CLIENT M/s.

KWALE INTERNATIONAL SUGAR COMPANY LTD, KENYA

CONSULTANT M/s. JP MUKHERJI & ASSOCIATES PVT LTD, PUNE, MH

EPC CONTRACTOR M/s. ISGEC HEAVY ENGINEERING LTD, NOIDA, UP

PROJECT 1x18 MW CO-GEN POWER PLANT

EPC ELECTRICAL
IKE ELECTRIC PVT. LTD.
CONTRACTOR
601 - 602, MARIEGOLD NECO GARDENS,
VIMAN NAGAR,
PUNE - 411 014
MAHARASHTRA
INDIA
PHONE - 020 - 66290300 / 301
TELEFAX - 020 - 66290302

DOCUMENT TITLE RELAY SETTING CHART FOR 33KV SWITCHYARD

DOCUMENT NO. IKE-ISGEC-KWL61-DOC-233

REVISION 00

DATE 11.10.2013

NO. OF SHEETS PREPARED BY CHECKED BY APPROVED BY

**Sheets (Including
ARD KBD ABH
Title Sheet)
RELAY SETTING CHART- 33KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
I 33KV Transformer Control and Relay Panel
1 87GT, 64R, 99 Numerical Transformer MICOM P 632 Differential Protection (87GT)
Protection Relay Idiff>=0.1-2.5 Iref Idiff>:0.1 LV: CTR: 500/1A
Idiff>=2.5-30 Iref HV: CTR: 200/1 A
Idiff>>>=2.5-30 Iref NCTR: *** A
m1: 0.15-1.5 m1: 0.2
m2: 0.15-1.5 m2: 0.7
IR,m2 (1.5-10.0 Iref) 4
Op.del, trip signal:0-100S

Restricted earthfault protection(64R)


Effective setting: 10% 10%In
High Impedance relay NCTR: *** A
Stabilising resistor
(0-1000) Ohm Rst: 200 ohm

2 50/51 Numerical MICOM P341 Overcurrent protection (51) IDMT


50N/51N Interconnection In: 0.08-4In 0.75*In characterictics
67/67N, 50LBB Protection Relay T: 0-100 sec 0.1 sec 3 Sec Curve
78, 27Z, 59, 81
60, 81R, 99, 27 Inst. Overcurrent protection (50)
In: 0.08-32In 6*In CTR: 200/1A
T: 0-100 sec 0 sec (Inst) PTR: 33KV/110V

Earth fault protection (51N) IDMT


Ie: 0.08-4In 0.2*In characterictics
T: 0-100 sec 0.1 Sec 3 Sec Curve

Inst.Earth fault protection (50N)


Ie: 0.08-4In 0.3*In
T: 0-100 sec 0.5 sec

1 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
RELAY SETTING CHART- 33KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
Dir. Overcurrent protection (67)
In: 0.08-32In 0.75*In RCA: 30 deg
T: 0-100 sec 0.35 sec

Dir. Earth fault protection (67N)


Ie: 0.08-32In 0.1*In RCA: 45 deg
T: 0-100 sec 0.35 sec

Under volatge protection (27)


U<: 10-120V 80 V
T: 0-100 sec 2 sec

Over voltage protection (59)


U>: 60-185V 121 V
T: 0-100 sec 3 sec

Under frequency protection (81U)


f<: 45-65Hz 47.7 Hz PTR: 33KV/110V
T: 0-100 sec 2 sec

Over frequency protection (81O)


f>: 45-65Hz 52 Hz
T: 0-100 sec 2 sec

Local Breaker back-up protection (50LBB)


In: 0.4-4*In 1*In CTR: 200/1A
Time delay 0.3 sec

df/dt protection (81R)


df/dt: 0.1-10Hz/sec 4 Hz/ sec
T: 0-100 sec Inst Inst

2 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
RELAY SETTING CHART- 33KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
Dead band lower frequency
45-65Hz 49 Hz

Dead band upper frequency


45-65Hz 51 Hz

Voltage Balance Relay (60)


