Professional Documents
Culture Documents
Transformer Protection
Instruction Manual
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR is dispatched separately from manufactured goods
and may not be received at the same time. Therefore this guide is provided to ensure that printed
information normally present on equipment is fully understood by the recipient.
Before carrying out any work on the equipment the user should be familiar with the contents of this
manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
The information in this chapter of the equipment documentation is intended to ensure that
equipment is properly installed and handled in order to maintain it in a safe condition.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason only qualified personnel may work on or operate the equipment.
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
DANGER means that dearth, severe personal injury, or considerable equipment damage will
occur if safety precautions are disregarded.
WARNING means that dearth, severe personal, or considerable equipment damage could occur
if safety precautions are disregarded.
CAUTION means that light personal injury or equipment damage may occur if safety
precautions are disregarded. This particularly applies to damage to the device and to
resulting damage of the protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high -voltage equipment must
be observed. Noncompliance may result in dearth, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
Earth
Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
Connection cable
Copyright
Release: R1.01 NR ELECTRIC CO., LTD.
P/N: EN_YJBH5100.0086.0002 69 Suyuan Avenue, Jiangning, Nanjing 211102, China
Copyright © NR 200 9. All rights reserved Tel: 86-25-87178185, Fax: 86-25-87178208
We reserve all rights to this document and to the information Website: www.nari-relays.com
contained herein. Improper use in particular reproduction and Email: nr_techsupport@nari-relays.com
dissemination to third parties is strictly forbidden except where
expressly authorized.
The information in this manual is carefully checked periodically,
and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or
improvement are greatly appreciated.
We reserve the rights to make technical improvements without
notice.
Table of Contents
Preface.............................................................................................................................................. i
Introduction .............................................................................................................................. i
4.2.6 Voltage and Current Drift Monitoring and Auto Adjustment .......................... 194
Chapter 1 Introduction
1.1 Application
1.2 Functions
Protective functions of PCS-978 are listed in the following table and function diagram is also
shown below.
of a fault in the power system, the fault current consists of three parts: the power
frequency components before the fault, the power frequency variables during the fault
and the transient variables during the fault. DPFC is the power frequency variables
The function diagrams for protecting a three-winding transformer and an autotransformer are
shown below.
*
*
*
U * / f*
*
*
U * / f*
Miscellaneous functions are list in the following table, such as metering, self-supervision and
oscillography, communication functions, and etc.
1.3 Features
Configurable Function
Modules of PCS-978 equipment adopt intelligent design, amount of input and output modules and
module slot position are configurable. User can increase or decrease the amount of AC input
module, binary input module and binary output module, and terminals of those modules can be
defined according to actual requirement. Besides, configurability is also reflected in software
design of equipment, which means that user can hide the protective element not used or add new
protective module not in standard configuration.
The hardware of equipment comprises a 64-bit microprocessor and two 32-bit digital signal
processors (DSP). Those processor can operate in parallel companied by fast A/D converter. The
64-bit microprocessor performs logic calculation and the DSP performs the protection calculation.
High performance hardware ensures real time calculation of all protection relays within a sampling
interval.
On the premise of 24 samples per cycle, all data measurement, calculation and logic
discrimination could be done within one sampling period. The event recording and protection logic
calculation are completed simultaneously.
Independent fault detectors in fault detector DSP module for connecting power supply of output
relays. The relay can drive a tripping output only when protection element on protection DSP
module operates with the fault detector in the fault detector DSP module operating simultaneously.
This kind of independent supervision of tripping outputs using fault detectors can avoid any
maloperation possibly caused by any hardware component faulure. This highly increases the
security.
Main and backup protection can be integrated in one set of protection equipment. Protection
information such as sampled data and binary inputs is shared by all elements. The equipment can
record all relevant waveforms of any fault.
Characteristic of percent differential with initial restraint is used and criteria for current transformer
saturation are accompanied.
△ → Y transfer method is used to adjust phase angle of secondary current on each side of the
transformer, and thus the faulty and healthy phase can possess its characteristic. Therefore,
restraint current and differential current can be phase-segregated, which can distinguish the faulty
phase from phase only with inrush current characteristic when transformer is energized.
Two discrimination principles for inrush current are provided: harmonics restraint and waveform
distortion restraint.
DPFC percent differential protection is regardless of the load current and is sensitive to small
internal fault current within the transformer. Its performance against current transformer saturation
is also good.
Positive sequence current restraint element is adopted to eliminate the influence of difference of
transient characteristic and saturation of various CT to zero-sequence percent differential
protection.
Distinguish of open and short circuit of CT against fault is more reliable due to combination of
voltage and current value method adopted
Maximum requirements to backup protection of all sides of the transformer are provided. The
tripping output circuit can be configured by tripping matrix and suitable to any mode of tripping.
Event Recorder including 1024 status change of binary input reports and 1024 alarm
reports
Disturbance recorder including 64 fault reports, and 64 waveforms, and file format of
waveform is compatible with international COMTRADE91 and COMTRADE99 file. Up to
80 analog inputs and 200 binary inputs can be recorded, and three oscillograph
triggering mode are supported, which are protection triggering, manual triggering,
remote triggering through PCS-PC software.
The HMI interface with a LCD and a 9-button keypad on the front panel is very friendly to the user.
Communication Ports
Two rear RS-485 ports and two Ethernet ports supporting or four Ethernet ports
(optional) with IEC 60870-5-103 or IEC 61850-8-1 protocol.
Various GPS clock synchronizations: second/minute pulse via binary input or RS -485, message
via communication ports and IRIG-B synchronization.
Protocol
IEC 60870-5-103 (Only for EIA-485) S
IEC 61850 (Only for 100BaseTX and 100BaseFX)* E
Support to GOOSE
Non Available 0
GOOSE Module 1
Connector Type
Plug In/Out Terminal P
Screw terminal S
*: The items marked with '*" are not included in the basic price and have an additional cost.
Burden
Quiescent condition <30W
Operating condition <45W
Port number 2
Baud rate 4800,9600,19200,38400,57600,115200
Transmission distance <1000m@4800bps
Electrical Maximal capacity 32
Twisted pair Screened twisted pair cable
RS-485 Protocol IEC 60870-5-103: 1997
(EIA) Safety level Isolation to ELV level
Port number 2
Connector type ST
Optical
Baud rate 4800,9600,19200,38400,57600,115200
(Optional)
Transmission standard 100Base-FX
Transmission distance <1500m
Prot number 1
Baud Rate 4800, 9600, 19200, 38400
RS-232 (EIA)
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Port number 1
Transmission distance <500m
RS-485 (EIA) Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
2.6 Certifications
ISO9001: 2000
ISO14001:2004
OHSAS18001: 1999
ISO10012:2003
CMMI L3
NOTE: There are some symbols mentioned in the following sections and the meaning of
Id -- differential current
0.01~200
Thermal overload coefficient ( k ) for tripping.
0.01~200
Thermal overload coefficient ( k ) for alarming.
Main protection of protection equipment consists of current differential protection, restricted earth
fault protection, winding differential protection and overexcitation protection and backup protection
consists of voltage controlled directional overcurrent protection, directional zero-sequence
overcurrent protection, impedance protection, overvoltage protection, undervoltage protection,
zero-sequence overvoltage protection, thermal overload protection, frequency protection,
mechanical protection and breaker failure protection. Besides, current transformer and voltage
transformer supervision functions also included.
The equipment has 2 plug-in modules (i.e. protection DSP module and fault detector DSP module)
for protection calculation. Protection DSP module is responsible for calculation of protection
element, and fault detector DSP module is responsible for calculation of fault detector of protection.
Fault detectors on fault detector DSP module picks up to connect positive pole of power supply of
output relays. The equipment output relays can operate to trip only if the fault detector on fault
detector DSP module picks up and the corresponding protection element on protection DSP
module operates simultaneously. Otherwise, the output relays can’
t operate to trip. An alarm
message will be issued with blocking tripping output if a protection element on protection DSP
module operates while the corresponding fault detector on fault detector element does not
operates.
The Fault detector of fault detector DSP module consists of several independent fault detectors,
which can monitor corresponding protection elements without influence to other protection
elements. For example, conventional percent differential protection will not operate to send trip
command until protection element of protection DSP module and the corresponding fault detector
of fault detector DSP module operate at the same time.
3.2.1 Features
Self-adaptive inrush current blocking criterion can enhance ability of differential protection to
avoid maloperation during transformer energization effectively and ensure high speed of
differential protection during normal operation if there is any fault.
△ → Y transfer method is adopted to adjust phase angle of secondary currents on each side of
the transformer, and thus the faulty and healthy phase can possess its characteristic.
Therefore, restraint current and differential current can be phase-segregated, which can
distinguish the faulty phase from phase only with inrush current characteristic when
transformer is energized.
DPFC percent differential protection which consists of power frequency fault component is
regardless of the load current and is sensitive to sm all internal fault current within the
transformer and has the strong ability of anti-CT saturation.
Percent differential protection with initial restraint slope consists of sensitive and insensitive
percent differential elements as well as independent CT saturation criterion.
Multi-phase CT broken circuit, multi-side CT broken circuit and CT short circuit can be
distinguished by combination of voltage and current.
The pickup of this fault detector will enable the percent current differential protection and
unrestraint differential protection.
Where:
I cdqd is the setting threshold of phase differential currents, i.e. setting [I_Pkp_PcntDiff].
I d 1.25Idt I dth
(Equation 3.2-2)
I d I 1 I 2 ... I m
Where:
I dt is the floating threshold value which will arise automatically and gradually according to
increasing of the output of deviation component. In order to ensure the threshold value of voltage
is slightly greater than the unbalance output, multiple 1.25 of the deviation component is
reasonable.
I 1 … . I m are the DPFC current of each side of transformer representatively.
This fault detector is regardless of direction of power flow and very sensitive. It has been set in
factory and does not need to be set on site. The pickup of this fault detector will enable DPFC
percent differential protection.
During the normal operation, the magnitude and angle of secondary currents of each side of
transformer are different due to the mismatch between the CT ratios and the power transformer
ratio, different voltage levels of each side, and transformer delta-wye connection. The current
difference between each side shall be eliminated before do the calculation of current differential
protection, which is realized by magnitude compensation (i.e. CT ration correction), phase shift
compensation and residual current elimination (i.e. Δ→ Y transforming).
Current compensation process is shown in the flowing figure by taken 2-winding transformer with
three-phase CT inputs for an example. In an ideal situation, the differential current ( i.e.
I d I
_ H I
_ L )should be zero during the normal operation of the transformer or an external
fault occurring.
Where:
I’
_H, I’
_L are secondary corrected currents of HV and LV sides respectively.
M1, M2 are matrixes of phase shifting and residual current elimination of HV and LV sides
respectively.
Kph1, Kph2 are corrected coefficients of HV and LV sides for magnitude compensation
respectively.
I dA
I A1 I A2 I A3 I A4
/ I / I / I I B4 / I 2e _ 4
I dB M 1
I B1 2e _ 1 M 2 I B2 2e _ 2 M 3 I B3 2e _ 3 M 4
I 1 I 2
I
dC
C
C
IC3
I C
4
1 2 3 4 5
I A5
I A6
I B6
M 5
I B5 / I 2e _ 5 M 6 / I 2e _ 6
I 5
I 6
C
C
6 7
(Equation 3.2-3)
I dA I
A1 I
A2 I A3 I
A4 I
A 5 I
A6
I dB I B1 I B 2 I B3 B 4 B 5 B
I I I 6 (Equation 3.2-4)
I dC I C1 I
C 2 I
C3 IC 4 IC5 IC 6
Where:
I
An , I
Bn , I
Cn are secondary values of corrected three-phase current of branch n (n=1, 2, 3, 4, 5,
6).
respectively.
1
I rA I
A1 I
A 2 I
A 3 I
A 4 I
A 5 I
A6
2
1
I rB I
B1 I
B 2 I
B 3 I
B 4 I
B 5 I
B6 (Equation 3.2-5)
2
1
I rC I
C1 I
C2 I C 3 I
C 4 I C5 I C6
2
Where:
Secondary currents of each side three-phase CT shall be connected to the equipment directly.
The secondary current phases of CTs at each side are adjusted by software and phase shift is
realized by Δ→ Y transform method. Thus the inrush current and fault current can be discriminated
definitely, and the operating speed of protection can be accelerated. For transformer connection
group Y/Δ-11, the phase shifting equations are as follows:
I ' A ( I A I 0 )
( I B I 0 ) (Equation 3.2-6)
'
I B
I ' C (I C I 0 )
I ' a ( I a I c ) / 3
(I b I a ) / 3 (Equation 3.2-7)
'
I b
I ' c ( I c I b ) / 3
Where:
I a , I b , I c are the secondary currents of CT at Δ side.
I ' a , I ' b , I ' c are the corrected currents of CT at Δ side.
I A , I B , I C are the secondary currents of CT at Y side.
I ' A , I ' B , I ' C are the corrected current of CT at Y side.
Protection equipment can select suitable phase sift matrixes automatically to complete phase shift
compensation according to three system settings [WdgConn_HVS], [Clk_MVS_WRT_HVS] and
[Clk_LVS_WRT_HVS]. [WdgConn_HVS] is to select the connection type of HV side winding, “0”
for wye winding and “1”for delta winding. [Clk_MVS_WRT_HVS] and [Clk_LVS_WRT_HVS] are
respectively to set the actual o’
clock of MV and LV side windings.
Phase shift matrixes are listed in the following table. For example, a transformer with connection
group YNd11y10, for HV side is taken as the reference side, the relative o’ clock of HV side is “0”.
The leading phase of MV side to HV side is 30°(its relative o’
clock is 11), and the leading phase of
2 1 1
1
0(12) 1 2 1
3
1 1
2
1 1 0
1
1
0 1 1
3
1 0 1
1 2 1
1
2 1 1 2
3
2 1 1
0 1 1
1
3 1 0 1
3
1 1 0
1 1 2
1
4 2 1 1
3
1 2 1
1 0 1
1
5 1 1 0
3
0 1 1
2 1 1
1
6 1 2 1
3
1 1 2
1 1 0
1
7 0 1 1
3
1 0 1
1 2 1
1
8 1 1 2
3
2 1 1
0 1 1
1
9 1 0 1
3
1 1 0
1 1 2
1
10 2 1 1
3
1 2 1
1 0 1
1
11 1 1 0
3
0 1 1
Sn
I1 e (Equation 3.2-8)
3U1 n
Where:
U1 n is rated voltage at calculated side of the transformer (i.e. the setting [U1n_HVS]).
I1n
I2 e (Equation 3.2-9)
nCT
Where:
When viewing settings and values of conventional current differential protection in the relay, user
will find the unit “Ie”(transformer secondary rated current). The current in differential protection
calculation is not actual secondary value but per unit value which can be got by actual secondary
value of each side of transformer divided by transformer secondary current of each side.
The currents used in this section analysis and the following analysis have been corrected, that
means the currents for following calculation are the products of the actual secondary current of
The Low setting percent differential protection with low pickup setting and restraint slope is also
called sensitive percent differential protection and is much more sensitive to operate when a slight
internal fault occurs. Three blocking elements, CT saturation, inrush current, CT circuit failure
(optional) and overexcitation (optional) have also been included for the protection in order to
prevent it from the unwanted operation during an external fault.
I I
d i
i1
Where:
kbl is the percent restraint coefficient (i.e. [Slope_PcntDiff]) with setting range 0.2 ~ 0.75, and 0.5
is recommended usually.
A percent differential protection with high slope and high setting is equipped with the equipment.
This protection, also called an insensitive differential protection, is blocked only by an inrush
current criterion.
High setting percent differential protection can accelerate the trip when serious inner faults occur.
Operation criterion of this high setting percent differential protection is:
Where:
Id I r I
, and e have same meaning as mentioned above.
NOTE: Parameters of this protection have been fixed in the program and do not need to
be configured by user.
The aim of unrestrained instantaneous differential protection for transformer is to accelerate the
trip speed for transformer’
s inner fault. Therefore the element does not need any blocking element,
but the setting should be greater than the maximum inrush current.
Unrestrained differential element shall operate to trip breakers at all sides of transformer when any
phase differential current is higher than its setting. Its operation criterion is:
Where:
Id
is the maximum value of three-phase differential current.
I cdsd is the setting of the unrestrained instantaneous differential protection(i.e. the setting
[I_InstDiff]).
DPFC (Deviation of Power Frequency Component) percent differential protection reflects deviation
of load condition which can perform a sensitive protection for the transformer. Lab test shows that
it is more sensitive in the heavy load condition than the conventional percent differential relay.
I d 1.25 I dt I dth
I d 0.6 I r
I r 2I e
I d 0.75 I r 0.3 I e I r 2I e
(Equation 3.2-13)
I r max{ I1 I2 .... I m }
I d I 1 I 2 .... I m
Where:
I dt is the floating threshold value which will arise automatically and gradually according to
increasing of output of deviation component. In order to ensure the threshold value is slightly
greater than the unbalance output, multiple 1.25 of the deviation component is reasonable and the
unwanted operation of relays will not occur during power swing or power frequency deviating.
I 1 … I m are DPFC currents of each branch (from 1 to m) of a transformer respectively.
I 1 is the DPFC differential current.
I r is the DPFC restraint current, it is the maximum current among the restraint current of three
phases.
with the percent differential protection, it is difficult to test the function on site, so we
recommend qualitative function test only on site.
Calculation of DPFC restraint current and differential current is phase-segregated. DPFC percent
differential protection is always blocked by inrush current, overexciation and CT circuit failure.
Due to high slope of DPFC percent differential protection, the protection has higher ability of
anti-CT saturation and can improve the sensitivity to slight inter-turn fault during normal operation
of transformer
1) Insensitive percent differential protection element will send tripping signal with blocking of CT
saturation, overexcitation, inrush current and CT circuit failure (optional). It can ensure
sensitivity of protection and avoid the unwanted operation when CT is saturated during an
external fault. Its operation area is the tint shadow area in the figure above.
2) Insensitive percent differential protection element will send tripping signal with blocking of
inrush current. It eliminates the influence of transient and steady saturations of CT during an
external fault and ensures reliable operation even if CT is in saturation condition during an
internal fault by means of its percent restraint characteristic. Its operation area is the deeper
shadow area in the figure above.
NOTE: Only the secondary harmonic criterion is adopted to distinguishing inrush current
3) Unrestrained instantaneous differential protection element will send tripping signal without any
blocking if differential current of any phase reaches its setting. Its operation area is over the
above two areas with the deepest dark shadow.
differential current
m
K= K=0.75
0.2 Ie K=0.6
restraint current
2 Ie
Where:
The value of m is defined by the branch number for DPFC percent differential protection
calculation.
In this protection equipment, the logic setting [Opt_Inrush_Ident] is provided for user to select the
restraint blocking principle. If the logic setting is set as “0”, discrimination by harmonics is
enabled, and if it is set as “1”, discrimination by waveform dist ortion is enabled.
In PCS-978 series protection equipment, the second and third harmonics of differential current can
be used to distinguish inrush current. Its criteria are:
I d _ 2 nd K 2 xb I d _ 1st
(Equation 3.2-14)
I K 3 xb I d _ 1 st
d _ 3 rd
Where:
I d _ 2 nd I d _ 3 rd
and are the second and third harmonics of phase differential current
respectively.
I d _ 1st
is the fundamental component of the differential current of the corresponding phase.
k 2 xb and k3 xb are the setting values of restraint coefficient of second and third harmonics
k 2 xb = 0.15 and k3 xb = 0.2 is recommended. In main protection setting table, they are
respectively,
[k_2ndHarm_PcntDiff] and [k_3rdHarm_PcntDiff] respectively.
When one of three phases current is distinguished as inrush current, the percent differential
protection of this phase and only this phase will be blocked.
The differential current is basically the fundamental sinusoidal wave during a fault. When the
transformer is energized plentiful harmonics will appear, the waveform will be distorted, interrupted
and unsymmetrical. A special algorithm can be used for discrimination of the inrush current.
S k b S
(Equation 3.2-15)
S S t
Where:
S is full cycle integrated value of the instantaneous value of differential current plus the
kb is a fixed constant.
Where:
is a proportional constant.
If any one phase can not meet above equation, the current can be considered as inrush current
and only percent differential relay will be blocked..
The equipment has the special energizing detection element for checking whether transformer is
in the process of being energized with no load or not automatically only by current criterion
(without additional breaker position signal). Once transformer in the process of being energized
with no load is detected, following self-adaptive measures are adopted to improve the ability to
avoid inrush current.
2) Protection equipment can be self-adaptive to enable the crossing block mode according to the
comprehensive characteristics of three-phase differential current. If inrush current is
distinguished, equipment enables crossing block mode for short time, and then switches to
phase-segregated blocking mode after a period.
3) f the secondary harmonic percent of differential current used as auxiliary criteria continues to
rise, then percent differential protection is kept being blocked
In order to prevent an unwanted operation of low setting differential protection caused by transient
or steady state saturation of CT during an external fault, the second and third harmonics of
secondary current of CT are used for the protection equipment to discriminate saturation of
three-phase CT. The criteria expression is as following:
Where:
I _ 1st
is the fundamental component of one phase current of some side.
I_ 2 nd
is the secondary harmonic of the same phase current.
I_ 3 rd
is the third harmonic of the same phase current.
If any harmonic of one phase current meets the above equation, it will be considered that it is CT
saturation to cause this phase differential current and sensitive percent differential element will be
blocked.
When a transformer is overexcited, the exciting current will increase sharply which may result in
an unwanted operation of differential protection. Therefore the overexcitation shall be
discriminated to block differential protection. The fifth harmonic of differential current is used as the
criterion of overexcitation discrimination.
Where:
I d _ 1st
is the fundamental component of differential current.
I d _ 5th
is the fifth harmonics of differential current.
k 5 xb is the constant of the fifth harmonics restraint coefficient and it is fixed at 0.25.
Where:
The base value for calculating per unit value of voltage is secondary rated voltage value (phase
voltage) of the voltage transformer, and the base value for calculating per unit value of frequency
is rated frequency. During normal operation, n = 1.
If overexciation factor is less than 1.4, percent differential protection is blocked when the fifth
harmonics restraint coefficient is greater than 0.25. If overexciation factor is greater than 1.4,
perent differential protection is no longer being blocked by overexciation.
If the differential current in any phase is greater than the alarm setting [I_Alm_Diff] without fault
detector of differential protection pickup and the state is keeping over 10s, differential current
abnormality alarm will be issued without blocking the protection.
Criteria
There are following two cases will be discriminated a CT circuit failure but not an internal fault, and
the protection relay can descrimiate which side the CT circuit failure ocurrs by the unbalcned
currents of each side.
First case, if none of following four conditions is satisfied after the fault detector of differential
current or zero-sequence differential current pickus up, it will be judged as CT circuit failure and
CT circuit failure alarm will be issued.
Any phase current of any side increases than that before the fault detector picks up.
The maximum phase current is greater than 1.1 Ie (Ie is secondary calculated rated current of
transformer) after the fault detector picks up.
Second case, if CT circuit abnormality of differential protection alarm (i.e. [Alm_Diff]) is issued and
negative-sequence current of one side is greater than 0.2 times maximum phase current of the
corresponding side, and then CT circuit failure will be judged.
Broken circuit and short circuit of differential CT secondary circuit can be judged more accurately
and reliably by adopting combined method of voltage and current.
By configuring different logic settings, user can gent following blocking functions to differential
protections after CT circuit failure alarm is issued. Once the alarm signal of differential CT circuit
failure is issued, it can be reset only when the failure is removed and equipment is reset (i.e the
binary input [BI_RstTarg] is energized).
1) The DPFC percent differential relay is always blocked during CT circuit failure.
2) Percent differential protection can be blocked when CT circuit failure is detected by configuring
the logic setting [En_CTS_Blk_Diff].
If this logic setting is set as “0”, percent differential protection is not blocked by with the
alarm signal being issued.
If this logic setting is set as “1”, only sensitive percent differential protection is blocked by
with the alarm signal being issued.
differential CT circuit or settings. Both shall be paid attention on site. For example,
differential circuits open can not cause protection pickup in case of light load but alarm will
be issued. If user treats this abnormality in time, the unwanted operation of percent
differential protection not blocked by CT circuit failure can be avoided when the load
increases or an external fault occurs.
NOTE: The operation time of percent differential protection with CT circuit failure being
distinguished is a littler greater than that of percent differential protection without CT circuit
failure.
Id_max>[I_InstDiff]
[EBI_Diff]
&
[VEBI_Diff] & [Op_InstDiff]
[En_InstDiff]
Flg_FD_Diff
Flg_Op_InsensPcntDiff
[EBI_Diff]
&
[VEBI_Diff] &
&
[En_PcntDiff]
Flg_Inrush_2ndHarm
Flg_Op_FD_Diff
Flg_Op_SensPcntDiff
[EBI_Diff]
&
[VEBI_Diff] ≥1 [Op_PcntDiff]
[En_PcntDiff]
Flg_CT_Sat
Flg_Inrush_2ndHarm
Flg_Inrush_3rdHarm
& &
[En_3rdHarm_Blk_Diff] &
Flg_CTS
&
[Opt_CTS_Blk_Diff]
Flg_OvExc_5thHarm
≥1
U * / f * >1.4
Flg_FD_Diff
Where:
[EBI_Diff] is the binary input of enabling conventional and DPFC current differential of differential
protections.
[VEBI_Diff] is the VEBI setting of enabling conventional and DPFC current differential of
differential protections.
Flg_FD_Diff is the internal flag indicating that the fault detector of differential current picks up.
Flg_Op_InsensPcntDiff is the internal flag indicating that operation criteria of insensitive percent
differential protection are satisfied.
Flg_Op_SensPcntDiff is the internal flag indicating that operation criteria of sensitive percent
differential protection are satisfied.
Flg_Inrush_2ndHarm is the internal flag indicating inrush current is distinguished by the secondary
harmonic criterion.
Flg_Inrush_3rdHarm is the internal flag indicating inrush current is distinguished by the third
harmonic criterion.
[En_3rdHarm_Blk_Diff] is the logic setting of enabling the third harmonic criterion used to
distinguish inrush current.
U * / f*
Where:
Flg_Op_DPFC_Diff is the internal flag indicating that operation criteria of DPFC differential
[EBI_Diff] is the binary input of enabling current differential protection including conventional
differential protection and DPFC differential protection.
Flg_FD_DPFC_Diff is the internal flag indicating the fault detector of DPFC differential current
picks up.
Flg_Inrush_2ndHarm is the internal flag indicating inrush current is distinguished by the secondary
harmonic criterion.
3.2.5 Setting
Setting explanation
1. [I_Pkp_PcntDiff]
Current setting of differential current is the minimum operating current of differential protection. It
shall be greater than the maximum unbalance current while transformer operates on normal rated
load, i.e.
Where:
K er is the ratio errors of CT (k=0.03X2 for class 10P; k=0.01X2 for clase 5P and TP).
U is the maximum deviation (in percent of rated voltage) due to tap changing within voltage
regulation range.
m is the error caused by the difference between ratios of CT at all side, and 0.05 is
recommended.
NOTE: Settings ([I_Pkp_PcntDiff], [I_InstDiff] and [I_Alm_Diff]) are all based on the
secondary rated current of the transformer (i.e. Ie). If a setting value got from calculation is
together with its unit Ampere, this setting shall be divided by secondary rated current of
this side of transformer, per unit value.
2. [I_InstDiff]
This setting is the unrestraint differential protection. Unrestraint differential protection can clear
serious internal fault quickly and prevent operation delay caused by CT saturation. It’ s setting
value I cdsd (ie. [I_InstDiff])Shall be greater than inrush current of transformer, generally
Where:
K is a multiple depending on the capacity of the transformer and impedance of the power
system.
K will be 3.0 - 6.0 for transformer with capacity 40 - 120 MVA and 2.0 - 5.0 for transformer with
capacity above 120 MVA. It is evident that the larger the transformer capacity or the power system
impedance, the smaller the K .
3. [Slope_PcntDiff]
This setting is the percent restraint coefficient of percent differential protection. Setting calculation
method of differential protection is provided here only for reference. For details, please refer to
relevant specification and setting calculation guidance.
Calculation of unbalanced current is different with the different type of transformer. Following
equations are given to calculate the maximum unbalanced current Iunb.max (secondary current)
in differential scheme for two-winding and three-winding transformer:
Where:
I k .max is the maximum value of fundamental component of external short circuit (secondary)
current;
K ap = 1.0 if CT at both sides are class TP, or Kap = 1.5 - 2.0 if CT at both sides are class P.
I unb. max K ap K cc K er I k . max Uh I k .h . max Um .I k. m.max mI I k .I . max mII I k .II .max
(Equation 3.2-23)
Where:
U h and U m are the maximum deviations (in percent of rated voltage) on HV and MV sides
due to tap changing within voltage regulation range.
I k.max is the maximum value of fundamental component of the short-circuit secondary current
flowing through CT at the fault side during an external fault at LV side.
I k.h. max and I k.m.max are the fundamental components of the secondary currents flowing through
CT at voltage regulating sides during this external fault.
I k.I . max and I k.II . max are the fundamental components of the secondary currents flowing through CT
at other sides during this fault.
m I and m II are the errors caused by difference between ratios of CT (auxiliary CT included) at
relevant sides.
Where
Where:
Ires .max is the maximum restraint current (secondary current), which is set according to diff erent
restraint currents during a short-circuit fault at each side.
