Continuous Thermal Overloading Capabilities of Ester Oil Transformers in Oil Directed Cooling Conditions
Continuous Thermal Overloading Capabilities of Ester Oil Transformers in Oil Directed Cooling Conditions
Abstract— The prediction of temperature distribution in to estimate the thermal parameters of transformer during
ester oil (natural and synthetic ester oil) filled transformer due normal and continuous over loading conditions in ester oil
to different types of cooling modes are important for thermal with respect to mineral oil.
designer in order to utilize the ester oil benefits of
Different types of cooling methods for transformer are
biodegradable, fire safety substations and continuous
overloading capabilities with respect to mineral oil. It is still a
generally developed based on quantity of heat to be handled
technical challenge for ester oil to utilize in transformers since with a suitable heat exchanger [1,2,8]. Hence, thermal
higher viscosity of ester oil will leads to reduce the heat performance of transformer windings relies on the
transfer process mainly in convection. With the ester oil in a continuous circulation of oil through different cooling
transformer, there will be reduction of convection fluid modes between radiator / cooler and winding. In oil
currents which leads to higher temperature in top forced/natural (OF/ON) cooling modes of transformer, oil
temperature oil and winding temperature rise in ester oil filled flow and heat transfer are strongly interconnected. Hence,
transformers. In this paper, the effects of mineral oil and ester buoyancy force and hot-streak dynamics play major roles to
oil on top oil rise, winding rise and hot-spot temperature estimate the oil flow distribution. In OD cooling modes, oil
arising from their potentially different thermal properties are flow and heat transfer are weakly interconnected [1,2].
investigated using Thermal hydraulic network model (THNM) Hence, the oil flow and temperature distributions in disc-
on 60/75/90MVA, 220/33kV transformer. The power losses are type transformer windings are analyzed in 60/75/90MVA,
calculated from FEM based simulations and experimental 220/33kV transformer under the influence of mineral oil,
data for thermal analysis using THNM model. The direct natural ester oil and synthetic ester oil on different cooling
impact of oil flow rate and total pressure drop over the modes of ONAN (for mineral oil transformer) / KNAN
windings in oil directed (OD) cooling modes are analyzed (ester oil transformer), ONAF/KNAF and ODAF/KDAF.
under rated loading and 120% continuous overloading
THNM models are used based on physical principles of
capabilities (108MVA) with respect to mineral oil.
conservation of mass, momentum and energy to estimate the
Keywords—Transformer winding, Ester oil, Thermal analysis prediction of top oil temperature, winding gradient, oil flow
of transformer, transformer overloading, transformer cooling, rate and hot-spot temperature above ambient temperature
Temperature rise test. thereby avoiding expensive experiments. THNM model
provides the temperature distribution in very short time with
I. INTRODUCTION an intermediate thermal solutions and accuracy between
The prediction of hot-spot temperature (highest simple design principles and computational fluid dynamics
temperature in the winding) is of great interest for thermal (CFD) [7].
designer and utilities since it will cause thermal degradation
of the insulation [1]. The uncontrolled hot-spot temperature II. TRANSFORMER OIL
resulting from poor thermal design or continuous The oil flow distribution in a disc type of winding in a
overloading of the transformer above the design value of power transformer has a direct impact on the thermal
temperature limits will lead to deterioration of winding performance of transformer which, in conjunction with
insulation and resulting in a complete thermal failure of the power loss distribution in the transformer winding (copper
transformer [1,2]. Hence, hot-spot temperature is the main loss and stay loss), determines the location and amplitude of
parameter to estimate the continuous over loading hot spot temperature [1,2,8-10]. Hence, principle for cooling
capabilities and longevity of the transformer (with the of transformer is transferring the generated heat due to
exception of premature failure) [1-5]. power losses from core and windings to an appropriate heat
In the recent years, transformer filled with ester oil are transfer agent such as liquid dielectrics (oil). The liquid
increasingly being used as dielectric coolant in addition to dielectric will carry the temperature through both
traditional mineral oil for transformers due to its advantages convection and conduction principles generated from
of reduced fire, ecofriendly, extended life of transformer and different types of windings and core to external cooling
continuous over loading capabilities [1-2]. The physical, components of radiator, conservator and cooling fans. The
chemical and thermal properties of ester oil are different dissipation of heat is usually facilitated by continuous
from mineral oil [6,7]. In order to get the continuous circulation of oil between the winding and the
overloading capabilities of ester oil, prediction of the cooler/radiator. Hence, selection of appropriate heat
temperature distribution and hot-spot temperature within the transfer agent to act as a coolant is essential for transformer
transformer winding is crucial due to higher viscosity of applications [6,7].
ester oil. Hence, it will be great interest for thermal designer
Authorized licensed use limited to: Centro Universitário Fei. Downloaded on August 27,2020 at 16:10:35 UTC from IEEE Xplore. Restrictions apply.
