Professional Documents
Culture Documents
APPENDIX – E
POWER SYSTEM STUDY REPORT
66 kV SWITCHYARD
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-1 (16/20 MVA)
CT RATIO 200/1
CBCT RATIO -
RELAY MODEL NO. MICOM P341
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 OVERCURRENT PROTECTION (50/51)
I>1
I>1 Function 1) IEC S Inverse IEC S Inverse
Non-directional ,Directional
I>1 Direction Directional Fwd Non-Directional
Fwd, Directional Rev
I>1 Current Set 0.08…4 @ 0.01 x In 0.8 (160 A) 1.2 (240 A)
I>1 Time Delay 0…100 @ 0.01 sec - -
I>1 TMS 0.025…1.2 @ 0.025 0.3 0.35
I>2
I>2 Function 1) IEC S Inverse Disabled
Non-directional ,Directional
I>2 Direction Directional Rev -
Fwd, Directional Rev
I>2 Current Set 0.08…4 @ 0.01 x In 0.8 (160 A) -
I>2 Time Delay 0…100 @ 0.01 sec - -
I>2 TMS 0.025…1.2 @ 0.025 0.3 -
I>3
I>3 Status Enabled / Disabled DT DT
Page 1 of 7
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-1 (16/20 MVA)
CT RATIO 200/1
CBCT RATIO -
RELAY MODEL NO. MICOM P341
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 OVERCURRENT PROTECTION (50/51)
Non-directional ,Directional
I>3 Direction Non-directional Non-Directional
Fwd, Directional Rev
I>3 Current Set 0.08…32 @ 0.01 x In 5 (1000 A) 16 (3200 A)
I>3 Time Delay 0…100 @ 0.01 sec 0.2 sec 0.1 sec
I>4
I>4 Status Enabled / Disabled DT DT
Non-directional ,Directional
I>4 Direction Directional Rev *Directional Rev (Direction are Looking Towards Grid)
Fwd, Directional Rev
I>4 Current Set 0.08…32 @ 0.01 x In 2.8 (560 A) 0.9 (180 A)
I>4 Time Delay 0…100 @ 0.01 sec 0.05 sec 0.2 sec
1)-Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse
2 EARTH FAULT PROTECTION (51N/50N)
IN>1
IN>1 Function 1) IEC S Inverse Disabled
Non-directional ,Directional
IN>1 Direction Directional Fwd -
Fwd, Directional Rev
Page 2 of 7
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-1 (16/20 MVA)
CT RATIO 200/1
CBCT RATIO -
RELAY MODEL NO. MICOM P341
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
2 EARTH FAULT PROTECTION (51N/50N)
IN>1 Current 0.08…4 @ 0.01 x In 0.3 (60 A) -
IN>1 Time Delay 0…100 @ 0.01 sec - -
IN>1 TMS 0.025…1.2 @ 0.025 0.2 -
IN>2
IN>1 Function 1) IEC S Inverse Disabled
Non-directional ,Directional
IN>2 Direction Directional Rev -
Fwd, Directional Rev
IN>2 Current 0.08…4 @ 0.01 x In 0.16 (32 A) -
IN>2 Time Delay 0…100 @ 0.01 sec - -
IN>2 TMS 0.025…1.2 @ 0.025 0.2 -
IN>3
IN>3 Status 1) DT DT
Non-directional ,Directional
IN>3 Direction Directional Rev *Directional Rev (Direction are Looking Towards Grid)
Fwd, Directional Rev
IN>3 Current 0.08…32 @ 0.01 x In 0.52 (104 A) 1 (200 A)
IN>3 Time Delay 0…100 @ 0.01 sec 0.3 sec 0.2 sec
Page 3 of 7
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-1 (16/20 MVA)
CT RATIO 200/1
CBCT RATIO -
RELAY MODEL NO. MICOM P341
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
2 EARTH FAULT PROTECTION (51N/50N)
IN>4
IN>4 Status 1) DT DT
Non-directional ,Directional
IN>4 Direction Directional Rev Non-Directional
Fwd, Directional Rev
IN>4 Current 0.08…32 @ 0.01 x In 0.6 (120 A) 0.17 (34 A)
IN>4 Time Delay 0…100 @ 0.01 sec 0.3 sec 0.1 sec
1)-Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse
3 UNDER VOLTAGE PROTECTION (27)
V< Measurement Mode Phase-Phase / Phase-Neutral Phase-Phase Phase-Phase
V< Operate Mode Any Phase / Three Phase Any Phase Any Phase
V<1
V< 1 Function Disabled / DT / IDMT DT DT
V<1 Voltage Set 10…120 @ 1V (Vn=100/120) 92 92
V<1 Time Delay 0…100 @ 0.01 sec 3 sec 3 sec
V<1 TMS 0.5…100 @ 0.5 - -
V<1 Poledead Inh Disabled / Enabled Disabled Disabled
Page 4 of 7
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-1 (16/20 MVA)
CT RATIO 200/1
CBCT RATIO -
RELAY MODEL NO. MICOM P341
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
3 UNDER VOLTAGE PROTECTION (27)
V<2
V<2 Function Disabled / DT Enabled Enabled
V<2 Voltage Set 10…120 @ 1V (Vn=100/120) 88 88
V<2 Time Delay 0…100 @ 0.01 sec 1.5 sec 1.5 sec
V<2 Poledead Inh Disabled / Enabled Disabled Disabled
4 OVER VOLTAGE PROTECTION (59)
V> Measurement Mode Phase-Phase / Phase-Neutral Phase-Phase Phase-Phase
V> Operate Mode Any Phase / Three Phase Any Phase Any Phase
V>1
V>1 Function Disabled / DT / IDMT DT DT
V>1 Voltage Set 60…185 @ 1V (Vn=100/120) 121 121
V>1 Time Delay 0…100 @ 0.01 sec 1 sec 1 sec
V>1 TMS 0.5…100 @ 0.5 - -
V>2
V>2 Function Disabled / DT DT DT
V>2 Voltage Set 60…185 @ 1V (Vn=100/120) 125 121
Page 5 of 7
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-1 (16/20 MVA)
CT RATIO 200/1
CBCT RATIO -
RELAY MODEL NO. MICOM P341
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
4 OVER VOLTAGE PROTECTION (59)
V>2
V>2 Time Delay 0…100 @ 0.01 sec 0.25 sec 1 sec
5 RATE OF CHANGE OF FREQUENCY RPROTECTION (81R)
df/dt Status Enabled / Disabled Disabled Disabled
df/dt Setting 0.1…10 @ 0.01 Hz/sec - -
df/dt Time Delay 0…100 @ 0.1 sec - -
df/dt f Low 45…65 @ 0.01 Hz - -
df/dt>1 f High 45…65 @ 0.01 Hz - -
df/dt>2 f High 45…65 @ 0.01 Hz - -
7 UNDER FREQUENCY PROTECTION (81U)
F<1
F<1 Status Enabled / Disabled Enabled Enabled
F<1 Setting 45…65 @ 0.01 Hz 48.2 48.2
F<1 Time Delay 0…100 @ 0.01 sec 1.5 sec 1.5 sec
F<2
F<2 Status Enabled / Disabled Enabled Enabled
Page 6 of 7
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-1 (16/20 MVA)
CT RATIO 200/1
CBCT RATIO -
RELAY MODEL NO. MICOM P341
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
7 UNDER FREQUENCY PROTECTION (81U)
F<1
F<2 Setting 45…65 @ 0.01 Hz 47.55 47.55
F<2 Time Delay 0…100 @ 0.01 sec 0.1 sec 1 sec
8 OVER FREQUENCY PROTECTION (81O)
F>1
F>1 Status Enabled / Disabled Enabled Enabled
F>1 Setting 45…65 @ 0.01 Hz 51.6 51.6
F>1 Time Delay 0…100 @ 0.01 sec 1 sec 1 sec
F>2
F>2 Status Enabled / Disabled Disabled Disabled
F>2 Setting 45…65 @ 0.01 Hz - -
F>2 Time Delay 0…100 @ 0.01 sec - -
Page 1 of 6
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-2 (16/20 MVA)
CT RATIO 200/1
CBCT RATIO -
RELAY MODEL NO. MiCOM P127
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 DIRECTIONAL/NON-DIRECTIONAL PHASE OVERCURRENT PROTECTION (67/50/51)
I>>>
Delay type 1) 1 - DT 1 - DT
tI>>> 0…150 @ 0.01 sec 0 sec 0.2 sec
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 DIRECTIONAL/NON-DIRECTIONAL EARTH OVERCURRENT PROTECTION (67N/50N/51N)
Ie>
Ie> ? No, Yes, DIR Yes *DIR (Direction are Looking Towards Grid)
Ie> 0.01…1 @ 0.005 x Ien 0.3 (60 A) 1 (200 A)
Delay type 1) 2 - IDMT IEC_SI 1 - DT
tIe> 0…150 @ 0.01 sec - 0.2 sec
Ie> TMS 0.025…1.5 @ 0.025 0.2 -
Ie>>
Ie>> ? No, Yes, DIR Yes Yes
Ie>> 0.01…8 @ 0.005 x Ien 0.52 (104 A) 0.17 (34 A)
Delay type 1) 1 - DT 1 - DT
tIe>> 0…150 @ 0.01 sec 0.3 sec 0.1 sec
Page 2 of 6
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-2 (16/20 MVA)
CT RATIO 200/1
CBCT RATIO -
RELAY MODEL NO. MiCOM P127
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
2 DIRECTIONAL/NON-DIRECTIONAL EARTH OVERCURRENT PROTECTION (67N/50N/51N)
Ie>>
Ie>> TMS 0.025…1.5 @ 0.025 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 PHASE UNDERVOLTAGE PROTECTION (27)
U<
U< ? NO, AND, OR AND AND
U< 2…130 @ 0.1 V 92 92
tU< 0…600 @ 0.01 Sec 3 sec 3 sec
U<<
U<< ? NO, AND, OR AND AND
U<< 2…130 @ 0.1 V 88 88
tU<< 0…600 @ 0.01 Sec 15 sec 15 sec
4 PHASE OVERVOLTAGE PROTECTION (59)
U>
U> ? NO, AND, OR AND AND
U> 2…260 @ 0.1 V 121 121
Page 3 of 6
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-2 (16/20 MVA)
CT RATIO 200/1
CBCT RATIO -
RELAY MODEL NO. MiCOM P127
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
4 PHASE OVERVOLTAGE PROTECTION (59)
U>
tU> 0…260 @ 0.01 Sec 1 sec 1 sec
U>>
U>> ? NO, AND, OR AND AND
U>> 2…260 @ 0.1 V 125 125
tU>> 0…600 @ 0.01 Sec 0.25 sec 0.25 sec
4 UNDER AND OVER FREQUENCY PROTECTION (81)
F1
F1? 81> or 81< or No 81< 81<
F1 45.1…64.9 @ 0.01 Hz 48.2 48.2
tF1> 0…600 @ 0.01 Sec 1.5 sec 1.5 sec
F2
F2? 81> or 81< or No 81< 81<
F2 45.1…64.9 @ 0.01 Hz 47.55 47.55
tF2> 0…600 @ 0.01 Sec 0.1 sec 1 sec
Page 4 of 6
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-2 (16/20 MVA)
CT RATIO 200/1
CBCT RATIO -
RELAY MODEL NO. MiCOM P127
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
4 UNDER AND OVER FREQUENCY PROTECTION (81)
F3
F3? 81> or 81< or No 81> 81>
F3 45.1…64.9 @ 0.01 Hz 51 51
tF3> 0…600 @ 0.01 Sec 1 sec 1 sec
F4
F4? 81> or 81< or No NO No
F4 45.1…64.9 @ 0.01 Hz - -
tF4> 0…600 @ 0.01 Sec - -
5 INRUSH BLOCKING
Inrush Block Yes / No Yes
Inrush H2 ration 10…35 @ 0.1 % 15
Inrush tReset 0…2 @ 0.1 sec 0.2
Block I> Yes / No No
Block I>> Yes / No Yes
Block I>>> Yes / No No
Block Ie> Yes / No No
Page 5 of 6
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-2 (16/20 MVA)
CT RATIO 200/1
CBCT RATIO -
RELAY MODEL NO. MiCOM P127
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
5 INRUSH BLOCKING
Block Ie>> Yes / No Yes
Block Ie>>> Yes / No No
Block Ie_d>, Ie_d>> Yes / No No
*Directional to be checked at site. (On site verification of CT *Directional to be checked at site. (On site verification of CT
REMARKS star point is required) star point is required)
Page 6 of 6
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-1 (16/20 MVA) POWER TR-2 (16/20 MVA)
CT RATIO 200/1 200/1
CBCT RATIO - -
RELAY MODEL NO. MICOM P632 MICOM P632
FUNCTION PARAMETER
Phase Rotation A–B–C/A–C–B A–B–C A–B–C A–B–C A–B–C
In CT. prim., end a 1…50000 @ 1 A 200 200 200 200
In CT. prim., end b 1…50000 @ 1 A 1250 1250 1250 1250
In CT.Y prim, end a 1…50000 @ 1 A 200 200 200 200
In CT.Y prim, end b 1…50000 @ 1 A 1250 1250 1250 1250
CT Orientation Iph, a Standard / Reversed Standard Standard Standard Standard
CT Orientation Iph, b Standard / Reversed Standard Standard Standard Standard
CT Orientation IY, a Standard / Reversed Standard Standard Standard Standard
CT Orientation IY, b Standard / Reversed Standard Standard Standard Standard
Evaluation IN, end a Calculated / Measured Measured Measured Measured Measured
Evaluation IN, end b Calculated / Measured Calculated Calculated Calculated Calculated
Blocked/
Hold Time Dyn.Settg Blocked Blocked Blocked Blocked
0…100 @ 0.01 sec
General
YES / NO Yes Yes Yes Yes
Enable USER
DIFF: Rated Ref
0.1…5000 @ 0.1 MVA 20 20 20 20
Power Sref
DIFF: Ref. Curr. Iref,a 0…50 @ 0.001 kA 0.175 0.175 0.175 0.175
DIFF: Ref. Curr. Iref,b 0…50 @ 0.001 kA 1.05 1.05 1.05 1.05
Matching fact. Kam, a 0…50 @ 0.001 1.143 1.143 1.143 1.143
Page 1 of 4
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-1 (16/20 MVA) POWER TR-2 (16/20 MVA)
CT RATIO 200/1 200/1
CBCT RATIO - -
