Professional Documents
Culture Documents
978-1-7281-3398-0/19/$31.00
Authorized licensed use limited to: Centro©2019 IEEE
Universitário Fei. Downloaded on August 27,2020 at 16:15:11 UTC from IEEE Xplore. Restrictions apply.
2019 22nd International Conference on Electrical Machines and Systems (ICEMS)
Based on the simulation analysis, the transformer overload When the transformer is overloaded, various changes will
capability is evaluated occur in the internal structure of the transformer, which will
accelerate the insulation aging of the transformer and reduce
II. THEORETICAL ANALYSIS OF TRANSFORMER the service life. The internal impact under the short-term
OVERLOAD emergency load is as follows:
A. The Characteristics and Impact of the Load Type Under the short-term emergency load, the temperature
There are many types of oil-immersed distribution will rise sharply, and the internal components will see
transformers. Different classification standards have different a large mechanical stress, which will cause partial
classifications. In the oil-immersed transformer load guide, cracking of the epoxy resin and severely reduce the
the load is classified into normal periodic load, long-term first- insulation capacity.
aid load, short-term first-aid load according to the magnitude
The overload current under short-term emergency load
of the load overload and the action time.
shows short-term and repeatability, which will cause
The current and temperature limits are shown in Table I in serious mechanical damage to the winding.
different insulation system temperatures.
When the temperature rises to a certain extent, the
The characteristic of normal periodic load is that during a mechanical properties will be degraded, resulting in a
certain period of a cycle, the load acting on the transformer greatly reduced insulation capability and short-circuit
and the internal temperature is higher, and the relative heat resistance of the transformer.
aging rate is greater than 1; However, in another period of time,
the applied load and temperature is lower, and the relative heat The internal impact under the short-term emergency load
aging rate is lower than 1; If the aging value of the period is as follows:
when the relative heat aging rate is greater than 1 can be When the internal temperature of the transformer is higher,
compensated by that less than 1, it can be considered that the the thermal aging of the mechanical and insulating properties
load has the same effect on the transformer as the rated load, of the conductor will be accelerated, and the degree of aging
and it is not necessary to evaluate the overload capability will be accumulated to a certain extent, which will reduce the
under the normal periodic load. insulation life of the transformer, especially when the
electrical equipment is short-circuited
TABLE I. MAXIMUM HOT SPOT TEMPERATURE AND CURRENT OF
DRY TRANSFORMER B. Hot spot temperature model theory and life loss analysis
Insulation System Maximum Winding Peak Hot Spot of dry transformer
Temperature(℃) Current Temperature (℃) The relationship between the hot spot temperature function
(p,u,)
105(A) 1.5 130
under continuous stable overload can is as follow[10]:
HS a HS (1)
120(E) 1.5 145
When the cooling method of the transformer is natural-air-
130(B) 1.5 155
cooled, the temperature rise of the hot spot under the given
155(F) 1.5 180 load is as follow:
HS = HS r I
180(H) 1.5 205 2m
(2)
200 1.5 225
When the cooling method of the transformer is forced-air-
220 1.5 245 cooled, the temperature rise of the hot spot under the given
The long-term emergency load is a type of load that occurs load is as follow:
due to the long-term exit of some equipment. This operation HS HS r I 2 CT
X
(3)
may last for several weeks or months, which will accelerate
the aging of the transformer, but does not directly endanger TK HS
the insulation safety. It usually occurs when the transformer is CT (4)
TK HS r
out of operation for a long time due to malfunction or overhaul,
the system mode is changed, and the load is increased, and the Where HS is the hot spot temperature rise under a given
new transformer cannot be put into operation in a short period load, HS r is the hot spot temperature under the rated load,
of time. Due to the overload mode, the internal temperature of I is the load rate, CT is the resistance temperature correction
the transformer will reach a steady state, so the overload
capacity can only be evaluated from the allowable overload coefficient, m is the empirical coefficient, a is the ambient
multiple. temperature, HS is the hot spot temperature at a given load
Short-term emergency load is caused by a fault in the rate, TK is the temperature constant of the conductor, X is the
power system, resulting in a serious change in load forcing Air cooling experience coefficient
distribution, causing severe overload in a short period of time.
This type of load can cause the internal temperature of the The hot spot temperature function relationship under
transformer to reach a dangerous level, resulting in faster transient overload is as follow:
aging of the transformer insulation. Therefore, in this load t
mode, the transformer overload capability is comprehensively t U i 1 e i (5)
evaluated from the allowable overload multiple and the
allowable overload time. HS t a (6)
Authorized licensed use limited to: Centro Universitário Fei. Downloaded on August 27,2020 at 16:15:11 UTC from IEEE Xplore. Restrictions apply.
2019 22nd International Conference on Electrical Machines and Systems (ICEMS)
C ( HS r e )
= (7)
Pt
Where i is the initial hot spot temperature rise at the
beginning of a load rate, t is the hot spot temperature rise
after the load change time, U is the final hot spot
temperature rise when the load rate I n does not change, t is
the time, is the time constant of the winding under a given
load, e is the influence of the iron core on the temperature
Fig. 2. The magnetic flux and magnetic induction density distribution in
rise of the winding hot spot when it is no-load, C is the the quarter cycle (0.005 s)
effective capacity of the winding, Pt is the total loss of the
winding under rated load and rated temperature rise. It can be seen from the figure that at 0.05s, there is almost
no magnetic field line inside the B-phase iron core, and the
III. EVALUATION OF TRANSFORMER OVERLOAD magnetic induction density is close to 0; The distribution of
CAPABILITY magnetic field lines and the distribution of magnetic induction
density inside the A-phase and C-phase iron cores are
A. Simulation Analysis Of Magnetic Field In Dry approximately symmetrically distributed; When the overload
Transformer Overload current reaches 1.2 times, the minimum magnetic flux of A
In this paper, the transient field of the dry type transformer and C phase cores is 0.0028115 Wb/m, the maximum
of type SCB10-50/10 is simulated the ANSYS finite element magnetic field line is 0.19979 Wb/m, the minimum magnetic
analysis software, and the 2DMaxwell model is built. When induction density of A and C phase cores is 0.13551 T, and
the transformer is overloaded, the internal magnetic lines and the maximum magnetic induction density is 2.0325 T.
magnetic flux changes are analyzed. The transformer model When the overload current reaches 1.5 times, the internal
and dimensional parameters are shown in the Fig.1 and table magnetic flux and magnetic induction density distribution of
II respectively. the transformer in the one-half cycle (0.01s) are shown in Fig.
3.
TABLE II. DIMENSIONAL PARAMETERS OF THE TRANSFORMER It can be seen from the figure that at 0.01s, the internal
2DMAXWELL MODEL magnetic lines of the A-phase iron core are most closely
distributed, and the magnetic induction density is the largest;
Parameter Length (mm) The internal magnetic field lines of the C-phase iron core are
Core diameter 100
the most sparse, and the magnetic induction density is the
smallest; When the overload current reaches 1.5 times, the
Core height 640 maximum value of the A-phase magnetic line distribution is
Core length 540 0.19995 Wb/m, and the maximum magnetic induction density
is 2.0353T.
Core air gap height 440
Core air gap width 120 In order to more clearly analyze the distribution of internal
magnetic lines during transformer overload, the horizontal
Winding height 340 direction of the longitudinal middle of the A-phase core is
Low voltage winding width 3 selected as the research path, and the curve of magnetic flux
High voltage winding width 6
and magnetic induction density is plotted as shown in the Fig.
4 and Fig. 5.
Epoxy resin thickness 1
It can be seen from the figure 4 that the magnetic field
By applying different overload ratio current excitations, lines in the middle part of the A-phase iron core gradually
the changes of magnetic lines and magnetic induction density increase in the horizontal direction, showing a linear
inside the transformer under different overload ratios can be distribution characteristic, with a minimum value of 0.005
obtained. When the overload current reaches 1.2 times, the Wb/m at 0 mm and a maximum value of 0.199 Wb/m at 100
magnetic flux and magnetic induction density distribution mm.
inside the transformer in the quarter cycle (0.005 s) are shown
in Fig. 2. It can be seen from the figure 5 that the magnetic induction
Authorized licensed use limited to: Centro Universitário Fei. Downloaded on August 27,2020 at 16:15:11 UTC from IEEE Xplore. Restrictions apply.
2019 22nd International Conference on Electrical Machines and Systems (ICEMS)
It can be seen from the figure 6 that when the initial load
rate is the same, the overload ratio is inversely proportional to
the allowable overload time. The longer the overload time, the
smaller the overload ratio is allowed. As the initial load rate
increases, the overload capacity of the dry-type transformer
gradually decreases. Under the same overload ratio, the
allowable overload time gradually decreases with the increase
of the initial load rate. When the ambient temperature is 20 °
C and the initial load factor is 0.6, if the transformer overload
ratio is limited to 1.5, the allowable overload time is 1000 s,
and the transformer overload ratio is limited to 2, the
allowable overload time is 556 s.
Fig. 4. The magnetic flux distribution of the A-phase core in the
horizontal direction
Fig. 5. The magnetic induction density distribution of the A-phase core in Fig. 7. The overload capacity of transformer when the ambient
the horizontal direction temperature is 40°C
density of the middle part of the A-phase core is almost Comparing the two figures, it can be seen that the ambient
constant in the horizontal direction, with a minimum value of temperature affects the overload capacity of the transformer,
1.96407T at 0mm and a maximum value of 1.96421T at mainly reflected in the impact of the initial load rate under
100mm. other identical conditions. When the ambient temperature is
B. Evaluation Of Transformer Overload Capability 40°C and the initial load ratio is 0.9, if the transformer
overload ratio is limited to 1.5, the allowable overload time is
Based on the internal magnetic field simulation analysis of 500 s. When the transformer overload ratio is limited to 2, the
the transformer overload in the previous section, combined allowable overload time is 254s.
with the hot spot temperature model in the second chapter, the
overload capacity of the dry transformer can be analyzed and IV. CONCLUTION
calculated, and the overload time allowed under different
overload multiples can be obtained. The ambient temperature When the dry distribution transformer is overloaded, the
is an important factor affecting the overload capacity of the internal temperature will rise sharply, the insulation aging will
transformer. This paper analyzes the overload capacity when be accelerated, the service life will be reduced, and the
the ambient temperature is 20 °C and 40 °C respectively. In transformer will be damaged in serious cases, which will
the two cases, the relationship between the overload ratio and affect the safe and stable operation of the distribution network.
the overload time of the dry transformer is shown in the Fig. Based on the hot spot temperature calculation model in
6 and Fig. 7. GBT 1094.12-2013 standard, this paper analyzes the overload
theory of transformers in detail. In the ANSYS software, the
internal magnetic field of the transformer is simulated when
the transformer is overloaded, and the internal magnetic lines
and magnetic induction density are compared under different
overload multiples. Based on the simulation analysis, the
transformer overload capability is evaluated and the
conclusions are as follows: When the ambient temperature is
20 ° C and the initial load factor is 0.6, if the transformer
overload ratio is limited to 1.5, the allowable overload time is
1000 s, and the transformer overload ratio is limited to 2, the
allowable overload time is 556 s. When the ambient
temperature is 40°C and the initial load ratio is 0.9, if the
transformer overload ratio is limited to 1.5, the allowable
overload time is 500 s. When the transformer overload ratio is
limited to 2, the allowable overload time is 254s.
Fig. 6. The overload capacity of transformer when the ambient ACKNOWLEDGMENT
temperature is 20 °C
Authorized licensed use limited to: Centro Universitário Fei. Downloaded on August 27,2020 at 16:15:11 UTC from IEEE Xplore. Restrictions apply.
2019 22nd International Conference on Electrical Machines and Systems (ICEMS)
This work was supported by Scientific Research Project of [6] K. Guangzhao. “Analysis of Epoxy Resin Vacuum Pressure Casting
China Railway Fourth Survey and Design Institute Group Dry Type Transformer,” Equipment Management and Maintenance,
vol 19, no 23, pp. 151-152, 2018.
Company Limited(2018K055). Yuning Hou is the
[7] G. Yinjun, L. Yan, L. “Naisheng. Calculation of Temperature Rise of
corresponding author. Amorphous Alloy Dry-type Transformer,” Transformer, vol 55, no 6,
pp. 1-5, 2018
REFERENCES
[8] T. Jinquan, C. Dingguo, Y. Xiangjiang. “Study on Thermal Time
[1] W. Wenheng. “Application Status and Future Development of Dry- Constant of Casting Winding of Epoxy Dry-type Transformer,”
type Transformers,”.Journal of Baotou Vocational and Technical Transformer, vol 55, no 6, pp. 21-24, 2018
College, vol 10, no 3, pp. 11-13, 2009. [9] G. Zhiwei, Y. Yan, W. Minmin. “Influence of temperature and
[2] X. Lingwei, M. Baoquan, G. Jianping. “Temperature Field Analysis of moisture on the aging of dielectric properties of mine dry-type
Resin Cast Dry-type Transformer,” Electrical Engineering, vol 19, no transformer Nomex insulation paper,” Transformer, vol 55, no 5, pp.
9, pp. 56-57, 2019 14-20, 2018
[3] L. Siwei, Y. Jiliang. “Evaluation of Heat Aging of Dry Type [10] General Administration of Quality Supervision, Inspection and
Transformers,” Transformer, vol 56, no 3, pp. 62-66, 2019. Quarantine of the People's Republic of China. GB/T 1094.12-2013
[4] K. Lin. “Analysis of overheating causes and remedial measures of dry- “Loading guide for dry-type power transformers”. Beijing: China
type transformer core,” Electromechanical information, vol 10, no 8, Standard Press, 2013.
pp. 25-26, 2019
[5] Z. Yuhua, F. Si. “Numerical Analysis of Temperature Field of Dry-
type Transformer Based on Fluid-Solid Thermal
Coupling,” .Transformer, vol 56, no 1, pp. 53-56, 2019.
Authorized licensed use limited to: Centro Universitário Fei. Downloaded on August 27,2020 at 16:15:11 UTC from IEEE Xplore. Restrictions apply.