The significant experience has been gained to determine temperature. In this study, the effect of bulging is also
the physical, chemical and thermal properties of commonly considered based on manufacturing practice to decide the
used petroleum based mineral oil [6], With increasing radial depth of the windings. To extend the life of the ester
interest in ester oil as a substitute for mineral oil, it is oil transformer, thermally upgraded paper is considered for
important to ensure that ester oil has adequate and winding conductors in order to get the benefits of ester oil.
acceptable properties for transformer applications since the In disc type transformer winding, oil is circulated through
chemical composition of ester oil is different from mineral a given radial and axial cooling duct to carry the heat from
oil. Generally, viscosity of the oil plays a major role in winding to external cooling medium [1,2,15-21]. Hence, oil
cooling, other than specific heat and thermal conductivity flows vertically upward from bottom of the winding to top
mainly in naturally cooled systems [6]. Ester oil is three of the windings through radial and axial cooling ducts. The
times viscous in nature with respect to mineral oil. The oil horizontal oil ducts between discs plays a significant role to
flow rate will be lower and further influence (or worsen) the transfer the heat from the windings than vertical ducts since
thermal performance of transformer (Table I). In addition, the width of the vertical cooling ducts are much shorter and
the thermal conductivity is higher than mineral oil and it it has only a single contact surface with the heat source.
will support for heat dissipation to some extent. If Therefore, oil flow distribution in the radial cooling duct
temperature of the oil increases, viscosity and thermal and axial cooling duct should be designed to match with loss
conductivity will decrease linearly whereas the specific distribution. Hence, design and dimensioning of axial and
thermal capacity increases. In addition, higher viscous radial cooling ducts has judiciously done in this transformer,
nature of ester oil may be useful to suppress the reverse flow which is based on typical manufacturing practices [1,2].
of oil in oil directed cooling modes and flow distribution Hence, radial cooling duct of 3mm for LV winding of
will be more uniform at the cost of a higher pressure drop continuous double disc with epoxy bounded CTC and 4.5
[1,2]. Ester oil has higher temperature stability to provide mm for HV winding of counter shield disc winding is
the higher overloading capabilities and greater solubility of provided.
water than mineral oil.
A relatively more uniform flow distribution is always
TABLE I. THERMAL PROPERTIES OF TRANSFORMER OIL desired in OD cooling mode through proper placement of oil
guiding washer and oil seal (oil guiding strips) to avoid
Thermal parameters of oil Mineral Ester oil potential localized overheating. Hence, 1.5mm thickness of
at 20oC oil oil guiding washer and oil seal are used inner diameter and
Natural Synthetic
ester oil ester oil outer diameter of each winding to cool the windings
Density in kg/m³ 0.89 0.91-0.92 0.97 effectively at the entrance and exit of each oil circulation
pass. The oil guiding washer and oil seal will act as an oil
Kinematic viscosity in 22 78-97 70
mm²/sec stopper in a vertical duct from one side and it will allow the
oil to pass into or out from the opposite side. Hence, oil flow
Thermal conductivity in 0.126 0.160- 0.144
W/kgoC 0.167
is directed in a zig-zag fashion with 6 passes in LV
windings and 9 passes in HV windings. Hence, the location
Specific heat in J/kg oC 1860 1943 1880 and number of oil guiding washers are properly selected
based on past experiences with THNM model analysis.
III. TRANSFORMER WINDING UNDER CONSIDERATION FOR
THERMAL ANALYSIS B. External cooling mode
Thermal modeling of transformer plays a major role for In this 60/75/90MVA, 220/33kV transformer, center to
the thermal performance of transformer during thermal center height of 16 radiator (hot dipped galvanized) and
design stage [11-14]. The transformer components can be number of fins per radiator are 3100mm and 30 respectively.
separated into internal and external components for thermal The 520mm width of radiator is utilized. The heat
modelling of transformer. All components outside tank are dissipation per fins at oil temperature of 50oC is 851W in
external components like radiators, condenser bushings, air natural and 1438W in air forced conditions. The cooling
conservator, external cooling pumps and fans. Internal surface area of the fins are 2.64m2. A 3 phase, 50Hz, 500W,
components are components inside the transformer main 900RPM fans are mounted at the horizontal position [5,6].
