 0

Comments

PT. INSPIRA ENERGI


PT. INSPIRA ENERGI SEKAWAN
ENGINEERING - PROCUREMENT - CONTRACTOR

LOW VOLTAGE CIRCUIT BREAKER TEST REPORT


Testing Company: Customer:
Address: Address:

Phone: Phone:
Name of Panel: INCOMING GEN 3 Contact Name:
Job/Contract #: Equipment Type: -
Date: 15/07/2022

BREAKER NAME PLATE DATA


Mfg: Family: EASYPACT Breaker Type: MT08
Standard: IEC Interrupt Rating: N1 Serial #:

TRIP UNIT DATA


Family: MICROLOGIC Type: 2.0 A Serial #:

TRIP UNIT BASIC PROTECTION SETTINGS


Parameter As Found As Left As Tested I2t Current Level
Sensor Rating (In) 800 A 800 A
LT Switch Setting (Io) x In A
Long Time Pickup (Ir) 1 x In 800 A
Long Time Delay (tr) 8 Sec
Inverse Definite Min.Time Lag
(Idmtl) OFF
Short Time Pickup (Isd, Im) 10 x Ir 10000 A
Short Time Delay (tsd) 0 Sec Off
Instantaneous Pickup (Ii) OFF x In Off A
Ground Fault Pickup (Ig) x In 0 A
Ground Fault Delay (tg) Sec
Ground Fault Push to Trip Button

FFTK File Name: LVMDP-2 Automatic Test Results


Parameter Test Current Level Trip Time Status
Long Time Pickup (Ir) 5600 A 7 x Ir 6,138 Sec Pass
Short Time Pickup (Isd, Im) 10000 A 10 x Ir 0,061 Sec Pass
Instantaneous Pickup (Ii) 0 0 x In 0
Ground Fault Pickup (Ig) 0 0 x In 0

Comments

PT. INSPIRA ENERGI


PT. INSPIRA ENERGI SEKAWAN
ENGINEERING - PROCUREMENT - CONTRACTOR

LOW VOLTAGE CIRCUIT BREAKER TEST REPORT


Testing Company: Customer:
Address: Address:

Phone: Phone:
Name of Panel: INCOMING GEN 4 Contact Name:
Job/Contract #: Equipment Type: -
Date: 15/07/2022

BREAKER NAME PLATE DATA


Mfg: Family: EASYPACT Breaker Type: MT08
Standard: IEC Interrupt Rating: N1 Serial #:

TRIP UNIT DATA


Family: MICROLOGIC Type: 2.0 A Serial #:

TRIP UNIT BASIC PROTECTION SETTINGS


Parameter As Found As Left As Tested I2t Current Level
Sensor Rating (In) 800 A 800 A
LT Switch Setting (Io) x In A
Long Time Pickup (Ir) 1 x In 800 A
Long Time Delay (tr) 8 Sec
Inverse Definite Min.Time Lag
(Idmtl) OFF
Short Time Pickup (Isd, Im) 10 x Ir 10000 A
Short Time Delay (tsd) 0 Sec Off
Instantaneous Pickup (Ii) OFF x In Off A
Ground Fault Pickup (Ig) x In 0 A
Ground Fault Delay (tg) Sec
Ground Fault Push to Trip Button

FFTK File Name: LVMDP-2 Automatic Test Results


Parameter Test Current Level Trip Time Status
Long Time Pickup (Ir) 5600 A 7 x Ir 6,146 Sec Pass
Short Time Pickup (Isd, Im) 10000 A 10 x Ir 0,064 Sec Pass
Instantaneous Pickup (Ii) 0 0 x In
Ground Fault Pickup (Ig) 0 0 x In

Comments

PT. INSPIRA ENERGI