RELAY MODEL NO. MICOM P632 MICOM P632
FUNCTION PARAMETER
Matching fact. Kam, b 0…50 @ 0.001 1.191 1.191 1.191 1.191
Vn prim., end a 0.1…1500 @ 0.1 kV 66 66 66 66
Vn prim., end b 0.1…1500 @ 0.1 kV 11 11 11 11
No Swap, A-B Swapped
Reversal end a No Swap No Swap No Swap No Swap
B-C Swapped, C-A Swapped
Page 2 of 4
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-1 (16/20 MVA) POWER TR-2 (16/20 MVA)
CT RATIO 200/1 200/1
CBCT RATIO - -
RELAY MODEL NO. MICOM P632 MICOM P632
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 DIFFERENTIAL PROTECTION
DIFF : m2 0.1…1.5 @ 0.01 1.5 1.5 1.5 1.5
DIFF : IR,m2 1.5…10 @ 0.1 Iref 4 4 4 4
DIFF: Op. Mode Inrush 1) Not Phase-Selective Not Phase-Selective Not Phase-Selective Not Phase-Selective
Page 3 of 4
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 66kV SWITCHYARD
FEEDER ID POWER TR-1 (16/20 MVA) POWER TR-2 (16/20 MVA)
CT RATIO 200/1 200/1
CBCT RATIO - -
RELAY MODEL NO. MICOM P632 MICOM P632
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 RESTRICTED EARTH FAULT PROTECTION
REF_1: CTS Effective Yes / No NO NO NO NO
REF_1: Idiff> 0.10…1 @ 0.01 Iref 0.2 0.2 0.2 0.2
Blocked/
REF_1: Idiff>> 2.5 3 2.5 3
2.5…30 @ 0.1 Iref
REF_1: m1 0…1 @ 0.01 0.2 0.2 0.2 0.2
REF_1: m2 0.15…1.50 @ 0.01 1.5 1.5 1.5 1.5
REF_1: IR, m2 0.1…1.5 @ 0.01 Iref 1 1 1 1
1) Low-Z Iph Sum Bias, Low-Z Iph Max. Bias, High Impedance
REMARKS
Page 4 of 4
POWER SYSTEM STUDY REPORT
11 kV SWITCHBOARD-1
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-1 ROOM (BUS-A)
FEEDER ID POWER TR-1 (16/20 MVA) I/C
CT RATIO 1250/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes
I> 0.1…25 @ 0.01 x In 0.8 (1000 A) 1.2 (1500 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - -
I> TMS 0.025…1.5 @ 0.001 0.71 0.28
I>>
I>> ? No, Yes Yes Yes
I>> 0.5…40 @ 0.01x In 2.55 (3187.5 A) 3.6 (4500 A)
Delay type 1) 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 0.09 sec 0.7 sec
I>> TMS 0.025…1.5 @ 0.025 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-1 ROOM (BUS-A)
FEEDER ID POWER TR-1 (16/20 MVA) I/C
CT RATIO 1250/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien 0.15 (187.5 A) -
Delay type 1) 2 - IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - -
Ie> TMS 0.025…1.5 @ 0.001 0.07 -
Ie>>
Ie>> ? No, Yes Yes Yes
Ie>> 0.01…8 @ 0.005 x Ien 0.6 (750 A) 0.02 (25 A)
Delay type 1) 1 - DT 1 - DT
tIe>> 0…150 @ 0.01 sec 0 sec 0.7 sec
Ie>> TMS 0.025…1.5 @ 0.001 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Inrush Block Yes / No No
Inrush H2 ratio 10…35 @ 0.1 % -
Inrush tReset 0…2 @ 0.1 sec -
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-1 ROOM (BUS-A)
FEEDER ID POWER TR-1 (16/20 MVA) I/C
CT RATIO 1250/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
3 INRUSH BLOCKING
Block I> Yes / No -
Block I>> Yes / No -
Block I>>> Yes / No -
Block Ie> Yes / No -
Block Ie>> Yes / No -
Block Ie>>> Yes / No -
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-1 ROOM (BUS-B)
FEEDER ID POWER TR-2 (16/20 MVA) I/C 11 kV SWITCHBOARD-2 - O/G
CT RATIO 1250/5 1250/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes Yes Yes
I> 0.1…25 @ 0.01 x In 0.77 (962.5 A) 1.2 (1500 A) 0.77 (962.5 A) 1.2 (1500 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - - - -
I> TMS 0.025…1.5 @ 0.001 0.25 0.28 0.25 0.28
I>>
I>> ? No, Yes Yes Yes Yes Yes
I>> 0.5…40 @ 0.01x In 2.0 (2500 A) 3.6 (4500 A) 2.2 (2750 A) 3.6 (4500 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 0.05 sec 0.7 sec 0.05 sec 0.7 sec
I>> TMS 0.025…1.5 @ 0.025 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No Yes No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-1 ROOM (BUS-B)
FEEDER ID POWER TR-2 (16/20 MVA) I/C 11 kV SWITCHBOARD-2 - O/G
CT RATIO 1250/5 1250/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien 0.1 (125 A) - 0.1 (125 A) -
Delay type 1) 2 - IDMT IEC_SI - 2 - IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - - - -
Ie> TMS 0.025…1.5 @ 0.001 0.1 - 0.1 -
Ie>>
Ie>> ? No, Yes Yes Yes Yes Yes
Ie>> 0.01…8 @ 0.005 x Ien 1 (1250 A) 0.01 (12.5 A) 1 (1250 A) 0.01 (12.5 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT
tIe>> 0…150 @ 0.01 sec 1 sec 0.7 sec 1 sec 0.7 sec
Ie>> TMS 0.025…1.5 @ 0.001 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Inrush Block Yes / No No No
Inrush H2 ratio 10…35 @ 0.1 % - -
Inrush tReset 0…2 @ 0.1 sec - -
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-1 ROOM (BUS-B)
FEEDER ID POWER TR-2 (16/20 MVA) I/C 11 kV SWITCHBOARD-2 - O/G
CT RATIO 1250/5 1250/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
3 INRUSH BLOCKING
Block I> Yes / No - -
Block I>> Yes / No - -
Block I>>> Yes / No - -
Block Ie> Yes / No - -
Block Ie>> Yes / No - -
Block Ie>>> Yes / No - -
Page 3 of 3
POWER SYSTEM STUDY REPORT
11 kV SWITCHBOARD-2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-A)
FEEDER ID EARTHING TR 11 kV SWITCHBOARD-3 O/G-1 BUS-D TIE
CT RATIO 200/5 600/5 600/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED RECOMMENDED RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes Yes Yes NO Yes
I> 0.1…25 @ 0.01 x In 0.15 (30 A) 0.15 (30 A) 0.90 (540 A) 0.9 (540 A) - 2.5 (1500 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI - 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - - - - - -
I> TMS 0.025…1.5 @ 0.001 0.4 0.4 0.4 0.2 - 0.22
I>>
I>> ? No, Yes Yes Yes Yes Yes NO Yes
I>> 0.5…40 @ 0.01x In 0.5 (100 A) 0.5 (100 A) 5 (3000 A) 5.5 (3300 A) - 6.7 (4020 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT - 1 - DT
tI>> 0…150 @ 0.01 sec 0.51 sec 0.51 sec 0.77 sec 0.4 sec - 0.55 sec
I>> TMS 0.025…1.5 @ 0.025 - - - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes Yes Yes No NO No
Ie> 0.01…2 @ 0.005 x Ien 0.15 (30 A) 0.15 (30 A) 0.2 (120 A) - - -
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI - - -
tIe> 0…150 @ 0.01 sec - - - - - -
Ie> TMS 0.025…1.5 @ 0.001 0.4 0.4 0.4 - - -
Ie>>
Ie>> ? No, Yes Yes Yes Yes Yes NO Yes
Ie>> 0.01…8 @ 0.005 x Ien 1 (200 A) 1 (200 A) 1 (600 A) 0.035 (21 A) - 0.035 (21 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT - 1 - DT
Page 1 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-A)
FEEDER ID EARTHING TR 11 kV SWITCHBOARD-3 O/G-1 BUS-D TIE
CT RATIO 200/5 600/5 600/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED RECOMMENDED RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
Ie>>
tIe>> 0…150 @ 0.01 sec 1 sec 1 sec 1 sec 0.4 sec - 0.55 sec
Ie>> TMS 0.025…1.5 @ 0.001 - - - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Inrush Block Yes / No No No No
Inrush H2 ratio 10…35 @ 0.1 % - - -
Inrush tReset 0…2 @ 0.1 sec - - -
Block I> Yes / No - - -
Block I>> Yes / No - - -
Block I>>> Yes / No - - -
Block Ie> Yes / No - - -
Block Ie>> Yes / No - - -
Block Ie>>> Yes / No - - -
Page 2 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-A)
FEEDER ID 11 kV BUS A (GRID I/C-1)
CT RATIO 1250/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes
I> 0.1…25 @ 0.01 x In 0.81 (1012.5 A) 1.2 (1500 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - -
I> TMS 0.025…1.5 @ 0.001 0.25 0.28
I>>
I>> ? No, Yes Yes Yes
I>> 0.5…40 @ 0.01x In 2.2 (2750 A) 3.6 (4500 A)
Delay type 1) 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 0.05 sec 0.7 sec
I>> TMS 0.025…1.5 @ 0.025 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-A)
FEEDER ID 11 kV BUS A (GRID I/C-1)
CT RATIO 1250/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie> 0.01…2 @ 0.005 x Ien 0.1 (125 A) -
Delay type 1) 2 - IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - -
Ie> TMS 0.025…1.5 @ 0.001 0.1 sec -
Ie>>
Ie>> ? No, Yes Yes Yes
Ie>> 0.01…8 @ 0.005 x Ien 1 (1250 A) 0.02 (25 A)
Delay type 1) 1 - DT 1 - DT
tIe>> 0…150 @ 0.01 sec 1 sec 0.7 sec
Ie>> TMS 0.025…1.5 @ 0.001 - -
Ie>>>
Ie>>> ? No, Yes No No
Ie>>> 0.01…8 @ 0.005 x Ien - -
tIe>>> 0…150 @ 0.01 sec - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-A)
FEEDER ID 11 kV BUS A (GRID I/C-1)
CT RATIO 1250/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
3 INRUSH BLOCKING
Inrush Block Yes / No No
Inrush H2 ratio 10…35 @ 0.1 % -
Inrush tReset 0…2 @ 0.1 sec -
Block I> Yes / No -
Block I>> Yes / No -
Block I>>> Yes / No -
Block Ie> Yes / No -
Block Ie>> Yes / No -
Block Ie>>> Yes / No -
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
FEEDER ID BFP-A STARTING CURRENT 168 A (6 x FLA)
RELAY MODEL NO. AREVA - MiCOM P220 STARTING TIME (100% RATED VOLTAGE)
MOTOR RATING (kW) 425 kW STARTING TIME (80% RATED VOLTAGE)
RATED VOLTAGE (kV) 11 kV NO. OF START (HOT/COLD)
FULL LOAD CURRENT (A) 28 A STARTING METHOD DOL Starter
RATED POWER FACTOR 92.14% CT RATIO 40/1
RATED EFFICIENCY 86.46% CBCT RATIO -
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 SHORT-CIRCUIT PROTECTION (50/51)
I>
I> 0.1…25 @ 0.05 x In Disabled Disabled
tI> 0…150 @ 0.01 sec - -
I>>
I>> 0.5…40 @ 0.05 x In 6 (240 A) 6.3 (252 A)
tI>> 0…150 @ 0.01 sec 1 sec 0.1 sec
2 EARTH FAULT PROTECTION (50N/51N)
IO>
IO> 0.002…1 @ 0.001 x IOn 0.2 0.5 (20 A)
tIO> 0…100 @ 0.01 sec 1 (IDMT IEC SI) 0.1 sec
IO>>
IO>> 0.002…1 @ 0.001 x IOn Disabled Disabled
tIO>> 0…100 @ 0.01 sec - -
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
FEEDER ID BFP-A STARTING CURRENT 168 A (6 x FLA)
RELAY MODEL NO. AREVA - MiCOM P220 STARTING TIME (100% RATED VOLTAGE)
MOTOR RATING (kW) 425 kW STARTING TIME (80% RATED VOLTAGE)
RATED VOLTAGE (kV) 11 kV NO. OF START (HOT/COLD)
FULL LOAD CURRENT (A) 28 A STARTING METHOD DOL Starter
RATED POWER FACTOR 92.14% CT RATIO 40/1
RATED EFFICIENCY 86.46% CBCT RATIO -
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
3 THERMAL REPLICA (49)
Iθ> 0.2…1.5 @ 0.01 x In 0.7 0.7 (28 A)
Te1 1…180 @ 1 min 28 28
Te2 1…360 @ 1 min 28 28
Tr 1…999 @ 1 min 180 180
Ke 0…10 @ 1 3 3
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
FEEDER ID BFP-A STARTING CURRENT 168 A (6 x FLA)
RELAY MODEL NO. AREVA - MiCOM P220 STARTING TIME (100% RATED VOLTAGE)
MOTOR RATING (kW) 425 kW STARTING TIME (80% RATED VOLTAGE)
RATED VOLTAGE (kV) 11 kV NO. OF START (HOT/COLD)
FULL LOAD CURRENT (A) 28 A STARTING METHOD DOL Starter
RATED POWER FACTOR 92.14% CT RATIO 40/1
RATED EFFICIENCY 86.46% CBCT RATIO -
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
4 STALL / LOCKED ROTOR PROTECTION (51 R)
I Stall 0.5…5 @ 0.01 x In 4 (160 A) 4 (160 A)
tIstall 0.1…60 @ 0.1 sec 4 Sec 4 sec
All other protection settings must be disabled.
Note:
Values in () are in terms of Primary Amps.
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-B)
FEEDER ID BUS COUPLER 18 MW TG (CPP-1)
CT RATIO 2500/5 1600/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes Yes No
I> 0.1…25 @ 0.01 x In 0.5 (1250 A) 0.6 (1500 A) 0.95 (1520 A) -
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI -
tI> 0…150 @ 0.01 sec - - - -
I> TMS 0.025…1.5 @ 0.001 0.2 0.22 0.4 -
I>>
I>> ? No, Yes No Yes Yes Yes
I>> 0.5…40 @ 0.05x In - 1.6 (4000 A) 3 (4800 A) 4.5 (7200 A)
Delay type 1) - 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec - 0.55 sec 0.78 sec 0.1 sec
I>> TMS 0.025…1.5 @ 0.001 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes No No Yes No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-B)
FEEDER ID BUS COUPLER 18 MW TG (CPP-1)
CT RATIO 2500/5 1600/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien - - 0.2 (320 A) -
Delay type 1) - - 2 - IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - - - -
Ie> TMS 0.025…1.5 @ 0.001 - - 0.4 -
Ie>>
Ie>> ? No, Yes No Yes Yes No
Ie>> 0.01…8 @ 0.005 x Ien - 0.01 (25 A) 1 (1600 A) -
Delay type 1) - 1 - DT 1 - DT -
tIe>> 0…150 @ 0.01 sec - 0.55 sec 1 sec -
Ie>> TMS 0.025…1.5 @ 0.001 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Blocking inrush Yes / No Yes No
Inrush harmonic ratio 10…35 @ 0.1 % 15% -
Inrush tReset time 0…2 @ 0.1 sec 0.2 -
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-B)
FEEDER ID BUS COUPLER 18 MW TG (CPP-1)
CT RATIO 2500/5 1600/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
3 INRUSH BLOCKING
Sel1 tI>> Yes / No Yes -
Sel1 tI>>> Yes / No No -
Sel1 tIe>> Yes / No Yes -
Sel1 tIe>>> Yes / No No -
Sel1 tIe_d> Yes / No No -
Sel1 tIe_d>> Yes / No No -
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-B)
FEEDER ID 11kV SWITCHBOARD-3 - O/G-2 TR-3 CPP 1 AUX
CT RATIO 600/5 150/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes Yes Yes
I> 0.1…25 @ 0.01 x In 0.90 (540 A) 0.9 (540 A) 0.75 (112.5 A) 0.8 (120 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - - - -
I> TMS 0.025…1.5 @ 0.001 0.4 0.2 0.4 0.3
I>>
I>> ? No, Yes Yes Yes Yes Yes
I>> 0.5…40 @ 0.01x In 5 (3000 A) 5.5 (3300 A) 4 (600 A) 7.8 (1170 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 0.77 sec 0.4 sec 0.5 sec 0 sec
I>> TMS 0.025…1.5 @ 0.025 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No Yes No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-B)
FEEDER ID 11kV SWITCHBOARD-3 - O/G-2 TR-3 CPP 1 AUX
CT RATIO 600/5 150/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien 0.395 (237 A) - 0.2 (30 A) -
Delay type 1) 2 - IDMT IEC_SI - 2 - IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - - - -
Ie> TMS 0.025…1.5 @ 0.001 0.4 - 0.4 -
Ie>>
Ie>> ? No, Yes Yes Yes Yes Yes
Ie>> 0.01…8 @ 0.005 x Ien 1 (600 A) 0.035 (21 A) 1 (150 A) 0.14 (21 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT
tIe>> 0…150 @ 0.01 sec 1 sec 0.4 sec 1 sec 0 sec
Ie>> TMS 0.025…1.5 @ 0.001 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Inrush Block Yes / No No Yes
Inrush H2 ratio 10…35 @ 0.1 % - 15%
Inrush tReset 0…2 @ 0.1 sec - 0.2
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-B)
FEEDER ID 11kV SWITCHBOARD-3 - O/G-2 TR-3 CPP 1 AUX
CT RATIO 600/5 150/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
3 INRUSH BLOCKING
Block I> Yes / No - No
Block I>> Yes / No - Yes
Block I>>> Yes / No - No
Block Ie> Yes / No - No
Block Ie>> Yes / No - Yes
Block Ie>>> Yes / No - No
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-B)
FEEDER ID BFP-B STARTING CURRENT 168 A (6 x FLA)
RELAY MODEL NO. SE - MiCOM P220 STARTING TIME (100% RATED VOLTAGE)
MOTOR RATING (kW) 425 kW STARTING TIME (80% RATED VOLTAGE)
RATED VOLTAGE (kV) 11 kV NO. OF START (HOT/COLD)
FULL LOAD CURRENT (A) 28 A STARTING METHOD DOL Starter
RATED POWER FACTOR 92.14% CT RATIO 40/1
RATED EFFICIENCY 86.46% CBCT RATIO -
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 SHORT-CIRCUIT PROTECTION (50/51)
I>
I> 0.1…25 @ 0.05 x In Disabled Disabled
Delay type 1) - -
tI> (DMT) 0…150 @ 0.01 sec - -
I>>
I>> 0.5…40 @ 0.05 x In 6 (240 A) 6.3 (252 A)
Delay type 1) DT DT
tI>> (DMT) 0…150 @ 0.01 sec 1 sec 0.1 sec
1) DT, IDMT, RI
2 EARTH FAULT PROTECTION (50N/51N)
IO>
IO> 0.002…1 @ 0.001 x IOn 0.2 (8 A) 0.5 ( 20 A)
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-B)
FEEDER ID BFP-B STARTING CURRENT 168 A (6 x FLA)
RELAY MODEL NO. SE - MiCOM P220 STARTING TIME (100% RATED VOLTAGE)
MOTOR RATING (kW) 425 kW STARTING TIME (80% RATED VOLTAGE)
RATED VOLTAGE (kV) 11 kV NO. OF START (HOT/COLD)
FULL LOAD CURRENT (A) 28 A STARTING METHOD DOL Starter
RATED POWER FACTOR 92.14% CT RATIO 40/1
RATED EFFICIENCY 86.46% CBCT RATIO -
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
2 EARTH FAULT PROTECTION (50N/51N)
IO>
tIO> 0…100 @ 0.01 sec 1 (IDMT IEC SI) 0.1 sec
IO>>
IO>> 0.002…1 @ 0.001 x IOn Disabled Disabled
tIO>> 0…100 @ 0.01 sec - -
3 THERMAL REPLICA (49)
Iθ> 0.2…1.5 @ 0.01 x In 0.7 0.7 (28 A)
Te1 1…180 @ 1 min 28 28
Te2 1…360 @ 1 min 28 28
Tr 1…999 @ 1 min 180 180
Ke 0…10 @ 1 3 3
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-B)
FEEDER ID BFP-B STARTING CURRENT 168 A (6 x FLA)
RELAY MODEL NO. SE - MiCOM P220 STARTING TIME (100% RATED VOLTAGE)
MOTOR RATING (kW) 425 kW STARTING TIME (80% RATED VOLTAGE)
RATED VOLTAGE (kV) 11 kV NO. OF START (HOT/COLD)
FULL LOAD CURRENT (A) 28 A STARTING METHOD DOL Starter
RATED POWER FACTOR 92.14% CT RATIO 40/1
RATED EFFICIENCY 86.46% CBCT RATIO -
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
4 UNBALANCE PROTECTION (46)
I2>
I2> 0.04…0.8 @ 0.01 x In 0.2 0.35 (14 A)
tI2> 0…200 @ 0.01 sec 4.94 Sec 1 sec
I2>>
I2>> 0.04…0.8 @ 0.01 x In 0.2 0.21 (8.4 A)
TMS I2>> 0.2…2 @ 0.001 - 0.9
5 STALL / LOCKED ROTOR PROTECTION (51 R)
I Stall 0.5…5 @ 0.01 x In 4 (160 A) 4 (160 A)
tIstall 0.1…60 @ 0.1 sec 4 Sec 4 sec
6 UNDER CURRENT (LOSS OF LOAD) (37)
I< 0.1…1 @ 0.01 x In 0.1 (4 A) 0.1 (4 A)
tI< 0.2…100 @ 0.1 sec 0.2 Sec 0.2 Sec
Tinhib 0.05…300 @ 0.1 sec 0.05 Sec 0.05 Sec
All other protection settings must be disabled. Page 3 of 3
Note:
Values in () are in terms of Primary Amps.
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-D)
FEEDER ID BUS-A TIE 11kV SWITCHBOARD-3 - O/G-3 TR-4 CPP 2 AUX
CT RATIO 1250/5 600/5 100/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED RECOMMENDED RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes Yes Yes Yes Yes
I> 0.1…25 @ 0.01 x In 0.44 (550 A) 1.2 (1500 A) 0.90 (540 A) 0.9 (540 A) 0.69 (69 A) 0.78 (78 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - - - - - -
I> TMS 0.025…1.5 @ 0.001 0.2 0.22 0.4 0.2 0.4 1.1
I>>
I>> ? No, Yes Yes Yes Yes Yes Yes Yes
I>> 0.5…40 @ 0.01x In 1.55 (1937.5 A) 3.2 (4000 A) 5 (3000 A) 5.5 (3300 A) 3.95 (395 A) 11 (1100 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 0.23 sec 0.55 sec 0.77 sec 0.4 sec 0.15 sec 0 sec
I>> TMS 0.025…1.5 @ 0.025 - - - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No Yes No Yes Yes
Ie> 0.01…2 @ 0.005 x Ien 0.3 (375 A) - 0.2 (120 A) - 0.315 (13.5 A) 0.2 (20 A)
Delay type 1) 2 - IDMT IEC_SI - 2 - IDMT IEC_SI - 2 - IDMT IEC_SI 1 - DT
tIe> 0…150 @ 0.01 sec - - - - - 0 sec
Ie> TMS 0.025…1.5 @ 0.001 0.2 - 0.4 - 0.1 -
Ie>>
Ie>> ? No, Yes Yes Yes Yes Yes No No
Ie>> 0.01…8 @ 0.005 x Ien 1.02 (1275 A) 0.02 (25 A) 1 (600 A) 0.035 (21 A) - -
Page 1 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-D)
FEEDER ID BUS-A TIE 11kV SWITCHBOARD-3 - O/G-3 TR-4 CPP 2 AUX
CT RATIO 1250/5 600/5 100/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED RECOMMENDED RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>>
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT - -
tIe>> 0…150 @ 0.01 sec 0.15 sec 0.55 sec 1 sec 0.4 sec - -
Ie>> TMS 0.025…1.5 @ 0.001 - - - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Inrush Block Yes / No No No Yes
Inrush H2 ratio 10…35 @ 0.1 % - - 15%
Inrush tReset 0…2 @ 0.1 sec - - 0.2
Block I> Yes / No - - No
Block I>> Yes / No - - Yes
Block I>>> Yes / No - - No
Block Ie> Yes / No - - Yes
Block Ie>> Yes / No - - No
Block Ie>>> Yes / No - - No
Page 2 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-D)
FEEDER ID BUS COUPLER
CT RATIO 1250/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes No
I> 0.1…25 @ 0.01 x In 0.5 (1250 A) -
Delay type 1) 2 - IDMT IEC_SI -
tI> 0…150 @ 0.01 sec - -
I> TMS 0.025…1.5 @ 0.001 0.1 -
I>>
I>> ? No, Yes No No
I>> 0.5…40 @ 0.01x In - -
Delay type 1) - -
tI>> 0…150 @ 0.01 sec - -
I>> TMS 0.025…1.5 @ 0.025 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes No No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-D)
FEEDER ID BUS COUPLER
CT RATIO 1250/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien - -
Delay type 1) - -
tIe> 0…150 @ 0.01 sec - -
Ie> TMS 0.025…1.5 @ 0.001 - -
Ie>>
Ie>> ? No, Yes No -
Ie>> 0.01…8 @ 0.005 x Ien - -
Delay type 1) - -
tIe>> 0…150 @ 0.01 sec - -
Ie>> TMS 0.025…1.5 @ 0.001 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Inrush Block Yes / No No
Inrush H2 ratio 10…35 @ 0.1 % -
Inrush tReset 0…2 @ 0.1 sec -
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-D)
FEEDER ID BUS COUPLER
CT RATIO 1250/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
3 INRUSH BLOCKING
Block I> Yes / No -
Block I>> Yes / No -
Block I>>> Yes / No -
Block Ie> Yes / No -
Block Ie>> Yes / No -
Block Ie>>> Yes / No -
REMARKS
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-C)
FEEDER ID 11kV SWITCHBOARD-3 O/G-4 8 MW TG (CPP-2)
CT RATIO 600/5 1250/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes Yes No
I> 0.1…25 @ 0.01 x In 0.90 (540 A) 0.9 (540 A) 0.5 (625 A) -
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI -
tI> 0…150 @ 0.01 sec - - - -
I> TMS 0.025…1.5 @ 0.001 0.4 0.2 0.2 -
I>>
I>> ? No, Yes Yes Yes Yes Yes
I>> 0.5…40 @ 0.01x In 5 (3000 A) 5.5 (3300 A) 3 (3750 A) 4 (5000 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 0.77 sec 0.4 sec 0.75 sec 0.1 sec
I>> TMS 0.025…1.5 @ 0.025 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No Yes No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-C)
FEEDER ID 11kV SWITCHBOARD-3 O/G-4 8 MW TG (CPP-2)
CT RATIO 600/5 1250/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien 0.2 (120 A) - 0.2 (250 A) -
Delay type 1) 2 - IDMT IEC_SI - 2 - IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - - - -
Ie> TMS 0.025…1.5 @ 0.001 0.4 - 0.1 -
Ie>>
Ie>> ? No, Yes Yes Yes Yes No
Ie>> 0.01…8 @ 0.005 x Ien 1 (600 A) 0.035 (21 A) 1 (1250 A) -
Delay type 1) 1 - DT 1 - DT 1 - DT -
tIe>> 0…150 @ 0.01 sec 1 sec 0.4 sec 1 sec -
Ie>> TMS 0.025…1.5 @ 0.001 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Inrush Block Yes / No No No
Inrush H2 ratio 10…35 @ 0.1 % - -
Inrush tReset 0…2 @ 0.1 sec - -
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-C)
FEEDER ID 11kV SWITCHBOARD-3 O/G-4 8 MW TG (CPP-2)
CT RATIO 600/5 1250/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
3 INRUSH BLOCKING
Block I> Yes / No - -
Block I>> Yes / No - -
Block I>>> Yes / No - -
Block Ie> Yes / No - -
Block Ie>> Yes / No - -
Block Ie>>> Yes / No - -
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. UNIT PROTECTION RELAY SETTING SHEETS
LOCATION TG (8MW) (CPP-2)
FEEDER ID 8 MW TG CPP-2 SUB TRANSIENT REACTANCE (Xd") 20%
RELAY MODEL NO. AREVA - MiCOM P341 TRANSIENT REACTANCE (Xd') 25%
GENERATOR RATING (MW) 8 MW STEADY STATE REACTANCE (Xd) 194%
GENERATOR RATING (MVA) 10 MVA GROUNDING NGR (100A, 63.5 Ohms)
RATED VOLTAGE (kV) 11 kV MAXIMUM UNBALANCE / NPS CURRENT & TIME
FULL LOAD CURRENT (A) 525 A OVER LOAD CAPABILITY
RATED POWER FACTOR (%) 80% CT RATIO 700/1
RATED EFFICIENCY (%) 97.70% CBCT RATIO
PROTECTION SETTINGS
EXISTING RECOMMENDED
NO. PROTECTION RANGE REMARKS
SETTING SETTINGS
1.0 RATE OF CHANGE OF FREQUENCY RPROTECTION (81R)
df/dt Status Enabled / Disabled Disabled Disabled
df/dt Setting 0.1…10 @ 0.01 Hz/sec - -
df/dt Time Delay 0…100 @ 0.1 sec - -
df/dt f Low 45…65 @ 0.01 Hz - -
df/dt f High 45…65 @ 0.01 Hz - -
ACTION
2.0 VECTOR SHIFT
V Shift Status Enabled / Disabled Disabled Disabled
V Shift Angle 2…30 @ 1 ° - -
ACTION
3.0 UNDER VOLTAGE PROTECTION (27)
V< Measurement Mode Phase-Phase / Phase-Neutral Phase - Phase -
V< Operate Mode Any Phase / Three Phase Any Phase -
V<1
V< 1 Function Disabled / DT / IDMT DT Disabled
Page 1 of 4
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. UNIT PROTECTION RELAY SETTING SHEETS
LOCATION TG (8MW) (CPP-2)
FEEDER ID 8 MW TG CPP-2 SUB TRANSIENT REACTANCE (Xd") 20%
RELAY MODEL NO. AREVA - MiCOM P341 TRANSIENT REACTANCE (Xd') 25%
GENERATOR RATING (MW) 8 MW STEADY STATE REACTANCE (Xd) 194%
GENERATOR RATING (MVA) 10 MVA GROUNDING NGR (100A, 63.5 Ohms)
RATED VOLTAGE (kV) 11 kV MAXIMUM UNBALANCE / NPS CURRENT & TIME
FULL LOAD CURRENT (A) 525 A OVER LOAD CAPABILITY
RATED POWER FACTOR (%) 80% CT RATIO 700/1
RATED EFFICIENCY (%) 97.70% CBCT RATIO
3.0 UNDER VOLTAGE PROTECTION (27)
V<1 Voltage Set 10…120 @ 1V (Vn=100/120) 99 -
V<1 Time Delay 0…100 @ 0.01 sec 2 sec -
V<1 TMS 0.5…100 @ 0.5 - -
V<1 Poledead Inh Disabled / Enabled Enabled -
V<2
V<2 Function Disabled / DT Disabled Disabled
V<2 Voltage Set 10…120 @ 1V (Vn=100/120) - -
V<2 Time Delay 0…100 @ 0.01 sec - -
V<2 Poledead Inh Disabled / Enabled - -
ACTION
4.0 OVER VOLTAGE PROTECTION (59)
V> Measurement Mode Phase-Phase / Phase-Neutral Phase - Phase -
V> Operate Mode Any Phase / Three Phase Any Phase -
V<1
V>1 Function Disabled / DT / IDMT DT Disabled
V>1 Voltage Set 60…185 @ 1V (Vn=100/120) 122 -
V>1 Time Delay 0…100 @ 0.01 sec 3 sec -
V>1 TMS 0.5…100 @ 0.5 - -
Page 2 of 4
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. UNIT PROTECTION RELAY SETTING SHEETS
LOCATION TG (8MW) (CPP-2)
FEEDER ID 8 MW TG CPP-2 SUB TRANSIENT REACTANCE (Xd") 20%
RELAY MODEL NO. AREVA - MiCOM P341 TRANSIENT REACTANCE (Xd') 25%
GENERATOR RATING (MW) 8 MW STEADY STATE REACTANCE (Xd) 194%
GENERATOR RATING (MVA) 10 MVA GROUNDING NGR (100A, 63.5 Ohms)
RATED VOLTAGE (kV) 11 kV MAXIMUM UNBALANCE / NPS CURRENT & TIME
FULL LOAD CURRENT (A) 525 A OVER LOAD CAPABILITY
RATED POWER FACTOR (%) 80% CT RATIO 700/1
RATED EFFICIENCY (%) 97.70% CBCT RATIO
4.0 OVER VOLTAGE PROTECTION (59)
V<2
V>2 Function Disabled / DT Disabled Disabled
V>2 Voltage Set 60…185 @ 1V (Vn=100/120) - -
V>2 Time Delay 0…100 @ 0.01 sec - -
ACTION
5.0 UNDER FREQUENCY PROTECTION (81U)
F<1
F<1 Status Enabled / Disabled Enabled Disabled
F<1 Setting 45…65 @ 0.01 Hz 48 -
F<1 Time Delay 0…100 @ 0.01 sec 2 sec -
F<2
F<2 Status Enabled / Disabled Disabled Disabled
F<2 Setting 45…65 @ 0.01 Hz - -
F<2 Time Delay 0…100 @ 0.01 sec - -
ACTION
6.0 OVER FREQUENCY PROTECTION (81O)
F>1
F>1 Status Enabled / Disabled Enabled Disabled
Page 3 of 4
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. UNIT PROTECTION RELAY SETTING SHEETS
LOCATION TG (8MW) (CPP-2)
FEEDER ID 8 MW TG CPP-2 SUB TRANSIENT REACTANCE (Xd") 20%
RELAY MODEL NO. AREVA - MiCOM P341 TRANSIENT REACTANCE (Xd') 25%
GENERATOR RATING (MW) 8 MW STEADY STATE REACTANCE (Xd) 194%
GENERATOR RATING (MVA) 10 MVA GROUNDING NGR (100A, 63.5 Ohms)
RATED VOLTAGE (kV) 11 kV MAXIMUM UNBALANCE / NPS CURRENT & TIME
FULL LOAD CURRENT (A) 525 A OVER LOAD CAPABILITY
RATED POWER FACTOR (%) 80% CT RATIO 700/1
RATED EFFICIENCY (%) 97.70% CBCT RATIO
6.0 OVER FREQUENCY PROTECTION (81O)
F>1
F>1 Setting 45…65 @ 0.01 Hz 51 -
F>1 Time Delay 0…100 @ 0.01 sec 2 sec -
F>2
F>2 Status Enabled / Disabled Disabled Disabled
F>2 Setting 45…65 @ 0.01 Hz - -
F>2 Time Delay 0…100 @ 0.01 sec - -
ACTION
7.0 UNDER CURRENT PROTECTION (37)
I< CURRENT SET 0.02…3.2 @ 0.01 In 0.1 A Disabled
IN< CURRENT SET 0.02…3.2 @ 0.01 In -
ISEF< CURRENT 0.001…0.8 @ 0.0005 In 0.02 A -
REMOVE I> START Enabled / Disabled Disabled Disabled
REMOVE IN> START Enabled / Disabled Disabled Disabled
ACTION
All other protection settings must be disabled.
Note:
Values in () are in terms of Primary Amps.
Page 4 of 4
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-C)
FEEDER ID BUS COUPLER
CT RATIO 1250/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes
I> 0.1…25 @ 0.01 x In 0.5 (1250 A) 1.2 (1500 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - -
I> TMS 0.025…1.5 @ 0.001 0.1 0.22
I>>
I>> ? No, Yes No Yes
I>> 0.5…40 @ 0.05x In - 3.2 (4000 A)
Delay type 1) - 1 - DT
tI>> 0…150 @ 0.01 sec - 0.55 sec
I>> TMS 0.025…1.5 @ 0.001 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes No No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-C)
FEEDER ID BUS COUPLER
CT RATIO 1250/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien - -
Delay type 1) - -
tIe> 0…150 @ 0.01 sec - -
Ie> TMS 0.025…1.5 @ 0.001 - -
Ie>>
Ie>> ? No, Yes No Yes
Ie>> 0.01…8 @ 0.005 x Ien - 0.02 (25 A)
Delay type 1) - 1 - DT
tIe>> 0…150 @ 0.01 sec - 0.55 sec
Ie>> TMS 0.025…1.5 @ 0.001 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Blocking inrush Yes / No No
Inrush harmonic ratio 10…35 @ 0.1 % -
Inrush tReset time 0…2 @ 0.1 sec -
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-C)
FEEDER ID BUS COUPLER
CT RATIO 1250/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
3 INRUSH BLOCKING
Sel1 tI>> Yes / No -
Sel1 tI>>> Yes / No -
Sel1 tIe>> Yes / No -
Sel1 tIe>>> Yes / No -
Sel1 tIe_d> Yes / No -
Sel1 tIe_d>> Yes / No -
T Sel1 0…500 @ 0.01 sec -
REMARKS
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-E)
FEEDER ID 11 kV BUS B (GRID I/C-2) TR-5 CPP 3 AUX 8 MW TG (CPP-3)
CT RATIO 1250/5 150/5 1250/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes Yes Yes Yes No
I> 0.1…25 @ 0.01 x In 0.5 (625 A) 1.2 (1250 A) 0.68 (102 A) 0.7 (105 A) 0.5 (625 A) -
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI -
tI> 0…150 @ 0.01 sec - - - - - -
I> TMS 0.025…1.5 @ 0.001 0.2 0.28 0.13 0.9 0.025 -
I>>
I>> ? No, Yes Yes Yes Yes Yes Yes Yes
I>> 0.5…40 @ 0.05x In 3 (3750 A) 3.6 (4500 A) 1.5 (225 A) 8.9 (1335 A) 1 (1250 A) 4 (5000 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 0.75 sec 0.7 sec 0.2 sec 0 sec 0.01 sec 0.1 sec
I>> TMS 0.025…1.5 @ 0.001 - - - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No Yes No Yes No
Ie> 0.01…2 @ 0.005 x Ien 0.2 (250 A) - 0.2 (30 A) - 0.2 (250 A) -
Delay type 1) 2 - IDMT IEC_SI - 2 - IDMT IEC_SI - 2 - IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - - - - - -
Ie> TMS 0.025…1.5 @ 0.001 0.1 - 0.1 - 0.025 -
Ie>>
Ie>> ? No, Yes Yes Yes Yes Yes Yes No
Page 1 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-E)
FEEDER ID 11 kV BUS B (GRID I/C-2) TR-5 CPP 3 AUX 8 MW TG (CPP-3)
CT RATIO 1250/5 150/5 1250/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>>
Ie>> 0.01…8 @ 0.005 x Ien 0.1 (125 A) 0.01 (12.5 A) 0.22 (125 A) 0.07 (10.5 A) 0.1 (125 A) -
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT 1 - DT -
tIe>> 0…150 @ 0.01 sec 0.1 sec 0.7 sec 0.15 sec 0 sec 1 sec -
Ie>> TMS 0.025…1.5 @ 0.001 - - - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Blocking inrush Yes / No No Yes No
Inrush harmonic ratio 10…35 @ 0.1 % - 15% -
Inrush tReset 0…2 @ 0.1 sec - 0.2 -
Sel1 tI>> Yes / No - Yes -
Sel1 tI>>> Yes / No - No -
Sel1 tIe>> Yes / No - Yes -
Sel1 tIe>>> Yes / No - No -
Sel1 tIe_d> Yes / No - No -
Sel1 tIe_d>> Yes / No - No -
Page 2 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-E)
FEEDER ID 11kV SWITCHBOARD-3 O/G-5 11kV SWITCHBOARD-3 O/G-6
CT RATIO 800/5 800/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes
I> 0.1…25 @ 0.01 x In 0.68 (544 A) 0.68 (544 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - -
I> TMS 0.025…1.5 @ 0.001 0.2 0.2
I>>
I>> ? No, Yes Yes Yes
I>> 0.5…40 @ 0.05x In 4.2 (3360 A) 4.2 (3360 A)
Delay type 1) 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 0.4 sec 0.4 sec
I>> TMS 0.025…1.5 @ 0.001 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes No No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-E)
FEEDER ID 11kV SWITCHBOARD-3 O/G-5 11kV SWITCHBOARD-3 O/G-6
CT RATIO 800/5 800/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien - -
Delay type 1) - -
tIe> 0…150 @ 0.01 sec - -
Ie> TMS 0.025…1.5 @ 0.001 - -
Ie>>
Ie>> ? No, Yes Yes Yes
Ie>> 0.01…8 @ 0.005 x Ien 0.015 (12 A) 0.015 (12 A)
Delay type 1) 1 - DT 1 - DT
tIe>> 0…150 @ 0.01 sec 0.4 0.4
Ie>> TMS 0.025…1.5 @ 0.001 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Blocking inrush Yes / No No No
Inrush harmonic ratio 10…35 @ 0.1 % - -
Inrush tReset time 0…2 @ 0.1 sec - -
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-2 ROOM (BUS-E)
FEEDER ID 11kV SWITCHBOARD-3 O/G-5 11kV SWITCHBOARD-3 O/G-6
CT RATIO 800/5 800/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
3 INRUSH BLOCKING
Sel1 tI>> Yes / No - -
Sel1 tI>>> Yes / No - -
Sel1 tIe>> Yes / No - -
Sel1 tIe>>> Yes / No - -
Sel1 tIe_d> Yes / No - -
Sel1 tIe_d>> Yes / No - -
T Sel1 0…500 @ 0.01 sec - -
Page 3 of 3
POWER SYSTEM STUDY REPORT
11 kV SWITCHBOARD-3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-1
FEEDER ID L-1 DT-1 (3.15 MVA) L-1 PAB-C TR (1.25 MVA) SWB-3 (BUS-A) I/C-1
CT RATIO 250/5 75/5 600/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED RECOMMENDED RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes YES Yes Yes Yes
I> 0.1…25 @ 0.01 x In 0.6 (150 A) 0.75 (187.5 A) 0.75 (56.2 A) 1 (75 A) 0.9 (540 A) 0.9 (540 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_VI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - - - - - -
I> TMS 0.025…1.5 @ 0.001 0.25 0.48 0.4 0.1 0.6 0.2
I>>
I>> ? No, Yes Yes Yes YES Yes Yes Yes
I>> 0.5…40 @ 0.01x In 2.5 (625 A) 10.9 (2725 A) 3 (225 A) 18.2 (1365 A) 5 (3000 A) 5.5 (3300 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 0.3 sec 0 sec 0.7 sec 0 sec 1 sec 0.4 sec
I>> TMS 0.025…1.5 @ 0.025 - - - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No YES No No No
Ie> 0.01…2 @ 0.005 x Ien 0.1 (25 A) - 0.2 (15 A) - - -
Delay type 1) 2 - IDMT IEC_SI - 2 - IDMT IEC_SI - - -
tIe> 0…150 @ 0.01 sec - - - - - -
Ie> TMS 0.025…1.5 @ 0.001 0.25 - 0.4 - - -
Ie>>
Ie>> ? No, Yes Yes Yes YES Yes Yes Yes
Page 1 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-1
FEEDER ID L-1 DT-1 (3.15 MVA) L-1 PAB-C TR (1.25 MVA) SWB-3 (BUS-A) I/C-1
CT RATIO 250/5 75/5 600/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED RECOMMENDED RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>>
Ie>> 0.01…8 @ 0.005 x Ien 0.7 (175 A) 0.08 (20 A) 1 (75 A) 0.27 (20.25 A) 1 (600 A) 0.035 (21 A)
Delay type 1) 1 - DT 1 - DT 1) DT 1 - DT 1 - DT 1 - DT
tIe>> 0…150 @ 0.01 sec 0.7 sec 0 sec 1 sec 0 sec 2 sec 0.4 sec
Ie>> TMS 0.025…1.5 @ 0.001 - - - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Inrush Block Yes / No Yes Yes No
Inrush H2 ratio 10…35 @ 0.1 % 15% 15% -
Inrush tReset time 0…2 @ 0.1 sec 0.2 0.2 -
Block I> Yes / No No No -
Block I>> Yes / No Yes Yes -
Block I>>> Yes / No No No -
Block Ie> Yes / No No No -
Block Ie>> Yes / No Yes Yes -
Block Ie>>> Yes / No No No -
Page 2 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-1
FEEDER ID BUS COUPLER L-1 DT-2 (3.15 MVA)
CT RATIO 600/5 250/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes Yes Yes
I> 0.1…25 @ 0.01 x In 0.9 (540 A) 0.9 (540 A) 0.80 (200 A) 0.75 (187.5 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_VI
tI> 0…150 @ 0.01 sec - - - -
I> TMS 0.025…1.5 @ 0.001 0.5 0.14 0.4 0.48
I>>
I>> ? No, Yes Yes Yes Yes Yes
I>> 0.5…40 @ 0.01x In 5 (3000 A) 5.1 (3060 A) 3 (750 A) 10.9 (2725 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 1 sec 0.2 sec 0.5 sec 0 sec
I>> TMS 0.025…1.5 @ 0.025 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No Yes No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-1
FEEDER ID BUS COUPLER L-1 DT-2 (3.15 MVA)
CT RATIO 600/5 250/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien 0.2 (120 A) - 0.2 (50 A) -
Delay type 1) 2 - IDMT IEC_SI - 2 - IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - - - -
Ie> TMS 0.025…1.5 @ 0.001 0.4 - 0.4 -
Ie>>
Ie>> ? No, Yes Yes Yes Yes Yes
Ie>> 0.01…8 @ 0.005 x Ien 1 (600 A) 0.035 (21 A) 1 (250 A) 0.08 (20 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT
tIe>> 0…150 @ 0.01 sec 1 sec 0.2 sec 1 sec 0 sec
Ie>> TMS 0.025…1.5 @ 0.001 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Inrush Block Yes / No No Yes
Inrush H2 ratio 10…35 @ 0.1 % - 15%
Inrush tReset time 0…2 @ 0.1 sec - 0.2
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-1
FEEDER ID BUS COUPLER L-1 DT-2 (3.15 MVA)
CT RATIO 600/5 250/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
3 INRUSH BLOCKING
Block I> Yes / No - No
Block I>> Yes / No - Yes
Block I>>> Yes / No - No
Block Ie> Yes / No - No
Block Ie>> Yes / No - Yes
Block Ie>>> Yes / No - No
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-1
FEEDER ID L-1 PAB-B TR (1.25 MVA) L-1 PAB-A TR (1.25 MVA)
CT RATIO 75/5 75/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes Yes Yes
I> 0.1…25 @ 0.01 x In 0.75 (56.2 A) 1 (75 A) 0.75 (56.2 A) 1 (75 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - - - -
I> TMS 0.025…1.5 @ 0.001 0.4 0.1 0.4 0.1
I>>
I>> ? No, Yes Yes Yes Yes Yes
I>> 0.5…40 @ 0.01x In 3 (225 A) 18.2 (1365 A) 3 (225 A) 18.2 (1365 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 0.75 0 sec 0.75 0 sec
I>> TMS 0.025…1.5 @ 0.025 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No Yes No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-1
FEEDER ID L-1 PAB-B TR (1.25 MVA) L-1 PAB-A TR (1.25 MVA)
CT RATIO 75/5 75/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien 0.2 (15 A) - 0.2 (15 A) -
Delay type 1) 2 - IDMT IEC_SI - 2 - IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - - - -
Ie> TMS 0.025…1.5 @ 0.001 0.4 - 0.4 -
Ie>>
Ie>> ? No, Yes Yes Yes Yes Yes
Ie>> 0.01…8 @ 0.005 x Ien 1 (75 A) 0.3 (22.5 A) 1 (75 A) 0.3 (22.5 A)
Delay type 1) 1) DT 1 - DT 1) DT 1 - DT
tIe>> 0…150 @ 0.01 sec 1 0 sec 1 0 sec
Ie>> TMS 0.025…1.5 @ 0.001 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Inrush Block Yes / No Yes Yes
Inrush H2 ratio 10…35 @ 0.1 % 15% 15%
Inrush tReset time 0…2 @ 0.1 sec 0.2 0.2
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-1
FEEDER ID L-1 PAB-B TR (1.25 MVA) L-1 PAB-A TR (1.25 MVA)
CT RATIO 75/5 75/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
3 INRUSH BLOCKING
Block I> Yes / No No No
Block I>> Yes / No Yes Yes
Block I>>> Yes / No No No
Block Ie> Yes / No No No
Block Ie>> Yes / No Yes Yes
Block Ie>>> Yes / No No No
REMARKS
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-1
FEEDER ID SWB-3 (BUS-B) I/C-2
CT RATIO 600/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes
I> 0.1…25 @ 0.01 x In 0.9 (540 A) 0.9 (540 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - -
I> TMS 0.025…1.5 @ 0.001 0.6 0.2
I>>
I>> ? No, Yes Yes Yes
I>> 0.5…40 @ 0.05x In 5 (3000 A) 5.5 (3300 A)
Delay type 1) 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 1 sec 0.4 sec
I>> TMS 0.025…1.5 @ 0.001 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-1
FEEDER ID SWB-3 (BUS-B) I/C-2
CT RATIO 600/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien 0.2 (120 A) -
Delay type 1) 2 - IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - -
Ie> TMS 0.025…1.5 @ 0.001 0.3 -
Ie>>
Ie>> ? No, Yes Yes Yes
Ie>> 0.01…8 @ 0.005 x Ien 1 (600 A) 0.035 (21 A)
Delay type 1) 1 - DT 1 - DT
tIe>> 0…150 @ 0.01 sec 2 sec 0.4 sec
Ie>> TMS 0.025…1.5 @ 0.001 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Blocking inrush Yes / No No
Inrush harmonic ratio 10…35 @ 0.1 % -
Inrush tReset time 0…2 @ 0.1 sec -
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-1
FEEDER ID SWB-3 (BUS-B) I/C-2
CT RATIO 600/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
3 INRUSH BLOCKING
Sel1 tI>> Yes / No -
Sel1 tI>>> Yes / No -
Sel1 tIe>> Yes / No -
Sel1 tIe>>> Yes / No -
Sel1 tIe_d> Yes / No -
Sel1 tIe_d>> Yes / No -
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-2
FEEDER ID BUS COUPLER-1 SWB-2 (BUS-D) I/C-3 L-2 DT-1 (2.5 MVA)
CT RATIO 800/5 600/5 200/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED RECOMMENDED RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes No Yes Yes Yes Yes Yes
I> 0.1…25 @ 0.01 x In - 0.68 (544 A) 0.9 (540 A) 0.9 (540 A) 0.54 (108 A) 0.75 (150 A)
Delay type 1) - 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_VI
tI> 0…150 @ 0.01 sec - - - - - -
I> TMS 0.025…1.5 @ 0.001 - 0.16 0.4 0.2 0.3 0.45
I>>
I>> ? No, Yes No Yes Yes Yes Yes Yes
I>> 0.5…40 @ 0.01x In - 3.9 (3120 A) 4 (2400 A) 5.5 (3300 A) 3 (600 A) 10.6 (2120 A)
Delay type 1) - 1 - DT 1 - DT 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec - 0.2 sec 0.77 sec 0.4 sec 0.55 sec 0 sec
I>> TMS 0.025…1.5 @ 0.025 - - - - - -
I>>>
I>>> ? No, Yes, Peak No No No No Yes No
I>>> 0.5…40 @ 0.01x In - - - - 10 (2000 A) -
tI>>> 0…150 @ 0.01 sec - - - - 0.01 sec -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes No No Yes No Yes Yes
Ie> 0.01…2 @ 0.005 x Ien - - 0.2 (120 A) - 0.2 (40 A) 0.1 (20 A)
Delay type 1) - - 2 - IDMT IEC_SI - 2 - IDMT IEC_SI 1 - DT
tIe> 0…150 @ 0.01 sec - - - - - 0 sec
Ie> TMS 0.025…1.5 @ 0.001 - - 0.4 - 0.2 -
Page 1 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-2
FEEDER ID BUS COUPLER-1 SWB-2 (BUS-D) I/C-3 L-2 DT-1 (2.5 MVA)
CT RATIO 800/5 600/5 200/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED RECOMMENDED RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>>
Ie>> ? No, Yes No Yes Yes Yes No No
Ie>> 0.01…8 @ 0.005 x Ien - 0.025 (20 A) 1 (600 A) 0.035 (21 A) - -
Delay type 1) - 1 - DT 1 - DT 1 - DT - -
tIe>> 0…150 @ 0.01 sec - 0.2 sec 1 sec 0.4 sec - -
Ie>> TMS 0.025…1.5 @ 0.001 - - - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Inrush Block Yes / No No No Yes
Inrush H2 ratio 10…35 @ 0.1 % - - 15%
Inrush tReset 0…2 @ 0.1 sec - - 0.2
Block I> Yes / No - - No
Block I>> Yes / No - - Yes
Block I>>> Yes / No - - No
Block Ie> Yes / No - - Yes
Block Ie>> Yes / No - - No
Block Ie>>> Yes / No - - No
Page 2 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-2
FEEDER ID BUS COUPLER -2 SWB-2 (BUS-C) I/C-4 L-2 DT-2 (2.5 MVA)
CT RATIO 800/5 600/5 200/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED RECOMMENDED RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes No No Yes Yes Yes Yes
I> 0.1…25 @ 0.01 x In - - 0.9 (540 A) 0.9 (540 A) 0.54 (108 A) 0.75 (150 A)
Delay type 1) - - 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_VI
tI> 0…150 @ 0.01 sec - - - - - -
I> TMS 0.025…1.5 @ 0.001 - - 0.6 0.2 0.3 0.45
I>>
I>> ? No, Yes No No Yes Yes Yes Yes
I>> 0.5…40 @ 0.01x In - - 5 (3000 A) 5.5 (3300 A) 3 (600 A) 10.6 (2120 A)
Delay type 1) - - 1 - DT 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec - - 1 sec 0.4 sec 0.55 sec 0 sec
I>> TMS 0.025…1.5 @ 0.025 - - - - - -
I>>>
I>>> ? No, Yes, Peak No No No No Yes No
I>>> 0.5…40 @ 0.01x In - - - - 10 (2000 A) -
tI>>> 0…150 @ 0.01 sec - - - - 0.01 sec -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes No No Yes No Yes Yes
Ie> 0.01…2 @ 0.005 x Ien - - 0.2 (120 A) - 0.2 (40 A) 0.1 (20 A)
Delay type 1) - - 2 - IDMT IEC_SI - 2 - IDMT IEC_SI 1 - DT
tIe> 0…150 @ 0.01 sec - - - - - 0 sec
Ie> TMS 0.025…1.5 @ 0.001 - - 0.3 - 0.2 -
Page 1 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-2
FEEDER ID BUS COUPLER -2 SWB-2 (BUS-C) I/C-4 L-2 DT-2 (2.5 MVA)
CT RATIO 800/5 600/5 200/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED RECOMMENDED RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>>
Ie>> ? No, Yes No No Yes Yes No No
Ie>> 0.01…8 @ 0.005 x Ien - - 1 (600 A) 0.035 (21 A) - -
Delay type 1) - - 1 - DT 1 - DT - -
tIe>> 0…150 @ 0.01 sec - - 2 sec 0.4 sec - -
Ie>> TMS 0.025…1.5 @ 0.001 - - - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Inrush Block Yes / No No No Yes
Inrush H2 ratio 10…35 @ 0.1 % - - 15%
Inrush tReset 0…2 @ 0.1 sec - - 0.2
Block I> Yes / No - - No
Block I>> Yes / No - - Yes
Block I>>> Yes / No - - No
Block Ie> Yes / No - - Yes
Block Ie>> Yes / No - - No
Block Ie>>> Yes / No - - No
Page 2 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-2
FEEDER ID L-2 PAB-D TR (1.25 MVA)
CT RATIO 50/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes
I> 0.1…25 @ 0.01 x In 0.4 (20 A) 0.72 (36 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - -
I> TMS 0.025…1.5 @ 0.001 0.3 0.09
I>>
I>> ? No, Yes Yes Yes
I>> 0.5…40 @ 0.05x In 2 (100 A) 15.4 (770 A)
Delay type 1) 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 0.55 0 sec
I>> TMS 0.025…1.5 @ 0.001 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-2
FEEDER ID L-2 PAB-D TR (1.25 MVA)
CT RATIO 50/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien 0.2 (10 A) -
Delay type 1) IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - -
Ie> TMS 0.025…1.5 @ 0.001 0.04 -
Ie>>
Ie>> ? No, Yes No Yes
Ie>> 0.01…8 @ 0.005 x Ien - 0.4 (20 A)
Delay type 1) - 1 - DT
tIe>> 0…150 @ 0.01 sec - 0 sec
Ie>> TMS 0.025…1.5 @ 0.001 - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Blocking inrush Yes / No Yes
Inrush harmonic ratio 10…35 @ 0.1 % 15%
Inrush tReset 0…2 @ 0.1 sec 0.2
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 LINE-2
FEEDER ID L-2 PAB-D TR (1.25 MVA)
CT RATIO 50/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
3 INRUSH BLOCKING
Sel1 tI>> Yes / No Yes
Sel1 tI>>> Yes / No No
Sel1 tIe>> Yes / No Yes
Sel1 tIe>>> Yes / No No
Sel1 tIe_d> Yes / No No
Sel1 tIe_d>> Yes / No No
REMARKS
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID BUS COUPLER - 4 L-3 PAB-A TR (1.25 MVA) L-3 DT-1 (2.5 MVA)
CT RATIO 800/5 100/5 200/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes Yes Yes Yes Yes
I> 0.1…25 @ 0.01 x In 0.6 (480 A) 0.68 (544 A) 1.2 (120 A) 0.72 (72 A) 0.66 (132 A) 0.72 (144 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_VI
tI> 0…150 @ 0.01 sec - - - - - -
I> TMS 0.025…1.5 @ 0.001 0.3 0.16 1.1 0.13 0.3 0.53
I>>
I>> ? No, Yes Yes Yes Yes Yes Yes Yes
I>> 0.5…40 @ 0.05x In 0.7 (560 A) 3.9 (3120 A) 3 (300 A) 14.8 (1480 A) 1.5 (300 A) 11.6 (2320 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 0.3 sec 0.2 sec 0.05 sec 0 sec 0.49 sec 0 sec
I>> TMS 0.025…1.5 @ 0.001 - - - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No Yes No Yes No
Ie> 0.01…2 @ 0.005 x Ien 0.2 (160 A) - 0.2 (20 A) - 0.2 (40 A) -
Delay type 1) 2 - IDMT IEC_SI - 2 - IDMT IEC_SI - 2 - IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - - - - - -
Ie> TMS 0.025…1.5 @ 0.001 0.2 - 0.2 - 0.2 -
Ie>>
Ie>> ? No, Yes Yes Yes Yes Yes Yes Yes
Page 1 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID BUS COUPLER - 4 L-3 PAB-A TR (1.25 MVA) L-3 DT-1 (2.5 MVA)
CT RATIO 800/5 100/5 200/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P122 MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>>
Ie>> 0.01…8 @ 0.005 x Ien 5 (4000 A) 0.025 (20 A) 0.5 (50 A) 0.2 (20 A) 0.31 (62 A) 0.1 (20 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT 1 - DT 1 - DT
tIe>> 0…150 @ 0.01 sec 0.5 sec 0.2 sec 0.05 sec 0 sec 0.5 sec 0 sec
Ie>> TMS 0.025…1.5 @ 0.001 - - - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Blocking inrush Yes / No No Yes Yes
Inrush harmonic ratio 10…35 @ 0.1 % - 15% 15%
Inrush tReset time 0…2 @ 0.1 sec - 0.2 0.2
Sel1 tI>> Yes / No - Yes Yes
Sel1 tI>>> Yes / No - No No
Sel1 tIe>> Yes / No - Yes Yes
Sel1 tIe>>> Yes / No - No No
Sel1 tIe_d> Yes / No - No No
Sel1 tIe_d>> Yes / No - No No
Page 2 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID BUS COUPLER - 5 L-3 DT-2 (2.5 MVA)
CT RATIO 800/5 200/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes No Yes Yes Yes
I> 0.1…25 @ 0.01 x In - 0.68 (544 A) 0.68 (136 A) 0.72 (144 A)
Delay type 1) - 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_VI
tI> 0…150 @ 0.01 sec - - - -
I> TMS 0.025…1.5 @ 0.001 - 0.16 0.17 0.53
I>>
I>> ? No, Yes No Yes Yes Yes
I>> 0.5…40 @ 0.05x In - 3.9 (3120 A) 1.5 (300 A) 11.6 (2320 A)
Delay type 1) - 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec - 0.2 sec 0.29 sec 0 sec
I>> TMS 0.025…1.5 @ 0.001 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes No No Yes No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID BUS COUPLER - 5 L-3 DT-2 (2.5 MVA)
CT RATIO 800/5 200/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien - - 0.2 (40 A) -
Delay type 1) - - 2 - IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - - - -
Ie> TMS 0.025…1.5 @ 0.001 - - 0.025 -
Ie>>
Ie>> ? No, Yes No Yes No Yes
Ie>> 0.01…8 @ 0.005 x Ien - 0.025 (20 A) - 0.1 (20 A)
Delay type 1) - 1 - DT - 1 - DT
tIe>> 0…150 @ 0.01 sec - 0.2 sec - 0 sec
Ie>> TMS 0.025…1.5 @ 0.001 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Blocking inrush Yes / No No Yes
Inrush harmonic ratio 10…35 @ 0.1 % - 15%
Inrush tReset 0…2 @ 0.1 sec - -
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID BUS COUPLER - 5 L-3 DT-2 (2.5 MVA)
CT RATIO 800/5 200/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
3 INRUSH BLOCKING
Sel1 tI>> Yes / No - Yes
Sel1 tI>>> Yes / No - No
Sel1 tIe>> Yes / No - Yes
Sel1 tIe>>> Yes / No - No
Sel1 tIe_d> Yes / No - No
Sel1 tIe_d>> Yes / No - No
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID L-3 PAB-B TR (1.25 MVA) L-3 PAB-C TR (1.25 MVA)
CT RATIO 100/5 100/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes Yes Yes Yes Yes
I> 0.1…25 @ 0.01 x In 1.2 (120 A) 0.72 (72 A) 1.2 (120 A) 0.72 (72 A)
Delay type 1) 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - - - -
I> TMS 0.025…1.5 @ 0.001 1.1 0.13 1.1 0.13
I>>
I>> ? No, Yes Yes Yes Yes Yes
I>> 0.5…40 @ 0.05x In 3 (300 A) 14.8 (1480 A) 3 (300 A) 14.8 (1480 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT
tI>> 0…150 @ 0.01 sec 0.05 sec 0 sec 0.05 sec 0 sec
I>> TMS 0.025…1.5 @ 0.001 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes Yes No Yes No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID L-3 PAB-B TR (1.25 MVA) L-3 PAB-C TR (1.25 MVA)
CT RATIO 100/5 100/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien 0.2 (20 A) - 0.2 (20 A) -
Delay type 1) 2 - IDMT IEC_SI - 2 - IDMT IEC_SI -
tIe> 0…150 @ 0.01 sec - - - -
Ie> TMS 0.025…1.5 @ 0.001 0.2 - 0.2 -
Ie>>
Ie>> ? No, Yes Yes Yes Yes Yes
Ie>> 0.01…8 @ 0.005 x Ien 0.5 (50 A) 0.2 (20 A) 0.5 (50 A) 0.2 (20 A)
Delay type 1) 1 - DT 1 - DT 1 - DT 1 - DT
tIe>> 0…150 @ 0.01 sec - 0 sec - 0 sec
Ie>> TMS 0.025…1.5 @ 0.001 0.05 - 0.05 -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Blocking inrush Yes / No Yes Yes
Inrush harmonic ratio 10…35 @ 0.1 % 15% 15%
Inrush tReset 0…2 @ 0.1 sec 0.2 0.2
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID L-3 PAB-B TR (1.25 MVA) L-3 PAB-C TR (1.25 MVA)
CT RATIO 100/5 100/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
3 INRUSH BLOCKING
Sel1 tI>> Yes / No Yes Yes
Sel1 tI>>> Yes / No No No
Sel1 tIe>> Yes / No Yes Yes
Sel1 tIe>>> Yes / No No No
Sel1 tIe_d> Yes / No No No
Sel1 tIe_d>> Yes / No No No
REMARKS
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID SWB-2 (BUS-E) I/C-5 SWB-2 (BUS-F) I/C-6
CT RATIO 800/5 800/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
I> ? No, Yes No Yes No Yes
I> 0.1…25 @ 0.01 x In - 0.68 (544 A) - 0.68 (544 A)
Delay type 1) - 2 - IDMT IEC_SI - 2 - IDMT IEC_SI
tI> 0…150 @ 0.01 sec - - - -
I> TMS 0.025…1.5 @ 0.001 - 0.2 - 0.2
I>>
I>> ? No, Yes No Yes No Yes
I>> 0.5…40 @ 0.01x In - 4.2 (3360 A) - 4.2 (3360 A)
Delay type 1) - 1 - DT - 1 - DT
tI>> 0…150 @ 0.01 sec - 0.4 sec - 0.4 sec
I>> TMS 0.025…1.5 @ 0.025 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> ? No, Yes No No No No
Page 1 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID SWB-2 (BUS-E) I/C-5 SWB-2 (BUS-F) I/C-6
CT RATIO 800/5 800/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
2 EARTH OVERCURRENT PROTECTION (50N/51N)
Ie>
Ie> 0.01…2 @ 0.005 x Ien - - - -
Delay type 1) - - - -
tIe> 0…150 @ 0.01 sec - - - -
Ie> TMS 0.025…1.5 @ 0.001 - - - -
Ie>>
Ie>> ? No, Yes No Yes No Yes
Ie>> 0.01…8 @ 0.005 x Ien - 0.015 (12 A) - 0.015 (12 A)
Delay type 1) - 1 - DT - 1 - DT
tIe>> 0…150 @ 0.01 sec - 0.4 - 0.4
Ie>> TMS 0.025…1.5 @ 0.001 - - - -
1) 1-DT, 2-IDMT (IEC_STI, IEC_SI, IEC_VI, IEC_EI, IEC_LTI, C02, C08, IEEE_MI, IEEE_VI, IEEE_EI, RI, RECT curve)
3 INRUSH BLOCKING
Inrush Block Yes / No No No
Inrush H2 ratio 10…35 @ 0.1 % - -
Inrush tReset 0…2 @ 0.1 sec - -
Page 2 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID SWB-2 (BUS-E) I/C-5 SWB-2 (BUS-F) I/C-6
CT RATIO 800/5 800/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P122 MiCOM P122
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
3 INRUSH BLOCKING
Block I> Yes / No - -
Block I>> Yes / No - -
Block I>>> Yes / No - -
Block Ie> Yes / No - -
Block Ie>> Yes / No - -
Block Ie>>> Yes / No - -
Page 3 of 3
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID PAB-1 PAB-2 PAB-3
RELAY MODEL NO. MiCOM P225 MiCOM P225 MiCOM P225
MOTOR RATING (kW) 550 kW 550 kW 550 kW
RATED VOLTAGE (kV) 3.3 kV 3.3 kV 3.3 kV
FULL LOAD CURRENT (A) 114 114 114
RATED POWER FACTOR 87% 87% 87%
RATED EFFICIENCY 96.40% 96.40% 96.40%
STARTING CURRENT 684 A (6 x FLA) 684 A (6 x FLA) 684 A (6 x FLA)
STARTING TIME (100% RATED VOLTAGE)
STARTING TIME (80% RATED VOLTAGE)
NO. OF START (HOT/COLD)
STARTING METHOD Soft Starter Soft Starter Soft Starter
CT RATIO 250/5 250/5 250/5
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
PROTECTION G1
1 START CRITERIA
Iutil 0.5…5 @ 0.01 x In 1.2 (300 A) 1.2 (300 A) 1.2 (300 A)
t Istart 1…200 @ 1 sec 25 sec 25 sec 25 sec
2 SHORT-CIRCUIT PROTECTION (50/51)
I>
I> 0.1…25 @ 0.05 x In 2 (500 A) Disabled 2 (500 A) Disabled 2 (500 A) Disabled
Delay type 1) IDMT IEC SI - IDMT IEC SI - IDMT IEC SI -
tI> (DMT) 0…150 @ 0.01 sec 1.5 - 1.5 - 1.5 -
I>>
I>> 0.5…40 @ 0.05 x In 3 (750 A) 4.1 (1025 A) 3 (750 A) 4.1 (1025 A) 3 (750 A) 4.1 (1025 A)
Delay type 1) DT DT DT DT DT DT
tI>> (DMT) 0…150 @ 0.01 sec 0.05 sec 0.1 Sec 0.05 sec 0.1 Sec 0.05 sec 0.1 Sec
1) DT, IDMT, RI
Page 1 of 5
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID PAB-1 PAB-2 PAB-3
RELAY MODEL NO. MiCOM P225 MiCOM P225 MiCOM P225
MOTOR RATING (kW) 550 kW 550 kW 550 kW
RATED VOLTAGE (kV) 3.3 kV 3.3 kV 3.3 kV
FULL LOAD CURRENT (A) 114 114 114
RATED POWER FACTOR 87% 87% 87%
RATED EFFICIENCY 96.40% 96.40% 96.40%
STARTING CURRENT 684 A (6 x FLA) 684 A (6 x FLA) 684 A (6 x FLA)
STARTING TIME (100% RATED VOLTAGE)
STARTING TIME (80% RATED VOLTAGE)
NO. OF START (HOT/COLD)
STARTING METHOD Soft Starter Soft Starter Soft Starter
CT RATIO 250/5 250/5 250/5
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
3 EARTH FAULT PROTECTION (50N/51N)
IO>
IO> 0.002…1 @ 0.001 x IOn 0.15 (37.5 A) 0.04 (10 A) 0.15 (37.5 A) 0.04 (10 A) 0.15 (37.5 A) 0.04 (10 A)
tIO> 0…100 @ 0.01 sec 0.2 sec 0.1 Sec 0.2 sec 0.1 Sec 0.2 sec 0.1 Sec
IO>>
IO>> 0.002…1 @ 0.001 x IOn 0.5 (125 A) Disabled 0.5 (125 A) Disabled 0.5 (125 A) Disabled
tIO>> 0…100 @ 0.01 sec 0.05 Sec - 0.05 Sec - 0.05 Sec -
4 UNDER VOLTAGE PROTECTION (27)
V<
V< 5…130 @ 0.1 x V 88 88 88 88 88 88
tV< 0…600 @ 0.01 sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec 2 Sec
5 THERMAL REPLICA (49)
Iθ> 0.2…1.5 @ 0.01 x In 0.47 (117.5 A) 0.47 (117.5 A) 0.47 (117.5 A) 0.47 (117.5 A) 0.47 (117.5 A) 0.47 (117.5 A)
Te1 1…180 @ 1 min 2 2 2 2 2 2
Page 2 of 5
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID PAB-1 PAB-2 PAB-3
RELAY MODEL NO. MiCOM P225 MiCOM P225 MiCOM P225
MOTOR RATING (kW) 550 kW 550 kW 550 kW
RATED VOLTAGE (kV) 3.3 kV 3.3 kV 3.3 kV
FULL LOAD CURRENT (A) 114 114 114
RATED POWER FACTOR 87% 87% 87%
RATED EFFICIENCY 96.40% 96.40% 96.40%
STARTING CURRENT 684 A (6 x FLA) 684 A (6 x FLA) 684 A (6 x FLA)
STARTING TIME (100% RATED VOLTAGE)
STARTING TIME (80% RATED VOLTAGE)
NO. OF START (HOT/COLD)
STARTING METHOD Soft Starter Soft Starter Soft Starter
CT RATIO 250/5 250/5 250/5
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
5 THERMAL REPLICA (49)
Te2 1…360 @ 1 min 2 2 2 2 2 2
Tr 1…999 @ 1 min 1 1 1 1 1 1
Ke 0…10 @ 1 3 3 3 3 3 3
Thermal alarm
20…100 @ 1 % 95% 90% 98% 90% 98% 90%
threshold
6 UNBALANCE PROTECTION (46)
I2>
I2> 0.04…0.8 @ 0.01 x In Disabled 0.23 (57.5 A) Disabled 0.23 (57.5 A) Disabled 0.23 (57.5 A)
tI2> 0…200 @ 0.01 sec - 1 sec - 1 sec - 1 sec
I2>>
I2>> 0.04…0.8 @ 0.01 x In Disabled 0.14 (35 A) Disabled 0.14 (35 A) Disabled 0.14 (35 A)
TMS I2>> 0.2…2 @ 0.001 - 0.6 - 0.6 - 0.6
4 STALL / LOCKED ROTOR PROTECTION (51 R)
I Stall 0.5…5 @ 0.01 x In 1.14 (285 A) 1.14 ( 285 A) 1.14 (285 A) 1.14 ( 285 A) 1.14 (285 A) 1.14 ( 285 A)
Page 3 of 5
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID PAB-1 PAB-2 PAB-3
RELAY MODEL NO. MiCOM P225 MiCOM P225 MiCOM P225
MOTOR RATING (kW) 550 kW 550 kW 550 kW
RATED VOLTAGE (kV) 3.3 kV 3.3 kV 3.3 kV
FULL LOAD CURRENT (A) 114 114 114
RATED POWER FACTOR 87% 87% 87%
RATED EFFICIENCY 96.40% 96.40% 96.40%
STARTING CURRENT 684 A (6 x FLA) 684 A (6 x FLA) 684 A (6 x FLA)
STARTING TIME (100% RATED VOLTAGE)
STARTING TIME (80% RATED VOLTAGE)
NO. OF START (HOT/COLD)
STARTING METHOD Soft Starter Soft Starter Soft Starter
CT RATIO 250/5 250/5 250/5
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
4 STALL / LOCKED ROTOR PROTECTION (51 R)
tIstall 0.1…60 @ 0.1 sec 5 Sec 5 sec 5 Sec 5 sec 5 Sec 5 sec
PROTECTION G2
1 START CRITERIA
Iutil 0.5…5 @ 0.01 x In 6 (1500 A) Disabled 6 (1500 A) Disabled 6 (1500 A) Disabled
t Istart 1…200 @ 1 sec 1 sec - 1 sec - 1 sec -
2 THERMAL REPLICA (49)
Iθ> 0.2…1.5 @ 0.01 x In 0.2 (50 A) Disabled - Disabled - Disabled
Te1 1…180 @ 1 min 1 - - - - -
Te2 1…360 @ 1 min 1 - - - - -
Tr 1…999 @ 1 min 1 - - - - -
Ke 0…10 @ 1 3 - - - - -
Thermal alarm
20…100 @ 1 % - - - - - -
threshold
Start-up inhibition 20…100 @ 1 % - - - - - -
Page 4 of 5
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION 11kV SWITCHBOARD-3 ROOM - LINE-3
FEEDER ID PAB-1 PAB-2 PAB-3
RELAY MODEL NO. MiCOM P225 MiCOM P225 MiCOM P225
MOTOR RATING (kW) 550 kW 550 kW 550 kW
RATED VOLTAGE (kV) 3.3 kV 3.3 kV 3.3 kV
FULL LOAD CURRENT (A) 114 114 114
RATED POWER FACTOR 87% 87% 87%
RATED EFFICIENCY 96.40% 96.40% 96.40%
STARTING CURRENT 684 A (6 x FLA) 684 A (6 x FLA) 684 A (6 x FLA)
STARTING TIME (100% RATED VOLTAGE)
STARTING TIME (80% RATED VOLTAGE)
NO. OF START (HOT/COLD)
STARTING METHOD Soft Starter Soft Starter Soft Starter
CT RATIO 250/5 250/5 250/5
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
3 UNDER VOLTAGE PROTECTION (27)
V<
V< 5…130 @ 0.1 x V 5V Disabled - Disabled - Disabled
tV< 0…600 @ 0.01 sec 0 Sec - - - - -
All other protection settings must be disabled.
Note:
Values in () are in terms of Primary Amps.
Page 5 of 5
POWER SYSTEM STUDY REPORT
PMCC - 101
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-101 (11 KV SWITCHBOARD-2 ROOM)
FEEDER ID TR-3 CPP 1 AUX
CT RATIO 3000/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P111
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
Configruration 1) On 1-trip
I> toc 2) toc 2 - IEC V Inverse
I> 0.5…3 @ 0.1 X In 1 (3000 A)
TIME DELAY / TMS 0.02…99.9 @ 0.01 sec 0.22
I>>
Configruration 1) On 1-trip
I>> 0.5…30 @ 0.1 X In 3 (9000 A)
TIME DELAY 0.02…99.9 @ 0.01 sec 0.4 sec
1) on 0 - disable, on 1 - trip, on 2 - Alarm
2) toc 0 - DT, toc 1 - IEC S Inverse, toc 2 - IEC V Inverse, toc 3 -IEC E Inverse
2 EARTH FAULT PROTECTION (50N/51N)
Io>
Configruration 1) On 1-trip
Io> toc 2) 2 - IEC V Inverse
Io> 0.01…0.1 @ 0.01 X In 0.18 (540 A)
TIME DELAY / TMS 0.02…99.9 @ 0.01 sec 0.58
Page 1 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-101 (11 KV SWITCHBOARD-2 ROOM)
FEEDER ID TR-3 CPP 1 AUX
CT RATIO 3000/5
CBCT RATIO -
RELAY MODEL NO. MiCOM P111
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
2 EARTH FAULT PROTECTION (50N/51N)
Io>>
Configruration 1) On 1-trip
Io>> toc 2) toc 0 - DT
Io>> 0.01…0.1 @ 0.01 X In 1 (3000 A)
TIME DELAY / TMS 0.02…99.9 @ 0.01 sec 0.4 sec
1) 0 - disable, 1 - trip, 2 - Alarm
2) 0 - DT, 1 - IEC S Inverse, 2 - IEC V Inverse, 3 -IEC E Inverse
REMARKS
Page 2 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-101 (11 KV SWITCHBOARD-2 ROOM)
FEEDER ID TR-3 CPP 1 AUX
NCT RATIO 3150/1
CBCT RATIO -
RELAY MODEL NO. CAG14
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 RESTRICTED EARTH FAULT PROTECTION (64R)
Pickup 0.2…0.8 @ 0.1 A 0.4 (1260 A) 0.2 (630 A)
REMARKS
Page 1 of 1
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-101 (11 KV SWITCHBOARD-2 ROOM)
FEEDER ID TR-3 CPP 1 AUX
NCT RATIO 3150/1
CBCT RATIO -
RELAY MODEL NO. CDG11
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 STANDBY EARTH FAULT PROTECTION (51NS)
Pickup 0.5…2 @ 0.25 A 1 (3150 A) 0.5 (1575 A)
TMS 0…1.0 @ 0.05 1 0.25
Char. NI-1.3 sec @ 10 x PSM NI-1.3 Sec NI-1.3 Sec
Page 1 of 1
POWER SYSTEM STUDY REPORT
PMCC – 104
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-104 (11 KV SWITCHBOARD-2 ROOM)
FEEDER ID TR-4 CPP 2 AUX
NCT RATIO 2000/1
CBCT RATIO -
RELAY MODEL NO. CAG 14
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 RESTRICTED EARTH FAULT PROTECTION (64R)
Pickup 0.2…0.8 @ 0.1 A 0.2 (400 A) 0.2 (400 A)
REMARKS
Page 1 of 1
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-104 (11 KV SWITCHBOARD-2 ROOM)
FEEDER ID TR-4 CPP 2 AUX
NCT RATIO 2000/1
CBCT RATIO -
RELAY MODEL NO. CDG 13
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 STANDBY EARTH FAULT PROTECTION (51NS)
Pickup 0.1…0.4 0.15 (300 A) 0.2 (400 A)
TMS 0…1.0 @ 0.05 0.5 0.85
Char. VI VI VI
REMARKS
Page 1 of 1
POWER SYSTEM STUDY REPORT
PMCC – 106
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-106 (11 KV SWITCHBOARD-2 ROOM)
FEEDER ID TR-5 CPP 3 AUX
NCT RATIO 2500/1
CBCT RATIO -
RELAY MODEL NO. CAG 14
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 RESTRICTED EARTH FAULT PROTECTION (64R)
Pickup 0.1…0.4 @ 0.05 A 0.25 (625 A) 0.2 (500 A)
REMARKS
Page 1 of 1
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-106 (11 KV SWITCHBOARD-2 ROOM)
FEEDER ID TR-5 CPP 3 AUX
NCT RATIO 2500/1
CBCT RATIO -
RELAY MODEL NO. CDG 11
PROTECTION SETTING
EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING
1 STANDBY EARTH FAULT PROTECTION (51NS)
Pickup 0.1…0.4 @ 0.05 A 0.15 (375 A) 0.2 (500 A)
TMS 0…1.0 @ 0.05 0.15 0.25
Char. NI-1.3 sec @ 10 x PSM NI-1.3 sec NI-1.3 sec
REMARKS
Page 1 of 1
POWER SYSTEM STUDY REPORT
PMCC - 102
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-102 (L-1 MCC ROOM)
FEEDER ID L-1 DT-1 DG SUPPLY INCOMER L-1 DT-2
CT RATIO 5000/5 1250/5 5000/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P111 MiCOM P111 MiCOM P111
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
Configruration 1) On 1-trip On 1-trip On 0 - Disabled On 1-trip On 1-trip
I> toc 2) toc 1 - IEC S Inverse toc 2 - IEC V Inverse - toc 1 - IEC S Inverse toc 2 - IEC V Inverse
I> 0.5…3 @ 0.1 X In 4.2 (21000 A) 1 (5000 A) - 4.2 (21000 A) 1 (5000 A)
TIME DELAY / TMS 0.02…99.9 @ 0.01 sec 0.1 0.29 - 0.1 0.29
I>>
Configruration 1) On 0 - Disabled On 0 - Disabled On 0 - Disabled Disabled Disabled
I>> 0.5…30 @ 0.1 X In - - - - -
TIME DELAY 0.02…99.9 @ 0.01 sec - - - - -
Ip>
Configruration 1) On 1-trip On 1-trip On 0 - Disabled On 1-trip On 1-trip
Ip> toc 2) toc 1 - IEC S Inverse toc 0 - DT - toc 1 - IEC S Inverse toc 0 - DT
Ip> (IDMT) 0.5…3 @ 0.1 X In 0.16 (800 A) - - 0.25 (1250 A) -
Ip> (DT) 0.5…30 @ 0.1 X In - 3.4 (17000 A) - - 3.4 (17000 A)
TIME DELAY 0.02…99.9 @ 0.01 sec 0.18 0.4 sec - 0.18 0.4 sec
1) on 0 - disable, on 1 - trip, on 2 - Alarm
2) toc 0 - DT, toc 1 - IEC S Inverse, toc 2 - IEC V Inverse, toc 3 -IEC E Inverse
2 EARTH FAULT PROTECTION (50N/51N)
Io>
Configruration 1) On 1-trip On 0 - Disabled On 1-trip
Io> toc 2) toc 2 - IEC V Inverse - toc 2 - IEC V Inverse
Io> 0.01…0.1 @ 0.01 X In 0.17 (850 A) - 0.17 (850 A)
TIME DELAY / TMS 0.02…99.9 @ 0.01 sec 0.58 - 0.58
Page 1 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-102 (L-1 MCC ROOM)
FEEDER ID L-1 DT-1 DG SUPPLY INCOMER L-1 DT-2
CT RATIO 5000/5 1250/5 5000/5
CBCT RATIO - - -
RELAY MODEL NO. MiCOM P111 MiCOM P111 MiCOM P111
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING SETTING SETTING
2 EARTH FAULT PROTECTION (50N/51N)
Io>>
Configruration 1) On 1-trip On 0 - Disabled On 1-trip
Io>> toc 2) toc 0 - DT - toc 0 - DT
Io>> 0.01…1 @ 0.01 X In 1 (5000 A) - 1 (5000 A)
TIME DELAY / TMS 0.02…99.9 @ 0.01 sec 0.4 sec - 0.4 sec
1) on 0 - disable, on 1 - trip, on 2 - Alarm
2) toc 0 - DT, toc 1 - IEC S Inverse, toc 2 - IEC V Inverse, toc 3 -IEC E Inverse
REMARKS
Page 2 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-102 (L-1 MCC ROOM)
FEEDER ID L-1 DT-1 L-1 DT-2
NCT RATIO 5000/1 5000/1
CBCT RATIO - -
RELAY MODEL NO. CAG 14 CAG 14
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 RESTRICTED EARTH FAULT PROTECTION (64R)
Pickup 0.2…0.8 @ 0.1 A 0.2 (1000 A) 0.2 (1000 A) 0.2 (1000 A) 0.2 (1000 A)
REMARKS
Page 1 of 1
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-102 (L-1 MCC ROOM)
FEEDER ID L-1 DT-1 L-1 DT-2
NCT RATIO 5000/1 5000/1
CBCT RATIO - -
RELAY MODEL NO. CDG 11 CDG 11
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 STANDBY EARTH FAULT PROTECTION (51NS)
Pickup 0.5…2 @ 0.25 A 1 (5000 A) 0.5 (2500 A) 2 (10000 A) 0.5 (2500 A)
TMS 0…1.0 @ 0.05 0.2 0.25 1 0.25
Char. NI-1.3 sec @ 10 x PSM 1.3 sec 1.3 sec 1.3 sec 1.3 sec
Page 1 of 1
POWER SYSTEM STUDY REPORT
PMCC – 103
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-103 (L-2 MCC ROOM)
FEEDER ID L-2 DT-1 L-2 DT-2
CT RATIO 4000/1 4000/1
CBCT RATIO - -
RELAY MODEL NO. MiCOM P111 MiCOM P111
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
Configruration 1) On 1-trip On 1-trip
I> toc 2) toc 2 - IEC V Inverse toc 2 - IEC V Inverse
I> 0.5…3 @ 0.1 X In 1 (4000 A) 1 (4000 A)
TIME DELAY / TMS 0.02…99.9 @ 0.01 sec 0.29 0.29
I>>
Configruration 1) On 1-trip On 1-trip
I>> 0.5…30 @ 0.1 X In 3.4 (13600 A) 3.4 (13600 A)
TIME DELAY 0.02…99.9 @ 0.01 sec 0.4 sec 0.4 sec
1) on 0 - disable, on 1 - trip, on 2 - Alarm
2) toc 0 - DT, toc 1 - IEC S Inverse, toc 2 - IEC V Inverse, toc 3 -IEC E Inverse
2 EARTH FAULT PROTECTION (50N/51N)
Io>
Configruration 1) On 1-trip On 1-trip
Io> toc 2) toc 2 - IEC V Inverse toc 2 - IEC V Inverse
Io> 0.01…0.1 @ 0.01 X In 0.16 (640 A) 0.16 (640 A)
TIME DELAY / TMS 0.02…99.9 @ 0.01 sec 0.58 0.58
Page 1 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-103 (L-2 MCC ROOM)
FEEDER ID L-2 DT-1 L-2 DT-2
CT RATIO 4000/5 4000/5
CBCT RATIO - -
RELAY MODEL NO. MiCOM P111 MiCOM P111
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
2 EARTH FAULT PROTECTION (50N/51N)
Io>>
Configruration 1) On 1-trip On 1-trip
Io>> toc 2) toc 0 - DT toc 0 - DT
Io>> 0.01…1 @ 0.01 X In 1 (4000 A) 1 (4000 A)
TIME DELAY / TMS 0.02…99.9 @ 0.01 sec 0.4 sec 0.4 sec
1) 0 - disable, 1 - trip, 2 - Alarm
2) toc 0 - DT, toc 1 - IEC S Inverse, toc 2 - IEC V Inverse, toc 3 -IEC E Inverse
REMARKS
Page 2 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-103 (L-2 MCC ROOM)
FEEDER ID L-2 DT-1 L-2 DT-2
NCT RATIO 4000/1 4000/1
CBCT RATIO - -
RELAY MODEL NO. CAG 14 CAG 14
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 RESTRICTED EARTH FAULT PROTECTION (64R)
Pickup 0.1…0.4 @ 0.05 A 0.2 (800 A) 0.2 (800 A) 0.2 (800 A) 0.2 (800 A)
REMARKS
Page 1 of 1
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-103 (L-2 MCC ROOM)
FEEDER ID L-2 DT-1 L-2 DT-2
NCT RATIO 4000/1 4000/1
CBCT RATIO - -
RELAY MODEL NO. CDG 11 CDG 11
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 STANDBY EARTH FAULT PROTECTION (51NS)
Pickup 0.1…0.4 @ 0.05 A 0.1 (400 A) 0.2 (800 A) 0.1 (400 A) 0.2 (800 A)
TMS 0…1.0 @ 0.05 1 0.3 1 0.3
Char. NI-1.3 sec @ 10 x PSM NI-1.3 sec NI-1.3 sec NI-1.3 sec NI-1.3 sec
REMARKS
Page 1 of 1
POWER SYSTEM STUDY REPORT
PMCC – 105
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-105 (L-2 MCC ROOM)
FEEDER ID L-3 DT-1 L-3 DT-2
CT RATIO 4000/1 4000/1
CBCT RATIO - -
RELAY MODEL NO. MiCOM P111 MiCOM P111
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 PHASE OVERCURRENT PROTECTION (50/51)
I>
Configruration 1) On 1-trip On 1-trip
I> toc 2) toc 2 - IEC V Inverse toc 2 - IEC V Inverse
I> 0.4…4 @ 0.1 X In 1 (3000 A) 1 (3000 A)
TIME DELAY / TMS 0.02…99.9 @ 0.01 sec 0.32 0.32
I>>
Configruration 1) On 1-trip On 1-trip
I>> 0.4…40 @ 0.1 X In 3.4 (13600 A) 3.4 (13600 A)
TIME DELAY 0.02…99.9 @ 0.01 sec 0.4 sec 0.4 sec
1) on 0 - disable, on 1 - trip, on 2 - Alarm
2) toc 0 - DT, toc 1 - IEC S Inverse, toc 2 - IEC V Inverse, toc 3 -IEC E Inverse
2 EARTH FAULT PROTECTION (50N/51N)
Io>
Configruration 1) On 1-trip On 1-trip
Io> toc 2) toc 2 - IEC V Inverse toc 2 - IEC V Inverse
Io> 0.01…0.1 @ 0.01 X In 0.17 (680 A) 0.17 (680 A)
TIME DELAY / TMS 0.02…99.9 @ 0.01 sec 0.58 0.58
Page 1 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-103 (L-2 MCC ROOM)
FEEDER ID L-3 DT-1 L-3 DT-2
CT RATIO 4000/1 4000/1
CBCT RATIO - -
RELAY MODEL NO. MiCOM P111 MiCOM P111
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
2 EARTH FAULT PROTECTION (50N/51N)
Io>>
Configruration 1) On 1-trip On 1-trip
Io>> toc 2) toc 0 - DT toc 0 - DT
Io>> 0.01…1 @ 0.01 X In 1 (4000 A) 1 (4000 A)
TIME DELAY / TMS 0.02…99.9 @ 0.01 sec 0.4 sec 0.4 sec
1) 0 - disable, 1 - trip, 2 - Alarm
2) 0 - DT, 1 - IEC S Inverse, 2 - IEC V Inverse, 3 -IEC E Inverse
REMARKS
Page 2 of 2
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-105 (L-2 MCC ROOM)
FEEDER ID L-3 DT-1 L-3 DT-2
NCT RATIO 4000/1 4000/1
CBCT RATIO - -
RELAY MODEL NO. CAG 14 CAG 14
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 RESTRICTED EARTH FAULT PROTECTION (64R)
Pickup 0.1…0.4 @ 0.05 A 0.1 (400 A) 0.2 (800 A) 0.1 (400 A) 0.2 (800 A)
REMARKS
Page 1 of 1
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony,
REVISION NO. : REV. 0 Unit - Mundra, GJ
Jetalpur Road,
Vadodara - 390 007. RELAY SETTING SHEETS
LOCATION PMCC-105 (L-2 MCC ROOM)
FEEDER ID L-3 DT-1 L-3 DT-2
NCT RATIO 4000/1 4000/1
CBCT RATIO - -
RELAY MODEL NO. CDG 11 CDG 11
PROTECTION SETTING
EXISTING RECOMMENDED EXISTING RECOMMENDED
NO. PROTECTION SETTING RANGE
SETTING SETTING SETTING SETTING
1 STANDBY EARTH FAULT PROTECTION (51NS)
Pickup 0.1…0.4 @ 0.05 A 0.15 (600 A) 0.2 (800 A) 0.15 (600 A) 0.2 (800 A)
TMS 0…1.0 @ 0.05 1 0.3 1 0.3
Char. NI-1.3 sec @ 10 x PSM NI-1.3 Sec NI-1.3 Sec NI-1.3 Sec NI-1.3 Sec
REMARKS
Page 1 of 1
POWER SYSTEM STUDY REPORT
Page 1 of 13
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY AND RELAY COORDINAITON PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony, Unit - PCBL,
REVISION NO. : REV. 0
Jetalpur Road, Mundra, GJ
Vadodara - 390 007. LVCB TRIP UNIT SETTING SHEET
PANEL TYPE OF CB SETTING EXISTING RECOMMENDED
FEEDER ID CB MODEL TRIP UNIT RANGE REMARKS
NO. FEEDER RATING PARAMETER SETTING SETTING
LOCATION: PMCC-104 (11 KV SWITCHBOARD-2 ROOM)
Ir 0.4 - 1.0 x In 1 1
tr 0.2-30 sec @ 6 x Ir 2 3.5
Isd 2 - 10 x In 4 4
1F2 TR-4 CPP 2 AUX I/C CN-CS 2000H 2000 SR18G tsd 20 - 400 msec 400 400 I2t OFF
Ii OFF, 2-16 x In 8 OFF
Ig 0.2 - 0.6 x In 0.3 0.3
tg OFF, 0.1-0.4, 1 sec 0.1 0.4 I2t OFF
Ir 0.4 - 1.0 x In 0.45 1
tr 2.5 sec @ 6 x Ir Fixed Fixed
Isd 2 - 10 x In 3 4
2F2 BOILER-2 MCC (6 MW) O/G CN-CS 1600S1 1600 SR18G tsd 20 - 400 msec 100 200 I2t OFF
Ii OFF, 2-16 x In OFF OFF
Ig 0.2 - 0.6 x In 0.3 0.3
tg OFF, 0.1-0.4, 1 sec 300 0.2 I2t OFF
LOCATION: BOILER-2 MCC (11 KV SWITCHBOARD-2 ROOM)
Ir 0.4 - 1.0 x In 0.45 0.65
tr 10 sec @ 6 x Ir Fixed Fixed
Isd 1.25 - 12 x In 2 4
1F2 BOILER-2 MCC (6 MW) I/C 3WT 2500 ETU37WT tsd 0, 0.02, 0.1 - 0.4 sec 0.2 0.2 I2t OFF
Ii ≥ 20 × In Fixed Fixed
Ig 100 - 1200 A, OFF OFF 300
tg 0.1 - 0.5 sec 0.4 0.2 I2t OFF
Page 2 of 13
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY AND RELAY COORDINAITON PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony, Unit - PCBL,
REVISION NO. : REV. 0
Jetalpur Road, Mundra, GJ
Vadodara - 390 007. LVCB TRIP UNIT SETTING SHEET
PANEL TYPE OF CB SETTING EXISTING RECOMMENDED
FEEDER ID CB MODEL TRIP UNIT RANGE REMARKS
NO. FEEDER RATING PARAMETER SETTING SETTING
LOCATION: PMCC-106 (11 KV SWITCHBOARD-2 ROOM)
Ir 0.4 - 1 x In 0.55 1
tr 0.5 - 30 sec @ 6Ir 2 2
Isd 0.6 - 12 x In 1.8 4
1F2 TR-5 CPP 3 AUX I/C UW2-25S 2500 UW-MTX3.5 tsd 20, 100 - 400 msec 400 400 I2t OFF
Ii OFF, 1.5-10 x In 3 OFF
Ig OFF, 0.2 - 0.6 x In 0.3 0.3
tg 0.1 - 0.4, 1 sec 300 0.4 I2t OFF
Ir OFF, 0.4 - 1 x In 1 1
tr 0.5 - 30 sec @ 6Ir 18 2
Isd 0.6 - 12 x In 3 4
UW-
2F BOILER-3 MCC (8 MW) O/G UW1-16S 1600 tsd 20, 100 - 400 msec 300 200 I2t OFF
MTX1.5G
Ii OFF,1.5-15 x In 3 OFF
Ig 0.2 - 0.6 x In 0.2 0.2
tg OFF, 0.1-1 sec 0.3 0.2 I2t OFF
LOCATION: BOILER-3 MCC (11 KV SWITCHBOARD-2 ROOM)
Ir OFF, 0.4 - 1 x In 0.9 1
tr 0.5 - 30 sec @ 6Ir 12 2
Isd 0.6 - 12 x In 3 4
UW-
1F BOILER-3 MCC (8 MW) I/C UW1-16N 1600 tsd 20, 100 - 400 msec 300 200 I2t OFF
MTX1.5G
Ii OFF,1.5-15 x In 4 OFF
Ig 0.2 - 0.6 x In 0.2 0.2
tg OFF, 0.1-1 sec 0.4 0.2 I2t OFF
Page 3 of 13
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY AND RELAY COORDINAITON PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony, Unit - PCBL,
REVISION NO. : REV. 0
Jetalpur Road, Mundra, GJ
Vadodara - 390 007. LVCB TRIP UNIT SETTING SHEET
PANEL TYPE OF CB SETTING EXISTING RECOMMENDED
FEEDER ID CB MODEL TRIP UNIT RANGE REMARKS
NO. FEEDER RATING PARAMETER SETTING SETTING
LOCATION: W.T.P CONTROL MCC ROOM
Ir 0.4 - 1.0 x In 0.8 1
tr 0.2-30 sec @ 6 x Ir 0.5 2
Isd 2 - 10 x In 3 4
1F PMCC-101 TIE CN-CS 1000H 1000 SR18G tsd 20 - 400 msec 100 ( I2t ON) 200 I2t OFF
Ii OFF, 2-16 x In 4 OFF
Ig 0.2 - 0.6 x In 0.3 0.3
tg OFF, 0.1-0.4, 1 sec 0.2 0.2 I2t OFF
Ir 0.4 - 1.0 x In 0.8 1
tr 0.2-30 sec @ 6 x Ir 6 3.5
Isd 2 - 10 x In 3 4
2F PMCC-106 TIE CN-CS 1000H 1000 SR18G tsd 20 - 400 msec 200 ( I2t ON) 200 I2t OFF
Ii OFF, 2-16 x In 3 OFF
Ig 0.2 - 0.6 x In 0.3 0.3
tg OFF, 0.1-0.4, 1 sec 0.2 0.2 I2t OFF
LOCATION: W.T.P MCC - W.T.P CONTROL MCC ROOM
Ir 0.4 - 1.0 x In 0.75 1
tr 0.2-30 sec @ 6 x Ir 6 2
Isd 2 - 10 x In 3 4
1F3 WTP CR MCC-1 I/C CN-CS 800S1 800 SR18G tsd 20 - 400 msec 200 100 I2t OFF
Ii OFF, 2-16 x In 4 OFF
Ig 0.2 - 0.6 x In 0.3 0.3
tg OFF, 0.1-0.4, 1 sec 0.3 0.1 I2t OFF
Page 4 of 13
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY AND RELAY COORDINAITON PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony, Unit - PCBL,
REVISION NO. : REV. 0
Jetalpur Road, Mundra, GJ
Vadodara - 390 007. LVCB TRIP UNIT SETTING SHEET
PANEL TYPE OF CB SETTING EXISTING RECOMMENDED
FEEDER ID CB MODEL TRIP UNIT RANGE REMARKS
NO. FEEDER RATING PARAMETER SETTING SETTING
LOCATION: L-1 MCC ROOM - PMCC-102
Ir 0.4 - 1.0 x In 0.85
tr 0.2-30 sec @ 6 x Ir 12 Feeder is having LVCB Release
Isd 2 - 10 x In 6 & Relay both for the
protection. Hence, settings are
2 L-1 DT-1 I/C-1 CN-CS 5000C 5000 SR18G tsd 20 - 400 msec 100 DISABLE
provided in Relay & settings in
Ii OFF, 2-16 x In 8 Release are recommended to
Ig 0.2 - 0.6 x In 0.6 be Disable
Page 5 of 13
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY AND RELAY COORDINAITON PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony, Unit - PCBL,
REVISION NO. : REV. 0
Jetalpur Road, Mundra, GJ
Vadodara - 390 007. LVCB TRIP UNIT SETTING SHEET
PANEL TYPE OF CB SETTING EXISTING RECOMMENDED
FEEDER ID CB MODEL TRIP UNIT RANGE REMARKS
NO. FEEDER RATING PARAMETER SETTING SETTING
LOCATION: L-1 MCC ROOM - PMCC-102
Ig 0.2 - 0.6 x In 0.3 0.3
6 BUS COUPLER-1 B/C CN-CS 5000C 5000 SR18G
tg OFF, 100-400 msec 400 300 I2t OFF
Ir 0.4 - 1.0 x In 1 1
tr 0.2-30 sec @ 6 x Ir 2 2
Isd 2 - 10 x In 6 4
7 DG SUPPLY I/C-2 CN-CS 1250H 1250 SR18G tsd 20 - 400 msec 400 400 I2t OFF
Ii OFF, 2-16 x In 8 OFF
Ig 0.2 - 0.6 x In 0.3 0.3
tg OFF, 0.1-0.4, 1 sec 0.1 0.4 I2t OFF
Ir 0.5 - 1.0 x In 1 1
tr 2.5 sec @ 6 x Ir Fixed Fixed
Isd 2 - 10 x Ir 6 4
9 BUS COUPLER-2 B/C CN-CS 5000C 5000 SR18G
tsd 20 - 400 msec 300 I2t OFF
Ig 0.2 - 0.6 x In 0.3 0.3
tg OFF, 100-400 msec 400 300 I2t OFF
Ir 0.5 - 1.0 x In 0.85
Feeder is having LVCB Release
tr 2.5 sec @ 6 x Ir Fixed
& Relay both for the
Isd 2 - 10 x Ir 6 protection. Hence, settings are
10 L-1 DT-2 I/C-3 CN-CS 5000C 5000 SR18G DISABLE
tsd 20 - 400 msec 100 provided in Relay & settings in
Release are recommended to
Ig 0.2 - 0.6 x In 0.3
be Disable
tg OFF, 100-400 msec 400
Page 6 of 13
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY AND RELAY COORDINAITON PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony, Unit - PCBL,
REVISION NO. : REV. 0
Jetalpur Road, Mundra, GJ
Vadodara - 390 007. LVCB TRIP UNIT SETTING SHEET
PANEL TYPE OF CB SETTING EXISTING RECOMMENDED
FEEDER ID CB MODEL TRIP UNIT RANGE REMARKS
NO. FEEDER RATING PARAMETER SETTING SETTING
LOCATION: L-1 MCC ROOM - PMCC-102
Ir 0.5 - 1.0 x In 1 1
tr 2.5 sec @ 6 x Ir Fixed Fixed
Page 7 of 13
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY AND RELAY COORDINAITON PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony, Unit - PCBL,
REVISION NO. : REV. 0
Jetalpur Road, Mundra, GJ
Vadodara - 390 007. LVCB TRIP UNIT SETTING SHEET
PANEL TYPE OF CB SETTING EXISTING RECOMMENDED
FEEDER ID CB MODEL TRIP UNIT RANGE REMARKS
NO. FEEDER RATING PARAMETER SETTING SETTING
LOCATION: L-1 MCC ROOM - PFIC-2 (600 kVAr)
tsd 20 - 400 msec 100 100 I2t OFF
Q1 PFIC-2 I/C CN-CS 1600H 1600 SR18G Ig 0.2 - 0.6 x In 0.6 0.2
tg OFF, 100-400 msec 400 100 I2t OFF
LOCATION: L1- MCC ROOM - PROJECT OFFICE & PFIC-3
Ir 0.4 - 1.0 x In 0.5 1
tr 2.5 sec @ 6 x Ir Fixed Fixed
Page 10 of 13
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY AND RELAY COORDINAITON PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony, Unit - PCBL,
REVISION NO. : REV. 0
Jetalpur Road, Mundra, GJ
Vadodara - 390 007. LVCB TRIP UNIT SETTING SHEET
PANEL TYPE OF CB SETTING EXISTING RECOMMENDED
FEEDER ID CB MODEL TRIP UNIT RANGE REMARKS
NO. FEEDER RATING PARAMETER SETTING SETTING
LOCATION: L-3 MCC ROOM - PMCC-105
Ir 0.4 - 1 x In DISABLE 1
tr 0.5 - 30 sec @ 6Ir - 2
Isd 0.6 - 12 x In 1 4
OMEGA
11F BUS COUPLER B/C 4000 UW-MTX3.5 tsd 20, 100 - 400 msec 100 300 I2t OFF
UW3-40H
Ii OFF, 1.5-15 x In DISABLE OFF
Ig OFF, 0.2 - 0.6 x In DISABLE 0.2
Page 11 of 13
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY AND RELAY COORDINAITON PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony, Unit - PCBL,
REVISION NO. : REV. 0
Jetalpur Road, Mundra, GJ
Vadodara - 390 007. LVCB TRIP UNIT SETTING SHEET
PANEL TYPE OF CB SETTING EXISTING RECOMMENDED
FEEDER ID CB MODEL TRIP UNIT RANGE REMARKS
NO. FEEDER RATING PARAMETER SETTING SETTING
LOCATION: L-3 MCC ROOM - PMCC-105
Ir 0.4 - 1 x In 0.8
tr 0.5 - 30 sec @ 6Ir 6 Feeder is having LVCB Release
Isd 0.6 - 12 x In 1.2 & Relay both for the
OMEGA protection. Hence, settings are
20F L-3 DT-2 I/C 4000 UW-MTX3.5 tsd 20, 100 - 400 msec 100 DISABLE
UW3-40H provided in Relay & settings in
Ii OFF, 1.5-10 x In 1.5 Release are recommended to
Ig OFF, 0.2 - 0.6 x In 0.2 be Disable
Page 12 of 13
SYSTEM PROTECTION PROJECT TITLE : POWER SYSTEM STUDY AND RELAY COORDINAITON PHILIPS CARBON BLACK LIMITED
Paramhans - 54, DOCUMENT NO. : SP/PCBL-M/PSS/0405/22/SS
Vishwas Colony, Unit - PCBL,
REVISION NO. : REV. 0
Jetalpur Road, Mundra, GJ
Vadodara - 390 007. LVCB TRIP UNIT SETTING SHEET
PANEL TYPE OF CB SETTING EXISTING RECOMMENDED
FEEDER ID CB MODEL TRIP UNIT RANGE REMARKS
NO. FEEDER RATING PARAMETER SETTING SETTING
LOCATION: L-3 MCC ROOM - MCC-111
Ir OFF, 0.4 - 1 x In 1 1
tr 0.5 - 30 sec @ 6Ir 4 2
Isd 0.6 - 12 x In 2 4
OMEGA UW-
15F MCC-111-B I/C-2 1250 tsd 20, 100 - 400 msec 100 200 I2t OFF
UW1-12N MTX1.5G
Ii OFF,1.5-15 x In OFF OFF
Ig 0.2 - 0.6 x In 0.2 0.2
tg OFF, 0.1-1 sec 0.3 0.2 I2t OFF
Page 13 of 13