According to the pickup current of differential relay I cdqd , the first keen point current Ires .01 , the
maximum restraint current Ires .max and the maximum restraint coefficient Kres .max , the slope of
configurable line of operation characteristic curve of percent differential relay, K bl , will be
calculated as following:
K I / I
K bl res cdqd res (Equation 3.2-26)
1 I res.01 / I res
I I cdqd
K bl op. max (Equation 3.2-27)
I k. max I res.01
Therefore, for percent differential relay, when I res .01 0.5 I e , we have:
I I cdqd
K bl op .max (Equation 3.2-28)
I k . max 0.5I e
4. [ k_2ndHarm_PcntDiff]
This setting is the restraint coefficient of second harmonics. This parameter is the blocking
threshold of the second harmonics in differential current when the transformer is energized.
Generally, it is set in the range of 10%~20%.
5. [k_3rdHarm_PcntDiff]
This setting is the restraint coefficient of the third harmonic. The criterion of distinguishing the 3rd
harmonic is added to block differential protection based on the facts that inrush involves 3rd
harmonics. Generally, it is set in the range of 10%~25%.
6. [I_Alm_Diff]
This setting is the alarm setting of differential current abnormality, and it shall be greater than
maximum differential current when the tap of on-load tap-changing transformer is not located in its
middle position, or the maximum differential current caused by other conditions.
NOTE: The setting [I_Alm_Diff] should be set less than the pickup setting [I_Pkp_PcntDiff],
and normally between the value of maximum differential current caused by the tap of
on-load tap-changing transformer not located in its middle position and the value of
minimum pickup setting.
7. [En_InstDiff]
The logic setting is used to enable or disable the unrestrained instant differential protection which
should be enabled in an actual project.
8. [En_PcntDiff]
The logic setting is used to enable or disable the conventional percent differential protection which
should be enabled in an actual project.
9. [En_DPFC_Diff]
The logic setting is used to enable or disable the conventional percent differential protection.
Recommended value: 1.
NOTE: The DPFC current differential protection settings have been fixed in program and
user does not need to set but only needs to select whether the protection is enabled or
not.
NOTE: When the secondary rated current of HV side multipled by the corresponding
correction coefficient is less than 0.4In (In is secondary ratec current of CT), DPFC
current differential protection must not be enabled. Otherwise, a corresponding alarm
message is issued with protective equipment being blocked.
10. [Opt_Inrush_Ident]
This logic setting is to select method of identifing inrush current to block differential protection.
11. [En_3rdHarm_Blk_Diff]
This is the logic setting of enable or diisable the third harmonic blocking function.
Recommended value: 1.
12. [En_CTS_Blk_Diff]
“0”: percent differential protection and restricted earth fault protection is not blocked by CT circuit
failure.
“1”: sensitive percent differential protection element and restricted earth fault protection is blocked
by CT circuit failure.
Recommended value: 1.
NOTE: When protection settings are configured and the maximum value of ratio of
calculated rated current of each side to secondary current of CT on that side is less than
0.4, this will be considered abnormal and wrong setting alarm will be sent.
13. [TrpLogic_Diff]
The tripping logic setting is used to specify which breakers will be tripped when current differential
protection operates. This logic setting comprises 16 binary bits as follows and is expressed by a
hexadecimal number of 4 digits from 0000H to FFFFH. The tripping logic setting of the equipment
is specified as follows:
bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
TrpOutp10
TrpOutp9
TrpOutp8
TrpOutp7
TrpOutp6
TrpOutp5
TrpOutp4
TrpOutp3
TrpOutp2
TrpOutp1
Function
N/A
N/A
N/A
N/A
N/A
N/A
NOTE: “TrpOutput1”just means to drive 1st group of tripping output contacts to pickup
The bit corresponding to the breaker to be tripped shall be set as“1”and other bits shall be “0”.
For example, if differential protection operates to make “TrpOutp1”, “TrpOutpu2”, “TrpOutp3”
contacts pickup, the bit “1”and bit “2”and bit “3”positions shall be filled with “1”and other bit
positions shall be filled with “0”. Then a hexadecimal number 0007H is formed as the tripping
output logic setting.
Please note that tripping output logic settings of the equipment have to be set on basis of
application-specific drawings.
NOTE: The logic setting [TrpLog_Diff] is shared by the unrestrained instant differential
14. [VEBI_Diff]
the relevant protection can be in service or out of service through remote command. It provides
convenience for operation management.
NOTE: When current differential protection is enabled, if the maximum CT ratio to the
minimum CT ratio related to the protection is greater than 16, this will be considered
abnormal and wrong setting alarm will be sent.
Input signals for current differential protection are list in the following table.
Output signals of current differential protections are list in following two tables.
The equipment provides three elements of restricted earth fault protection, which are applied for
autotransformer, two-winding and three-winding transformers.
The criterion of fault detector of restricted earth fault protection is as follows. The pickup of this
fault detector will enable restricted earth fault protection of the corresponding side.
Where:
The difference between current differential protection and restricted earth fault protection is that
the first one is based on ampere-turn balance and the later is based on ampere balance of
calculated zero-sequence current and zero-sequence current from neutral point zero-sequence
CT.
Three phase currents and neutral point current are the inputs to the restricted earth fault protection
of a three-phase winding. Polarity of three-phase CT is at busbar side, and that of neutral point
zero-sequence CT is at transformer side as shown in the Figure 3.3-1.
DANGER: Before REF protection of some side is put into operation on site, polarity of
zero-sequence CT at neutral point of the side must have been checked right by an
energizing test of the side or a test of simulating an external fault of the side in primary
system. Otherwise a maloperation may occur during an external earth fault.
*
Where:
0d
I Klph1I 01 / I 2n_ CT1 Klph2I 02 / I 2n_ CT2 Klph3I 03 / I 2n _CT3 Klph4 I04 / I2n _CT4 KlphNPI NP / I 2n _CTNP
1 2 3 4 4 5
(Equation 3.3-2)
I 0 d I
01 I
02 I 03
I04
I
NP (Equation 3.3-3)
Where:
I 01, I 02, I 03, I04 are secondary values of calculated zero-sequence currents of each branch.
I
01, I 03, I
02 , I 04 are secondary corrected zero-sequence currents of each branch.
I
NP is the secondary corrected current from zero-sequence CT at neutral point.
Klph1 , Klph2 , Klph3 , Klph4 are corrected coefficients of each branch of magnitude compensation
respectively.
compensation respectively.
, I
I 0 r max{ I01 , I
02, I03 04 , I
0 NP } (Equation 3.3-4)
Where:
If CTs used for REF have different primary rated values, then the current compensation is carried
out in the program automatically. Following gives the criteria of calculating correction coefficient.
I I1n _ max
K lph 1n K lb and K lb min( , 2. 95) (Equation 3.3-5)
I 1n _ max I 1n _ min
Where:
I1n _ min is the minimum value among primary values of all CTs for REF protection.
I1n _ max is the maximum value among primary values of all CTs for REF protection.
This calculation method is to take the minimum CT ration of all calculated sides as the base ration
and the CT ration at other sides are considered as multiples of the base ratio. If the multiple of the
maximum CT ratio to the minimum CT ratio is greater than 2.95, then the multiple shall be taken as
2.95 and other sides shall be calculated proportionally. Otherwise, the multiple shall be taken as
1, and the currents on other sides will be calculated proportionally.
The currents used in the following analysis have been corrected, that means the currents for
following calculation are the products of the actual secondary current of each side multiplying its
own correction coefficient ( K lph ).
I 0d I 0cdqd I 0r 0 .5 I n
I K 0b1
I 0r 0. 5 I n I 0 cdqd
0d
I 0r max{ I 01 , I 02 , I 03 , I 04 , I 0 NP } (Equation 3.3-6)
I 0d I 01 I 02 I 03 I 04 I 0 NP
Where:
I 01 、 I 02 、 I03 、 I 04 are the calculated zero-sequence currents each branch of the corresponding
side.
I 0cdqd is the pick up value of zero-sequence percent differential protection (i.e. the setting
[I_Pkp_PcntREF]).
K 0 bl is the percent restraint coefficient of zero-sequence percent differential protection (i.e. the
setting [Slope_PcntREF]), and 0.5 is recommended.
If the pick up value of REF protection is greater than 0.5 In (i.e. I 0cdqd 0. 5I n ), its keen point
I 0 d I 0 cdqd I 0 r I n
I 0 d K 0 b1 I 0 r I n
I 0cdqd
I 0 r max{ I 01 , I 02 , I 03 , I 04 , I 0 NP } (Equation 3.3-7)
I 0 d I 01 I 02 I 03 I 04 I 0 NP
Operation characteristic of restricted earth fault protection ( I 0cdqd 0.5I n ) is showed in the
following figure.
I0d
K0bl
[I_Pkp_PcntREF] I0r
restraint current
0.5 In
Where:
The value of m is defined by the branch number for REF protection calculation.
Unbalanced three phases of CT can cause zero-sequence. Besides, larger zero-sequence may be
produced because three-phase CT characteristics can not be identical completely during an
external phase-to-phase fault or three-phase symmetrical fault current, which may lead
maloperation of restricted earth fault protection. Therefore, protection equipment shall solve such
problems.
Where:
0 is a proportional constant.
The CT saturation detection principle of REF protection is same to the CT saturation detection
principle of current differential protection, and please refers to section 3.2.3.8 for details.
The CT supervision for REF protection is divided into two kinds: zero-sequence differential CT
circuit abnormality without the pickup of the fault detector of REF protection and differential CT
circuit failure with the pickup of the fault detector pickup.
If the following operation formula is met and the state is keeping over 10s, CT circuit abnormality
alarm of REF protection will be issued without blocking the protection.
Where:
Criteria
If none of following four conditions is satisfied after the fault detector of differ ential current or
zero-sequence differential current picks up, it will be judged as CT circuit failure and CT circuit
failure alarm will be issued.
2) Any phase current of any side increases than that before the fault detector picks up.
3) The maximum phase current is greater than 1.1 Ie (Ie is secondary calculated rated current of
transformer) after the fault detector picks up.
Broken circuit and short circuit of differential CT secondary circuit can be judged more accurately
and reliably by adopting combined method of voltage and current.
By configuring different logic settings, user can gent following blocking functions to restricted earth
fault protection after CT circuit failure alarm is issued. Once the alarm signal of differential CT
circuit failure is issued, it can be reset only when the failure is removed and equipment is reset (i.e.
the binary input [BI_RstTarg] is energized).
Restricted earth fault protection of each side can be blocked when CT circuit failure is detected by
configuring the logic setting [En_CTS_Blk_REF].
If this logic setting is set as “0”, the protection is not blocked by with the alarm signal
being issued.
If this logic setting is set as “1”, the protection is blocked by with the alarm signal being
issued.
differential CT circuit or settings. Both shall be paid attention on site. For example,
differential circuits open can not cause protection pickup in case of light load but alarm will
be issued. If user treats this abnormality in time, the unwanted operation of percent
differential protection not blocked by CT circuit failure can be avoided when the load
increases or an external fault occurs.
NOTE: The operation time of REF protection with CT circuit failure being distinguished is a
Where:
Flg_Op_REF_HVS is the internal flag indicating that operation criterion of REF protection of HV
side is satisfied.
Flg_CTS is the internal flag indicating that instant CT circuit failure is distinguished by the criterion.
Flg_FD_REF_HVS is the internal flag indicating that the fault detector of REF protection of HV
side picks up.
3.3.4 Setting
Setting explanation
Three REF protections are equipped for each side of transformer, and they have the same setting
principles.
1. [ I_Pkp_PcntREF]
The pickup current of REF protection shall be greater than the maximum unbalance current while
transformer operates on normal rated load, i.e.
Where:
K er is the ratio errors of CT (for type 10P, K er = 0.03×2; for type 5P and TP, K er =0.01X2).
m is the error caused by the difference between ratios of CTs, and 0.05 is recommended.
Note that the pickup setting of the REF protection takes the secondary rated current of CT (i.e. In,
1A or 5A) as its unit, whose setting value is calculated with the reference to the side having the
minimum ratio among all CTs for the REF protection. If it is the actual current value to the
reference side in actual setting calculation, then this actual value will be divided by the secondary
rated current of CT (i.e. In , 1A or 5A) to derive the setting value.
In actual projects, the measured unbalance current of the zero-sequence differential circuit under
the maximum load current can be referred to.
The setting should not be less than 0.1In and the recommended value is 0.2In~0.5In.
NOTE: The unit (i.e. In) of the setting calculation ([I_Pkp_PcntREF]) is the secondary
rated current of CT, and the minimum corrected coefficient of the side is taken as the
reference side. If a setting value got from calculation is together with its unit Ampere, this
setting value shall be divided by the secondary rated current of CT to get per unit value
which is the configuration value input to protection equipment.
2. [Slope_PcntREF]
The setting is percent restraint coefficient of winding differential protection, which shall be greater
than unbalance current caused by zero-sequence current flowing through the transformer during
an external fault.
Where:
K ap = 1.0 if CT at both sides are class TP, or Kap = 1.5~ 2.0 if CT at both sides are class P.
Generally, in practical setting calculation for projects, K 0bl can be taken as 0.3
0.7
3. [En_CTS_Blk_REF]
NOTE: When REF protection is enabled, if the maximum CT ratio to the minimum CT ratio
related to the protection is greater than 16, this will be considered abnormal and wrong
setting alarm will be sent.
4. [En_REF]
The logic setting is used to enable or disable the REF protection of the corresponding side.
5. [TrpLog_REF]
The tripping logic setting is used to specify which breakers will be tripped when REF protection
operates. Please refer to the description of the setting [TrpLog_Diff] in section 3.2.5 for details.
6. [VEBI_REF]
This setting is the VEBI setting of enabling REF protection. Please refer to the setting [VEBI_Diff]
in section 3.2.5 for details.
NOTE: When restricted earth fault protection is enabled, if the maximum CT ratio to the
minimum CT ratio related to the protection is greater than 16, this will be considered
abnormal and wrong setting alarm will be sent.
Input signals of restricted earth fault protection are list in the following table.
Output signals of restricted earth fault protection are list in following two tables.
Where:
DANGER: When winding differential protection is used as stub differential protection, the
polarity of CT must be checked. If polarities of the circuit breaker CT and the bush CT of
some side of a transformer are both at busbar side, either of them must be reversed by
PCS-PC software
I wdA I A1 I A2 I A3
I wdB
I I I
K wph1B1 / I 2 n _ CT1 K wph2 B2 / I 2n _ CT 2 K wph3 B3 / I 2 n _ CT 3
I wdC
I C1 IC2 IC3
I 0
I I I
wd
01
02
03
1 2 3 4
I A4 I A5
I I B5
K wph4 B4
/ I K wph 5 / I
I C 4 2 n _ CT 4 I C 5 2n _ CT5
I 04
I
05
5 6
(Equation 3.4-2)
I dA I A1 I
A2 I
A3 I
A 4 I A5
dB
I I B1 I B2 I B3 I B4 I B5
(Equation 3.4-3)
I
dC I
C1 I
C2 I
C3 I
C4 I 5
C
I d 0 I 01
I 02 I 03
I 04
I 05
Where:
I wdA I wdB I wdC I wd 0 are respectively three phase and zero-sequence winding differential currents.
I An , I Bn , I Cn , I n 0 are respectively secondary values of three phase currents and calculated
zero-sequence current of branch n (n=1, 2, 3, 4 ,5).
I
An , I , I
Bn , I Cn n 0 are respectively secondary values of corrected three phase currents and calculated
respectively.
branch.
1
I rA 2 I A1 I
A 2 I
A 3 I
A4 I A5
1
I rB I B1 I
B 2 I
B 3 I
B 4 I
B5
2
(Equation 3.4-4)
1
I rC I C1 I C
2 I C3 I C4 I C5
2
1
I wr0 I 01 I 02
I 03
I 04
I 05
2
Where:
I rA , I rB , I rC , I wr0 are secondary values of three phase restraint currents and zero-sequence
restraint current respectively.
If CTs used for winding differential protection have differential primary rated value, then the current
compensation is carried out in the program automatically. Following gives the criteria of calculating
correction coefficient.
I I 1n _ max
K wph 1n K b and K wb min( , 2. 95) (Equation 3.4-5)
I 1n _ max I1n _ min
Where:
I1n _ min is the minimum value among primary values of all CTs for winding differential protection.
I1n _ max is the maximum value among primary values of all CTs for winding differential protection.
This calculation method is to take the minimum CT ration of all calculated sides as the base ration
and the CT ration at other sides are considered as multiples of the base ratio. If the multiple of the
maximum CT ratio to the minimum CT ratio is greater than 2.95, then the multiple shall be taken as
2.95 and other sides shall be calculated proportionally. Otherwise, the multiple shall be taken as
1, and the currents on other sides will be calculated proportionally.
The currents used in the following analysis have been corrected, that means the currents for
following calculation are the products of the actual secondary current of each side multiplying its
own correction coefficient ( K wph ).
The operation criteria of winding differential protection are as follows, and maximum 5 branches
I wd I wcdqd I wr 0.5I n
I K wb1 I wr 0.5I n
I wcdqd
wd
wr
I max{ I w1 , I w 2 , I w 3 , I w 4 , I w 5 } (Equation 3.4-6)
I wd I w 1 I w 2 I w 3 I w 4 I w 5
Where:
Iwcdqd is the pickup setting of winding differential protection of the corresponding side, of i.e.
[I_Pkp_PcngWdgDiff]
If the pick up value of winding differential protection is greater than 0.5 In (i.e. I 0cdqd 0. 5I n ), its
keen point current will be set at I n automatically, the operating equation is as follows:
I wd I wcdqd I 0 r I n
I K wb1 I wr I n
I wcdqd
wd
wr
I max{ I w1 , I w 2 , I w 3 , I w 4 , I w 5 } (Equation 3.4-7)
I wd I w 1 I w 2 I w 3 I w 4 I w 5
Operation characteristic of restricted earth fault protection ( I wcdqd 0.5 I n ) is showed in the
following figure.
differential current
K= m
Where:
The value of m is defined by the branch number for winding differential protection calculation.
If the following operation formula is met and the state is keeping over 10s, CT circuit abnormality
alarm of REF protection will be issued without blocking the protection.
Where:
Criteria
If none of following four conditions is satisfied after the fault detector of differential current or
zero-sequence differential current picks up, it will be judged as CT circuit failure and CT circuit
failure alarm will be issued.
2) Any phase current of any side increases than that before the fault detector picks up.
3) The maximum phase current is greater than 1.1 Ie (Ie is secondary calculated rated current of
transformer) after the fault detector picks up.
Broken circuit and short circuit of differential CT secondary circuit can be judged more accurately
and reliably by adopting combined method of voltage and current.
By configuring different logic settings, user can gent following blocking functions to winding
differential protections after CT circuit failure alarm is issued. Once the alarm signal of differential
CT circuit failure is issued, it can be reset only when the failure is removed and equipment is reset
(i.e. the binary input [BI_RstTarg] is energized).
Winding differential protection of each side can be blocked when CT circuit failure is detected by
configuring the logic setting [En_CTS_Blk_WdgDiff].
If this logic setting is set as “0”, the protection is not blocked by with the alarm signal
being issued.
If this logic setting is set as “1”, the protection is blocked by with the alarm signal being
issued.
differential CT circuit or settings. Both shall be paid attention on site. For example,
differential circuits open can not cause protection pickup in case of light load but alarm will
be issued. If user treats this abnormality in time, the unwanted operation of percent
differential protection not blocked by CT circuit failure can be avoided when the load
increases or an external fault occurs.
Where:
Flg_Op_WdgDiff_HVS is the internal flag indicating that operation criterion of winding differential
protection of HV side is satisfied.
HVS: [En_WdgDiff] is the logic setting of enabling winding differential protection of HV side.
Flg_CTS is the internal flag indicating that instant CT circuit failure is distinguished by the criterion.
Flg_FD_WdgDiff_HVS is the internal flag indicating that the fault detector of winding differential
protection of HV side picks up.
3.4.4 Setting
Setting explanation
Three winding differential protections are equipped for each side of transformer, and they have the
same setting principles.
7. [ I_Pkp_PcntREF]
The pickup current of winding differential protection shall be greater than the maximum unbalance
current while transformer operates on normal rated load, i.e.
Where:
K er is the ratio errors of CT (for type 10P, K er = 0.03×2; for type 5P and TP, K er =0.01X2).
m is the error caused by the difference between ratios of CTs, and 0.05 is recommended.
Note that the pickup setting of the winding differential protection takes the secondary rated current
of CT (i.e. In, 1A or 5A) as its unit, whose setting value is calculated with the reference to the side
having the minimum ratio among all CTs for the winding differential protection. If it is the actual
current value to the reference side in actual setting calculation, then this actual value will be
divided by the secondary rated current of CT (i.e. In , 1A or 5A) to derive the setting value.
In actual projects, the measured unbalance current of the winding differential circuit under the
maximum load current can be referred to.
The setting should not be less than 0.1In and the recommended value is 0.2In~0.5In.
NOTE: The unit (i.e. In) of the setting calculation ([I_Pkp_PcntWdgDiff]) is the secondary
rated current of CT, and the minimum corrected coefficient of the side is taken as the
reference side. If a setting value got from calculation is together with its unit Ampere, this
setting value shall be divided by the secondary rated current of CT to get per unit value
which is the configuration value input to protection equipment.
8. [Slope_PcntWdgDif]
The setting is percent restraint coefficient of winding differential protection, which calculation
Where:
K ap = 1.0 if CT at both sides are class TP, or Kap = 1.5~ 2.0 if CT at both sides are class P.
Generally, in practical setting calculation for projects, K wbl can be taken as 0.30.7
9. [En_CTS_Blk_WdgDiff]
This is logic setting of enabling winding differential protection blocked by CT circuit failure.
NOTE: When winding differential protection is enabled, if the maximum CT ratio to the
minimum CT ratio related to the protection is greater than 16, this will be considered
abnormal and wrong setting alarm will be sent.
10. [En_WdgDiff]
The logic setting is used to enable or disable the winding differential protection of the
corresponding side.
11. [TrpLog_WdgDiff]
The tripping logic setting is used to specify which breakers will be tripped when winding differential
protection operates. Please refer to the description of the setting [TrpLog_Diff] in section 3.2.5 for
details.
12. [VEBI_WdgDiff]
This setting is the VEBI setting of enabling winding differential protection. Please refer to the
setting [VEBI_Diff] in section 3.2.5 for details.
NOTE: When winding differential protection is enabled, if the maximum CT ratio to the
minimum CT ratio related to the protection is greater than 16, this will be considered
abnormal and wrong setting alarm will be sent.
Input signals of restricted earth fault protection are list in the following table.
Output signals of restricted earth fault protection are list in following two tables.
Ia_Corr_WdgDiff_MBrn
Three phase corrected currents of winding differential protection
Ib_Corr_WdgDiff_MBrn
of MV side branch n (n=1, 2, 3, 4, 5).
3
Ic_Corr_WdgDiff_MBrn
side.
Phase B restraint current of winding differential protection of MV
23 Irb_WdgDiff_MVS
side.
Phase C restraint current of winding differential protection of MV
24 Irc_WdgDiff_MVS
side.
Zero-sequence restraint current of winding differential protection
25 Ir0_WdgDiff_MVS
of MV side.
Phase A threshold current of winding differential protection of MV
26 Itha_WdgDiff_MVS
side.
Phase B threshold current of winding differential protection of MV
27 Ithb_WdgDiff_MVS
side.
Phase C threshold current of winding differential protection of MV
28 Ithc_WdgDiff_MVS
side.
Zero-sequence threshold current of winding differential
29 Ith0_WdgDiff_MVS
protection of MV side.
Phase A differential current of winding differential protection of LV
30 Ida_WdgDiff_LVS
side.
Phase B differential current of winding differential protection of
31 Idb_WdgDiff_LVS
LV side.
Phase C differential current of winding differential protection of
32 Idc_WdgDiff_LVS
LV side.
Zero-sequence differential current of winding differential
33 I0d_WdgDiff_LVS
protection of LV side.
Phase A restraint current of winding differential protection of LV
34 Ira_WdgDiff_LVS
side.
Phase B restraint current of winding differential protection of LV
35 Irb_WdgDiff_LVS
side.
Phase C restraint current of winding differential protection of LV
36 Irc_WdgDiff_LVS
side.
Zero-sequence restraint current of winding differential protection
37 Ir0_WdgDiff_LVS
of LV side.
Phase A threshold current of winding differential protection of LV
38 Itha_WdgDiff_LVS
side.
Phase B threshold current of winding differential protection of LV
39 Ithb_WdgDiff_LVS
side.
Phase C threshold current of winding differential protection of LV
40 Ithc_WdgDiff_LVS
side.
Zero-sequence threshold current of winding differential
41 Ith0_WdgDiff_LVS
protection of LV side.
42 Ang(Ia)_HBr1-HBrn
Three phase angles between the current of HV side branch 1
43 Ang(Ib)_HVS1-HVSn
and the current of HV side branch n (n=2, 3, 4, 5).
44 Ang(Ic)_HBr1-HBrn
Angle between zero-sequence current of HV side branch 1 and
45 Ang(3I0)_HBr1-HBrn
zero-sequence current of HV side branch n (n=2, 3, 4, 5).
46 Ang(Ia)_MBr1-MBrn
Three phase angles between the current of MV side branch 1
47 Ang(Ib)_MBr1-MBrn
and the current of MV side branch n (n=2, 3, 4, 5).
48 Ang(Ic)_MBr1-MBrn
Angle between zero-sequence current of MV side branch 1 and
49 Ang(3I0)_MBr1-MBrn
zero-sequence current of MV side branch n (n=2, 3, 4, 5).
50 Ang(Ia)_LBr1-LBrn
Three phase angles between the current of LV side 1 and the
51 Ang(Ib)_LBr1-LBrn
current of LV side n (n=2, 3, 4, 5).
52 Ang(Ic)_LBr1-LBrn
Angle between zero-sequence current of LV side branch 1 and
53 Ang(3I0)_LBr1-LBrn
zero-sequence current of LV side branch n (n=2, 3, 4, 5).
No.1 to No. 27 items are measured values and phase angles for LCD display
Overexcitation protection is used to prevent transformer damage due to overvoltage and low
frequency. Two definite-time stages and one inverse-time stage for tripping and one definite-time
stage for alarm are equipped with overexcitation protection.
The side overexcitation protection being equipped can be selected by user through PCS-PC
software.
The fault detector picks up after the corresponding time delay, when measured U * / f* is greater
The fault detector picks up when overexcitation U * / f * accumulated value is greater than
inverse time protection setting and the corresponding time delay is expired.
Two-stage definite overexcitation and one-stage overexciation alarm element are equipped.
Where:
The base value for calculating per unit value of voltage is secondary rated voltage value (phase
voltage) of the voltage transformer, and the base value for calculating per unit value of frequency
is rated frequency. During normal operation, n = 1.
Several groups of setting point with independent settings can be configured for simulating the
inverse-time operation characteristics curve and this protection can satisfy overexcitation
requirements of different transformers.
U* / f*
Overexcitation calculation factor comprises overexcitation information at current instant and also
overexcitation information integrated over various time intervals since its beginning.
Inverse-time characteristic curve can be specified by several overexcitation multiple settings, and
the relation between various settings of n and t are:
n0≥n1 ≥ n2 ≥ n3 ≥ n4 ≥ n5 ≥ n6 ≥ n7 ≥ n8 ≥ n9
t0 ≤t1 ≤ t2 ≤ t3 ≤ t4 ≤ t5 ≤ t6 ≤ t7≤ t8 ≤ t9
Where
t0 is the time delay corresponding to the upper-limit multiple setting, i.e. [t0_InvOvExc].
t9 is the time delay corresponding to the lower-limit multiple setting , i.e. [t9_InvOvExc].
ni (i=1,… 8) is the setting of the corresponding point of overexcitation, i.e. [ki_InvOvExc] (i=1,… ,8).
ti (i=1,… 8) is the setting of the corresponding point of overexcitation, i.e. [ki_InvOvExc] (i=1,… ,8).
Because voltage is used for the calculation of overexciation protection, the protection shall be
disabled when voltage transformer of the side where the protection is equipped is out of service.
Inverse-time overexcitation alarm and trip elements both equipped. If only alarm element is
enabled, an alarm signal will be issued after calculated time delay is expired, but if only trip
element is enabled, an alarm signal message will be issued after 0.7 times calculated time delay is
expired and a trip signal will be issued after calculated time delay is expired.
[EBI_In_VT_XXX]
[En _In_VT_XXX] & [t_Alm_DefOvExc]
& [Alm_DefOvExc]
[En_Alm_DefOvExc]
U / f > [k_Alm_DefOvExc]
[EBI_In_VT_XXX]
&
[En_In_VT_XXX]
[EBI_OvExc]
&
[VEBI_OvExc] & [t_DefOvExcn] [Op _DefOvExc]
[En_Trp_DefOvExc]
&
U / f > [k_DefOvExcn]
Flg_FD_DefOvExc
[EBI_In_VT_XXX]
&
[En_In_VT_XXX]
[En _Alm_InvOvExc]
& & Alm_InvOvExcn]
U / f > [k9_InvOvExc]
[En_Trp_InvExc]
&
U / f > [k9_InvOvExc]
[EBI_In_VT_XXX]
&
[En_In_VT_XXX]
[EBI_OvExc]
&
[VEBI_OvExc] & [Op_InvOvExcn]
[En_Trp_InvExc]
&
U / f > [k9_InvOvExc]
Flg_FD_InvOvExc
Where:
[EBI_In_VT_XXX] is the binary input of enabling VT of XXX (XXX= HVS, MVS or LVS) side into
service.