tank like core, windings with their supporting insulation In this paper, 36inch marathon make 415V, 3 phase, 50Hz
structure, solid insulations and liquid insulations. The with volumetric flow of 22100m3/hr fan is selected.
thermal performance can be decided based on how external For oil directed (OD) cooling mode, oil is pumped from
and internal cooling components will work together. the radiators and delivered to the bottom of the transformer
windings. In addition, the static pressure drop over a disc
A. Internal cooling mode
type of winding will decide the pump selection for oil forced
The transformer rating of 60/75/90MVA, 220/33kV and directed cooling modes [22]. The higher rated pump
YNyn0, 3phase 3 limb are considered for thermal capacity (higher oil velocity) will provide higher rate of heat
overloading capabilities of ester oil filled transformer. The dissipation. In this transformer, 6 inches, 1800LPM, 1.2kW,
geometry of a disc type of low voltage (33kV), high voltage 415V, 3phase 50Hz, BC-30/1 is considered for the analysis.
winding (220kV) with tap winding (coarse and fine) consists
of thermally upgraded paper covered copper conductors. C. Transformer power loss estimation
The quantification of the bulging mainly in conductor The generation of heat in the winding is mainly due to
insulation depends upon quality of the conductor, type of core loss, resistive loss (I2R loss) in copper strands and stray
winding, insulation thickness and width of the conductor. If loss due to leakage/high current field within the transformer
the bulging is high, then there will be a reduction of cooling once the transformer is energized. The resistive losses are
duct causing an end effect increase of conductor directly proportional to resistivity of the material, whereas
Authorized licensed use limited to: Centro Universitário Fei. Downloaded on August 27,2020 at 16:10:35 UTC from IEEE Xplore. Restrictions apply.
the winding eddy loss due to leakage field is inversely Q = hA(Tsurface − Toil )
proportional to resistivity. The loss distribution can be (2)
calculated independently with consideration of winding Where,
geometry, transformer loading level and leakage flux h- Local heat transfer coefficient at hot-spot in oil domain
distribution, etc., Due to uneven distribution of electrical (W/m2.oC)
losses within transformer, the temperature profile within the A- Surface area in m2
transformer will not be uniform because of the non-uniform Tsurface- Hot-spot temperature in fluid domain (oC)
oil flow distribution and cooling structure. The accurate - object's surface temperature
prediction of power losses (no-load and load) distribution is Toil - Bulk oil temperature surrounding the hot-spot (oC)
the main criteria for thermal analysis. In this paper, the main
focus is on oil flow and heat transfer processes in the If viscosity of the oil is higher, then convection process
winding with given loss distributions using FEM based will be lesser for heat transfer. Hence, due to utilization of
technique and experimental data of load loss. ester oil for transformer applications, there will be reduction
of amount of convection fluid currents. The heat dissipation
IV. HEAT TRANSFER PRINCIPLE from tank occurs by both radiation and natural convection.
The heat transfer modes are mainly by conduction, The cooling of externally mounted radiators will also occur
convection and sometimes by radiation [1,2,16,17]. If the by radiation principle. In addition, radiation will be very less
transformer is energized the heat sources are generated due with respect to convection principle. The entire radiator
to power losses which will causes the oil and winding surface does not participate in heat transfer mechanism by
temperature to rise above the ambient temperature. radiation [16,17]. The heat transfer by radiation is expressed
According to heat transfer theory, heat will transfer from the by Stephan-Boltzmann law:
hottest temperature mainly at winding conductor to P = ES A (Tradiating surface − Tambient)
atmospheric temperature (Tambient) through windings, (3)
insulation papers, oil, tank and external radiators based on Where,
winding coolant arrangement. η- Stephan-Boltzmann constant (5.67×10-8 W/(m2 °C))
The conduction principle within each copper strand is E - Surface emissivity factor
negligible due to higher thermal conductivity and small size SA - Surface area for radiation in m2
of the copper strand used in the windings. The heat transfer Tradiating surface- Average temperature of radiating surface
from the core to oil and windings to oil is considered as (oC)
conduction process since they are designed to be in good
contact. The temperature drop across the conductor V. TRANSFORMER ANALYSIS RESULTS
insulation due to the conduction heat transfer principles can If the thermal performance of transformer is well taken
be calculated by Fourier’s law of thermal conduction. The care at the time of design, then it provides lower top oil,
thermal conductivity of oil-impregnated paper insulation is average winding rise and hot-spot temperature. The oil flow
temperature dependent [16,17]. The rate of heat conduction distribution and pressure drop over the winding due
through a copper conductor is proportional to temperature different thermal properties of mineral oil and ester oil are
gradient across the paper insulation and heat transfer area of important for thermal analysis for the following reasons.
paper insulation and it is given by
• Oil flow rate is directly related to thermal
dT performance and a more uniform oil flow distribution
= Q • R = k p
dX (1) is highly preferred to avoid hot-spot temperature.
