PSTX30...

1250

In Line with main contactor closed only during operation. 1L1 3L2 5L3

Alt. with fuses


2-wire control
O/I F1.1 .2 .3

O E
1 3 4 7 10

1/L1
3/L2
5/L3
Soft starter

DOL (only 470

Anybus
and larger)
PSTX Com 1 K1

2/T1
4/T2
6/T3
I E K7 21
+ 24V Com 2
20

Default:Top of ramp
23 +(B)

Com 3
19 GND

Default: Event
HMI

Default: Run
18 DGND 24 -(A) 1L1 3L2 5L3
K4 K5 K6

100-250V
50/60 Hz
K7
17 In2 25 T1

Temp In
16 In1 26 T2 PSTX
27 T3
15 In0
28 +24V

Analog out
14 Stop
13 Start 29 +
30 GND

22 2 5 6 8 9 11 12 2T1 4T2 6T3

K7 K1

2T1 4T2 6T3

W1
V1
U1
Coil consumption for main contactors.
Pull-in max 15A
3-wire control Holding max 1.5A
M
20 +24V If the pull-in or holding values are higher, the
19 GND main contactors must be controlled via an
auxiliary contactor.
O E 18 DGND

I E 14 Stop

13 Start

Björn Johansson Approved RE Application diagram PSTX in line

David Wikström 161019 B


1SFB536005G5006

ABB AB, Control Products