[En_In_VT_XXX] is the logic setting of enabling VT of XXX (XXX= HVS, MVS or LVS) side into
service.
Flg_FD_DefOvExc is the internal flag indicating that the fault detector of definite-time
overexcitation protection picks up.
Flg_FD_InvOvExc is the internal flag indicating that the fault detector of inverse-time overexciation
protection picks up.
3.5.4 Setting
Table 3.5-1 Settings of overexcitation protection
NOTE: The conversion relation in case that the rated voltage of the transformer is not
NOTE: User can set the location of the overexciation protection being equipped only
1. [k_DefOvExc1], [k_DefOvExc2]
These are settings of stage 1 and stage 2 of definite-time overexcitation protection respectively,
which are set as required.
2. [t_DefOvExc1], [t_DefOvExc2]
These are time delays of stage 1 and stage 2 of definite-time overexcitation protection respectively,
which are set as required
3. [k_Alm_DefOvExc]
4. [t_Alm_DefOvExc]
This is time delay of definite-time overexcitation alarm element, which is set as required.
5. [En_DefOvExc ]
Inverse-time overexcitation protection is set with reference to the curve given by the transformer
manufactory.
[k_Alm_InvOvExc]<[k0_InvOvExc]<[k0_InvOvExc]<… <[k9_InvOvExc]
[t_Alm_InvOvExc]>[t0_InvOvExc]>[t1_InvOvExc]>… >[t9_InvOvExc]
1. [ki_InvOvExc] (i=0,1, … , 9)
These are time delays of each section of inverse-time overexciation characteristeic curve
3. [k_Alm_InvOvExc]
4. [t_Alm_InvOvExc]
5. [En_Alm_InvOvExc ]
This logic setting is used to enable or disable definite-time overexciation for alarming.
6. [En_Trp_InvOvExc ]
This logic setting is used to enable or disable definite-time overexciation protection for tripping.
1. [TrpLog_OvExc]
The tripping logic setting is used to specify which breakers will be tripped when overexcitation
protection operates. Please refer to the description of the setting [TrpLog_Diff] in section 3.2.5 for
details.
2. [VEBI_OvExc]
This setting is the VEBI setting of enabling overexcitation protection. Please refer to the setting
[VEBI_Diff] in section 3.2.5 for details.
The pickup of this fault detector will enable underfrequency protection, which operation criterion is
as follows.
Where:
[f_UF1], [f_UF2], [f_UF3] and [f_UF4] are the frequency settings of stage 1, stage 2, stage 3 and
stage 4 of underfrequency protection respectively.
The pickup of this fault detector will enable overfrequency protection which operation criterion is as
follows.
Where:
[f_OF1] and [f_OF2] are the setting of stage 1 and stage 2 o frequency settings of overfrequency
protection respectively.
Operation criteria of underfrequency protection and overfrequency protection are shown in the
following two equations respectively, and the corresponding protection operates when one
operation criterion is met. Undervoltage blocking element is equipped to block overfrequency and
underfrequency protections when positive-sequence voltage is less than 30V.
Where:
f is system frequency.
Where:
df / dt is the frequency slip speed and the time step (i.e. dt ) for the calucation is equal to 5
cycle.
Underfrequency protection can be blocked by the frequency slip speed (df/dt). If the logic setting
[En_df/dt_UFn] (n=1, 2, 3 or 4) is set as “1”, when (Equation 3.6-3) and (Equation 3.6-4) are met, it
is decided that a fault occurred and the corresponding stage underfrequency protection is blocked
at the same time for the purpose of waiting for operation of other related protection. The blocking
signal will not reset until the system frequency recovers, i.e. the system frequency is greater than
the setting [f_Recov]. If the logic setting is set as “0”, when (Equation 3.6-3) and (Equation 3.6-4)
are met, the stage underfrequency protection will be released to operate.
Operation criterion of overfrequency protection
Where:
f is system frequency.
[EBI_In_VT_XXX]
&
[En_In_VT_XXX]
[EBI_FreqProt]
[VEBI_FreqProt] &
& [t_OFn]
[En_UFn] [Op_OFn]
f > [f_OFn]
Flg_UnderVolt
Flg_FD_OF
[EBI_In_VT_XXX]
&
[En_In_VT_XXX]
[EBI_FreqProt]
[VEBI_FreqProt] &
[En_UFn] [t_UFn]
& [Op_UFn]
f < [f_UFn]
Flg_UnderVolt
Flg_FD_UF
-df/dt≥[df/dt_UF]
&
[En_df/dt_UFn]
Where:
[EBI_In_VT_XXX] is the binary input of enabling VT of XXX (XXX= HVS, MVS or LVS) side into
service.
[En_In_VT_XXX] is the logic setting of enabling VT of XXX (XXX= HVS, MVS or LVS) side into
service.
f is system frequency.
Flg_UnderVolt is the internal flag indicating that undervoltage blocking element pickus up, which
means that the positive-sequence voltage is less than 30V.
Flg_FD_UF is the internal flag indicating that the fault detector of underfrequency protection picks
up.
Flg_FD_OF is the internal flag indicating that the fault detector of overfrequency protection picks
up.
3.6.4 Setting
Setting explanation
1. [f_Recov]
The setting is the lowest frequency threshold of fault recovery, i.e. the recognized normal level of
frequency after a fault is eliminated.
After some stage of underfrequency protection is blocked by df/dt, the stage underfrequency
protection will not be released to operate unless that system frequency increases to be greater than
the setting [f_Recov].
2. [ df/dt_UF]
The setting of df/dt blocking underfrequency protection is set to avoid the underfrequency
protection operating during a short-circuit fault. When the variation of system frequency is greater
than the setting, some stage of underfrequency protection can be blocked if the corresponding
logic setting of the stage protection is enabled.
3. [f_UFX] (X=1, 2, 3, 4)
This is the frequency setting of stage X (X=1, 2, 3, 4) of underfrequency protection, which should
be set according to system frequency and stability control strategy.
4. [t_UFX] (X=1, 2, 3, 4)
This is the time delay of stage X (X=1, 2, 3, 4) of underfrequency protection, which should be set
according to system frequency and stability control strategy.
5. [En_UFX] (X=1, 2, 3, 4)
This is the logic setting of enabling stage X (X=1, 2, 3, 4) of underfrequency protection, which
should be set according to the actual number of load shedding stage.
6. [En_df/dt_UFX] (X=1, 2, 3, 4)
This is the logic setting of enabling stage X (X=1, 2, 3, 4) of underfrequency protection being
blocking by df/dt, which should be set according to requirements.
7. [TrpLog_UFX] (X=1, 2, 3, 4)
The tripping logic setting is used to specify which breakers will be tripped when stage X (X=1, 2, 3,
4) of underfrequency protection of some side operates. Please refer to the description of the
setting [TrpLog_Diff] in section 3.2.5 for details.
8. [f_OFX] (X=1, 2)
This is the frequency setting of stage X (X=1, 2) of overfrequency protection, which should be set
according to system frequency and stability control strategy.
9. [t_OFX] (t=1, 2)
This is the time delay of stage X (X=1, 2) of overfrequency protection, which should be set
according to system frequency and stability control strategy.
Where:
3.7.3 Setting
Setting explanation
NOTE: Before mechanical protection is put into service, input signals for the logic module
1. [t_MRX] (X=1, 2, 3, 4)
This is the time delay of MRX (X=1, 2, 3, 4) mechanical protection for tripping. If the function of
tripping with time delay is not needed the setting can be set as “0”.
2. [En_MRX] (X=1, 2, 3, 4)
This is the tripping logic setting of enabling MRX mechanical protection to trip.
3. [TrpLog_MRX] (X=1, 2, 3, 4)
The tripping logic setting is used to specify which breakers will be tripped when stage X (X=1, 2, 3,
4) of mechanical protection operates. Please refer to the description of the setting [TrpLog_Diff] in
section 3.2.5 for details.
4. [VEBI_MR]
This setting is the VEBI setting of enabling mechanical protection. Please refer to the setting
[VEBI_Diff] in section 3.2.5 for details
Three impedance protection elements of HV, MV, and LV sides are provided with totally same
configuration.
Fault detector of impedance protection includes the fault detector of DPFC phase-to-phase current
and the fault detector of negative-sequence current. Impendence protection will be enabled for
500 ms if any fault detector picks up to enable impedance protection and will keep be enabled if
phase-to-phase or phase-to-earth impedance relay operates.
Where:
It is the floating threshold value which will arise automatically and gradually according to
increasing of the output of deviation component. In order to ensure the threshold voltage is
slightly greater than the unbalance voltage, multiple 1.25 of the deviation component is
reasonable.
I th is the fixed threshold of 0.2 In and does not need to be set on site.
Where:
Following figure shows operating characteristic of phase-to-phase impedance relay with reach
angle 78º. In this figure, Zn is the reverse impedance setting (pointing to system direction) and
Zp is the forward impedance setting (pointing to transformer direction).
jx
Zp
m
R
Zn
Following figure shows operating characteristic of phase-to-earth impedance relay with reach
angle 78º. In this figure, Zn is the reverse impedance setting (pointing to system direction) and
Zp is the forward impedance setting (pointing to transformer direction).
jx
Zp
m
R
Zn
U ( I k * 3I 0 ) ZP
90Arg
270 (Equation 3.8-4)
U( I k * 3I 0 )Z n
Where:
z z
k 0 1 is the zero-sequence compensation coefficient (i.e. setting [K0_ZPE_HVS ]) and
3z1
recommended value is 0~2. “k”is generally 0.6 if protection direction points to local busbar, and “k”
is 0~0.1, if protection direction points to transformer.
PCS-978 adopts releasing power swing blocking to avoid maloperation of distance protection
resulting from power swing. In another word,in order to avoid unwanted operation of impedance
relay during system oscillation, the protection is blocked all along under the normal condititon and
power swing. Only if fault (internal fault or power swing with internal fault) is detected, power swing
blocking for distance protection is released by PSBR element.
There is a logic setting [En_PSBR_Ctrl_Z] to enable or disable PSBR function. If it is set as “1”
then, the PSBR function is enabled. Otherwise, i t is disabled.
Power swing blocking for distance element will be released if any of the following PSBR elements
operate.
If any of the following condition is matched, FD PSBR will operate for 160ms.
1) Positive sequence overcurrent element with setting higher than maximum load current does
not operate before one of the fault detectors of backup protection operates.
2) Positive sequence overcurrent element with setting higher than maximum load current not
operates before one of the fault detectors of backup protection operates, but the duration is less
than 10ms.
I 0 I 2 m I1 (Equation 3.8-5)
The “m”is a internal fixed coefficient which can ensure UF PSBR operate during power swing with
internal unsymmetrical fault, while not operate during power swing or power swing with external
fault
If a three-phase fault occurs and FD PSBR is invalid (160ms after GFD operates), neither FD
PSBR nor UF PSBR will be able to operate to release the distance protection. Thus, SF PSBR is
provided for this case specially. This detection is based on measuring the voltage at power swing
center:
Where:
: the angle between positive sequence voltage and positive sequence current
1) when 0.03U N U OS 0.08U N , the SF PSBR element will operate after 150ms.
2) when 0.1U N U OS 0.25U N , the SF PSBR element will operate after 500ms.
NOTE: If time delay of impedance protection is more than 1.5 s, PSBR function is not
When VT circuit failure is detected, the impedance protection will be disabled automatically.
When VT of one side is maintained or bypass circuit breaker is closed with its relevant VT having
not been switched on, in order to avoid unwanted operation of impedance protection of this side,
the binary input [EBI_In_VT_XXX] (XXX represents HVS, MVS or LVS) shall be de-energized and
impedance protection is disabled automatically.
Where:
Flg_Pkp_PSB is the internal flag indicating that power swing blocking releasing element picks up.
Flg_Op_ZPP1_HVS is the internal flag indicating that stage 1 of phase -to-phase impendence
protection of HV side satisfies the operation criterion.
Flg_VTS_HVS is internal flag indicating that VT supervision program detects VT circuit failure
HVS:[En_PSBR_ZPP1] is the logic setting of enabling power swing blocking releasing element to
control stage 1 of phase-to-phase impendence protection of HV side.
[En_Bak_HVS] is the logic setting of enabling all the backup protections of HV side.
Flg_FD_Z_HVS is the operation of the fault detector of DPFC phase-to-phase current or that of
negative-sequence current of HV side, which are used to enable impendence protection.
3.8.4 Setting
Setting explanation
NOTE: When current protection fails to satisfy the sensitivity requirement or follow the
coordination requirement between power girds, impedance protection can be used as the
backup protection of transformer. The impedance protection provided by PCS-978 is plain
impedance relay and its positive and reverse impedance values can be set independently.
The two settings are positive impedance settings of the stage n of phase-to-phase and
phase-to-earth impedance protections respectively, and the protection direction of the positive
impedance setting points to a transformer.
If impedance protection is used for protecting transformer, the following conditions as below can
be included:
Based on that there is the enough sensitivity for the fault at the opposite side busbar, the following
formula can be get:
Zop K sen Zt
Where:
Based on coordination with the outgoing line of opposite side, the following formula can be get:
Where:
Zt is the secondary impedance value of the transformer.
Kinf is the infeed coefficient and shall be the minimum value under various operation modes.
Z op K rel K inf Z
tmax + t
t=
Where:
The two settings are is logic setting of enabling stage n of phase-to-phase and phase-to-earth
impedance protection respectively, which shall be set as required.
“0”: disable the stage protection. “1”: enable the stage protection.
5. [K0_ZPE]]
This is the logic setting of enabling power swing blocking releasing function.
“0”: disable the function; “1”: enable the function.
When the time delay of impedance protection can not be set greater than the period of power
swing, it is suggested that power swing blocking releasing function shall be enabled. , and the
recommended value is 1.
7. [TrpLog_ZPPn], [TrpLog_ZPEn] (n=1, 2)
These tripping logic settings are used to specify which breakers will be tripped when stage n of
phase-to-phase or phase-to-earth impedance protection operates. Please refer to the description
of the setting [TrpLog_Diff] in section 3.2.5 for details.
8. [VEBI_Z_XXX] (XXX=HVS, MVS, LVS)
This setting is the VEBI setting of enabling impedance protection. Please refer to the setting
[VEBI_Diff] in section 3.2.5 for details.
Output signals of impedance protections of HV, MV and LV sides are list in the following table.
The function of phase overcurrent protection for transformer is to avoid some physical damages to
the transformer when an external fault occurs with a long-term through fault current. The
directional element is to select protection direction to protect transformer or system. The voltage
control element can improve the sensitivity of overcurrent protection without considering some
special conditions like the motor self-starting process, so the operating threshold setting of
overcurrent protection could be lower properly.
Four phase overcurrent protection elements of HV, MV, and LV sides and common winding (CW)
are provided with totally same configuration, which can be controlled by directional element and
voltage control element and be blocked by harmonic blocking element by configuring
corresponding logic settings.
Criteria:
Where:
[I_OC1], [I_OC2], [I_OC3] and [I_OC4] are respectively the current settings of stage 1, stage 2,
stage 3 and stage 4 of definite-time overcurrent protection of the corresponding side.
The pickup of this fault detector will enable definite-time overcurrent protection of corresponding
side.
When phase current of one side is greater than base current setting [I_OCn] (n=1, 2, 3 or 4), the
fault detector picks up to enable stage n (n=1, 3, 4 or 4) of inverse-time overcurrent protection at
relevant side.
There are four stages of overcurrent protection are equipped for each side of transformer, which
can be definite-time or inverse-time overcurrent protection by configuring the logic setting XXX:
[Opt_Characteristic_OCn] (XXX represents HVS, MVS, LVS, CW; n=1, 2, 3, 4) “0”for definite-time
overcurrent protection , and “1”for inverse-time overcurrent protection.
Where:
Inverse delay characteristics (IDMT) defined in IEC60255-3 are adopted, which formula is shown
as follows.
Kt
t (I ) Tp
I (Equation 3.9-3)
( ) 1
Ip
Where :
I p is base current (also called current limit), i.e. setting [I_OCn] (n=1, 2, 3 or 4).
User can get different inverse delay characteristic curves by configuring above settings, and four
common inverse delay characteristics with parameters are list in the following table.
The voltage control element will pickup if phase-to-phase voltage is lower than its setting or
negative-sequence voltage is greater than its setting.
Criteria:
Where:
Voltage of other side can be used as the input of voltage control element, and there are logic
settings used to select which side voltage control element to control OC protection of some side.
The logic setting [En_VCE_Ctrl_OCn] (n=1, 2, 3, 4) is used to select which stage overcurrent
protection is controlled by local voltage control element. For example, if setting HVS:
[En_VCE_Ctrl_OC1] is set as “1”, stage 1 overcurrent protection of HV side will be controlled by
the voltage control element of HV side. Otherwise it will not.
Positive sequence voltage with memory is used in directional element. There is no dead zone for
directional element during close-in three-phase short circuit fault due to its memory function. The
directional relay is connected in the naught degree mode. The polarity of CT connected to
protection equipment is shown in the application scheme figure, and the positive polarity of CTs of
each side shall be at the side near busbar.
Protection direction of each stage of overcurrent protection can be set respectively by the logic
setting [Opt_Dir_Ctrl_OCn] (n=1, 2, 3, 4). If the setting is set as “1”, its direction is to protect
transformer and reach angle is 45º, and if the setting is set as “2”, its direction is to protect power
system and reach angle is 225º. If this setting is set as “0”, the corresponding stage of the
protection is not controlled by directional element. The operating characteristic is shown in the
following figure in which the shadow zone is the operation zone of the directional element.
Operation criteria of directional element are as follows, when protection direction is to protect
transformer.
Phase A: -45°<arg(U1)-arg(Ia)<135°
Phase C: 75°<arg(U1)-arg(Ic)<-255°
Operation criteria of directional element are as follows, when protection direction is to protect
power system.
Phase A: 135°<arg(U1)-arg(Ia)<315°
Phase C: -105°<arg(U1)-arg(Ic)<75°
Where:
Ul Ul
φlm=45°
φlm =225°
NOTE: The protection direction mentioned above is based on that the positive polarity of
CT is at the side of busbar. Otherwise actual protection direction is not consistent to that
mentioned above.
Voltage control element and directional element both picks up to release overcurrent protection
when VT circuit failure is distinguished, which means voltage controlled directional overcurrent
protection becomes overcurrent protection without any control element.
When VT of one side is maintained or bypass circuit breaker is closed with its relevant VT having
not been switched on, in order to ensure correct operation of voltage controlled directional
overcurrent protection, the binary input [EBI_In_VT_XXX] (XXX represent HVS, MVS or LVS)
should be de-energized. Then voltage control element and directional element both pick up to
release overcurrent protection which becomes overcurrent protection without any control element.
The equipment has harmonic blocking functions. When the following operation equation is
satisfied, harmonic blocking element picks up to block overcurrent protection.
Where:
Logic schemes of overcurrent protection of each side are same, and that of HV side is taken as an
Logic schemes of voltage control element of each side are same, and that of HV side is taken as
an example to show the logic diagram.
U _ min
U2
Where:
Flg_VTS_HVS is the internal flag indicating that VT circuit failure of HV side is distinguished.
Flg_Pkp_VCE_HVS is the internal flag indicating that the local VCE for controlling OC of HV side
picks up.
Where:
Flg_Direction_OC_HVS is the internal flag indicating that DE decides the fault is in the protection
direction of overcurrent protection of HV side.
I _ max
Where:
Flg_Pkp_VCE_HVS is the internal flag indicating that the local VCE for controlling HV side OC
protection picks up.
Flg_Pkp_DE_HVS is the internal flag indicating that directional element of HV side picks up.
side.
HVS:[En_Harm_Blk_OCn]
≥1
Flg_Pkp_Harm_HVS
HVS:[En_VCE_Ctrl_OCn]
≥1
Flg_Pkp_VCE_HVS
HVS:[Opt_Dir_Ctrl_OCn]=0
≥1 & [ Op_OCn_HVS]
Flg_Pkp_DE_HVS
I _ max >HVS:[I_OCn]
[EBI_OC_HVS]
&
[VEBI_OC_HVS]
HVS:[En_OCn]
HVS:[Opt_Characteristic_OCn]=1
Flg_FD_InvOC_HVS
Where:
3.9.4 Setting
The setting of backup protection is usually related to the rated current of various sides of the
transformer. The calculation method is the same for the rated currents on various sides. The
following shows an example for the HV side.
Sn
The rated current of HV side is: I1 n
3U 1n
Where:
I 1n
The secondary rated current of HV side is: I 2n .
n CT
Where:
Overcurrent Elements
The method for configuring overcurrent settings varies with the need and wiring mode.
[I_OCn] is current setting of stage n of definite-time overcurrent protection or base current setting
OC protection.
For the setting [I_OCn] is used in definite-time overcurrent protection, there are following three
ways to set the setting.
1) The setting is set according to rated current of transformer. The operating current of the
current relay should be greater than the rated current of the transformer, whose calculation
formula is as follows:
K
I op rel I n (Equation 3.9-7)
Kr
Where:
Where:
Kbr is branch coefficient of current, which is equal to the ratio of the current passing through
this protection equipment to the current passing through the faulty line during an earth fault at
the end of protection section of the coordinated stage of overcurrent protection of the power
line.
3) The setting is set to ensure enough sensitivity of the protection during a fault at the local side
busbar.
Where:
Imin is the minimum current value during a short-circuit fault at the local side bus.
Recommended value: when coordination is not considered, following formula can be taken for the
stage with the lowest setting.
K
I op rel I n (Equation 3.9-10)
Kr
Where:
If there is more than one stage, settings of other stages can be amplified in sequence.
For the setting [I_OCn] is used in inverse-time overcurrent protection, the setting should be
configured as follows.
1) The setting is set according the rated current of transformer, which can be set equal to the
minimum value of current settings of definite-time overcurrent protection.
Where:
2. [t_DefOCn] (n=1, 2, 3, 4)
1) In coordination with the main protection of the transformer, the following formula is
recommended.
t =0.5s
Where:
2) In coordination with the phase-to-phase overcurrent protection of the line, the following
formula is recommended.
t = t max + t
Where:
t n1 t n t
Where:
Recommended value: when no coordination is required, the minimum operating time can be set as
2s, with other time delays amplified in sequence.
3. [En_OCn] (n=1, 2, 3, 4)
This logic setting is used to enable or disable some stage of overcurrent protection.
0”disable the protection; 1”enable the protection.
4. [k_BaseTime_InvOCn] (n=1, 2, 3, 4)
If stage n of inverse-time OC protection coordinates with a line, the setting should be set equal to
the base time of inverse-time OC protection of the line.
If stage n of inverse-time OC protection is used independently, recommended value is 0.05s~3.2s
5. [t_MinDly_InvOCn] (n=1, 2, 3, 4)
[k_TimeMulti_InvOCn] and [k_Exponent_InvOCn] are respectively the time multiplier ( Kt ) and the
exponent ( ) of stage n of inverse-time OC protection, which are set according to the model of
inverse-time OC protection. Parameters of different models of inverse-time OC protection
supported by the relay are shown in the table below.
Extremely Inverse 2 80
7. [TrpLog_OCn] (n=1, 2, 3, 4)
The tripping logic setting is used to specify which breakers will be tripped when stage n (n=1, 2, 3,
4) of overcurrent protection operates. Please refer to the description of the setting [TrpLog_Diff] in
section 3.2.5 for details.
8. [VEBI_OC_XXX] (XXX=HVS, MVS, LVS, CW)
This setting is the VEBI setting of enabling overcurrent protection of some side. Please refer to the
setting [VEBI_Diff] in section 3.2.5 for details
1. [Vpp_UV_VCE]
The voltage setting of undervoltage relay should be greater the lowest voltage during starting
process of largest motor started.
1) When voltage for undervoltage relay is taken from LV side VT, t he calculation formula is as
follows:
U
U op min (Equation 3.9-12)
K rel
Kr
Where:
U op is the setting .
U min is the minimum possible phase-to-phase voltage during normal operation of the
transformer which can be normally taken as 0.9Un (Un is secondary value of the rated line
voltage.
2) When voltage for undervoltage relay is taken from HV side VT, the calculation formula is as
follows:
Where:
3) For a step-up transformer in a power plant, when voltage for undervoltage relay is taken from
VT of generator, the setting should be greater than the possible lowest voltage during
generator operation in loss of excitation condition. The calculation formula is as follows:
Where:
2. [V_NegOV_VCE]
The setting should be greater than the unbalance voltage during transform er normal operation,
which can be derived through actual measurement.
Where:
U op 2 is the setting.
3. [k_Harm_Blk_OC]
4. [En_VCE_Ctrl_OCn] (n=1, 2, 3, 4)
This logic setting is used to enable or disable the function that certain stage of overcurrent
protection of some side is controlled by voltage control element (VCE).
If multi-stage protection is enabled, it is recommended that the first stage be controlled by voltage
control element. If only one stage of OC protection is enabled, it is recommend that this stage not
be controlled by VCE.
5. [Opt_Dir_Ctrl_OCn] (n=1, 2, 3, 4)
This is the logic setting of selecting control mode of directional element to stage n of OC
protection.
“0”: control function disabled.
“1”: protect transformer.
“2”: protect power system.
If only one stage of OC protection is enabled, it is recommend that this stage not be controlled by
directional element.
6. [En_Harm_Blk_OCn] (n=1, 2, 3, 4)
This is the logic setting of enabling some stage of OC protection to be blocked by harmonics.
If there is no special requirement, it is recommend to be set as “0”.
“0”: the blocking function is disabled; “1”: the blocking function is enabled.
Zero-sequence overcurrent relay is mainly used as the backup protection of earth fault for
transformer with neutral point earthed solidly.
Four zero-sequence overcurrent protection elements of HV, MV, and LV sides and common
winding (CW) are provided with totally same configuration, which can be controlled by directional
element and be blocked by harmonic blocking element.
The current from zero-sequence CT at neutral point is used for the protection calculation.
Operation criteria:
Where:
3I0 is the current from the zero-sequence CT or calculated three times of zero-sequence current of
one side.
[I_ROC1], [I_ROC2], [I_ROC3] and [I_ROC4] are respectively the current settings of stage1, stage
The pickup of the fault detector will enable definite-time zero-sequence overcurrent protection at
the relevant side.
When zero-sequence current from zero-sequence CT of one side is greater than base current
setting [I_ROCn] (n=1, 2, 3 or 4), the fault detector picks up to enable stage n (n=1, 3, 4 or 4) of
inverse-time zero-sequence overcurrent protection at relevant side.
There are four stages of zero-sequence overcurrent protection are equipped for each side of
transformer, which can be definite-time or inverse-time zero-sequence overcurrent protection by
configuring the logic setting XXX: [Opt_Characteristic_ROCn] (XXX represents HVS, MVS, LVS,
CW; n=1, 2, 3, 4), “0”for definite time characteristic, and “1”for inverse time characteristic.
inverse-time characteristic by user freely, but if user wants to configure more stages as
inverse-time characteristics please inform the manufacturer when placing an order.
NOTE: Zero-sequence current for ROC protection, RDE element and harmonic
calculation are from the same source. If the setting [En_3I0_Calc_ROC] is set as “0”,
then the current from zero-sequence CT is used, and otherwise the calculated
zero-sequence current is used.
Where:
3I0 is the current from the zero-sequence CT or calculated three times of zero-sequence current of
one side.
Inverse delay characteristics defined in IEC60255-3 are adopted, which formula is shown as
follows.
Kt
t (I 0 ) Tp
I0 (Equation 3.10-3)
( ) 1
Ip
Where:
I p is base current (also called current limit), i.e. setting [I_ROCn] (n=1, 2, 3 or 4).
User can get different inverse delay characteristic curves by configuring above settings, and four
common inverse delay characteristics with parameters are list in the following table.
Protection direction of each stage of zero-sequence overcurrent protection can be set respectively
by the logic setting [Opt_Dir.RD_Ctrl_ROCn] (n=1, 2, 3, 4). If the setting is set as “1”, its direction
is to protect power system and reach angle is 255º, and if the setting is set as “2”, its direction is to
protect transformer and reach angle is 75º. If this setting is set as “0”, the corresponding stage of
the protection is not controlled by zero-sequence directional element. The operating characteristic
is shown in the following figure in which the shadow zone is the operation zone of the residual
directional element.
Operation criteria of directional element are as follows, when protection direction is to power
system.
Operation criteria of directional element are as follows, when protection direction is to transformer.
Where:
I0 is the current from the zero-sequence CT or calculated three times of zero-sequence current of
one side.
and zero-sequence CT being set as the function figures in Chapter 1 shows. Otherwise
actual protection direction is not consistent to that mentioned above.
When VT of one side is maintained or bypass circuit breaker is closed with its relevant VT having
not been switched on, in order to ensure correct operation of controlled directional
zeros-sequence overcurrent protection, the binary input [EBI_In_VT_XXX] (XXX represent HVS,
MVS or LVS) should be de-energized. Then zero-sequence directional element picks up to release
zero-sequence overcurrent protection which becomes zero-sequence overcurrent protection
without any control element.
Operation criterion:
Where:
Where:
Flg_Direction_ROC_HVS is the internal flag indicating that DE decides the fault is in the protection
direction of overcurrent protection of HV side.
Flg_VTS_HVS is the internal flag indicating that VT circuit failure of HV side is distinguished.
Where:
3I0 is the current from the zero-sequence CT or calculated three times of zero-sequence current of
HV side.
Where:
3.10.4 Setting
Table 3.10-2 Settings of zero-sequence overcurrent protection (HVS, MVS, LVS, CW)
Time multiplier ( Kt ) of
7 k_TimeMult_InvROC1 0.01~200 0.01
inverse-time ROC protection
stage 1.
Exponent () of inverse-time
8 k_Exponent_InvROC1 0.01~10 0.01
ROC protection stage 1.
0: disable Logic setting of enabling/disabling
9 En_ROC1 0, 1
1: enable ROC protection stage 1.
Logic setting of enabling/disabling
0: disable
10 En_Harm_Blk_ROC1 0, 1 function of harmonic blocking
1: enable
ROC stage 1.
Logic setting of selecting control
mode of zero-sequence
11 Opt_Dir.RD_Ctrl_ROC1 0~2 1
directional element to stage OC
protection stage 1.
Tripping logic setting of ROC
12 TrpLog_ROC1 0000~FFFF
protection stage 1
Logic setting of selecting
13 Opt_Characteristic_ROC1 0, 1 1 characteristic of ROC protection
stage 1.
Current setting of ROC protection
14 I_ROC2 0.05~150A 0.01A
stage 2.
Time delay of definite-time ROC
15 t_DefROC2 0~20s 0.001s
protection stage 2.
Time multiplier ( Kt ) of
18 k_TimeMult_InvROC2 0.01~200 0.01
inverse-time ROC protection
stage 2.
Exponent () of inverse-time
19 k_Exponent_InvROC2 0.01~10 0.01
ROC protection stage 2.
0: disable Logic setting of enabling/disabling
20 En_ROC2 0, 1
1: enable ROC protection stage 2.
Time multiplier ( Kt ) of
29 k_TimeMult_InvROC3 0.01~200 0.01
inverse-time ROC protection
stage 3.
Exponent () of inverse-time
30 k_Exponent_InvROC2 0.01~10 0.01
ROC protection stage 3.
0: disable Logic setting of enabling/disabling
31 En_ROC3 0, 1
1: enable ROC protection stage 3.
Logic setting of enabling/disabling
0: disable
32 En_Harm_Blk_ROC3 0, 1 function of harmonic blocking
1: enable
ROC stage 3.
Logic setting of selecting control
mode of zero-sequence
33 Opt_Dir.RD_Ctrl_ROC3 0~2 1
directional element to stage OC
protection stage 3.
Tripping logic setting of ROC
34 TrpLog_ROC3 0000~FFFF
protection stage 3
Logic setting of selecting
35 Opt_Characteristic_ROC3 0, 1 1
characteristic of ROC protection
Time multiplier ( Kt ) of
40 k_TimeMult_InvROC4 0.01~200 0.01
inverse-time ROC protection
stage 4.
Exponent () of inverse-time
41 k_Exponent_InvROC4 0.01~10 0.01
ROC protection stage 4.
0: disable Logic setting of enabling/disabling
42 En_ROC4 0, 1
1: enable ROC protection stage 4.
Logic setting of enabling/disabling
0: disable
43 En_Harm_Blk_ROC4 0, 1 function of harmonic blocking
1: enable
ROC stage 4.
Logic setting of selecting control
mode of zero-sequence
44 Opt_Dir.RD_Ctrl_ROC4 0~2 1
directional element to stage OC
protection stage 4.
Tripping logic setting of ROC
45 TrpLog_ROC4 0000~FFFF
protection stage 4.
Logic setting of selecting
46 Opt_Characteristic_ROC4 0, 1 1 characteristic of ROC protection
stage 4.
VEBI_ROC_XXX Logic setting of enabling ROC
0: disable
47 (XXX=HVS, MVS, LVS, 0, 1 protection of the corresponding
1: enable
CW) side.
The method for configuring overcurrent settings varies with the need and wiring mode.
Where:
K br is the branching coefficient of the zero sequence current, which is equal to ratio of zero
sequence current passing through this protection equipment to passing through the faulty line
during an earth fault at the end of protected section of stage 1 of residual overcurrent
protection of the power line. Maximum value among various operation conditions being taken.
I op.o is the setting (secondary value) of the related stage of coordinating zero-sequence
2) The setting is set to ensure enough sensitivity of the protection during a fault at the local side
busbar.
Where:
Imin is the minimum zero-sequence current value during a short-circuit fault at the local side
bus.
If the setting [I_ROCn] is used in inverse-time ROC protection, the setting should be configured as
follows.
Inverse-time ROC protection coordinates with inverse-time ROC protection of a power line, so the
setting is set according the following formular.
Where:
1) The time delay of zero-sequence overcurrent protection coordinates with the corresponding
line zero-sequence protection. Following equation is recommended:
t = t max + t
Where:
tmax is the maximum operating time delay of coordinated stage of the line zero-sequence
overcurrent protection.
t n1 t n t
Where:
3) If stage n OC protection is used as instant OC, the setting can be set as “0”.
Recommended value: when no coordination is required, the minimum operating time can be set as
2s, with other time delays amplified in sequence.
This logic setting is used to enable or disable some stage of zero-sequence overcurrent
protection.
0”disable the protection; 1”enable the protection.
11. [k_BaseTime_InvROCn] (n=1, 2, 3, 4)
If stage n of inverse-time ROC protection coordinates with a line, the setting should be set equal to
the base time of inverse-time ROC protection of the line.
If stage n of inverse-time ROC protection is used independently, recommended value: 0.05s~3.2s
12. [t_MinDly_InvROCn] (n=1, 2, 3, 4)
the exponent ( ) of stage n of inverse-time ROC protection, which are set according to the model
of inverse-time ROC protection. Parameters of different models of inverse-time ROC protection
supported by the relay are shown in the table below.
Extremely Inverse 2 80
1. [k_Harm_Blk_ROC]
[Opt_Dir_Ctrl_ROCn] (n=1, 2, 3, 4)
This is the logic setting of selecting control mode of directional element to stage n of ROC
protection.
“0”: control function disabled.
“1”: protect transformer.
“2”: protect power system.
If only one stage of ROC protection is enabled, it is recommend that this stage not be controlled by
zero-sequence directional element.
2. [En_Harm_Blk_ROCn] (n=1, 2, 3, 4)
This is the logic setting of enabling some stage of ROC protection to be blocked by harmonics.
If there is no special requirement, it is recommend to be set as “0”.
“0”: the blocking function is disabled; “1”: the blocking function is enabled.
Output signals of zero-sequence overcurrent protection are list in the following table.
Three overvoltage protection elements of HV, MV, and LV sides are provided with totally same
configuration.
Criteria:
Where:
[V_OV1] and [V_OV2] are respectively the voltage settings of stage 1 and stage 2 of definite-time
overvoltage protection of corresponding side.
The pickup of this fault detector will enable definite-time overvoltage protection of corresponding
side.
When phase voltage of one side is greater than base voltage setting [I_OVn] (n=1 or 2), the fault
detector picks up to enable stage n (n=1 or 2) of inverse-time overvoltage protection at relevant
side.
There are two stages of overvoltage protection are equipped for each side of transformer, which
can be definite-time or inverse-time overvoltage protection by configuring logic setting
[Opt_Characteristic_OVn].
Overvoltage protection has two modes for selection according to the logic setting [Opt_Mode_OV].
If [Opt_Mode_OV] is set as “0”, when the maximum phase voltage satisfies operation
equation of overvoltage protection, the protection operates after its time delay.
If [Opt_Mode_OV] is set as “1”, when three phase voltage all satisfy operation equation of
overvoltage protection, the protection operates after its time delay.
Two operation criteria of definite-time overvoltage protection are as follows, which of them is
selected depending on the logic setting [Opt_Mode_OV].
U a [V _ OVn]
U b [V _ OVn]
(Equation 3.11-3)
U c [V _ OVn]
Where:
[V_OVn]is the setting of stage n (n=1 or 2) of overvoltage protection of the corresponding side.
When [Opt_Mode_OV] is set as “0”(Equation 3.11-2) is selected as operation equation, and when
[Opt_Mode_OV] is set as “1”, (Equation 3.11-3) is selected.
Inverse delay characteristics (IDMT) defined in IEC60255-3 are adopted, which formula is shown
as follows.
Kt
t(U ) Tp
U
( ) 1 (Equation 3.11-4)
Up
Where :
U p is base voltage (also called voltage limit), i.e. setting [V_OCn] (n=1 or 2).
User can get different inverse delay characteristic curves by configuring above settings, and four
common inverse delay characteristics with parameters are list in the following table.
Logic schemes of overvoltage protection of each side are same, and that of HV side is taken as an
example to show the logic diagram.
U _ max
U a ,U b ,Uc
Where:
Flg_VTS_HVS is the internal flag indicating that VT circuit failure of HV side is distinguished.
HVS :[Opt_Mode_OV] is the logic setting of selecting operation criterion of overvoltage protection.
U _ max
U a ,Ub ,U c
Where:
3.11.4 Setting
Setting explanation
[V_OVn] is the voltage setting of stage n of definite-time overvoltage protection or base voltage
If the setting [V_OVn] is used as current setting of definite-time OV protection, it shall be set
according to the equipment affordability, generally:
U op (1.3 ~ 1.5)U n
Where:
U n is the secondary rated phase voltage value. In case of multi stages to be used, the
U n U n
recommended maximum value is 1.3 and the value differential is 0.2 .
If the setting [I_OVn] is used in inverse-time OV protection, the setting should be configured as
follows.
U op K P *U max
Where:
U max is the minimum voltage under which the equipment can operate for a long term.
2. [t_DefOVn] (n=1, 2)
The time delay of stage 1 of definite-time overvoltage protection shall be set according to the
equipment affordability, and the recommended value is 0.3s~1s. In case of multi stages to be used,
the recommended maximum value is 0.3s and the time differential is 0.5s.
3. [k_BaseTime_InvOVn] (n=1, 2)
This is the base time ( T p ) of inverse-time OV protection, and it shall be set according to the
equipment affordability, and the recommended setting value is 0.05s~3.2s.
4. [t_MinDly_InvOVn] (n=1, 2)
This is the minimum delay of stage n of inverse-time OV protection.
Recommended value: 0.3s.
[k_TimeMulti_InvOVn] and [k_Exponent_InvOVn] are respectively the time multiplier ( Kt ) and the
exponent ( ) of stage n of inverse-time OV protection, which are set according to the model of
inverse-time ROC protection. Parameters of different models of inverse-time OV protection
supported by the relay are shown in the table below.
Extremely Inverse 2 80
6. [En_OVn] (n=1, 2)
This logic setting is used to enable or disable some stage of phase overvoltage protection.
This is the logic setting of selecting operation criteria of overvoltage protection, which shared by
“0": when the maximum phase voltage satisfies operation equation of overvoltage protection, the
protection operates after its time delay.
“1”: when three phase voltage all satisfy operation equation of overvoltage protection, the
protection operates after its time delay.
8. [TrpLog_OVn] (n=1, 2)
The tripping logic setting is used to specify which breakers will be tripped when stage n of phase
overvoltage protection operates. Please refer to the description of the setting [TrpLog_Diff] in
section 3.2.5 for details.
This setting is the VEBI setting of enabling phase overvoltage protection of some side. Please
refer to the setting [VEBI_Diff] in section 3.2.5 for details
Three zero-sequence overvoltage protection elements of HV, MV, and LV sides are provided with
totally same configuration.
Operation criteria:
Where:
[V_ROV1] and [V_ROV2] are respectively the voltage settings of stage 1 and stage 2 of
zero-sequence overvoltage protection of the corresponding side.
The pickup of the fault detector will enable definite-time zero-sequence overvoltage protection at
the relevant side.
When zero-sequence voltage of one side is greater than base voltage setting [I_ROVn] (n=1 or
2), the fault detector picks up to enable stage n (n=1 or 2) of inverse-time zero-sequence
overvoltage protection at relevant side.
There are two stages of zero-sequence overvoltage protection are equipped for each side of
transformer, which can be definite-time or inverse-time zero-sequence overvoltage protection by
configuring logic setting [Opt_Characteristic_ROVn].
Where:
[V_ROVn] is the voltage setting of stage n (n=1, 2) of zero-sequence overvoltage protection of the
corresponding side.
Inverse delay characteristics (IDMT) defined in IEC60255-3 are adopted, which formula is shown
as follows.
Kt
t(U ) Tp
U (Equation 3.12-3)
( ) 1
Up
Where :
U p is base voltage (also called voltage limit), i.e. setting [V_ROVn] (n=1 or 2).
User can get different inverse delay characteristic curves by configuring above settings, and four
common inverse delay characteristics with parameters are list in the following table.
Where:
3U0 is t3U0 is the zero-sequence voltage from the broken-delta VT of one side.
HVS:[En_ROVn] is the logic setting of enabling stage n (n=1 or 2) of ROV protection of HV side.
HVS:[I_OVn] is the base voltage of stage n (n=1 or 2) of inverse-time ROV protection of HV side.
3.12.4 Setting
Setting explanation
2. [t_DefROVn] (n=1, 2)
This is the time delay of some stage of definite-time ROV protection, and it shall be set to keep the
stage protection away from the influence of transient characteristic and the recommended value is
0.3s~0.5s. In case of multi stages to be used, the minimum value will be considered to be 0.3s,
and the voltage differential shall be 0.5s.
This is the base time ( T p ) of inverse-time ROV protection, and it shall be set according to the
the exponent ( ) of stage n of inverse-time ROV protection, which are set according to the model
of inverse-time ROV protection. Parameters of different models of inverse-time ROV protection
supported by the relay are shown in the table below.
Extremely Inverse 2 80
The tripping logic setting is used to specify which breakers will be tripped when stage n of
zero-sequence overvoltage protection operates. Please refer to the description of the setting
[TrpLog_Diff] in section 3.2.5 for details.
This setting is the VEBI setting of enabling zero-sequence overvoltage protection of some side.
Please refer to the setting [VEBI_Diff] in section 3.2.5 for details
Input signals of zero-sequence overvoltage protection are list in the following table.
Three undervoltage protection elements of HV, MV, and LV sides are provided with totally same
configuration.
The pickup of this fault detector will enable definite-time undervoltage protection of corresponding
side, which operation criterion is as follows.
Where:
[V_UV1] and [V_UV2] are the voltage settings of stage 1 and stage 2 of definite-time overvoltage
protection of corresponding side respectively.
The calculation of the fault detector of undervoltage protection will not be carried out when any of
the following three conditions is met.
1) The positive-sequence voltage is greater than 30V or negative-sequence voltage is less than
8V.
2) VT is out of service.
Two stages of zero-sequence overvoltage protection are equipped for each side of transformer,
and the operation equation is as follows.
Where:
Where:
Undervoltage protection can be blocked by the voltage slip speed (du/dt). If the logic setting
[En_du/dt_UVn] (n=1 or 2) is set as “1”, when (Equation 3.13-2) and (Equation 3.13-3) are met, it
is decided that a fault occurred and the corresponding stage of undervoltage protection is blocked
at the same time for the purpose of to wait for other related protections operating. If the logic
setting is set as “0”, when (Equation 3.13-2) and (Equation 3.13-3) are met, the stage of
undervoltage protection is released to operate. The blocking signal will not reset until the system
voltage recovers i.e. the system voltage is greater than the setting [V_Recov].
Logic schemes of undervoltage protection of each side are same, and that of HV side is taken as
Where:
Flg_VTS_HVS is the internal flag indicating that VT circuit failure of HV side is distinguished.
[En_du/dt_UVn] is the logic setting of enabling du/dt blocking stage n (n=1, or 2) of undervoltage
protection.
Flg_FD_UV_HVS is the internal flag indicating that operation criterion of UV protection is satisfied.
3.13.4 Setting
Setting explanation
1. [V_Recov]
The setting is the lowest voltage threshold of fault recovery, i.e. the recognized normal level of voltage
after a fault is eliminated.
After some stage of undervoltage protection is blocked by du/dt, the stage undervoltage protection will
not be released to operate unless that system voltage increases to be greater than the setting
[V_Recov].
side)
2. [ du/dt_UV]
The setting of du/dt blocking undervoltage protection is set to avoid the undervoltage protection
operating during a short-circuit fault. When the variation of system voltage is greater than the
setting, some stage of undervoltage protection can be blocked if the corresponding logic setting of
the stage protection is enabled.
This is the voltage setting of stage n (n=1, 2) of undervoltage protection, which should be set
according to voltage control strategy.
This is the time delay of stage n (n=1, 2) of undervoltage protection, which should be set according
to voltage control strategy.
This is the logic setting of enabling stage n (n=1, 2) of undervoltage protection, which should be
set according to he actual number of load shedding stage.
This is the logic setting of enabling stage n (n=1, 2) of undervoltage protection being blocking by
du/dt, which should be set according to requirements.
Four thermal overload protection elements of HV, MV, and LV sides and common winding are
provided with totally same configuration.
When phase current of one side is greater than base current setting [Ib_ThOvLd], the fault
detector picks up to enable thermal overload protection at relevant side.
Three thermal overload protection elements with the same characteristic and independent settings
are provided for each side of transformer, and their thermal time characteristic defined in IEC
I 2 I 2p
t
ln (Equation 3.14-1)
I ( k
2
IB ) 2
Where:
Thermal overload protection provides tripping function, sending alarm signal function and sending
blocking signal for closing breaker, and the protection can be enabled or disabled by the logic
setting [En_ThOvLd]. When the heat accumulation of winding is greater than setting
[k_Trp_ThOvLd] or [k_Alm_ThOvLd], the protection operates to trip circuit breaker or to send
alarm signal. After thermal overload protection operates to trip, heat accumulation can not
dissipate in short time, so two contacts “BO_ThOvLd_Blk_ClsCB”are provided to block closing
circuit breaker. When heat accumulation value is less than 0.7x[k_Trp_ThOvLd], the contacts drop
off.
NOTE: When binary input [EBI_ThemOvLd_XXX] ( XXX represents HVS, MVS, LVS etc.)
Logic schemes of thermal overload protection of each side are same, and that of HV side is taken
as an example to show the logic diagram.
Where:
Flg_FD_ThOvLd_HVS is the internal flag indicating that the fault detector of thermal overload
3.14.4 Setting
Table 3.14-1 Settings of thermal overload protection (HVS, MVS, LVS, CW)
Setting explanation
1. [Ib_ThOvLd]
This is the base current ( I B ) of thermal overload protection, which is generally recommended to
2. [ThTime_ThOvLd]
This the thermal time constant ( )decided by the thermal characteristic of the transformer
winding.
3. [k_Trp_ThOvLd]
This is the hermal overload coefficient ( k ) for tripping shall be set according actual requirements,
4. [k_Alm_ThOvLd]
This is the thermal overload coefficient ( k ) for alarming shall be set according to actual
5. [En_ThOvLd]
6. [TrpLog_ThOvLd]
The tripping logic setting is used to specify which breakers will be tripped when thermal overload
protection operates. Please refer to the description of the setting [TrpLog_Diff] in section 3.2.5 for
details.
This setting is the VEBI setting of enabling thermal overload protection of some side. Please refer
to the setting [VEBI_Diff] in section 3.2.5 for details.
Output signals of thermal overload protection are list in the following table.
Three breaker failure protections of HV, MV, and LV sides are provided with totally same
configuration. When trip signal from those protection relay is received, the protection operate to
trip each side breaker of transformer.
When operation criteria (refer to the following section) are satisfied, the corresponding fault
detector picks up.
When the binary input of external tripping is energized and current element picks up, a trip
command will be issued after a delay to trip circuit breakers at each side of transformer.
Where:
Where:
Where:
Where:
It is the floating threshold value which will arise automatically and gradually according to
increasing of the output of deviation component. In order to ensure the threshold voltage is
slightly greater than the unbalance voltage, multiple 1.25 of the deviation component is
reasonable.
I th is the fixed threshold of 0.1 In and does not need to be set on site.
When the binary input [BI_ExtTrp_BFP] is keeping being energized for 10s, the alarm signal
[Alm_BI_ExtTrp_BFP] is issued with blocking breaker failure protection.
Logic schemes of breaker failure protection of each side are same, and that of HV side is taken as
an example to show the logic diagram.
I _ max
I _ max
I 1 . 25* I t I th
Where:
HVS: [I_OC_BFP] is the current setting of breaker failure protection of the corresponding side.
[BI_ExtTrp_BFP_HVS] is the binary input of external tripping signal to initiate breaker failure
protection of HV side.
Flg_FD_BFP_HVS is the internal flag indicating that fault detector of breaker failure protection of
HV side picks up.
3.15.4 Setting
Setting explanation
1. [I_OC_BFP]
This is phase current setting of breaker failure protection, and it shall be set greater than the
normal load current.
I op Ie
Recommended value: = 1.1×
2. [I_ROC_BFP]
I op0 In
Recommended value: = 0.1×
3. [I_NegOC_BFP]
I op2 In
Recommended value: = 0.1×
4. [t_BFP]
If other protection operation contacts are connected to PCS-978 to initiate breaker failure
protection, the time delay shall be greater than the maximum time of circuit beaker being tripped.
Recommended value: 2s~2.5s.
If breaker failure protection contacts from other protection are connected to PCS-978, the contact
can be used to intertrip circuit breakers of each side of transformer and the setting can be set as
0.05s.
5. [En_OC_Ctrl_BFP]
This is the logic setting of enabling phase current element to control breaker failure protection.
“0”: disabling the control element; “1”: enabling the control element.
6. [En_NegOC_Ctrl_BFP]
This is the logic setting of enabling negative-sequence current element to control breaker failure
protection.
“0”: disabling the control element; “1”: enabling the control element.
7. [En_ROC_Ctrl_BFP]
This is the logic setting of enabling zero-sequence current element to control breaker failure
protection.
“0”: disabling the control element; “1”: enabling the control element.
8. [En_DPFC_Curr_Ctrl_BFP]
This is the logic setting of enabling DPFC current element to control breaker failure protection.
“0”: disabling the control element; “1”: enabling the control element.
9. [En_BFP]:
This is the logic setting of enabling breaker failure protection, which not only can be used for
independent breaker failure protection, but also can be used to intertrip circuit breakers of each
side of main transformer. If this protection is used as breaker failure protection, it only can be used
at one side with single circuit breaker. If there are two or more circuit breakers at one side, then
this protection can not be used as independent breaker failure protection. It has no restriction
when being used as intertripping function.
8. [TrpLog_BFP]
The tripping logic setting is used to specify which breakers will be tripped when breaker failure
protection operates. Please refer to the description of the setting [TrpLog_Diff] in section 3.2.5 for
details.
This setting is the VEBI setting of enabling breaker failure protection of some side. Please refer to
the setting [VEBI_Diff] in section 3.2.5 for details.
Output signals of breaker failure protection are list in the following table.
Four overload alarm elements of HV, MV, and LV sides and common winding (CW) are provided
with totally same configuration.
3.16.1 Principle
When following criterion is satisfied, overload alarm element operates to send its alarm
message after the corresponding delay and output contacts pick up at the same.
Where:
Logic schemes of overload alarm element of each side are same, and that of HV side is taken as
an example to show the logic diagram.
I _ max
Where:
I _ max
is the maximum value of three-phase current of HV side.
3.16.3 Setting
Table 3.16-1 Settings of overload alarm element (HVS, MVS, LVS, CW)
Setting explanation
1. [I_Alm_OvLdn] (n=1, 2)
The current setting of overload alarm element of some side shall be greater than the normally
operating load current of the transformer.
Iop K * Ie
,
Where
2. [t_Alm_OvLdn] (n=1, 2)
This is the time delay of some stage of overload alarm element of some side.
The setting is set according to actual requiems and recommended value 6s~10s.
3. [En_Alm_OvLdn] (n=1, 2)
The logic setting is used to enable or disable some stage of overload alarm element of some side.
Four overload for initiating cooler elements of HV, MV, and LV sides and common winding (CW)
are provided with totally same configuration.
3.17.1 Principle
When following criterion is satisfied, overload for initiating cooler element operates to send its
alarm message after the corresponding delay and output contacts pick up at the same.
Where:
[I_InitCooln_OvLd] is the current setting of stage n (n=1, or 2) of overload for initiating cooler.
Logic schemes of overload for initiating cooler element of each side are same, and that of HV side
is taken as an example to show the logic diagram.
I _ max
Where:
I _ max
is the maximum value of three-phase current of HV side.
HVS:[t_InitCooln_OvLd] is the delay of stage n (n=1 or 2) of overload for initiating cooler element
of HV side.
3.17.3 Setting
Table 3.17-1 Settings of overload for initiating cooler element (HVS, MVS, LVS, CW )
Setting explanation
1. [I_InitCool_OvLdn] (n=1, 2)
This is the current setting of some stage of overload for initiating cooler element of some side,
which is set as followings:
Iop K * Ie
,
Where
2. [t_InitCool_OvLdn] (n=1, 2)
This is the time delay of some stage of overload for initiating cooler element of some side.
3. [En_InitCool_OvLdn] (n=1, 2)
The logic setting is used to enable or disable of some stage of overload for initiating cooler
element of some side.
“0”disable the initiating cooler element; “1”: enable the initiating cooler element.
The setting shall be set according to the actual cooling equipment and if an air cooler is equipped,
the overload for initiating cooler element is recommended to be enabled.
Output signals of overload for initiating element are list in the following table.
Four overload for blocking on-load tap change (OLTC) elements of HV, MV, and LV sides and
common winding are provided with totally same configuration.
3.18.1 Principle
When following criterion is satisfied, overload for blocking on-load tap change element operates to
send its alarm message after the corresponding delay and output contacts pick up at the same.
Where:
Logic schemes of overload for blocking OLTC element of each side are same, and that of HV side
is taken as an example to show the logic diagram.
I _ max
Where:
I _ max
is the maximum value of three-phase current of HV side.
3.18.3 Setting
Table 3.18-1 Settings of overload for blocking OLTC element (HVS, MVS, LVS, CW)
Setting explanation
1. [I_BlkOTLC_OvLd]
This is the current setting of overload for blocking OLTC of some side, which is set as followings:
Iop K * Ie
,
Where
2. [t_BlkOLTC_OvLd]
This is the time delay of overload for blocking OLTC element of some side.
3. [En_BlkOLTC_OvLd]
The logic setting is used to enable or disable of overload for blocking OLTC element of some side.
“0”disable the initiating cooler element; “1”: enable the initiating cooler element.
Output signals of overload for blocking OLTC are list in the following table.
Four zero-sequence overvoltage alarm elements of HV, MV, and LV sides and common winding
are provided with totally same configuration.
3.19.1 Principle
When following criterion is satisfied, zero-sequence overvoltage alarm element operates to
send its alarm message after the corresponding delay and output contacts pick up at the
same.
Where:
Logic schemes of zero-sequence overvoltage alarm element of each side are same, and that of
HV side is taken as an example to show the logic diagram.
Where:
3.19.3 Setting
Table 3.19-1 Settings of zero-sequence overvoltage alarm element (HVS, MVS, LVS, CW)
Setting explanation
1. [V_Alm_ROV]
This is voltage setting of zero-sequence overvoltage alarm element of some side, when LV side is
connected to an ungrounded system.
2. [t_Alm_ROV]
This is the time delay of zero-sequence overvoltage alarm element of some side, which is set as
0.2~5s.
3. [En_Alm_ROV]
The logic setting is used to enable or disable zero-sequence overvoltage alarm element of some
side.
When the side is connected to ungrounded system, it is recommended to enable the element.
Output signals of zero-sequence overvoltage alarm element are list in the following table.
Four zero-sequence overcurrent alarm elements of HV, MV, and LV sides and common winding
are provided with totally same configuration.
3.20.1 Principle
Where:
Logic schemes of zero-sequence overcurrent alarm element of each side are same, and that of
HV side is taken as an example to show the logic diagram.
Where:
3.20.3 Setting
Table 3.20-1 Settings of zero-sequence overcurrent alarm element (HVS, MVS, LVS, CW)
Setting explanation
1. [V_Alm_ROC]
This is current setting of zero-sequence overcurrent alarm element of some side, which shall be
set according to system zero-sequence network structure and the actual measured maximum
zero-sequence current during normal operation.
The recommended value for the setting is 0.5 times minimum current setting of zero-sequence
overcurrent protection of the corresponding side and shall be greater than 0.1 I n ( In is the
2. [t_Alm_ROC]
This is the time delay of zero-sequence overcurrent alarm element of some side, which is set as
10s.
3. [En_Alm_ROC]
The logic setting is used to enable or disable zero-sequence overcurrent alarm element of some
side.
The zero-sequence overcurrent alarm element is not recommended to be enabled for the system
the load of which is long-time imbalance.
3.21.1 Principle
A voltage element is equipped to collect three-phase voltage and zero-sequence voltage of each
side and to carry out calculation, and then send the calculation result to other protective elements
which need that information. Voltage element includes single-phase and three-phase voltage
inputs.
If one of following two criteria is met and there is no any one fault detector picked up, VT circuit
abnormality alarm will be issued after 10s. The abnormality alarm will be reset after 10s if
equipment returns to normal condition.
1) Positive sequence voltage is less than 30 V and any phase current is greater than 0.04 In.
2) Positive sequence voltage is less than 30 V and the breaker is in closed position;
3) The negative-sequence voltage is greater than 8 V and zero-sequence voltage is grater than
6V.