***
***

Overfluxing Protection Relay (99)


***
***

Vector surge protection (78)


dv/dt: 2-30 deg 7 deg

Standby Earth fault protection (51G)


Ie: 0.08-4In 0.3 * In CTR: 200/1 A
T: 0-100 sec 0.3 Sec IDMT curve (3 sec)

3 50/51 Numerical MICOM P111L IDMT overcurrent protection (51)


50N/51N protection relay In: 0.08-4In 0.9 * In
(LV side of GT) TMS: 0.025-1 0.1 Sec IDMT curve (3 sec)

Inst. Overcurrent protection (50)


In: 0.08-32In 6 * In CTR: 500 / 1 A
T: 0-100 sec 0 Sec PTR: 11kV / 110 V

3 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
RELAY SETTING CHART- 33KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
IDMT Earth fault protection (51N)
Ie: 0.08-4In 0.2 * In IDMT curve (3 sec)
TMS: 0.1-1 0.3 Sec

Inst.Earth fault protection (50N)


Ie: 0.08-4In 0.3 * In
T: 0-100 sec 0.3 Sec

4 27, 59 Numerical MICOM P921 Under voltage protection (27)


59D protection relay U<: 10-120V 0.8
T: 0-100 sec 0.5 sec

Over voltage protection (59)


U>: 60-185V 1.1
T: 0-100 sec 0.5 sec

Neutral displacement protection (59DLV)


V: 5.4 -20V 5.4 V
TMS 0.1 sec

NOTE: a) All settings are referred with respect to secondary values.


b) All the other functions which are not mentioned in this chart shall be disabled.

4 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
CLIENT M/s. KWALE INTERNATIONAL SUGAR COMPANY LTD, KENYA

CONSULTANT M/s. JP MUKHERJI & ASSOCIATES PVT LTD, PUNE, MH

EPC CONTRACTOR M/s. ISGEC HEAVY ENGINEERING LTD, NOIDA, UP

PROJECT 1x18 MW CO-GEN POWER PLANT

EPC ELECTRICAL
IKE ELECTRIC PVT. LTD.
CONTRACTOR
601 - 602, MARIEGOLD NECO GARDENS,
VIMAN NAGAR,
PUNE - 411 014
MAHARASHTRA
INDIA
PHONE - 020 - 66290300 / 301
TELEFAX - 020 - 66290302

DOCUMENT TITLE RELAY SETTING CHART FOR 132KV SWITCHYARD

DOCUMENT NO. IKE-ISGEC-KWL61-DOC-133

REVISION 00

DATE 11.10.2013

NO. OF SHEETS PREPARED BY CHECKED BY APPROVED BY

**Sheets (Including
ARD KBD ABH
Title Sheet)
RELAY SETTING CHART- 132KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
I 132KV Transformer Control and Relay Panel
1 87GT, 64R, 99 Numerical Transformer MICOM P 632 Differential Protection (87GT)
Protection Relay Idiff>=0.1-2.5 Iref Idiff>:0.1 LV: CTR: 1500/1A
Idiff>=2.5-30 Iref HV: CTR: 150/1 A
Idiff>>>=2.5-30 Iref NCTR: *** A
m1: 0.15-1.5 m1: 0.2
m2: 0.15-1.5 m2: 0.7
IR, m2 (1.5-10.0 Iref) 4
Op.del, trip signal:0-100S

Restricted earthfault protection(64R)


Effective setting: 10% 10%In
High Impedance relay NCTR: *** A
Stabilising resistor
(0-1000) Ohm Rst:200 ohm

2 50/51 Numerical MICOM P341 Overcurrent protection (51) IDMT


50N/51N Interconnection In: 0.08-4In 0.75*In characterictics
67/67N, 50LBB Protection Relay T: 0-100 sec 0.1 3 Sec Curve
78, 27Z, 59, 81
60, 81R, 99, 27 Inst. Overcurrent protection (50)
In: 0.08-32In 6*In CTR: 150/1A
T: 0-100 sec 0 sec (Inst) PTR: 132KV/110V