Where, • The total pressure drop over a winding with total oil
Δθ- Local heat flux density at the hot-spot location flow rate in the winding will determine oil split
(W/m2) among windings (LV, HV and tap winding in the
Q- Average heat flux in all the discs (W/m2) same phase) connected hydraulically in parallel in
R- Ratio of hot-spot heat flux to average heat flux ON modes [22].
-Ratio of power loss at the hot-spot to average power
A. Temperature distribution and oil flow rate
loss
kp- Paper thermal conductivity (W/m.oC ) The oil flow distribution in conjunction with power loss
dT- Temperature gradient across conductor insulation distribution will determine the temperature distribution
(oC) within the windings other than ambient temperature,
transformer design, loading conditions and cooling
dX- Thickness of thermally upgraded paper insulation
provided. The temperature of transformer filled with ester
(m) oil is higher than transformer filled with mineral oil and this
The heat dissipation from core and windings occurs temperature difference is highlighted in “Fig.1”. “Fig.1(a)”
mainly due to convection mode of heat transfer. The & “Fig.1(b)” provides the temperature distribution, oil flow
convection process within the oil is generally very rate, top and bottom oil temperature and winding
complicated phenomenon since it is dependent upon temperature rise of transformer. The temperature
physical properties of oil and physical situation [1,2,16,17]. distribution within the windings is not uniform due to
The convection heat transfer rate is generally expressed by uneven power loss distribution. Since, viscosity of ester oil
Newton’s law of cooling for prediction of highest is higher, top oil temperature rise, winding temperature
temperature in oil domain. The basic relationship for heat rises of LV and HV windings are increased due to lesser oil
transfer by convection as flow rate and reduction of convection fluid currents [22].
Authorized licensed use limited to: Centro Universitário Fei. Downloaded on August 27,2020 at 16:10:35 UTC from IEEE Xplore. Restrictions apply.
63MVA rating – ONAN (for mineral oil transformer) / KNAN (Ester oil transformer)
o
Top oil: 34.7 C Top oil: 37.7oC Top oil: 38oC
17.7m3/hr 14.8m3/hr 15.5m3/hr
75MVA rating – ONAF (for mineral oil transformer) / KNAF (Ester oil transformer)
o
Top oil: 27.4 C Top oil: 31.7oC Top oil: 32oC
20.2m3/hr 16.9m3/hr 17.7m3/hr
59.6oC 58.7oC
33.2 oC 33.3 oC 59.2oC 55.7oC 63.7oC 59.4oC
33.5 oC 30.2 oC 37.5 oC 33.2
Authorized licensed use limited to: Centro Universitário Fei. Downloaded on August 27,2020 at 16:10:35 UTC from IEEE Xplore. Restrictions apply.
Temperature distribution in oC
LV winding disc
Temperature distribution in oC
HV winding disc
Fig. 1(b). Temperature distribution of mineral oil and ester oil due to different types of cooling modes.
Authorized licensed use limited to: Centro Universitário Fei. Downloaded on August 27,2020 at 16:10:35 UTC from IEEE Xplore. Restrictions apply.
From “Fig.1”, the flow rate of ester oil is lowered by 12- rate must, consequently, guarantee that the insulation
17% with respect to mineral oil under ONAN / KNAN and temperature is kept below the allowable temperature as
ONAF/ KNAF conditions. The flow rate difference between much as possible. Hot-spot temperature is a function of Re
mineral oil and natural ester oil is 3.5% to 6% under ODAF and Pr in OD cooling mode [1,2]. It indicates that, if Re is
conditions. The bottom oil temperature of ester oil is lower higher (i.e., higher oil flow rate) then oil flow will be
than mineral oil. At the same time top oil temperature is uneven in OD cooling mode which will leads to reverse oil
higher for ester oil than mineral oil in ONAN /KNAN and flow.
ONAF/KNAF conditions. It indicates that, overall inlet oil
flow rate is lower ester oil and it leads to increase the higher