In the duration of abnormality, action of each element related to voltage is decided by the relevant
logic settings as mentioned in above sections.
NOTE: When VT of some side is out of service, criteria of VT circuit failure on that side
NOTE: For the secondary phase-to-phase voltage of VT is equal to 110V, the threshold
Input signals of current element are list in the following table. The name of each group current
input can be defined by user through PCS-PC software, and the related alarm message and
sampled value change correspondingly.
Output signals of current element are list in the following two tables.
3.22.1 Principle
A current element is equipped to collect three-phase voltage and zero-sequence voltage of each
side and to carry out calculation, and then send the calculation result to other protective elements
which need that information. Current element includes single-phase and three-phase voltage
inputs.
When the negative-sequence current of some side is greater than 0.06In, CT circuit abnormality
alarm will be issued after 10s, and be reset after 10s if equipment returns to normal condition.
Input signals of current element are list in the following table. The name of each group current
input can be defined by user through PCS-PC software, and the related alarm message and
sampled value change correspondingly.
Tripping output element consists of tripping matrix of protection element and programmable
tripping output element. Each protection element has its corresponding tripping logic setting used
to configure tripping output contacts of each element, and 10 programmable tripping output
elements are equipped for visualization programming of user level.
Tripping pulse of protection equipment shall be broadened and held to ensure circuit breakers are
tripped reliably after a tripping command is issued, which is realized by by tripping output element.
After any protection element operates, 120ms tripping pulse is issued at first. Then equipment
detects whether operation element drops off or not, if the protection element dropps off, tripping
pulse will be gone after 120ms, and if not, tripping pulse will be broadened and held until the
element drops off.
Each protection element has its corresponding tripping logic setting used to configure tripping
output contacts of each element, and total 10 groups of tripping output contacts can be controlled
by tripping logic settings. Therefore, user can configure the tripping output contacts of each
protection element individually though the corresponding tripping logic setting, and following figure
shows the tripping matrix map of protection element.
1 2 3 4 5 6 7 8 9 10
[TrpLog_Diff]
HVS:[TrpLog_REF]
MVS:[TrpLog_REF]
LVS:[TrpLog_REF]
[TrpLog_OvExc]
[TrpLog_MR1]
HVS:[TrpLog_OC1]
HVS: [TrpLog_ROC1]
10 groups of independent tripping output contacts can be defined to trip HV side, MV side, and
LVS side etc. Each group of tripping contacts can correspond to certaint amount of contacts on
binary output plug-in modules.
Tripping logic settings are used to specify which breakers will be tripped when some protection
element operates. This logic setting comprises 16 binary bits as follows and is expressed by a
hexadecimal number of 4 digits from 0000H to FFFFH. The tripping logic setting of the equipment
is specified as follows:
bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
TrpOutp10
TrpOutp9
TrpOutp8
TrpOutp7
TrpOutp6
TrpOutp5
TrpOutp4
TrpOutp3
TrpOutp2
TrpOutp1
Function
N/A
N/A
N/A
N/A
N/A
N/A
NOTE: “TrpOutput1”just means to drive 1st group of tripping output contacts to pickup
The bit corresponding to the breaker to be tripped shall be set as“1”and other bits shall be “0”.
For example, if differential protection operates to make “TrpOutp1”, “TrpOutpu2”, “TrpOutp3”
contacts pickup, the bit “1”and bit “2”and bit “3”positions shall be filled with “1”and other bit
positions shall be filled with “0”. Then a hexadecimal number 0007H is formed as the tripping
output logic setting, i.e. [TrpLog_Diff] shall be set as “0007H”.
Please note that tripping output logic settings of the equipment have to be set on basis of
application-specific drawings.
10 programmable tripping output elements with inputs, outputs and settings are provided for
visualization programming of user level.
Users can program output of existing elements by visualization programming software if existing
tripping output matrixes of protection element provided by protective equipment can not meet
application requirements completely.
For example, if user need stage 1 of overcurrent protection of HV side operate to issue trip
command after its operation criterion is satisfied “AND”receiving a binary input which can be a
blocking signal from other protection equipment, users can complete the function configuration as
following steps.
1) Set tripping logic setting of stage 1 of overcurrent protection of HV side as “0”, i.e.
[TrpLog_Diff]=0000H.
3) Connect final logic programming output to input of programming tripping output elment.
4) Set corresponding programmable tripping logic setting to complete the function configuration.
Please refer to logic chapter for detailed operation steps.
3.23.4 Setting
Table 3.23-1 Settings of programmable tripping output element
Setting explanation
This is tripping logic setting of programmable tripping output element. If the programmable tripping
output element is used, please set the setting by referring to the setting [TrpLog_Diff] in section
3.2.5 for details, and if not, the setting is recommended to be set as 0000.
Output signals of programmable tripping output element are list in the following table.
3.24.1 Principle
In order to better support logic programming function, 20 intermediate variables are provided.
The user can distribute the middle results of logic programming to intermediate variables, and
use the intermediate variables to carry out other logic programming. Not only intermediate
variable display is supported by the equipment, but also its state change report is recorded by the
equipment.
The relay also provides some auxiliary functions, such as on-line data metering, binary input
status, event and disturbance recording, etc. All these make the relay meet the demands of the
modern power grid requirements.
Besides traditional binary inputs and outputs can be connected to PCS equipments, GOOSE
binary inputs and outputs are supported by PCS equipments. In a digital substation supporting
GOOSE, GOOSE interfaces are connected to switches in the process level. A GOOSE.txt file
recording the related information of GOOSE input and output is exported at the same time when a
CID file is exported from a SCD file through a software tool. After the equipment parses the
GOOSE.txt, it sends out signals desired by other equipment on the network and receives its
desired signals (binary inputs). Because only an optical fiber is needed for the connection between
one equipment and other equipments, cables used in substation construction are reduced greatly.
During the normal operation of equipment, heart beat messages are sent out constantly for the
receiver detection, which improves the reliability of transmitting GOOSE si gnals. After PCS
equipment parses the GOOSE.txt file, it detects the desired heart beat messages according to
GOOSE control blocks. When those messages are not received during 2xTATL (TATL: Time Allow
to Live), the equipment will issue the alarm of link disconnection of the corresponding GOOSE
control block. Besides, the equipment checks the number of received data from a GOOSE control
block, and if the number is not consistence with the GOOSE.txt, an alarm message will be issued
at once.
Each output data is equipped with a sending VEBI setting. PCS protection equipment is equipped
with an output GOOSE control block associated with a GOOSE data set, which can meet the
requirement of most substations and also can be customized according to user needs. PCS
equipment supports maximum 64 GOSSE control blocks.
3.25.2 Setting
Setting explanation
These settings are displayed in the menu ”SETTINGS”-> “EQUIP SETTINGS”. When there is
an abnormality network communication, the binary input [GBI_XX] (XX=1, 2, 3, 4) is set as the
corresponding default value.
These settings are displayed in the menu “SETTINGS” -> “EQUIP DESCRON”. When a
receiving GOOSE binary input is defined with a specific name, its corresponding alarm signal will
be changed simultaneously, but the corresponding default setting and GOOSE binary input are
not changed.
These settings are called GOOSE functional VEBI settings and recorded as binary input
change report, which can be located in the menu "SETTINGS” -> “GOOSE VEBI
SETTINGS”.
These settings are called GOOSE VEBI settings and recorded as binary input change
reports, which can be located in the menu "SETTINGS”-> “GOOSE VEBI SETTINGS”.
Input signals for GOOSE function module are list in the following table.
Output signals of GOOSE function module are list in following two tables.
Handling suggestion:
4. Please check the GOOSE configuration file and the network. (No.6)
Though the protection system is in non-operating state under normal conditions, it is waiting for a
power system fault to occur at any time and must operate for the fault without fail. When
equipment is in energizing process before the LED “HEALTHY”is on, the equipment needs to be
checked to ensure no errors. Therefore, the automatic supervision function, which checks the
health of the protection system when startup and during normal operation, plays an important role.
The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.
In case a fatal fault is detected during automatic supervision, the equipment will be blocked out. It
means that relay is out of service. Before you must re-energize the relays or reset CPU module
and MON module to make relay back into service, please find out the cause and inform the
factory.
When a failure is detected by the automatic supervision, it is followed with an LCD message, LED
indication and alarm contact outputs. At the same time event recording will record the failure alarm
which can be viewed in event recording report and be printed.
All chips on each module are monitored to ensure whether they are damaged or have errors. If
any one of them is detected damaged or having error, the corresponding alarm signal
[Alm_DSP_ProtBrd] or [Alm_DSP_FDBrd] is issued with equipment being blocked.
AC current and voltage samplings of protection DSP module and fault detector DSP module are
monitored and if the samples are detected to be wrong or inconsistent, an alarm [Alm_Sample] will
be issued and the relay will be blocked.
This relay has 10 setting groups, while only one is active at the same time. The settings of active
setting group are checked to ensure they are reasonable. If settings are checked to be
unreasonable or out of setting scopes, a corresponding alarm signal will be issued, and the
protective device is also blocked.
If a fault detector on protection or fault detector DSP module keeps picking up for 10s, the
corresponding alarm signal [Alm_PersistFD_ProtBrd] or [Alm_PersistFD_FDBrd] will be issued
without equipment being blocked.
If the operating fault detector on fault detector DSP module is not inconsistent with the tripping
element on protection module, the alarm signal [Alm_InconsistFD] is issued without equipment
being blocked.
Zero point of voltage and current may drift influenced by variation of temperature or other
environment factors. The equipment continually automatically traces the drift and adjusts it to
normal value.
Module configuration is checked automatically during equipment initialization, if plug -in module
configuration is not consistent to the design drawing of an applied -specific, the alarm signal
[Alm_BoardConfig] is issued with the equipment being blocked.
All the alarm signals issued during secondary circuit supervision have being introduced in chapter
“Description of Operation Theory”, so please refer to sections “Current Element”and “Voltage
Element”of the chapter “Description of Operation Theory”for details.
The VTS logic in the relay is designed to detect the VT secondary circuit to ensure that voltage
measurement is the actual value of power system. When VT failure is detected, equipment can
automatically adjust the configuration of protective elements whose stability would be affected by
voltage element to avoiding maloperation.
The CTS function will be always processed all the time, which includes following two aspects
The CTS logic in the relay is designed to detect the CT secondary circuit to ensure that current
measurement is the actual value of power system. The main purpose of the CTS function is to
detect faults in the secondary circuits of CT and avoid influence on the operation of corresponding
protection functions.
NOTE : Following alarm messages and corresponding LED indicators are fixed in
equipment software. Besides, there are other programmable LED indicators configured
according to user requirement.
Equipment hardware circuits and software working conditions are always monitored by the relay. If
any abnormality occurs, the corresponding alarm message will be issued on the LCD of the
equipment.
When some light failures are detected, part of protection functions probably be disabled and
others can still work. Some server failures of hardware or software will result in the equipment
being blocked and the contacts of equipment failure will operate at same time. During that
condition, the protection relay has to be out of service for maintenance.
NOTE:If alarm signal is issued with equipment being blocked, please try to make a fault
diagnosis by referring the issued alarm messages but not to simply reboot or re-power the
relay. If user cannot find the failure reason on site, please inform manufacturer for
maintenance.
Handling suggestion:
5. No special treatment is needed, and only wait for the completion of testing.(No.1)
6. Please inform the manufacturer or agent for maintenance. After the abnormality is eliminated,
“ALARM”LED will go off automatically and equipment returns to normal operation. (No.2)
7. Please check secondary circuits and protection settings. After the abnormality is eliminated,
“ALARM” LED will go off automatically and equipment returns to normal operation.
(No.3~No.4)
8. Please check if the power supply circuit of BI module is connected correctly. After the
abnormality is eliminated, “ALARM”LED will go off automatically and equipment returns to
normal operation. (No.5)
9. Please checking setting value scope and re-set the corresponding settings. After the
abnormality is eliminated, the equipment can returns to normal operation by re-energizing it.
(No.6)
10. No special treatment is needed. The equipment will return to normal operation after the
completion of setting modification. (No.7)
11. Please check whether the configuration of plug-in module is consistent to the designing
drawing of an applied-specific project, or inform the manufacturer or agent for maintenance.
After the abnormality is eliminated, the equipment can returns t o normal operation by
12. Please inform the manufacturer or agent for maintenance. After the abnormality is eliminated,
the equipment can returns to normal operation by re-energizing it. (No.9~No.14)
During the equipment normal operation, VT and CT circuit and some binary input circuits are
always monitored by the relay. If any abnormality of them occurs or any alarm element operates,
the corresponding alarm message will be issued on the LCD of the equipment without blocking
equipment.
When this kind of alarm messages are issued, user need to find the abnormality reason, and then
take corresponding measures to eliminate the alarm message to make the equipment return to the
normal operation.
Handing suggestion:
1. Please check the corresponding CT secondary circuit. After the abnormality is eliminated,
“ALARM”LED will go off automatically and equipment returns to normal operation. (No.1,
No.9~No.15)
2. Please check the corresponding CT secondary circuit. After the abnormality is eliminated,
equipment can return to normal operation by energizing the binary i nput [BI_RstTarg].
(No.1~No.8)
3. Please check the corresponding sampling values and VT/ CT secondary circuit to find out the
reason resulting in the abnormality. If sample values of the equipment are not correct, please
inform the manufacturer or agent for maintenance, and if it is caused by the failure of the
VT/CT secondary circuit or primary system, please finish troubleshooting according to the
operating code of protection relay. (No.16~No.17)
6. Please check the secondary circuit of the corresponding binary input. (No.52~No.54)
The relay also provides some auxiliary functions, such as on-line data metering, binary input
status, event and disturbance recording, etc. All these make the relay meet the demands of the
modern power grid requirements.
5.2 Metering
The equipment performs continuous measurement of the analogue input quantities. The
measurement data shown below is displayed on the LCD of the relay front panel or on the local or
remote PC.
Equipment samples 24 points per cycle. Calculate the RMS value in each interval and LCD will be
updated every 0.5 second.
By navigating the path “SETTINGS”— >“SLD SETTINGS”, primary or secondary sampled values
can be selected to be displayed by configuring the setting [Opt_ DisplayValue]. User can view
these data on LCD by navigating the menu “VALUES”, or by PCS-PC software or SAS software.
1. RMS Value
Calculated value
Differential current and restraint threshold for conventional current differential protection
Zero-sequence currents and zero-sequence restraint thresholds for each REF protection
Winding differential current and restraint threshold for winding differential protection
2. Phase angle
Angle between corrected currents of each side for conventional current differential protection
Please refer to each protection element in the chapter “Description of Operation Theory”for
detailed sample value and phase angle,
5.3.1 Introduction
Event recording
Present recording
All the recording information except waveform can be viewed on local LCD or by printing.
Waveform must be printed or be extracted using PCS-PC software and a waveform software.
The equipment can store the latest the latest 1024 abnormality alarm reports, the latest 1024
binary input stage changing reports respectively. All the records are stored in non-volatile memory,
and when the available space is exhausted, the oldest report is automatically overwritten by the
latest one
An abnormality alarm being detected during relay self-check supervision or an alarm of secondary
circuit abnormality or protection alarm element will also be logged as individual events.
When binary input status changes, the change information will be displayed on LCD and logged as
binary input change report at the same time.
5.3.3.1 Application
Use the disturbance recorder to achieve a better understanding of the behavior of the power
network and related primary and secondary equipment during and after a disturbance. An analysis
of the recorded data provides valuable information that can be used to improve existing equipment.
This information can also be used when planning for and designing new installations.
5.3.3.2 Design
Disturbance recorder is consisted of tripping report and fault waveform. Disturbance recorder is
triggered by fault detector. The equipment can store 64 pieces of trip reports and waveforms in
non-volatile memory.
When protection operates, the operating information will be displayed on LCD and logged as trip
record at same time, which can be viewed in trip report. Here fault recording includes two kinds of
cases:
2) The fault detector element operates associated with the operation of protective elements.
The equipment can store 64 pieces of trip reports in non-volatile memory. If a new fault occurs
when 64 faults have been stored, the oldest will be overwritten by the latest one..
1) Sequence number
Each operation will be recorded with a sequence number in the report and displayed on LCD
screen.
The time resolution is 1 ms using the relay internal clock. Initiating date and time is when a fault
detector picks up. Relative time is the time when protection element operates to send tripping
signal after fault detector picks up.
3) Faulty phase
The faulty phase detected by the operating element is showed in the record report.
4) Trip mode
This shows the protection element that issues the tripping command. If no protection operates to
trip but only equipment fault detector picks up, fault report will record the title of fault detector.
MON module of the relay can store 64 pieces of fault waveform oscillogram in non-volatile memory.
If a new fault occurs when 64 fault waveform recorders have been stored, the oldest will be
overwritten by the latest one.
Each fault record consists of all analog and digital quantities related to protection, such as original
current and voltage, differential current, alarm elements, and binary inputs and etc.
Each time recording includes 2-cycle waveform before a fault detector pickup, and most 250
cycles can be recorded.
Present recording is used to record a piece of waveform of present operation equipment which
can be trigger manually on LCD of equipment or remotely through PCS-PC software. Recording
content of present recording is same to that of disturbance recording.
Each time recording includes 2-cycle waveform before triggering, and most 250 cycles can be
recorded.
The PCS-978 adopts 64-bit microchip processor CPU produced by FREESCALE as control core
for logic calculation and management function, meanwhile, adopts high-speed digital signal
processor DSP to be in charge of all the protection calculation. 24 points are sampled in every
cycle and parallel processing of sampled data can be realized in each sampling interval to ensure
ultrahigh reliability and safety of protection equipment.
The working process of the equipment is as follows: firstly, the current and voltage is converted
into small voltage signal and sent to protection calculation module (also called DSP module 1) and
fault detector calculation module (also called DSP module 2) respectively, and accesses into DSP
after being filtered and converted by AD. When MON module completes all the protection
calculation, the result will be sent to 64-bit CPU on MON module to be recorded. DSP module 1
carries out protection logic calculation, tripping output, and MON module completes SOE
(sequence of event) record, waveform recording, printing, communication between protection and
SAS and communication between HMI and CPU. The work process of fault detector calculation
module is similar to that of protection calculation module, and the only difference is, when fault
detector calculation module decides a fault detector picks up, only positive power supply of output
relay is switched on.
The PCS-978 is comprised of intelligent modules, except that few particular modules’position
cannot be changed in the whole device, the others like AI (analog input) module such as AC
current, AC voltage, DC current, and etc., and IO (input and output) module such as binary input,
tripping output, signal output, and etc can be flexibly configured according to the remained slot
positions.
MON module provides functions like management function, completed event record, setting
management, and etc.
DSP modules are totally the same, to carry out filtering, sampling and protection calculation
and fault detector calculation respectively.
AI module converts AC current and voltage to low voltage signals with current transformers
and voltage transformers respectively.
BI module provides binary input, and the binary is inputted via 24V/36V/110V/125V/
220V/250V opto-coupler (configurable).
BO signal module provides all kinds of signal output contact, including annunciation signal,
remote signal, fault and disturbance signal, operation abnormal signal and etc.
HMI module is comprised of LCD, keypad, LED indicator and test serial ports, and it is
convenient for user to perform human-machine interaction with equipment.
GOOSE Module (optional) is applied for realization of GOOSE level interlocking, and for
connection to ECVT with supporting IEC61850-9-1and IEC61850-9-2 protocols.
PCS -978
HEALTHY
ALARM TRANSFORMER PROTECTION
TRIP
ENT
NR1102D NR1156A NR1156A NR1504 NR1504 NR1521A NR1521A NR1521B NR1523B NR1301A
1 2 3 1 2 3 5V BJ
4 5 6 4 5 6 BJJ BSJ
1 COM1
2 BSJ1
3 BJJ 1
4 COM2
5 BSJ2
6 BJJ2
7 24 V
8 24VGND
9
10 DC+
11 DC-
12 FGND
BJJ BSJ
2 BSJ1
3 BJJ1
4 COM2
5 BSJ2
6 BJJ2
7 24 V
8 24VGND
9
10 DC+
11 DC -
12 FGND
optional
4U chassis has 16 slots, and the irremovable modules are power supply module, MON module
and DSP module.
DSP module 1
DSP module 2
MON module
PWR module
Figure 6.2-1 Rear view of fixed module position of 4U equipment
Besides the fixed four modules are shown in above figure, there are twelve slots can be flexibly
configured.
AI module, BI module and BO module can be configured at position between slot B04 to slot
07.
A DC current input module (also called DC AI module) can be configured at any slot between
slot B04 and slot B11, which can provide 6 DC current inputs.
If the slots from slot B04 to slot B11 are not used up, the BI module and BO module can be
configured at the rest slots.
BI module and BO module can be configured at any slot between slot B12 and slot B15.
8U chassis consists of two 4U chassises, and the upper layer is the first layer (layer 1) and the
lower layer is the second layer (layer 2). The irremovable modules are power supply module, MON
module and DSP module in the first layer, and second layer is mainly used to configure AC
modules.
DSP module 1
DSP module 2
MON module
PWR module
Figure 6.2-2 Rear view of fixed module position of 8U equipment
Besides the fixed four modules are shown in above figure, there are twenty nine slots can be
flexibly configured.
8U chassis support duplicate power modules and one power module is fixed configured at slot
B16 and the other one must be configured at slot B31.
Layer 2 is applied for configuration of analog input modules. Maximum 7 AC AI modules with
84 analog input channels can be configured between slot B17 and slot B29.
Each AC AI module occupies two slots where two DC AI modules can be configured.
Slot B30 and slot B31 are blank, i.e. module can not be equipped at those slots.
After finishing AI module configuration, BI module and BO module can be configured at the
rest slots of layer 2 except slot B30, slot B31 and slot B32.
AC AI module 2
DSP module 1
DSP module 2
MON module
PWR module
BI module
Figure 6.2-3 Typical configurations 1
PWR module
BI module 1
BI module 2
AC AI module 2
AC AI module 3
AC AI module 4
AC AI module 1
Equipment consists of power supply module, MON module, DSP module, Analog input module,
opto-coupler input module, tripping output module, and signal output module. The definition and
application of each module and its terminal is introduced as follows.
The power supply module is a DC/DC or AC/DC converter with electrical insulation between input
and output. The power supply module has an input voltage range as described in chapter 2
“Technical Data”. The standardized output voltages are +3.3V, +5V, ±12V and +24V DC. The
tolerances of the output voltages are continuously monitored.
The +3.3V DC output provides power supply for the microchip processors, and the +5V DC output
provides power supply for all the electrical elements that need +5V DC power supply in this device.
The ±12V DC output provides power supply for A/D conversion circuits in this device, and the
+24V DC output provides power supply for the static relays of this device.
The use of an external miniature circuit breaker is recommended. The miniature circuit breaker
must be in the on position when the device is in operation and in the off position when the device is
in cold reserve.
A 12-pin connector is fixed on the front of the power supply module. The pin definition of the
connector is described as below.
NR1301A
COM 1 01 01
BO_Fail_1
BSJ1 02 02
BO_Alm_Abnor_1
BJJ1 03 03
COM 2 04
04
BSJ2 05 BO_Fail_1
05
BJJ2 06 BO_Alm_Abnor_1
06
24V+ 07
24V- 08
09
DC + 10
DC - 11
FGND 12
Grounding S crew
Grounding Bus
NOTE: The rated voltage of DC power supply module is self-adaptive to 220Vdc and
110Vdc, but the power supply in other DC voltage level or power supply of AC voltage
need to be specially ordered, and check if the rated voltage of power supply module is
the same as the voltage of external control power supply before equipment being put into
service.
NOTE: The DC power supply module provides pin 12 and earth connector for grounding
of equipment. The pin 12 shall be connected to earth connector and the connected to the
earth copper bar of panel via dedicated grounding wire.
NOTE: Efficient grounding is the most important measure for equipment to prevent EMI,
so efficient grounding must be ensured before the device is put into operation.
The terminals of MON modules and its wiring method are shown in the following figure.
The MON module consists of high-performance built-in processor, FLASH, SRAM, SDRAM,
Ethernet controller and other peripherals. Its functions include management of the complete
device, human machine interface, communication and waveform recording etc.
The MON module uses the internal bus to receive the data from other modules of the device. It
communicates with the LCD module by RS-485 bus. This module is provided with 100BaseT
Ethernet interfaces, RS-485 communication interfaces, PPS/IRIG-B differential time
synchronization interface and RS-232 printing interface.
ET HERNET
ETHERNET
ET HERNET
ETHERNET
GPS
GPS
GPS
PRINT
PRINT
ETHERNET
ETHERNET
ETHERNET
ET HERNET
GPS
GPS
G PS
PRINT
The correct method of connection is shown in Figure 6.3-3. Generally, the shielded cables with two
pairs of twisted pairs inside shall be applied. One pair of the twisted pairs are respectively used to
connect the “+”and “–”terminals of difference signal; the other pair of twisted pairs are used to
connect the signal ground of the interface, i.e. connect the signal groundings of all the devices
connected with the bus to the twisted pair. The module reserves a free terminal for all the
communication ports; the free terminal has no connection with any signal of the device; it is used
to connect the external shields of the two cables when connecting multiple devices in series. The
external shield of cable shall be grounded at one of the ends.
When the module is connected to conventional CT/VT, it can perform the synchronous data
acquisition through the AC input board; when the module is connected to ECVT, it can receive the
real-time synchronous sample data from merging unit through the multi-mode optical-fibre
interface.
The module can provide 2,048 kbit/s or 64 kbit/s single-mode optical-fibre to exchange data and
signal with the opposite-side protection device
The module consists of high-performance digital signal processor, optical-fibre interface, 16-digit
high-accuracy ADC that can perform synchronous sampling and other peripherals. The functions
of this module include analog data acquisition, calculation of fault detector elements and providing
positive power supply to output relay.
When the module is connected to conventional CT/VT, it can perform the synchronous data
acquisition through the AC input board; when the module is connected to ECVT, it can receive the
real-time synchronous sample data from merging unit through the multi-mode optical-fibre
interface.
DSP module 1 and DSP module 2 have same hardware configuration. The following figure shows
rear views and terminal definitions for different type of DSP modules; the corresponding module
shall be adopted in accordance with concrete situation.
Module ID Description
NR1156A 48 analog sampling channels, applied for conventional CT/VT.
4 transmitting channels and 4 receiving channels, applied for ECVT to
NR1151A
receive signal directly.
No analog sampling channel, applied for ECVT to receive signal from
NR1151D
motherboard bus
It is used to ECVT, 8 receiving channels, applied for ECVT to receive signal
NR1152A
directly.
The NR1504 module is a standard binary input module, which can provide 25 binary inputs, the
inputted voltage can be selected to be 24V, 48V, 110V, 220V, 125V and 250V and the module has
opto-coupler power monitor circuit. Pins ~14 and ~15 are power supply inputs for opto-coupler.
A 22-pin connector is fixed on the front of the binary input module. The pin definition of the
connector is described as below.
NOTE: The rated voltage of binary input is optional: 24V, 46V, 110V , 220V, 125V or 250V,
which must be definitely declared in the technical scheme and the contract. It is
necessary to check whether the rated voltage of BI module meets the demand of the
engineering before putting the relay into operation.
The application of the binary input [BI_BlkComm] for digital substation communication adopting
IEC61850 protocol is given as follows.
1) The protection device should send the state of this binary input to client.
2) When this binary input is energized, the bit “Test”of quality (Q) in the message sent
should be set as “1”.
3) When this binary input is energized, the client cannot remote control the isolator link
and circuit breaker, modify settings and switch setting group.
4) According to the value of the bit “Test”of quality (Q) in the message sent, the client
discriminate whether this message is maintenance message, and then deal with it
correspondingly. If the message is the maintenance message, the content of the
message will be not displayed real-time message window, not issue audio alarm, but
should refresh the picture so as to ensure that the state of the picture is in step with the
actual state. The maintenance message should be stored, and can be inquired by
independent window.
1) When this binary input is energized, the bit “Test”in the GOOSE message sent by the
protection device should be set as “1”.
2) For the receiving end of GOOSE message, it will compare the value of the bit “Test”in
the GOOSE message received by it with the state of its own binary input (i..e
[BI_BlkComm]), the message will be thought as invalid unless they are conformable.
1) When this binary input of merging unit is energized, the bit “Test”of quality (Q) of
sampling data in the SV message sent should be set as “1”.
2) For the receiving end of SV message, if the value of bit “Test”of quality (Q) of sampling
data in the SV message received by it is “1”, the relevant protection functions will be
disabled, but under maintenance state, the protection device should calculate and
display the magnitude of sampling data.
3) For duplicated protection function configurations, all merging units of control module
configured to receive sampling should be also duplicated. Both dual protection devices
and dual merging units should be fully independent each other, and one of them is in
maintenance state will not affect the normal operation of the other.
NR1521A and NR 1521B modules are two standard binary output modules. NR1521A can provide
11 tripping output contacts, and each output contact can be controlled separately by positive
power supply of fault detector. NR1521B can provide 9 tripping output contacts, and two signal
output contacts, and each output contact can be controlled separately by positive power supply of
fault detector. The contacts provide by NR1521A and NR1521B are all normally open (NO)
contacts.
[BO_Trp_n] (n=1,2,… ,11) and [BO_Signal_n] (n=1, 2) can be configured as a specified tripping
output contact and a signal output contact respectively by PCS-PC software according to user
requirement.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
NR1521A NR1521B
BO_Trp_1+ 01 01 BO_Trp_1+ 01 01
BO_Trp_1 BO_Trp_1
BO_Trp_1- 02 02 BO_Trp_1- 02 02
BO_Trp_2+ 03 03 BO_Trp_2+ 03 03
BO_Trp_2 BO_Trp_2
BO_Trp_2- 04 04 BO_Trp_2- 04 04
BO_Trp_3+ 05 05 BO_Trp_3+ 05 05
BO_Trp_3 BO_Trp_3
BO_Trp_3- 06 06 BO_Trp_3- 06 06
BO_Trp_4+ 07 07 BO_Trp_4+ 07 07
BO_Trp_4 BO_Trp_4
BO_Trp_4- 08 08 BO_Trp_4- 08 08
BO_Trp_5+ 09 09 BO_Trp_5+ 09 09
BO_Trp_5 BO_Trp_5
BO_Trp_5- 10 10 BO_Trp_5- 10 10
BO_Trp_6+ 11 11 BO_Trp_6+ 11 11
BO_Trp_6 BO_Trp_6
BO_Trp_6- 12 12 BO_Trp_6- 12 12
BO_Trp_7+ 13 13 BO_Trp_7+ 13 13
BO_Trp_7 BO_Trp_7- BO_Trp_7
BO_Trp_7- 14 14 14 14
BO_Trp_8+ 15 15 BO_Trp_8+ 15 15
BO_Trp_8 BO_Trp_8
BO_Trp_8- 16 16 BO_Trp_8- 16 16
BO_Trp_9+ 17 17 BO_Trp_9+ 17 17
BO_Trp_9 BO_Trp_9
BO_Trp_9- 18 18 BO_Trp_9- 18 18
BO_Trp_10+ 19 19 BO_Signal_1+ 19 19
BO_Trp_10- 20 BO_Trp_10 BO_Signal_1- 20 BO _Signal_1
20 20
BO_Trp_11+ 21 21 BO_Signal_2+ 21 21
BO_Trp_11- 22 BO_Trp_11 BO_Signal_2- 22 BO _Signal_2
22 22
The NR1523B module is a standard binary output module for signal, which can provide 11 signal
output contacts. Among those contacts, contacts [BO_Signal_n] (n=1,2,… ,7, 10,11) are normally
open (NO) contacts and [BO_Signal_8] and [BO_Siganl_9] are normally closed (NC) contacts. All
contacts can be configured as specified signal output contacts of some protection by PCS-PC
software according to user requirement. Besides the contact [BO_signal_11] is a magnetic latched
NO contact defined as protection tripping signal fixedly.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
NR1523B
BO_Signal_1+ 01 01
BO_Signal_1
BO_Signal_1- 02 02
BO_Signal_2+ 03 03
BO_Signal_2
BO_Signal_2- 04 04
BO_Signal_3+ 05 05
BO_Signal_3
BO_Signal_3- 06 06
BO_Signal_4+ 07 07
BO_Signal_4
BO_Signal_4- 08 08
BO_Signal_5+ 09 09
BO_Signal_5
BO_Signal_5- 10 10
BO_Signal_6+ 11 11
BO_Signal_6- 12 BO_Signal_6
12
BO_Signal_7+ 13 13
BO_Signal_7- 14 BO_Signal_7
14
BO_Signal_8+ 15 15
BO_Signal _8
BO_Signal_8- 16 16
BO_Signal_9+ 17 17
BO_Signal_9- 18 BO_Signal_9
18
BO_Signal _10+ 19 19
BO_Signal_10- 20 BO_Signal_10
20
BO_Signal _11+ 21 21
BO_Signal_11- 22 BO_Signal_11
22
NOTE: If user needs more magnetic latched contacts or normally closed (NC) contacts,
The analog input module can transform these high AC input values to relevant low AC output
value for the DSP module. The transformers are used both to step-down the currents and voltages
to levels appropriate to the electronic circuitry of this device and to provide effective isolation
between this device and the power system. A low pass filter circuit is connected to each
transformer (CT or VT) secondary circuit for reducing the noise of each analog AC input signal.
NOTE: The rated value of the input current transformer is optional: 1A or 5A. The rated
value of the CT must be definitely declared in the technical scheme and the contract.
NOTE: Because the rated value of the input current transformer is optional, it is
necessary to check whether the rated values of the current transformer inputs are
accordant to the demand of the engineering before putting the device into operation.
The NR1401 can provide 12-channel analog signal inputs, and each channel can be configured as
a specified current or voltage input channel by PCS-PC software according to user requirement.
There are three kinds of typical application module as follwing shows.
A 24-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
NOTE: In above figure, I1, I2, I3, I4, I5, I6, I7, I8, I9, I10, I11, I12 and U1, U2, U3, U4, U5,
NOTE: If user needs other analog input configuration, please declare in the technical
Transducer input module NR1410B can receive six input signals which can be 4~20mA current or
0~5V voltage from external dcmA output transducer. Hardware and software are provided to
receive these signals from the external transducers and convert these signals into a digital for use
as required. There are four pins 13, 16, 19 and 22 on the module are ground terminals of the
equipment.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
Typical connection of output transducers is shown in the figure below, and there is a jumper
between pin S1 and pin S6 on module NR1401B to control the input signal type of the module.
Output Transducer
To_Transducer_24V
Transducer_24V_Return
4-20mA
dcmA_In_+
NR1410B
S1
Jumper
S6
dcmA_In_- R
4-20mA shunt disabled and return paths interconnected and 0~5V measure
S1~S6 (OFF)
provided.
S1~S6 (ON) Input resistance with 4-20mA shunt enabled and 4~20mA measure provided.
This module consists of high-performance digital signal processor, two 100M optical-fibre Ethernet,
two 100M RJ-45 Ethernet and other peripherals. The module supports GOOSE function and IEC
61850-9-1 and IEC 61850-9-2 Protocols. Its functions include that the protective device receives
data from the merging unit and sending GOOSE command to the intelligent control device etc.
This module is not required when the GOOSE function is not applied.
The sending and receiving functions of GOOSE should be completed through configuring the
sending module and receiving module.
NR1126B NR1126D
SC Interface ST Interface
100M FX 100M FX
SC Interface ST Interface
100M FX 100M FX
RX1
ST Interface RX 1
ST Interface
IRIGB IRIGB
The PCS-978 provides output contacts which are controlled by tripping logic settings (or called
tripping matrix setting). The tripping logic setting of each protection element can be set so that the
flexible tripping mode of each protection can be realized as user required.
The tripping logic setting in form of [TrpLog_xxx] is comprised of 10-bit binary number, but that
displayed on the LCD is 3-bit hexadecimal number. Each binary bit controls a set of tripping output
contacts. When the protection element operates, if the corresponding bit is set as “1”, the relevant
output contacts will pick up; if the bit is set as “0”, the relevant output relays will not pick up.
For typical configuration 1 of PCS-978 in 4U, two NR1521A modules are equipped with being
installed adjacently in slot S28 and slot S29, and then tripping output contacts controlled by logic
setting are list in the following table.
Contact
Bit Tripping output group Controlled contacts
amount
2801-2802, 2803-2804,
0 TrpOutp1: the 1st group of tripping output contacts 3
2805-2806
2 TrpOutp3: the 3rd group of tripping output contacts 2811-2812, 2813 -28 14 2
2901-2902, 2903-2904
5 TrpOutp6: the 6th group of tripping output contacts 3
2905-2906,
7 TrpOutp8: the 8th group of tripping output contacts 2911-2912, 2913 -29 14 2
2919-2920
9 TrpOutp10: the 10th group of tripping output contacts 2
2921-2922
10 No definition
11 No definition
12 No definition
13 No definition
14 No definition
15 No definition
NOTE: Controlled contacts are represents with its slot position and pin number. For
example, contact 2801-2802 means terminal 01-02 of the module at the slot B28, i.e. 28
represents the slot position of module, 01(02) represents the pin number on the module.
There are two types of output contact tripping output contact and signal output contact.
The protection equipment provides tripping contacts for tripping breaker generally. These contacts
are fixed on the tripping output modules. The number of tripping contacts can be flexibly
configured according to user requirement.
The signal output contacts are classified into two types based on the sources: tripping signal
output contact and abnormal signal output contact. The tripping signal output contact picks up
when protective equipment operates and the abnormal signal output contact picks up when
protective equipment is in abnormal operation. Signals are divided into three types based on their
applications: annunciation signal, remote signal and fault&disturbance record (FDR) signal. The
annunciation signal is sent to local control panel the remote signal is sent to substation automation
system, the FDR signal is provided to independent fault recorder device. The annunciation output
contact is generally magnetic latched, so it needs manual reset and then the output contact can
drop off.
The number of signal output contacts can be flexibly configured according t user requirement.
When the protection element operates, the equipment sends tripping command to drive the
tripping output contact and signal contact simultaneously. For example, when differential
protection operates, in addition to the pickup of tripping output contact controlled by the tripping
logic setting, the signal contacts are closed simultaneously, producing annunciation signal, remote
signal and FDR signal respectively. These contacts are assigned to contacts on signal output
module by PCS-PC software as user requirement.
When some abnormal operation conditions are detected by protection equipment, the equipment
will send abnormal message to be displayed on the LCD and generate abnormal alarm signal.
These signals, such as equipment failure signal, CT circuit failure and so on, are used to produce
annunciation signal, remote signal and FDR signal. Please refer to power supply module for
detailed abnormal signal output contact.
The abnormal operation contacts include initiating cooler, blocking on-load tap changing (OLTC)
function and etc. These contacts are assigned to contacts on signal output module by PCS-PC
software as user requirement.
The equipment has 10 setting groups for protection to coordinate with the mode of power system
operation, one of which is assigned to be active. However, common settings are shared by all
protection setting groups, and settings of protection element are set according to secondary
values.
NOTE: All current settings in this chapter are secondary current converted from primary
current by CT ratio. Zero sequence current or voltage setting is configured acc ording to
3I0 or 3U0 and negative sequence current setting according to I2 or U2.
Setting list
Setting explanation
1. Un_BinaryInput
The setting is used to set the voltage level of binary input module. If low-voltage BI module is
equipped, 24V or 48V can be set according to the actual requirement, and if high-voltage BI
module is equipped, 110V or 220V can be set according to the actual requirement.
These settings are special for GOOSE function module, and if GOOSE function module is not
equipped and these settings will not displayed at this submenu.
Setting path
Setting list
Setting explanation
These are used for Ethernet communication based on the 103 protocol. When the IEC 61850
protocol is applied, the IP address of Ethernet A will be GOOSE source MAC address.
4. [COMX_Protocol] (X=1, 2)
2: Modbus Protocol
5. [En_BlkComm]
It is set as “1”when the equipment is in maintenance. During such period, the fault report due to
test will not be sent upstream through communication ports, while local display and printing will not
be affected.
It is set as “0”when the equipment is in service. The relation between this setting and binary input
[BI_BlkComm] is “OR”, i.e. as long as one of them is set as “1”, such information as fault report
and waveform will not be sent upstream.
6. [En_Auto_Prin]t
If automatic print is required for fault report after protection operating, it is set as “1”. Otherwise, it
should be set to “0”.
7. [En_HiSpeed_Print]
It is set as “0”for common printing with high definition, while it is set as “1”for high -speed printing.
8. [Opt_TimeSync]
1: IRIG-B differential
9. [En_DuralNet_GOOSE]
It is the logic setting of enabling the GOOSE module to work in dual Ethernet mode.
“0”: Disable the NET B link of the GOOSE module, and then the GOOSE module can only work in
single Ethernet mode.
Setting path
Setting list
Setting explanation
1. [ Active_Grp]
Number of protection setting group. Four group settings are provided, but the system settings
are common for each group.
2. [Equip_Name]
This setting is used to set the name of the equipment being protected by the relay. Maximum
six characters of ASCII code, for report printing only.
During the calculation of current differential protection, in order to get current correction ratio
of each side of the transformer automatically, these basic parameters are needed, such as
transformer capacity, phase-to-phase primary voltages of each side and CT ratios of each
side.
[WdgConn_HVS] is the setting of selecting the winding connection mode of side 1. “0”is for Y
winding and “1”is for delta winding.
These logic settings are used to set connection group of transformer for the calculation of
differential protection in the equipment.
5. [U1n_XXX]
Setting principle of rated voltages of each side is to take the primary rated voltage marked on
the nameplate of transformer as the primary rated voltage of corresponding side. For an
on-load tap changing transformer, the voltage of transformer with tap in middle position can
be taken as the value of this setting. As to other kind of transformers, actual operation voltage
(i.e. phase-to-phase voltage) shall be taken as this setting value, otherwise the calculation of
correction coefficient may be wrong
For example, if the voltage at 220kV side is 230kV for an on-load tap changing transformer
with tap in its middle position, and then the setting is set as 230kV.
NOTE: For one side not used in the relay, please set the primary rated voltage value (i.e.
6. [U1n_VT_XXX], [U2n_VT_XXX]
These settings are primary voltage and secondary voltage values of the three-phase VT of
three side of a transformer respectively, which are phase-to-phase voltage values.
7. [I1n_CT_XXX], [I2n_CT_XXX]
Set the settings [I1n_CT_XXX] and [I2n_CT_XXX] respectively according to the actual
primary value and secondary value of the corresponding side CT.
NOTE: For some CT not used, the secondary rated current value of the corresponding CT
NOTE: If the summation value of currents of multi CTs at one side is used as for backup
NOTE: For some CT not used, the secondary rated current value of the corresponding CT
5. [En_In_VT_XXX]
This is the logic setting of enabling or disabling VT of XXX side into service.
If VT of some side is not installed or the protection equipment is in service, the setting should
be set as “0”.
Setting path
Setting list
Setting explanation
1. [NameDef_CB_XXX]
This setting is used for user to define the name of circuit breaker of XXX side only for SLD display
according to user habit. For example HV side circuit breaker is named as 5001.
2. [NameDef_CB_XXX]
This setting is used to define the name of tripping output group n (n=1,2,… , 10). For example,
“TrpOutp1”is named as “TrpHVS”(i.e. Trip HV side breaker).
Setting path
SLD settings are dedicated for configuring single line diagram (SLD) on LCD display of the
protected transformer. User can set the branches of each side of transformer for the SLD on LCD
by the following settings which are stored in non-volatile memory, so the LCD can always display
the latest configured SLD.
The winding connection mode of SLD is controlled by the logic settings [WdgConn_HVS],
[Clk_MVS_WRT_HVS] and [Clk_LVS_WRT_HVS] in “SYSTEM SETTINGS”menu.,
Setting list
Setting explanation
These settings are to configure branch amount of each side of transformer for SLD displaying on
local LCD. If the setting of one side is set as “0”,
“2”two braches
Setting path
Each virtual enabling binary input (VEBI) setting is one of the conditions that decide whether the
relevant protection is in service, when this relay is energized. Each VEBI is an “AND”condition
of enabling the relevant protective element with the corresponding binary input and logic
setting. Through SAS or RTU, the virtual enabling binary input can be set as “1”or “0”; and it
means that the relevant protection can be in service or out of service through remote command. It
provides convenience for operation management.
Setting List
Setting path
PCS-PC software, assorted with UAPC platform device, is developed in order to meet customer’ s
demand on functions of device such as device configuration and programmable design. It selects
substation as the core of data management and the device as fundamental unit, supporting one
substation joint to govern many ones of the devices. The software provides on-line and off-line
functions: on-line mode: Ethernet connected with the device to support IEC 60870-5-103 protocol
and downloading of binary files through Ethernet net; off -line mode: off-line setting configuration.
In addition, it also supports programmable logic to meet customer’ s corresponding demand. For
any detail, please refer to Instruction Manual of PCS-PC Auxiliary Software.
Overall functions:
Warning: The system configuration shall only be operated by professionals who are
familiar with protection object and protection device. Or else, any incorrect configuration
may cause serious damage to the device during its operation. In general, these
configuration works have been completed before equipment leaving factory.
Warning: If the system configuration is really need, user must select “Run the whole
1. Select number of 3-phase current branch supported by the equipment (no more than 10).
2. Define name of each group of 3-phase current input (I1~I10), e.g. HV side I branch, MV side,
etc. There will be corresponding changes in displaying CT alarm message and sampling
value item relevant to current.
Presently, PCS-978 provides two types of AC module for selection: full current module (12
current input) and 6 current inputs and 6 voltage inputs module (the last 3 voltage inputs shall
vary according to phase voltage or zero sequence voltage input.).
4. Configuration steps
(1) Firstly click “Three_phase_current configuration”in configuration tree and unfold it:
After unfolding:
(2) Confirm number of 3-phase current of protected transformer that leads to protection
equipment and input it to configuration software; meanwhile, name selected 3-phase
current inputs.
(3) Continually unfold selected 3-phase current input and configurate AC input number of
phase A, B and C corresponding to AI module. When the AC input number is “0”, it
means that there is no effective input defined.
1. Select number of zero-sequence current branches supported by the equipment (no more than
10).
2. Define name of each group of 3-phase zero-sequence current input(I1g~I10g), e.g. HV side
zero-sequence, MV side zero-sequence, etc. There will be corresponding changes in
displaying CT alarm message and sampling value item relevant to zero-sequence current.
1. Select voltage branch (including 3-phase voltage and zero sequence voltage) number
supported by the equipment (no more than 3).
2. Define name of each group of voltage input, e.g. HV side, MV side, etc. There will be
corresponding changes in displaying VT alarm message and sampling value item relevant to
voltage.
4. Small VTs of the equipment for collecting zero-sequence voltage and phase voltage are
different. Please pay attention during voltage configuration.
1. Select “Enable” for the next operation or “Disable” for hiding the protective function in
protective equipment.
3. Protective equipment needs to know which side each curren t branch engaged in current
differential protection belongs to and make configuration for current branch at each side.
Effective and ineffective current branch configurations are set as “1”and “0”respectively. For
example, there are two branches at HV side defined as “Branch_1_current_configuration”and
“Branch_2_current_configuration”respectively; therefore, “1”shall be set at corresponding
position and “0”is for others. PCS-PC software has the function of automatic mutual exclusion.
Once one current is confined to be at HV side, it will not be configured to other sides.
1. Select “Enable” for the next operation or “disable” for hiding the protective function in
protective equipment.
2. Make configuration of restricted earth fault (REF) protection of each side and select current
engaged in REF protection calculation. REF protection of some side is able to be configured
with three groups of 3-phase current and one group of zero-sequence current at most. If there
is one branch no used, select “NONE”. For example, I1 and I2 are two branches at HV side
and I1g is zero-sequence current at HV side; these three groups of current form REF
protection at HV side. It is able to set “Three_phase_current_1_configuration” as “I1”,
“Three_phase_current_2_configuration” as “I2”, “Three_phase_current_3_configuration” as
“NONE”and “Zero_sequence_current_configuration”as “I1g”.
1. Select “Enable” for the next operation or “disable” for hiding the protective function in
protective equipment.
2. Make configuration of winding differential protection of each side and select current engaged
in the protection calculation. Winding differential protection of some side is able to be
configured with maximum five groups of 3-phase current. If there is one branch no used, select
“NONE”.
3. Make configuration of current direction. Configure the current direction according to the actual
CT polarity in order to ensure that winding differential current is equal to zero during the
normal operation. For example, if I1 and I2 two branches are engaged for winding differential
protection and the differential current calculation equation is I1-I2 according to the actual CT
polarity, then “Three_phase_current_2_direction_reverse”is set as “Enabled”.
1. Select “Enable” for the next operation or “disable” for hiding the protective function in
protective equipment.
2. Configure current with the range of None, I1 , I2, … ,and I10 for backup protection at one side,
and “1”for used, “0”for not used. Current for protection calculation is summation of currents of
all branches at this side.
3. Select zero-sequence current with the range of I1g, I2g, … , and I10g for backup protection.
4. Select voltage with the range of U1, U2 and U3 for backup protection.
5. For example, if current value for backup protection at HV side is summation of I1 and I2,
corresponding value of I1 and I2 shall be set as “1”and others set as 1. Zero-sequence current
is I1g, so pull down the menu to select I1g in configuration for zero-sequence current input. If
voltage is selected to be U1, pull down the menu to select U1 in voltage configuration.
Overexcitation protection and frequency protection share the same voltage, and user can select
the voltage to do relevant calculation by configuration software with a range U1~U3.
2. Select whether frequency tracking function shall be enabled. (The logic setting is in the
submenu of system settings.)
3. Select time delay mode of backup protection in frequency tracking. This configuration can not
work until the device has enabled frequency tracking function. There are two parameters –
time and cycle– available for selection. In time mode, operation time of backup protection is
time delay setting; in cycle mode, operation time of backup protection is the cycles calculated
from time delay setting and rated system frequency.
For example: when rated system frequency is 50Hz, the value of time delay setting is 1s. In
actual operation, system frequency is 49Hz when protection operates and the equipment is in
frequency tracking state, so the actual time delay amounts 50 cycles or 1.02s
( 1/49*50=1.02s). Selection of time delay mode shall coincide with time delay mode of
protection equipment. For instance, if PCS-978 equipment works with other microcomputer
protection equipment, it is recommended to select cycle mode (Microcomputer protection
usually adopts sampling cycle as interval.); while if it works with IC (integrated circuit) time
relay, time mode can be selected.
1. Configure voltages to be displayed at each side, with a range of None, I1, I2 and I3.
2. Configure currents to be displayed at each side, with a range from I1g toI10g.
4. Configure zero-sequence currents to be displayed at each side, with a range from I01 toI010
1. Select voltage displayed at each side with a range none, U1, U2 and U3.
4. For example, if there are two branches I1 and I2 at HV side; and zero-sequence current is I1g
and voltage is U1, voltage shall be selected to be “1”and that at position corresponding to
current and others shall be “1”and “0”respectively.
1. This equipment provides 20 LED indicators, among which the first three are “HEALTHY”LED,
“ALARM“LED and “TRIP”LED and the rest 17 LEDs can be configured by users as required.
2. The right tree structure in the software provides elements for lighting up, including protection
elements, alarm elements and binary input elements.
3. Use “KeepLight”to choose whether hold LED or not. In case of “Yes”selected, resetting must
be performed by the resetting button once it is lit. In case of “No”selected, the signals will reset
automatically once the input signal returns.
4. If users hope the user-defined LED 1 (the fourth one) is lit and held when differential protection
operates; the user-defined LED 2 (the fifth one) is lit and not held when restricted earth fault
protection of HV side operates , configure it as per the following picture.
1. Pin number of user-defined binary input on module is provided on the left of the interface.
2. The next step is to set debounce time (unit: ms) of the corresponding binary inputs. Debounce
mode can be from 0 to 1 or from 1 to 0, which can be set separately.
3. The “BinaryIn BinaryOut List”at the right is the corresponding function of the binary input,
which needs the user to configure. User can draw it from the right list.
4. The available variables are: binary inputs of enabling protective function, binary input of
mechanical signal, output of programmable logic.
In case of binary inputs of enabling protective function, the binary input is enabled when it is “1”.
If some binary input of enabling protective function has no corresponding connection, it is fixed
enabled.
If mechanical signal input is connected, the corresponding module must be mechanical module
NR1533. On condition that “Destination”is connected, no any operation is executed within the
program, and only directly transform input into output used as input of programmable logic.
2. There are total 7 groups of binary output, and each group includes one contact or two
contacts.
3. Users can draw the elements from the right list, serving as input for contact outputting.
4. The optional signals include: protection elements, alarm elements, binary inputs and fault
detector signal of protection element.
5. In the event that user want to use the first group output contacts (i.e. contacts (pin1,pin2), (pin3,
pin4) on board 15) as alarm output contacts of thermal overload of HV side, find the
corresponding alarm element in the right tree structure and draw it to the corresponding
position of the “Board15_Pin1_2_Pint3_4”.
1. Users can configure the communication parameters, system settings, SLD settings and etc.
2. Each stage of protection can be configured. For example, the maximum configuration of
overcurrent protection of HV side is four stages, and characteristic of each stage can be
configured as definite time, standard inverse time, very inverse time, extremely inverse time,
long-time inverse time, user-defined inverse time, or out of service.
3. Users can select to show or hide some setting, and modify typical setting values.
A 320×240 backlight LCD visible in dim lighting conditions for monitoring status, fault
diagnostics and setting, etc.
LED indicators on the front panel for denoting the status of this protection operation.
A 9-key keypad on the front panel of the device for full access to the device.
PCS-978 has two types of chassis 4U and 8U shown in the following two figures.
G RP
C
ES
5
PCS-978
HEALTHY
ALARM TRANSFORMER PROTECTION
TRIP
RP
G
ENT
C
ES
1 3
4
2
9.1.1 Functionality
The HMI module helps to draw your attention to something that has occurred which may
activate a LED or a report display on the LCD.
You as the operator may have own interest to view a certain data.
Use menus navigate through menu commands and to locate the data of interest.
The keypad and keys on the front panel of the equipment provide convenience to the operator to
view a certain data or change the device’
s setting.
The keypad contains nine keys, and each key has different function to the other one. Figure 9.1-3
P
GR
E SC
Figure 9.1-3 Keypad mounted on the front panel
NOTE:
Any setting change shall be confirmed by simply pressing “+”, “”, “”, “-“, “ENT”in
sequence.
Any report delete operation shall be executed by pressing “+”, “-“, “+”, “-“, “ENT”in
sequence.
NOTE:
The “HEALTHY”LED can only be turned on by energizing the equipment again to restart
the relay.
The “TRIP”LED is turned on once any protection element operates and remains lit even
after the trip command goes off. The “TRIP” LED can be turned off by pressing the
signal RESET button on the front panel.
Other LED indicators with no labels are programmable and user can configure them to be
lit by signals of operation element, alarm element and binary output contact according to
requirement through PCS-PC software.
It is used to access the hardware of the protection device via HyperTerminal. This port is only used
to monitor the communication state by engineering debugging personnel and debug the program
by developers.
9.1.5 Communication
The MON module is comprised by embedded processor of high performance, FLASH, SRAM,
SDRAM, Ethernet controller and other peripheral equipments. It can realize the management,
human machine interface, communication and waveform recording of the whole device. The MON
module uses the data of other modules in the receiver device of internal bus, and communicates
with LCD panel via RS-485 bus.
Take NR1102A as an example, its rear view and the definition of terminals are shown as Figure
9.1-6. This module is equipped with two 100BaseT Ethernet interface, PPS/IRIG -B differential
synchronization interface and RS-232 printer interface.
The Ethernet interface can be used to communication with PC via auxiliary software (PCS-PC) by
connecting the protection device with PC, so as to fulfill on-line function (please refer to the
instruction manual of PCS-PC). At first, the connection between the protection device and PC
must be established. Through setting the IP address and subnet mask of corresponding Ethernet
interface in the menu “SETTINGS→ EQUIP_SETTINS”, it should be ensured that the protection
device and PC are in the same network segment. For example, setting the IP address and subnet
mask of network A. (using network A to connect with PC)
The IP address and subnet mask of protection device should be [IP_Addr_NetA]= 198.87.96.XXX,
[Subnet_Mask_A]=255.255.255.0, [En_NetA]=1. (XXX can be any value from 0 to 255 except
102)
9.2.1 Overview
Press “▲ ”of any running interface and enter the main menu. Select different submenu by “▲ ”and
“▼ ”. Enter the selected submenu by pressing “ENT”or “► ”. Press “◄ ”and return to the previous
menu. Press “ESC”and exit the main menu directly. For sake of executing the command menu
again, one command menu will be recorded in the quick menu after its first execution. Five latest
menu commands can be recorded in the quick menu. When the five menu commands are
recorded, the latest menu command will cover the earliest one, adopting the “first in first out”
principle. It is arranged from top to bottom and in accordance with the execution order of command
menus. Press “▲ ”to enter the main menu with the interface as shown in the following diagram:
For the first powered protective device, there is no recorded shortcut menu. Press “▲ ”to enter the
main menu with the interface as shown in the following diagram:
INTERFACE
TEST_MODE
VERSION
CLOCK
LOCAL_CTRL
SETTINGS
REPORT
VALUES
Under the main interface, press “▲ ”to enter the main menu, and select submenu by pressing “▲ ”,
“▼ ”and “ENT”. The command menu adopts a tree shaped content structure. The above diagram
provides the integral structure and all the submenus under menu tree of the protection device.
9.2.2 VALUES
This menu is mainly used to display the real time sampling value of current and voltage and the
input state of the protection device, which fully reflects the running environment of the protection
device. As long as the displayed values of the equipment consist with the actual running situation,
basically, the protection device can work normally. This menu is set to greatly facilitate the
debugging and maintenance of people on site.
9.2.2.1 PROT_MEASUREMENT
9.2.2.2 FD_MEASUREMENT
9.2.2.3 BI_STATE
9.2.2.4 COMM_STATE
9.2.3 REPORT
This menu is used for displaying the fault report, abnormal record, binary signal and running
reports , so that the operator can load to view and use as the reference of analyzing accidents and
maintaining the device. All the reports are stored in non-volatile memory, it can still record the
reports even if it losses its power.
9.2.4 PRINT
This menu is used for printing device description, setting, fault report, abnormal record report,
binary signal, waveform and information related with 103 Protocol.
9.2.4.1 SETTINGS
9.2.4.2 WAVEFORM
9.2.5 SETTINGS
This menu is used for checking the setting of device equipment parameter, virtual binary input
setting, protection setting, logic setting and system parameter, as well as modifying any of the
above setting items. Moreover, it can also execute the setting copy between different setting
groups.
9.2.6 LOCAL_CTRL
This menu is used for resetting the tripping relay with latch, protection device signal lamp, LCD
display, as the same as the resetting function of binary input. Record the currently acquired
waveform data of the protection device under normal condition for printing and uploading SAS.
Besides, it can send out the request of program download.
9.2.7 CLOCK
The current time of internal clock can be viewed here. The time is displayed in the form
YY-MM-DD and hh:mm:ss. All values are presented with digits and can be modified.
9.2.8 VERSION
In this menu the LCD displays software information of DSP module, MON module and HMI module,
which consists of version, creating time of software, CRC codes and management sequence
number.
This menu is mainly used for developers to debug the program and for engineers to maintain
device. It can be used to check module information and item fault message, and fulfill the
9.2.10 INTERFACE
This menu is mainly used for set LCD display language. This menu includes the following
command menus.
9.3.1 Overview
There are five kinds of LCD display, SLD (single line diagram) display, tripping reports, alarm
reports, binary input changing reports and control reports. Tripping reports and alarm reports will
not disappear until these reports are acknowledged by pressing the RESET button in the
protection panel (i.e. energizing the binary input [BI_RstTarg]). User can press both “ENT”and
“ESC”at the same time to switch the display among trip reports, alarm reports and the SLD display.
Binary change reports will be displayed for 5s and then it’
ll return to the previous display interface
automatically. Control reports will not pop up and can only be viewed by navigating the
corresponding menu.
After the protection device is powered and turns into the initiating interface, it takes 30 seconds to
complete the initialization of protection device. During the initialization of protection device, the
“HEALTHY”indicator of the protection device goes out.
Under normal condition, the LCD will display the following interface. The LCD adopts white color
as its backlight that is activated if once there is any keyboard operation, and is extinguished
automatically after 60 seconds of no operation.
When the equipment is powered on, based on actual connection of the transformer, the LCD will
display single line diagram on its connection diagrams. If the transformer has three windings and 2
branches on LV side, the LCD will display by configuring the logic settings.
The displayed content of the interface contains: the current date and time of the protection device
(with a format of yy-mm-dd hh:mm:ss:), the currently valid setting group number, the three-phase
current and voltage sampling values of each side, differential current, zero-sequence differential
current, frequency etc.
This protection device can store 64 times of fault reports and 64 times of fault waveforms. When
there is protection element operating, the LCD will automatically display the latest fault report, and
two kinds of LCD display interfaces will be available depending on whether there is self-check
report at present.
If the device has no self-check report, the display interface will only show the fault report.
TRP REPORT NO.2 shows the titile and SOE number of the report.
2008-11-28 07:10:00:200 shows the time when fault detector picks up, the format is
year–month-date and hour:minute:second:millisecond.
0ms FD_PcntDiff shows fault detector of protection element and operation time of fault
detector is set as 0ms fixedly.
24ms AB Op_PcntDiff shows the relative operation time and operation element of protection
element
All the protection elements have been list in chapter “Description of Operation Theory”, and please
refer to each protection element for details. Operation reports of fault detector and the reports
related to oscillography function are showed in the following table.
For the situation that the fault report and the self-check alarm report occur simultaneously in the
following figure, the upper half part is fault report, and the lower half part is self-check report. As to
the upper half part, it displays separately the record number of fault report, fault name, generating
time of fault report (with a format of yy-mm-dd hh:mm:ss:), protection element and tripping element.
If there is protection element, there are relative time on the basis of fault detector element and fault
phase. At the same time, if the total lines of protection element and tripping element are more than
3, a scroll bar will appear at the right. The height of the black part of the scroll bar basically
indicates the total lines of protection element and tripping element, and its position suggests the
position of the currently displayed line in the total lines. The scroll bar of protection element and
tripping element will roll up at the speed of one line per time. When it rolls to the last three lines, it’
ll
roll from the earliest protection element and tripping element again. The displayed content of the
lower half part is similar to that of the upper half part.
ALM REPORT NO.4 shows the SOE number and title of the report
2008-11-28 09:18:47:500 shows the real time of the report: year–month-date and
hour:minute:second:millisecond
All the alarm elements have been listed in chapter “Automatic Supervision”.
No.004 BI CHG REPORT shows the number and title of the report
2008-11-28 09:18:47:500 shows date and time when the report occurred, the format is
year–month-date and hour:minute:second:millisecond
EBI_Diff 0->1 shows the state change of binary input, including binary input name,
original state and final state
Binary inputs have been listed in input signal table and virtual binary inputs list in output table and
VEBI settings lit in setting list table in chapter “Description of Operation Theory”and please refer to
each protection element for details.
This protection device can store 1024 pieces of the control report (i.e. user operating reports).
During the running of the protection device, the running report will be displayed after any operation
of it is conducted.
CTRL REPORT NO. 4 shows the title and the number of the report
2008-11-28 10:18:47:569 shows date and time when the report occurred, the format is
year–month-date and hour:minute:second:millisecond
2. Press the key “▲ ”or “▼ ”to move the cursor to the “VALUES”menu, and then press the
“ENT”or “► ”to enter the menu.
3. Press the key “▲ ”or “▼ ”to move the cursor to any command menu item, and then press
the key “ENT”to enter the submenu.
4. Press the “▲ ”or “▼ ”to page up/down (if all information cannot be displayed in one
display screen, one screen can display 14 lines of information at most).
5. Press the key “◄ ”or “► ”to select pervious or next command menu.
6. Press the key “ENT”or “ESC”to exit this menu (returning to the “VALUES”menu).
2. Press the key “▲ ”or “▼ ”to move the cursor to the “REPORT”menu, and then press the
key “ENT”or “► ”to enter the menu.
3. Press the key “▲ ”or “▼ ”to move the cursor to any command menu, and then press the
key “ENT”to enter the submenu.
6. Press the key “◄ ”or “► ”to select pervious or next command menu.
7. Press the key “ENT”or “ESC”to exit this menu (returning to the “REPORT”menu).
For the fault report, view the single item fault report by the command menu
“ITEM_TRP_REPORT”, and the item fault report produces with change of any item of fault report.
The item fault report can save for 1024 events at most.
2. Press the key “▲ ”or “▼ ”to move the cursor to the “TEST MODE”menu, and then press
the key “ENT”or “► ”to enter the menu.
5. Press the key “ESC”to exit this menu (returning to the “TEST MODE”menu).
2. Press the key “▲ ”or “▼ ”to move the cursor to the “TEST MODE”menu, and then press
the key “ENT”or “► ”to enter the menu.
3. Press the key “▲ ”or “▼ ”to move the cursor to the command menu “BOARD_INFO”, and
then press the “ENT”to enter the menu.
5. Press the key “ENT”or “ESC”to exit this menu (returning to the “TEST MODE”menu).
2. Press the key “▲ ”or “▼ ”to move the cursor to the “PRINT”menu, and then press the
“ENT”or “► ”to enter the menu.
3. Press the key “▲ ”or “▼ ”to move the cursor to any command menu, and then press the
“ENT”to enter the menu.
Press the “+”or “-”to select pervious or next record. After pressing the key “ENT”,
the LCD will display “Start Printing... ”, and then automatically exit this menu
(returning to the menu “PRINT”). If the printer doesn’
t complete its current print task
and re-start it for printing, and the LCD will display “Printer Busy… ”. Press the key
“ESC”to exit this menu (returning to the menu “PRINT”).
5. If selecting the “SETTINGS”, press the key “ENT”or “► ”to enter the next level of menu.
6. After entering the submenu “SETTINGS”, press the key “▲ ”or “▼ ”to move the cursor,
and then press the key “ENT”to print the corresponding default value. If selecting any
item to printing:
Press the key “+”or “-”to select the setting group to be printed. After pressing the key
“ENT”, the LCD will display “Start Printing… ”, and then automatically exit this menu
(returning to the menu “SETTINGS”). Press the key “ESC”to exit this menu (returning to
the menu “SETTINGS”).
7. After entering the submenu “WAVEFORM”, press the “+”or “-”to select the waveform
item to be printed and press ”ENT”to enter. If there is no any waveform data, the LCD will
display “No Waveform Data!”(Before executing the command menu “HVS_WAVE”, it is
necessary to execute the command menu “TRIG_OSCILLOG” in the menu
“LOCAL_CTRL”, otherwise the LCD will display “No Waveform Data!”). With waveform
data existing:
Press the key “+”or “-”to select pervious or next record. After pressing the key “ENT”,
the LCD will display “Start Printing… ”, and then automatically exit this menu (returning to
the menu “WAVEFORM”). If the printer does not complete its current print task and
re-start it for printing, and the LCD will display “Printer Busy… ”. Press the key “ESC”to
exit this menu (returning to the menu “WAVEFORM”).
2. Press the key “▲ ”or “▼ ”to move the cursor to the “SETTINGS”menu, and then press
the key “ENT”or “► ”to enter the menu.
3. Press the key “▲ ”or “▼ ”to move the cursor to any command menu, and then press the
key “ENT”to enter the menu.
6. Press the key “◄ ”or “► ”to select pervious or next command menu.
7. Press the key “ESC”to exit this menu (returning to the menu “SETTINGS”).
NOTE:
If the displayed information exceeds 14 lines, the scroll bar will appear on the right side of
the LCD to indicate the quantity of all displayed information of the command menu and the
relative location of information where the current cursor points at.
2. Press the key “▲ ”or “▼ ”to move the cursor to the “SETTINGS”menu, and then
press the key “ENT”or “► ”to enter the menu.
3. Press the key “▲ ”or “▼ ”to move the cursor to any command menu, and then press
the key “ENT”to enter the menu.
6. Press the key “◄ ”or “► ”to select pervious or next command menu.
7. Press the key “ESC”to exit this menu (returning to the menu “SETTINGS”).
Press the key “+”or “-”to modify the value (if the modified value is of multi-bit, press
the key “◄ ”or “► ”to move the cursor to the digit bit, and then press the “+”or “-”to
modify the value), press the key “ESC ”to cancel the modification and return to the
displayed interface of the command menu “EQUIP_SETTINGS”. Press the key “ENT”
to automatically exit this menu (returning to the displayed interface of the command
menu “EQUIP_SETTINGS”).
Move the cursor to continue modifying other setting items. After all setting values are
modified, press the key “◄ ”, “► ”or “ESC”, and the LCD will display “Save or Not?”.
ESC”or press the key “◄ ”or “► ”to move the cursor. Select the
Directly press the “
“Cancel”, and then press the key “ENT”to automatically exit this menu (returning to the
displayed interface of the command menu “EQUIP_SETTINGS”).
Press the key “◄ ”or “► ”to move the cursor. Select “No”and press the key “ENT”, all
modified setting item will restore to its original value, exit this menu (returning to the
menu “SETTINGS”).
Press the key “◄ ”or “► ”to move the cursor to select “Yes”, and then press the key
“ENT”, the LCD will display password input interface.
correct, LCD will display “Save Settings… ”, and then exit this menu (returning to the
displayed interface of the command menu “EQUIP_SETTINGS”), with all modified
setting items as modified values.
NOTE:
For different setting items, their displayed interfaces are different but their modification
methods are the same.
NOTE:
2. DIFF_PROT_SETTINGS
Group NO select
Group NO To be Edited 02
Then move the cursor to the modified value and press “ENT”to enter. If the setting
[I_Pkp_PcntDiff] is selected to modify, then press the “ENT”to enter and the LCD will
+”or “-”to modify the value and then press
display the following interface. is shown the “
the “ENT”to enter.
10. If selecting the other menus, move the cursor to the setting to be modified, and then
press the “ENT”.
2. Press the key “▲ ”or “▼ ”to move the cursor to the “SETTINGS”menu, and then press
the key “ENT”or “► ”to enter the menu;
3. Press the key “▲ ”or “▼ ”to move the cursor to the command menu “COPY_SETTINGS”,
and then press the key “ENT”to enter the menu. The following display will be shown on
LCD.
Press the key “+ ”or “- ”to modify the value. Press the key “ESC”, and return to the
menu “SETTINGS”. Press the “ENT”, the LCD will display the interface for password
input, if the password is incorrect, continue inputting it, press the key “ESC”to exit the
password input interface and return to the menu “SETTINGS”. If the password is correct,
the LCD will display “Copy Settings Success!”, and exit this menu (returning to the menu
“SETTINGS ”).
Press the “+”or “- ”to modify the value, and then press the key “ESC”to exit this menu
(returning to the main menu). After pressing the key “ENT”, the LCD will display the password
input interface. If the password is incorrect, continue inputting it, and then press the key “ESC”to
exit the password input interface and return to its original state. If the password is correct, the
“HEALTHY”indicator of the protection device will go out, and the protection device will re-check
the protection setting. If the check doesn’
t pass, the protection device will be blocked. If the check
is successful, the LCD will return to its original state.
2. Press the “+”, “-”, “+”, “-”and key “ENT”; Press the key “ESC”to exit this menu
(returning to the original state). Press the key “ENT”to carry out the deletion.
NOTE:
The operation of deleting device report will delete all messages saved by the protection
device, including tripping report, alarm report and binary change report except user
operation reports (i.e. control reports). Furthermore, the report is irrecoverable after
deletion, so the function shall be used with great cautious.
2. Press the key “▲ ”or “▼ ”to move the cursor to the “CLOCK”menu, and then press the
key “ENT”to enter clock display.
CLOCK
Year 2008
Month 11
Day 28
Hour 20
Minute 59
Second 14
3. Press the key “▲ ”or “▼ ”to move the cursor to the date or time to be modified.
4. Press the key +”or “-”, to modify value, and then press the key “ENT”to save the
modification and return to the main menu.
5. Press the key “ESC”to cancel the modification and return to the main menu.
2. Press the key “▲ ”or “▼ ”to move the cursor to the “VERSION”menu, and then press the
key “ENT”to display the software version.
2. Press the key “▲ ”or “▼ ”to move the cursor to the “TEST MODE”menu, and then press
the key “ENT”or “► ”to enter the menu.
3. Press the key “▲ ”or “▼ ”to move the cursor to the command menu “COMM_TEST”, and
then press the key “ENT”to enter the menu, at this moment, the LCD will display
“Entering Communication Test… ”.
4. Press the key “▲ ”or “▼ ”to move the cursor to select the corresponding command menu
“All Test”, “Trip Test”, “Alarm Test”and “BI Test”.
5. If selecting the “All Test”, press the “ENT”, and the device will successively carry out the
“Trip Test”, “Alarm Test”and “BI Test”.
6. If selecting the “Trip Test”, “Alarm Test”or “BI Test”, press the key “ENT”.
7. Press the +”or “-”to page up/down, and then press the key “▲ ”or “▼ ”to move the
scroll bar. (taking the “Trip Test”as an example):
Move the cursor to select the corresponding protection elements. Press the key “ENT”to
execute the communication test one by one, the SAS will receive the corresponding fault
report, and view the fault report produced by communication test in the command menu
“ITEM_TRP_REPORT”. Press the key “ESC”to return to the diagram of Figure 9.4-8.
NOTE:
If no input operation is carried out within 60s, exit the communication transmission and
return to the “TEST MODE”menu, at this moment, the LCD will display “Communication
Test Timeout and Exiting...”.
If selecting the “Alarm Test”or “BI Test”, not only the SAS can receive the corresponding
self-check report or binary signals, but also the self-check report or binary signals
produced by communication test can be respectively viewed by the two command menus
of “ALM_REPORT”and “BI_CHG_REPORT”in the menu “REPORT”.
8. Press the key “ESC”to exit this menu (returning to the menu “TEST MODE”, at this
2. Press the key “▲ ”or “▼ ”to move the cursor to the “INTERFACE”menu, and then press
the key “ENT”or “► ”to enter the menu.
3. Press the key “▲ ”or “▼ ”to move the cursor to the command menu “LANGUAGE”, and
then press the key “ENT”to enter the menu and the following display will be shown on
LCD.
4. Press the key “▲ ”or “▼ ”to move the cursor to the language user preferred and press
the key “ENT”to execute language switching. After language switching is finished, LCD
will return to the menu “INTERFACE”, and the display language is changed. Otherwise,
press the key “ESC”to cancel language switching and return to the menu “INTERFACE”.
NOTE:
The LCD interface provided in this chapter is only a reference and available for explaining
specific definition of LCD. The displayed interface of the actual protection device may be
some different from it, so you shall be subject to the actual protection device.
Chapter 10 Communications
The rear EIA RS-485 interface is isolated and is suitable for permanent connection of whichever
protocol is selected. The advantage of this type of connection is that up to 32 protective devices
can be “daisy chained”together using a simple twisted pair electrical connection.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the relay.
This protective device provides two rear RS-485 communication ports, and each port has three
terminals in the 12-terminal screw connector located on the back of the relay and each port has a
ground terminal for the earth shield of the communication cable. Please refer to the section of
“Communication Interface module”for details of the connection terminals. The rear ports provide
RS-485 serial data communication and are intended for use with a permanently wired connection
to a remote control center.
The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’s connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed
definition of which terminal is which. If the master is unable to communicate with the product, and
the communication parameters match, then it is possible that the two-wire connection is reversed.
The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end
across the signal wires (refer to Figure 10.2-1). Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in which case
separate external components will not be required. However, this product does not provide such a
facility, so if it is located at the bus terminus then an external termination resistor will be required.
The EIA RS-485 standard requires that each device is directly connected to the physical cable that
is the communications bus. Stubs and tees are expressly forbidden, such as star topologies. Loop
bus topologies are not part of the EIA RS-485 standard and are forbidden by it also.
Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length
must not exceed 500m. The screen must be continuous and connected to ground at one end,
normally at the master connection point; it is important to avoid circulating currents, especially
when the cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. At no stage must the signal ground be connected to the cables
screen or to the product’
s chassis. This is for both safety and noise reasons.
10.2.1.4 Biasing
It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal
level has an indeterminate state because the bus is not being actively driven. This can occur when
all the slaves are in receive mode and the master is slow to turn from receive mode to transmit
mode. This may be because the master purposefully waits in receive mode, or even in a high
impedance state, until it has something to transmit. Jabber causes the receiving device(s) to miss
the first bits of the first character in the packet, which results in the slave rejecting the message
and consequentially not responding. Symptoms of these are poor response times (due to retries),
increasing message error counters, erratic communications, and even a complete failure to
communicate.
Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There
should only be one bias point on the bus, which is best situated at the master connection point.
The DC source used for the bias must be clean; otherwise noise will be injected. Note that some
devices may (optionally) be able to provide the bus bias, in which case external components will
not be required.
NOTE:
It is extremely important that the 120Ω termination resistors are fitted. Failure to do so
will result in an excessive bias voltage that may damage the devices connected to the
bus.
As the field voltage is much higher than that required, NR cannot assume
responsibility for any damage that may occur to a device connected to the network as
a result of incorrect application of this voltage.
Ensure that the field voltage is not being used for other purposes (i.e. powering logic
inputs) as this may cause noise to be passed to the communication network.
This protective device can provide four rear Ethernet interfaces (optional) and they are unattached
each other. Parameters of each Ethernet port can be configured in the submenu “EQUIP
SETTINGS”.
It is recommended to use twisted screened eight-core cable as the communication cable. A picture
is shown bellow.
Each equipment is connected with an exchanger via communication cable, and thereby it forms a
star structure network. Dual-network is recommended in order to increase reliability. SCADA is
also connected to the exchanger and will play a role of master station, so the every equipment
which has been connected to the exchanger will play a role of slave unit.
The IEC specification IEC60870-5-103: Telecontrol Equipment and Systems, Part 5: Transmission
Protocols Section 103 defines the use of standards IEC60870-5-1 to IEC60870-5-5 to perform
communication with protective device. The standard configuration for the IEC60870-5-103
protocol is to use a twisted pair EIA RS-485 connection over distances up to 500m. It also supports
to use an Ethernet connection. The relay operates as a slave in the system, responding to
commands from a master station.
To use the rear port with IEC60870-5-103 communication, the relevant settings of the protective
device must be configured. To do this use the keypad and LCD user interface. In the submenu
“EQUIP SETTINGS”, set the parameters [COM1_Protocol], [COM2_Protocol] and [COM_Baud].
For using the Ethernet port with IEC60870-5-103 communication, the IP address and submask of
each Ethernet port can be set in the same submenu. Please refer to the corresponding section in
Chapter “Settings”for further details.
The protective device conforms to compatibility level 2; compatibility level 3 is not supported.
Initialization (reset)
Time synchronization
General interrogation
General functions
Disturbance records
Two EIA RS-485 standardized ports are available for IEC60870-5-103 in this protective device.
The transmission speed is optional: 4800 bit/s, 9600 bit/s, 19200 bit/s or 38400 bit/s.
The link layer strictly abides by the rules defined in the IEC60870-5-103.
10.3.2 Initialization
Whenever the protective device has been powered up, or if the communication parameters have
been changed, a reset command is required to initialize the communications. The protective
device will respond to either of the two reset commands (Reset CU or Reset FCB), the difference
is that the Reset CU will clear any unsent messages in the transmit buffer.
The protective device will respond to the reset command with an identification message ASDU 5,
the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB
depending on the nature of the reset command.
The protective device time and date can be set using the time synchronization feature of the
IEC60870-5-103 protocol. The protective device will correct for the transmission delay as specified
in IEC60870-5-103. If the time synchronization message is sent as a send/confirm message then
the protective device will respond with a confirmation. Whether the time-synchronization message
is sent as a send confirmation or a broadcast (send/no reply) message, a time synchronization
class 1 event will be generated/produced.
If the protective device clock is synchronized using the IRIG-B input then it will not be possible to
set the protective device time using the IEC60870-5-103 interface. An attempt to set the time via
the interface will cause the protective device to create an event with the current date and time
taken from the IRIG-B synchronized internal clock.
The GI can be used to read the status of the relay, the function numbers, and information numbers
that will be returned during the GI cycle. The GI cycle strictly abides by the rules defined in the
IEC60870-5-103.
Refer the IEC60870-5-103 standard can get the enough details about general interrogation.
The generic functions can be used to read the setting and protection measurement of the relay,
and modify the setting. Two supported type identifications are ASDU 21 and ASDU 10. For more
details about generic functions, see the IEC60870-5-103 standard.
0001 Equip_Description
0002 Trip_Element
0003 Self-Check_Alarm
0004 Binary_Input
0005 Control
0006 System_Settings
0007 Diff_Prot_Settings
0008 HVS_REF_Settings
0009 MVS_REF_Settings
0010 LVS_REF_Settings
0011 OvExc_Prot_Settings
0012 Freq_Prot_Settings
0013 HVS_BakProt_Settings
0014 MVS_BakProt_Settings
0015 LVS_BakProt_Settings
0016 Trp_Logic_Settings
0017 VEBI_Settings
18 GOOSE_VEBI_Settings
19 Device_Settings
20 Comm_Settings
21 Equip_Descrion_Settings
22 SLD_Settings
23 Setting_Group
24 Prot_HVS_Metering
25 Prot_MVS_Metering
26 Prot_LVS_Metering
27 Diff_Corr_Curr_Metering
28 REF_Corr_Curr_Metering
29 Wdg_Corr_Curr_Metering
30 Calc_Diff_Curr_Metering
31 Calc_REF_Curr_Metering
32 Calc_WDG_Curr_Metering
33 OvExc_Metering
34 Curr_Ang_Bet_Sides_Metering
35 Volt_Ang_Bet_Sides_Metering
36 Ang_Bet_Curr&Volt_Metering
37 Diff_COrr_Curr_Ang_Meteirng
38 REF_COrr_Curr_Ang_Meteirng
39 Wdg_COrr_Curr_Ang_Meteirng
40 Disturb_Info_Analog
41 Disturb_Info_Binary00
42 Disturb_Info_Binary01
43 Disturb_Info_Binary02
44 Fault_Data
45 Control Report
set as “0”, to modify protection settings remotely will not be allowed. Moreover,
equipment parameters are not allowed to be modified remotely whether the item
[VEBI_Remote_Cfg] is “1”or “0”.
NOTE:The above table is only an example and it will change with the differential
protection configurations.
This protective device can store up to eight disturbance records in its memory. A pickup of the fault
detector or an operation of the relay can make the protective device store the disturbance records.
The disturbance records are stored in uncompressed format and can be extracted using the
standard mechanisms described in IEC60870-5-103.
The IEC60870-5-103 interface over Ethernet is a master/slave interface with the relay as the slave
device. It is properly developed by NR too. All the service of this relay is based on generic
functions of the IEC60870-5-103. The following table lists all the group number of this relay. And
this relay will send all the relevant information about group caption to the SAS or RTU after
establishing a successful communication link.
Please refer to Table 10.3-4 for detailed description of generic service group numbers.
The IEC 61850 standard is the result of years of work by electric utilities and vendors of electronic
equipment to produce standardized communications systems. IEC 61850 is a series of standards
describing client/server and peer-to-peer communications, substation design and configuration,
testing, environmental and project standards. The complete set includes:
IEC 61850-5: Communications and requirements for functions and device models
IEC 61850-7-1: Basic communication structure for substation and feeder equipment -
Principles and models
IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract
communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder equipment –
Common data classes
IEC 61850-7-4: Basic communication structure for substation and feeder equipment –
Compatible logical node classes and data classes
IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over
serial unidirectional multidrop point to point link
IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over
ISO/IEC 8802-3
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.
The PCS-978 series relay supports IEC 61850 server services over TCP/IP communication
protocol stacks. The TCP/IP profile requires the PCS-978 series to have an IP address to establish
communications.
1. MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. Actual MMS protocol services are mapped to IEC 61850 abstract services in
IEC61850-8-1.
2. Client/server
This is a connection-oriented type of communication. The connection is initiated by the client, and
communication activity is controlled by the client. IEC61850 clients are often substation computers
running HMI programs or SOE logging software. Servers are usually substation equipment such
as protection relays, meters, RTUs, transformer, tap changers, or bay controllers.
3. Peer-to-peer
IEC61850 defines an object-oriented approach to data and services. An IEC61850 physical device
can contain one or more logical device(s) (for proxy). Each logical device can contain many logical
nodes. Each logical node can contain many data objects. Each data object is composed of data
attributes and data attribute components. Services are available at each level for performing
Each IED represents one IEC61850 physical device. The physical device contains one logical
device, and the logical device contains many logical nodes. The logical node LPHD contains
information about the IED physical device. The logical node LLN0 contains information about the
IED logical device.
The GGIO logical node is available in the PCS-978 series relays to provide access to digital status
points (including general I/O inputs and warnings) and associated timestamps and quality flags.
The data content must be configured before the data can be used. GGIO provides digital status
points for access by clients. It is intended that clients use GGIO in order to access digital status
values from the PCS-978 series relays. Clients can utilize the IEC61850 buffered reporting
features available from GGIO in order to build sequence of events (SOE) logs and HMI display
screens. Buffered reporting should generally be used for SOE logs since the buffering capability
reduces the chances of missing data state changes. All needed status data objects are transmitted
to HMI clients via buffered reporting, and the corresponding buffered reporting control block
(BRCB) is defined in LLN0.
Most of analog measured values are available through the MMXU logical nodes, and metering
values in MMTR, the else in MMXN, MSQI and so on. Each MMXU logical node provides data
from a IED current/voltage “source”. There is one MMXU available for each configurable source.
MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2 provides
data from CT/VT source 2 (usually for monitor and display purpose). All these analog data objects
are transmitted to HMI clients via unbuffered reporting periodically, and the corresponding
unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical nodes provide the
following data for each source:
MMXU.ST.Hz: frequency
The following list describes the protection elements for all PCS-978 series relays. The specified
relay will contain a subset of protection elements from this list.
PTUC: undercurrent
PTOC: phase overcurrent, zero sequence overcurrent and overcurrent when CTS
PTUV: undervoltage
PTUF: underfrequency
The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pic kup)
flags “PTRC.ST.Str.general”. The operate flag for PTOC1 is “PTOC1.ST.Op.general”. For the
PCS-978 series relay protection elements, these flags take their values from related module for
the corresponding element. Similar to digital status values, the protection trip information is
reported via BRCB, and it also locates in LLN0.
Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. Most of the public services, the common settings, control
values and some device oriented data objects are available here. The public services may be
BRCB, URCB and GSE control blocks and similar global defines for the whole device; the
common settings include all the setting items of communication settings. System settings and
some of the protection setting items, which can be configured to two or more protection elements
(logical nodes). In LLN0, the item Loc is a device control object, this Do item indicates the local
operation for complete logical device, when it is true, all the remote control commands to the IED
will be blocked and those commands make effective until the item Loc is changed to false. In
PCS-978 series relays, besides the logical nodes we describe above, there are some other logical
nodes below in the IEDs:
LPHD: Physical device information, the logical node to model common issues for physical
device.
PTRC: Protection trip conditioning, it shall be used to connect the “operate”outputs of one or
more protection functions to a common “trip”to be transmitted to XCBR. In addition or alternatively,
any combination of “operate”outputs of protection functions may be combined to a new “operate”
of PTRC.
RDRE: Disturbance recorder function. It triggers the fault wave recorder and its output refers
to the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System”(IEC
60255-24). All enabled channels are included in the recording, independently of the trigger mode.
IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured
to transmit information of protection trip information (in the Protection logical nodes), binary status
values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The
reporting control blocks can be configured in CID files, and then be sent to the IED via an
IEC61850 client. The following items can be configured.
TrgOps: Trigger options. The following bits are supported by the PCS-978 series
relays:
- Bit 1: Data-change
- Bit 4: Integrity
OptFlds: Option Fields. The following bits are supported by the PCS-978 series relays:
- Bit 1: Sequence-number
- Bit 2: Report-time-stamp
- Bit 3: Reason-for-inclusion
- Bit 4: Data-set-name
- Bit 5: Data-reference
- Bit 8: Conf-revision
- Bit 9: Segmentation
MMS file services are supported to allow transfer of oscillography, event record or other files from
a PCS-978 series relay.
10.5.4.3 Timestamps
The timestamp values associated with all IEC61850 data items represent the time of the last
change of either the value or quality flags of the data item.
IEC61850 specifies that each logical node can have a name with a total length of 11 characters.
The name is composed of:
Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable.
Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is
recommended that a consistent naming convention be used for an entire substation project.
IEC61850 specifies the type of peer-to-peer data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
VLANs. Devices that transmit GOOSE messages also Devices that transmit GOOSE messages
also function as servers. Each GOOSE publisher contains a “GOOSE control block”to configure
and control the transmission.
The transmission is also controlled via device setting “GOOSE Group ID”in the setting submenu
“EQUIP SETUP”. The “GOOSE Group ID”setting item defines a definite IED group in which the
IED can communicate with each other via GOOSE protocol, and if GOOSE Group ID is configured
to “0”, GOOSE service is blocked in this IED. IEC61850 recommends a default priority value of 4
for GOOSE. Ethernet traffic that does not contain a priority tag has a default priority of 1. More
details are specified in IEC61850 part 8-1. IEC61850 recommends that the Ether-type Application
ID number be configured according to the GOOSE source.
The PCS-978series relays support IEC61850 Generic Object Oriented Substation Event (GOOSE)
communication. All GOOSE messages contain IEC61850 data collected into a dataset. It is this
dataset that is transferred using GOOSE message services. The GOOSE related dataset is
configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between PCS-978 series relays.
IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must be
correct to achieve the successful transfer of data. It is critical that the configured datasets at the
transmission and reception devices are an exact match in terms of data structure, and that the
GOOSE addresses and name strings match exactly.
Where:
C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
M: Mandatory
Where:
C2: Shall be "M" if support for LOGICAL-NODE model has been declared
C3: Shall be "M" if support for DATA model has been declared
C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has
been declared
C5: Shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
The PCS-978relays support IEC61850 logical nodes as indicated in the following table. Note that
the actual instantiation of each logical node is determined by the product order code.
Nodes PCS-978
L: System Logical Nodes
LPHD: Physical device information YES
LLN0: Logical node zero YES
P: Logical Nodes For Protection Functions
PDIF: Differential YES
PDIR: Direction comparison -
PDIS: Distance YES
PDOP: Directional overpower -
PDUP: Directional underpower -
PFRC: Rate of change of frequency -
PHAR: Harmonic restraint YES
PHIZ: Ground detector -
Nodes PCS-978
PIOC: Instantaneous overcurrent YES
PMRI: Motor restart inhibition -
PMSS: Motor starting time supervision -
POPF: Over power factor -
PPAM: Phase angle measuring -
PSCH: Protection scheme -
PSDE: Sensitive directional earth fault YES
PTEF: Transient earth fault -
PTOC: Time overcurrent YES
PTOF: Overfrequency YES
PTOV: Overvoltage YES
PTRC: Protection trip conditioning YES
PTTR: Thermal overload YES
PTUC: Undercurrent -
PTUV: Undervoltage YES
PUPF: Underpower factor -
PTUF: Underfrequency YES
PVOC: Voltage controlled time overcurrent YES
PVPH: Volts per Hz YES
PZSU: Zero speed or underspeed -
R: Logical Nodes For Protection Related Functions
RDRE: Disturbance recorder function YES
RADR: Disturbance recorder channel analogue -
RBDR: Disturbance recorder channel binary -
RDRS: Disturbance record handling -
RBRF: Breaker failure YES
RDIR: Directional element YES
RFLO: Fault locator -
RPSB: Power swing detection/blocking YES
RREC: Autoreclosing -
RSYN: Synchronism-check or synchronizing -
C: Logical Nodes For Control
CALH: Alarm handling -
CCGR: Cooling group control -
CILO: Interlocking -
Nodes PCS-978
CPOW: Point-on-wave switching -
CSWI: Switch controller -
G: Logical Nodes For Generic References
GAPC: Generic automatic process control -
GGIO: Generic process I/O YES
GSAL: Generic security application -
I: Logical Nodes For Interfacing And Archiving
IARC: Archiving -
IHMI: Human machine interface -
ITCI: Telecontrol interface -
ITMI: Telemonitoring interface -
A: Logical Nodes For Automatic Control
ANCR: Neutral current regulator -
ARCO: Reactive power control -
ATCC: Automatic tap changer controller -
AVCO: Voltage control -
M: Logical Nodes For Metering And Measurement
MDIF: Differential measurements -
MHAI: Harmonics or interharmonics -
MHAN: Non phase related harmonics or interharmonic -
MMTR: Metering -
MMXN: Non phase related measurement -
MMXU: Measurement YES
MSQI: Sequence and imbalance -
MSTA: Metering statistics -
S: Logical Nodes For Sensors And Monitoring
SARC: Monitoring and diagnostics for arcs -
SIMG: Insulation medium supervision (gas) -
SIML: Insulation medium supervision (liquid) -
SPDC: Monitoring and diagnostics for partial discharges -
X: Logical Nodes For Switchgear
TCTR: Current transformer YES
TVTR: Voltage transformer YES
Y: Logical Nodes For Power Transformers
YEFN: Earth fault neutralizer (Peterson coil) -
Nodes PCS-978
YLTC: Tap changer -
YPSH: Power shunt -
YPTR: Power transformer YES
Z: Logical Nodes For Further Power System Equipment
ZAXN: Auxiliary network -
ZBAT: Battery -
ZBSH: Bushing -
ZCAB: Power cable -
ZCAP: Capacitor bank -
ZCON: Converter -
ZGEN: Generator -
ZGIL: Gas insulated line -
ZLIN: Power overhead line -
ZMOT: Motor -
ZREA: Reactor -
ZRRC: Rotating reactive component -
ZSAR: Surge arrestor -
ZTCF: Thyristor controlled frequency converter -
ZTRC: Thyristor controlled reactive component -
The general object oriented substation event (GOOSE) defined in IEC61850 standard is based on
the fast Ethernet multi-broadcasting message transmission, taking place of the hard-wired
communication mode between classic intelligent electronic device (IED) and providing a fast,
efficient and reliable method for communication among logic nodes.
The GOOSE service supports the exchange of public data comprised of data sets, it is used to
protect the data transmission which requires high real-time like tripping, breaker position and
interlocked information. The information exchange of GOOSE service is based on the
publish/subscribe mechanism, and any IED device in the same GOOSE network can be
conducted as subscription terminal to receive data and as publication terminal to provide
data to other IED device as well, so that the increasing or modification of communication data
between IED devices can be realized in a much easier way.
The PCS-978 series devices use independent high efficient DSP board to realize GOOSE, so it
has super-high real-time property and reliability. Two 100M FDX optical fiber Ethernet interfaces
on the DSP board can be corresponded to differe nt VLAN networks. The GOOSE dual-networks
configuration improves the reliability and stability of system.
In order to ensure the real-time property and reliability of GOOSE service, GOOSE message
adopts ASN.1 code which relates to basic encoding rule (BER) and transmit data directly in
Ethernet link layer without passing through TCP/IP protocol and also adopts special
receiving/sending mechanism.
Sending of the GOOSE message adopts heartbeat message and position-altering message fast
resending combination mechanism. If the data in GOOSE data sets is not changed, the heartbeat
message whose interval is T0 will be sent, the status number (stnum) in message will not be
changed and the sequence number (sqnum) will be increased progressively. If the data in GOOSE
data set is changed, after sending a frame of position -altering message, the position-altering
message will be fast resent in the interval of T0, T1, T2, and T3. The status number (stnum) in the
message whose data is position-altered will be increased, and the sequence number (sqnum) will
be started from zero.
The GOOSE receiving can detect link interrupt according to the TATL (Time Allow to Live) in the
GOOSE message. The GOOSE data receiving mechanism can be divided into single frame
receiving and dual-frames receiving. The intelligent operation box uses dual-frames receiving
mechanism and update data after receiving two frames of messages with the same GOOSE data.
Other protection and monitoring devices use single frame receiving mechanism and update data
immediately after receiving position-altering message (stnum changed). If the status number
(stnum) in the received message is not changed, dual-frames message confirmation will be used
to update data.
GOOSE will alarm the abnormal conditions produced during receiving/sending process, the
GOOSE alarms mainly include: GOOSE network A/B network link breaking alarm, GOOSE
configuration inconformity alarm and GOOSE network A/B network-storm alarm.
The GOOSE network A/B link breaking alarm is: this alarm will be produced when correct GOOSE
message is not received in 2 times of the TATL ( Time Allow to Live).
The GOOSE configuration inconformity alarm is: the attribute of GOOSE control block of GOOSE
publisher and subscriber like configuration version number must be identical. Otherwise this
GOOSE configuration inconformity alarm will be produced.
The GOOSE network A/B network-storm alarm is: when network-storm is produced in GOOSE
network, if data flow of network port is beyond normal range and abnormal message is produced,
this GOOSE network A/B network-storm alarm will be produced.
When service status of the device is set to 1, the GOOSE message sent by the device has a Test
Flag and receiving terminal can obtain service status of sending terminal by the test flag of
message. When the service status of sending terminal conforms to that of receiving terminal, the
device will carry out normal processing to the received GOOSE data. When the service status of
sending terminal doesn’
t conform to that of receiving terminal, the device will process the received
GOOSE data accordingly to ensure that the serviced device will not influence the normal running
of device, improving the flexibility and reliability of GOOSE service.
On-load Voltage
GGIO1 SPCSO2. stVal TrStrp
Regulation Lock-out
11.1 Introduction
The chapter contains instructions on how to install, commission and maintenance the protection
equipment. It can also be used as a reference if a periodic test is performed. The chapter covers
procedures for mechanical and electrical installation, energizing and checking of external circuitry,
setting and configuration as well as verifying settings and performing a directionality test.
1) The “Safety information” presents warning and note signs, which the user should draw
attention to.
2) The “Overview”gives an overview over the major task when installing and commissioning the
protection equipment.
4) The “Installing the protection equipment” contains instructions on how to install the
protection equipment.
5) The “Checking the external circuitry” contains instructions on how to check that the
protection equipment is properly connected to the protection system.
10) The “Final check”contains instructions on how to do final check to make the equipment
ready for being put into service.
The chapter is addressing the installation, commissioning and maintenance personnel responsible
for taking the protection into normal service and out of service. The installation personnel must
have a basic knowledge in handling electronic equipment. The commissioning and maintenance
personnel must be well experienced in using protection equipment, test equipment, protection
functions and the configured functional logics in the protection.
This section contains safety information. Warning signs are presented which attend the user to be
careful during certain operations in order to avoid human injuries or damage to equipment.
Warning signs
WARNING!
Strictly follow the company and country safety regulations. Working in a high voltage
environment requires serious approach to avoid human injuries and damage to
equipment.
Do not touch circuitry during operation. Potentially lethal voltages and currents are
present.
Always avoid touching the circuitry when the cover is removed. The product contains
electronic circuitries which can be damaged if exposed to static electricity (ESD). The
electronic circuitries also contain high voltage which is lethal to humans.
Always use suitable isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present.
Never unmount the front or back cover from a powered equipment or from a protection
equipment connected to powered circuitry. Potentially lethal voltages and currents are
present.
Caution signs
CAUTION!
Always transport modules using certified conductive bags. Always handle modules using
Do not connect live wires to the protection equipment. Internal circuitry may be damaged.
Always use a conductive wrist strap connected to protective ground when replacing
modules. Electrostatic discharge (ESD) may damage the module and protection
equipment circuitry.
Take care to avoid electrical shock if accessing wiring and connection protection
equipment when installing and commissioning.
Note signs
NOTE!
Changing the active setting group will inevitably change the protection equipment’
s
operation. Be careful and check regulations before making the change.
The protection assembly is designed for a maximum continuous current of four times
rated value.
Activating the other setting group without proper configuration may seriously affect the
protection equipment’
s operation.
11.3 Overview
The settings for each function must be calculated before the commissioning task can start. A
configuration, made in the configuration and programming tool, must also be available if the
protection equipment does not have a factory configuration downloaded.
The protection equipment is unpacked and visually checked. It is preferably mounted in a cubicle.
The connection to the protection system has to be checked in order to verify that the installation
was successful.
The installation and commissioning task starts with configuring the digital communication modules,
if included. The protection equipment can then be configured and set, which means that settings
and a configuration has to be applied if the protection equipment does not have a factory
configuration downloaded. Then the operation of each included function according to applied
settings has to be verified by secondary injection. A complete check of the configuration can then
be made. A conformity test of the secondary system has also to be done. When the primary
system has been energized a directionality check should be made.
Carefully examine the protection panel, protection equipment inside and other parts
inside to see that no physical damage has occurred since installation.
Panel wiring:
Check the conducting wire used in the panel to assure that their cross section meet the
requirement. Carefully examine the wiring to see that they are no connection failure exists.
Label:
Check all the isolator links, terminal blocks, ferrules, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.
Check each plug-in module of the equipments on the panel to make sure that they are well
installed into the equipment without any screw loosened.
Earthing cable:
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator links and push buttons work normally
and smoothly.
3) Check that all items are included in accordance with the delivery documents.
The user is requested to check that all software functions are included according to the delivery
documents after the terminal has been energized.
These product checks cover all aspects of the protection, which should be checked to ensure that
the protection not only has not been physically damaged prior to commissioning but also functions
correctly and all input quantity measurements are within the stated tolerances.
11.5.1 Overview
The mechanical and electrical environmental conditions at the installation site must be within
permissible range according to the technical data of the protection equipment. Dusty, damp places,
places liable to rapid temperature variations, powerful vibrations and shocks, surge voltages of
high amplitude and fast rise time, strong induced magnetic fields or similar extreme conditions
Sufficient space must be available in front of and at rear of the protection panel to allow access for
maintenance and future modifications. Flush mounted protection equipment should be mounted
so that equipment modules can be added and replaced without excessive demounting.
11.5.2 Dimensions
The equipment adopts IEC standard chassis and is rack with modular structure. It uses an integral
faceplate and plug terminal block on backboard for external connections. PCS-978is IEC 4U high
or 8U high and 19”wide. Following figures shows dimensions and the panel cut-out of two kinds of
chassis.
101.6
177.0
179.0
465 .0
450.0
8-Ф 6.8
Switching operations in HV installations generate transient over voltages on control signal cables.
There is also a background of electromagnetic RF fields in electrical installations that can induce
spurious currents in the devices themselves or the leads connected to them.
All these influences can influence the operation of electronic apparatus. On the other hand,
electronic apparatus can transmit interference that can disrupt the operation of other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
NOTE: All these precautions can only be effective if the station ground is of good quality.
The cubicle must be designed and fitted out such that the impedance for RF interference of the
ground path from the electronic device to the cubicle ground terminal is as low as possible.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.
NOTE: If the above conditions are not fulfilled, there is a possibility of the cubicle or parts
of it forming a resonant circuit at certain frequencies that would amplify the transmission
of interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (refer to Figure 11.5-5).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
NOTE: For metallic connections please observe the voltage difference of both materials
The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip
(braided copper).
There is a ground terminal on the rear panel (refer to Figure 11.5-6), and the ground braided
copper strip can be connected with it. Take care that the grounding strip is always as short as
possible. The main thing is that the device is only grounded at one point. Grounding loops from
unit to unit are not allowed.
There are some ground terminals on some connectors of the equipments, and the sign is “GND”.
All the ground terminals are connected in the cabinet of this equipment. So, the ground terminal on
the rear panel (refer to Figure 11.5-6) is the only ground terminal of this device.
High frequency currents are produced by interference in the ground connections and because of
skin effect at these frequencies, only the surface region of the grounding strips is of consequence.
The grounding strips must therefore be of (preferably tinned) braided copper and not round copper
conductors, as the cross-section of round copper would have to be too large.
Data of braided copper strip: threaded M4, 4.0mm2. Proper terminations must be fitted to both
ends (press/pinch fit and tinned) with a hole for bolting them firmly to the items to be connected.
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
Always make sure established guidelines for this type of terminal is followed during installation.
When necessary, use screened twisted-pair cables to minimize susceptibility. Otherwise, use any
kind of regular nonscreened tinned RK cable or equivalent.
When using screened cabling always use 360° full screen cable bushing to ensure screen
coupling. Ensure that all signals of the single circuit are in the same single cable. Avoid mixing
current and voltage measuring signals in the same cable. Also use separate cables for control and
measuring circuits.
Heavy-duty terminal block, M4 threaded terminal ends. VT circuit must be connected with the
protective device through an MCB.
Auxiliary power cords can be directly screw fixed on the rear panel of power board.
Welding terminals. Those devices are supplied with sufficient M4 screws for making connections
to the rear mounted terminal blocks using ring terminals, with a recommended maximum of two
ring terminals per terminal.
To meet the insulation requirements of the terminal block, for the sake of safety, an insulating
sleeve should be fitted over the ring terminal after crimping.
The wire used for all connections to the welding terminal blocks and heavy duty terminal blocks,
except the EIA RS-485 port, should have a minimum voltage rating of 300Vrms.
It is recommended that the auxiliary power circuit wiring should be protected by using a 16A high
rupture capacity (HRC) fuse of type NIT or TIA. For safety reasons, current transformer circuits
must never be open.
Connect the unit to the grounding bar of the cubicle with green/yellow conductor; connected to the
protective Earthing terminal at the back of the PWR board. Attend that the earth wire must be as
short as possible. All cautions have to be taken to ensure the best electrical conductivity,
particularly the contact quality, stainless conductor. The impedance between the equipment
Earthing terminal and the Earth must be less than 20mΩ under 12Volt, 50Hz. What matters is that
the device has to be only grounded at one point. Loop grounding from unit to unit is not allowed.
Connectors are generally color coded; connect blue or dark grey cable connectors to blue or dark
grey (receive) back-side connectors. Connect black or grey cable connectors to black or grey
(transmit) back-side connectors.
Fiber optical cables are sensitive to handling. Do not bend too sharply. The minimum curvature
radius is 15 cm for plastic fibers and 25 cm for glass fibers. If cable straps are used, apply with
loose fit.
NOTE: Always hold the connector, never the cable, when connecting or disconnecting
optical fibres. Do not twist, pull or bend the fibre. Invisible damage may increase fibre
damping thus making communication impossible.
When using galvanic connection between the synchronizer equipment and communication
equipment or point-to-point galvanic connection between two equipments it is essential that the
cable installation is carefully done. This is true regardless of type of module used, only the
possible length of the cable differs. The factors that must be taken into account is the susceptibility
for noise disturbance, due to that the levels of the communication signal are very low. For a best
result, a cable with twisted pairs with screen should be used.
The user must check the installation, which includes verifying that the relay is connected to the
other parts of the protection system. This is done with the relay and all connected circuits
de-energized.
Check that the wiring is in strict accordance with the supplied wiring diagram.
Polarity check
Grounding check
The polarity check verifies the integrity of the circuits and the phase relationship. The check should
be performed as close as possible to the relay. The primary injection test verifie s the CT ration and
the wiring all the way through from the primary system to the relay. Injection must be performed for
each phase-to-neutral circuit and each phase-to-phase pair. In each case currents in all phases
and the neutral line are measured.
Check that the value of the auxiliary supply voltage remains with the permissible range under all
operating conditions. Check that the polarity is correct according to the instruction manual on the
rear plate of PWR board.
Preferably, disconnect the binary input connector form the binary input cards. Check all connected
signals so that both input level and polarity are in accordance with the relay’
s specifications.
NOTE: The binary inputs may be energized from an external dc auxiliary supply (e.g. the
station battery) in some installations. Check that this is not the case before connecting
the field voltage otherwise damage to the protection may result. The status of each binary
input can be viewed using either PCS-PC software installed in a portable PC or by
checking the front man-machine interface LCD. When each binary input is energized the
display will change to indicate the new state of the inputs.
Preferably, disconnect the binary output connector form the binary output cards. Check all
connected signals so that both load and polarity are in accordance with the relay’
s specifications.
Before the procedures in this section can be carried out the connection to external circuitry must
have been checked which ensures that the installation was made correctly.
The user must energies the power supply to the relay to start it up. This could be done in a
numerous of ways, from energizing a whole cubicle to energizing a single relay. The user should
reconfigure the relay settings. The relay time must be set. The self -supervision function should
also be checked to verify that the relay unit operates properly. The user could also check the
software version, the relay’
s serial number, the installed modules, and their ordering number to
ensure that the relay is according to delivery and ordering specifications.
Connect the relay to DC power supply correctly and turn the relay on. Check program version and
forming time displayed in command menu to ensure that are corresponding to what ordered.
If the time and date is not being maintained by substation automation system, the date and time
should be set manually.
Set the date and time to the correct local time and date using menu item “CLOCK”. Refer to the
section “Adjust the Clock”for detailed procedures.
In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date will
be maintained. Therefore when the auxiliary supply is restored the time and date will be correct
and not need to set again.
To test this, remove the auxiliary supply from the relay for app roximately 30s. After being
re-energized, the time and date should be correct.
On power up, the green LED “HEALTHY”should have illuminated and stayed on indicating that
the protective device is healthy.
The relay has latched signal relays which remember the state of the trip, auto-reclose when the
relay was last energized from an auxiliary supply. Therefore these indicators may also illuminate
when the auxiliary supply is applied. If any of these LEDs are on then they should be reset before
proceeding with further testing. If the LED successfully reset, the LED goes out. There is no testing
required for that that LED because it is known to be operational.
It is likely that alarms related to voltage transformer supervision will not reset at this stage.
The customer specific values for each setting parameter have to be available. Each function
included in the relay has several setting parameters which has to be set in order to make the relay
behave as intended. A default value is provided for each parameter from factory.
Download from a PC or laptop with PCS-PC software or remotely by SCADA. Front port
communication has to be established before the settings can be downloaded.
Input manually through the local HMI (refer to section “Input Operation through Keypad”).
To change settings through the local HMI need a password which is “+”, “◄ ”, “▲ ”and “-”keyboard
on the front panel.
Unless previously agreed to the contrary, the customer will be responsible for determining the
application-specific settings to be applied to the protection and for testing of any scheme logic
applied by external wiring and/or configuration of the protection’
s internal programmable scheme
logic.
This test should only be performed where the protection is to be accessed from a remote location
and will vary depending on the communications standard being adopted.
It is not the intention of the test to verify the operation of the complete system from the relay to the
remote location, just the protection’ s rear communications port and any protocol converter
necessary.
Multifunctional dynamic current and voltage injection test set with interval timer.
Multimeter with suitable AC current range and AC/DC voltage ranges of 0-440V and 0-250V
respectively.
NOTE: Modern test set may contain many of the above features in one unit.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500 V (for
insulation resistance test when required).
A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).
At the same time, the calculated settings, substation configuration diagram, the protective device
diagram and the instruction manual is essential to test the protective device.
The equipment has to be set before the testing can start. Only the functions that are used should
be tested.
All used setting groups should be tested. The user can release the functions to be tested and
prevent other functions from operation by setting the corresponding parameters. The user could
also energize the binary input [BI_BlkComm] to disable communication function to ensure that no
events are reported to remote station during the test.
The setting checks ensure that all of the application-specific protection settings (i.e. both the
protection’
s function and programmable scheme logic settings), for the particular installation, have
been correctly applied to the protection.
Insulation resistance tests are only necessary during commissioning if it is required for them to be
done and they have not been performed during installation.
Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:
DC power supply
Output contacts
Communication ports
This test verified that the accuracy of current measurement is within the acceptable tolerances.
Apply rated current to each current transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the relays menu.
The measurement accuracy of the protection is 2.5% or 0.02In. However, an additional allowance
must be made for the accuracy of the test equipment being used.
NOTE: The closing circuit should remain isolated during these checks to prevent
This test verified that the accuracy of voltage measurement is within the acceptable tolerances.
Apply rated voltage to each voltage transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the relays menu.
The measurement accuracy of the relay is 2.5% or 0.1V. However an additional allowance must be
made for the accuracy of the test equipment being used.
NOTE: The closing circuit should remain isolated during these checks to prevent
This test checks that all the binary inputs on the equipment are functioning correctly.
The binary inputs should be energized one at a time, see external connection diagrams for
terminal numbers.
Ensure that the voltage applied on the binary input must be within the operating range.
The status of each binary input can be viewed using relay menu. Sign “1”denotes an energized
input and sign “0”denotes a de-energized input.
Test method:
To unplug all the terminals sockets of this protective device, and do the Insulation resistance test
for each circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection.
In order to acquire the details of protection operation, it is convenient to print the fault report of
protection device. The printing work can be easily finished when operator presses the print button
on panel of protection device to energize binary input [BI_Print] or operate control menu. What
should be noticed is that only the latest fault report can be printed if operator presses the print
button. A complete fault report includes the content shown as follows.
3) Self-check and the transition of binary input in the process of devices start
After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been
necessary to disconnect any of the external wiring from the protection in order to perform the
wiring verification tests, it should be ensured that all connections are replaced in accordance with
the relevant external connection or scheme diagram.
If the protection is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the protection is put into service.
Ensure that all event records, fault records, disturbance records and alarms have been cleared
and LED’
s has been reset before leaving the protection.
Chapter 12 Maintenance
NR numerical relay PCS-978is designed to require no special maintenance. All measurement and
signal processing circuit are fully solid state. All input modules are also fully solid state. The output
relays are hermetically sealed.
Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows for a corrective
rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals are
not required.
Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.
It is only allowed to plug or withdraw relay board when the supply is reliably switched off. Never
allow the CT secondary circuit connected to this equipment to be opened while the primary system
is live when withdrawing an AC module. Never try to insert or withdraw the relay board when it is
unnecessary.
Check weld spots on PCB whether they are well soldered without any rosin joint. All dual inline
components must be well plugged.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the event record.
Failures detected by supervision are traced by checking the “ALM REPORT”screen on the LCD.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name (AI, PWR, CPU, SIG, BI, BO,
etc.) and hardware type-form as the removed module. Furthermore, the CPU module replaced
should have the same software version. In addition, the AI module, PWR module, BI module, IO
module and RLY module replaced should have the same ratings.
The module name is indicated on the top front of the module. The software version is indicated in
LCD menu “VERSION”.
earthed wrist band and placing modules on an earthed conductive mat. Otherwise, many
of the electronic components could suffer damage. After replacing the CPU module, check
the settings.
1) Replacing a module
Short circuit all AC current inputs and disconnect all AC voltage inputs
WARNING: Hazardous voltage can be present in the DC circuit just after switching off the
Unplug the ribbon cable on the front panel by pushing the catch outside.
After replacing the CPU module, input the application-specific setting values again.
WARNING: Units and modules may only be replaced while the supply is switched off
and only by appropriately trained and qualified personnel. Strictly observe the basic
precautions to guard against electrostatic discharge.
earthed wrist band and placing modules on an earthed conductive mat. Otherwise,
many of the electronic components could suffer damage. After replacing the CPU
module, check the settings.
DANGER: After replacing modules, be sure to check that the same configuration is set
as before the replacement. If this is not the case, there is a danger of the unintended
operation of switchgear taking place or of protections not functioning correctly. Persons
may also be put in danger.
12.5 Cleaning
Before cleaning the relay, ensure that all AC/DC supplies, current transformer connections are
isolated to prevent any chance of an electric shock whilst cleaning. Use a smooth cloth to clean
the front panel. Do not use abrasive material or detergent chemicals.
12.6 Storage
The spare relay or module should be stored in a dry and clean room. Based on IEC standard
60255-6 the storage temperature should be from-40°C to 70°C, but the temperature of from -10°C
to 40°C is recommended for long-term storage.
13.1 Decommissioning
To switch off the PCS-978, switch off the external miniature circuit breaker of the power supply.
DANGER: Before disconnecting the power supply cables that connected with the PWR
module of the PCS-978 make sure that the external miniature circuit breaker of the power
supply is switched off.
DANGER: Before disconnecting the cables that are used to connect analog input module
with the primary CTs, make sure that the primary CTs aren’
t in service.
13.1.3 Dismantling
The PCS-978rack may now be removed from the system cubicle, after which the cubicles may
also be removed.
DANGER: When the station is in operation, make sure that there is an adequate safety
13.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
NOTE: Strictly observe all local and national regulations when disposing of the device.
Software Manual
Source Documentation
Release Release
PCS-978_Instruction Manual_General_R1.00
R1.00
(EN_YJBH5100.0086.0001).doc
R1.00
PCS-978_Instruction Manual_General_R1.01
R1.01
(EN_YJBH5100.0086.0002).doc
Manual
Section Page No. Description of change Note
Release
R1.00 Original release
Modify protection theory, settings and logic
R1.01 3.6 83~89 diagram of undervoltage protection and
underfrequence protection
Adding description of settings calculation and
3.13 148~152
configuration.
Modify the correction coefficient calculation
methods of current differential protection, restricted
Chapter 3 21~188
R1.01 earth fault protection and winding differential
protection.
The polarity of zero-sequence CT at neutral point is
All the
changed to be at transformer side and modify the
menu
corresponding figures and descriptions.