Earth fault protection (51N) IDMT


Ie: 0.08-4In 0.2*In characterictics
T: 0-100 sec 0.1 Sec 3 Sec Curve

Inst.Earth fault protection (50N)


Ie: 0.08-4In 0.3*In
T: 0-100 sec 0.5 sec

1 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
RELAY SETTING CHART- 132KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
Dir. Overcurrent protection (67)
In: 0.08-32In 0.75*In RCA: 30 deg
T: 0-100 sec 0.35 sec

Dir. Earth fault protection (67N)


Ie: 0.08-32In 0.1*In RCA: 45 deg
T: 0-100 sec 0.35 sec

Under volatge protection (27)


U<: 10-120V 80 V
T: 0-100 sec 2 sec

Over voltage protection (59)


U>: 60-185V 121 V
T: 0-100 sec 3 sec

Under frequency protection (81U)


f<: 45-65Hz 47.7 Hz PTR: 132KV/110V
T: 0-100 sec 2 sec

Over frequency protection (81O)


f>: 45-65Hz 52 Hz
T: 0-100 sec 2 sec

Local Breaker back-up protection (50LBB)


In: 0.4-4*In 1*In CTR: 150/1A
Time delay 0.3 sec

df/dt protection (81R)


df/dt: 0.1-10Hz/sec 4 Hz/ sec
T: 0-100 sec Inst

2 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
RELAY SETTING CHART- 132KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
Dead band lower frequency
45-65Hz 49 Hz

Dead band upper frequency


45-65Hz 51 Hz

Voltage Balance Relay (60)


***
***

Overfluxing Protection Relay (99)


***
***

Vector surge protection (78)


dv/dt: 2-30 deg 7 deg

Standby Earth fault protection (51G)


Ie: 0.08-4In 0.3 * In CTR: 150/1 A
T: 0-100 sec 0.3 Sec IDMT curve (3 sec)

3 50/51 Numerical MICOM P111L IDMT overcurrent protection (51)


50N/51N protection relay In: 0.08-4In 0.7 * In
(LV side of GT) TMS: 0.025-1 0.1 Sec IDMT curve (3 sec)

Inst. Overcurrent protection (50)


In: 0.08-32In 6 * In CTR: 1500 / 1 A
T: 0-100 sec 0 Sec PTR: 11kV / 110 V

3 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
RELAY SETTING CHART- 132KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
IDMT Earth fault protection (51N)
Ie: 0.08-4In 0.2 * In IDMT curve (3 sec)
TMS: 0.1-1 0.3 Sec

Inst.Earth fault protection (50N)


Ie: 0.08-4In 0.3 * In
T: 0-100 sec 0.3 Sec

4 50/51 Numerical MICOM P127 IDMT overcurrent protection (51)


50N/51N protection relay In: 0.08-4In 0.7 * In
(HV side of GT) TMS: 0.025-1 0.1 Sec IDMT curve (3 sec)

Inst. Overcurrent protection (50)


In: 0.08-32In 6 * In CTR: 1500 / 1 A
T: 0-100 sec 0 Sec PTR: 132kV / 110 V

IDMT Earth fault protection (51N)


Ie: 0.08-4In 0.2 * In IDMT curve (3 sec)
TMS: 0.1-1 0.3 Sec

Inst.Earth fault protection (50N)


Ie: 0.08-4In 0.3 * In
T: 0-100 sec 0.3 Sec

5 27, 59 Numerical MICOM P921 Under voltage protection (27)


59D protection relay U<: 10-120V 0.8
T: 0-100 sec 0.5 sec

Over voltage protection (59)


U>: 60-185V 1.1
T: 0-100 sec 0.5 sec

Neutral displacement protection (59DLV)


V: 5.4 -20V 5.4 V
TMS 0.1 sec

NOTE: a) All settings are referred with respect to secondary values.


b) All the other functions which are not mentioned in this chart shall be disabled.

4 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH