Professional Documents
Culture Documents
https://doi.org/10.1007/s12273-021-0814-7
Research Article
Xiangfei Kong1, Yufan Chang1, Nana Li1, Han Li1 (), Wei Li2
1. School of Energy and Environmental Engineering, Hebei University of Technology, Tianjin 300401, China
2. North China Municipal Engineering Design & Research Institute Co., Ltd., Tianjin 300110, China
Abstract Keywords
The relative location of inlets and outlets plays an important role in thermal comfort and energy non-uniform ventilation;
conservation under ventilation modes for the building non-uniform indoor environment. Hence, a air terminal positions;
comparison study of thermal comfort and energy efficiency of eight widely-used ventilation thermal comfort;
modes for space heating was conducted in this study. Both subjective experiments and verified energy saving;
subjective experiment
computational fluid dynamics (CFD) models were carried out. In the subjective experiments, the
vote of local thermal sensation (LTS), overall thermal sensation (OTS) and draft sensation were
Article History
collected. In the CFD simulations, RNG k-ε model was applied to compare and analyze the air
Received: 24 December 2020
temperature field, turbulence intensity, ventilation effectiveness and air diffusion performance
Revised: 21 April 2021
index (ADPI). The thermal comfort results showed that the air inlets are better located at the
Accepted: 30 May 2021
mid-height level of a wall, and the outlets are located at the same or higher height. While the
results of the energy efficiency suggested that the inlets are better installed at the lower level of a © Tsinghua University Press and
wall, and the outlets should be placed far from the inlets. Since the results were conflict, the Springer-Verlag GmbH Germany,
economic–comfort ratio was introduced to calculate and compare the thermal comfort and part of Springer Nature 2021
energy efficiency simultaneously. The final results concluded that it can achieve excellent thermal
comfort performance without sacrificing energy efficiency when the inlets are at the height of
1.2 m of the front wall, and the outlets are at 1.2 m height of the back wall. Hence it is the best
choice for the winter air distribution in northern China. This study can offer a guideline for the air
terminal arrangements in non-uniform ventilation under heating mode.
E-mail: lihan18113@hebut.edu.cn
2 Kong et al. / Building Simulation
due to the lack of fresh air and air movement. The residents the air inlet is better located close to the center of the room.
need to open the windows every now and then to obtain Kuo and Chung (1999) pointed out that better indoor
enough fresh air, thus resulting in large amount of high- thermal comfort can be achieved with longer supply air
concentration air pollutants entering the room, which throw in the occupied zone by simulating different relative
seriously threatens the residents’ health (Wilkinson 1999; positions of supply and exhaust air terminals. Fong et al.
Wang et al. 2018). Meanwhile, to improve the outdoor (2015) compared mixing ventilation, displacement ventilation,
environment during the heating season, coal-to-electricity and stratum ventilation with a total of six exhaust positions
clean heating project is also vigorously promoted in northern in a typical classroom. The research results concluded that
China. Mechanical ventilation, which uses electricity and can the thermal comfort performance presents better when
provide enough fresh air and air movement simultaneously, exhausts are located on the same level of the opposite wall.
is gaining more and more attention (Chen and Chen 2019). The researches so far are more focused on multiple
Therefore, it is imperative to find a proper mechanical outlets positions under one non-uniform ventilation mode
ventilation mode that possesses the characteristics of (Yao and Lin 2014; Qin and Lu 2021). The existing non-
better indoor air quality as well as energy-saving for space uniform ventilation modes have not been comprehensively
heating. compared, and the effect of the relative positions of inlet
At present, mechanical ventilation systems are normally and outlet is not considered. Moreover, above studies mainly
divided into two categories, namely fully mixing system pay attention to summer cooling applications, there is a lack
and non-uniform system (i.e., displacement ventilation, of research on the location of the air inlets and outlets
stratum ventilation, and personalized ventilation) (Cao et positions for non-uniform ventilation for winter heating.
al. 2014). Nowadays, fully mixing ventilation is the most With the expansion of coal-to-electricity projects in northern
popular ventilation mode, which is committed to creating a China, mechanical ventilation for space heating has become
uniform environment for the entire room (Ahn et al. 2018). a trend. Non-uniform ventilations show outstanding
However, in practical application, only limited space with energy-saving performance (Lee et al. 2013) and better
good thermal comfort requirement is occupied (Yang et al. indoor thermal comfort (Li et al. 2020), thus promising
2019). Hence, mixing ventilation is inevitable to cause winter applications (Kong et al. 2020) by overcoming the
unnecessarily energy waste. Thence, non-uniform ventilation shortcomings of conventional ventilations. Therefore, it is of
is triggered more and more focus due to its energy-saving great significance to investigate the non-uniform ventilation
and high-efficiency (Sekhar and Zheng 2018; Ai et al. 2019). performance for winter heating.
Studies show that the displacement ventilation and stratum In addition, most studies focus on the effect on thermal
ventilation can realize energy-saving of 41.72% and 74.71% comfort with less considering the effect on the energy
respectively relative to the mixing ventilation (Lin et al. efficiency (Cheng et al. 2015). Moreover, most of the previous
2011). Under the background of low-carbon economy, it research conclusions are obtained by CFD simulation
is a trend of transforming the traditional fully mixing (Almesri and Awbi 2011), the research using the more
ventilation system into non-uniform ventilation systems realistic method of subjective experiments are relatively
(Shao et al. 2020). Because the non-uniform ventilation only lacking. Therefore, in this study, both the indoor thermal
focuses on organizing airflow into target area, the airflow comfort and energy-saving performance under non-uniform
pattern under non-uniform ventilation modes has different ventilation with different relative positions of inlets and
design methods compared with mixing ventilation (Melikov outlets were discussed. Both verified CFD simulations
et al. 2002). With the development of the non-uniform and subjective experiments are conducted. The conclusions
ventilation, it is found that better thermal comfort can be obtained in this study can help to realize reasonable
achieved with proper design (Kong et al. 2019). non-uniform ventilation for space heating by considering
For non-uniform ventilation methods, airflow charac- thermal comfort and energy saving simultaneously.
teristics and thermal comfort are not only affected by the
supply air temperature and supply air velocity, but also 2 Methodology
influenced by the positions of inlets and outlets (Lau and
Chen 2007). Awad et al. (2008) studied the outlet positions 2.1 Study cases
on the influence of indoor airflow patterns and velocity.
The research results showed that the thermal stratification To explore the reasonable air distribution method that can
layers were significantly affected by the outlet positions. efficiently build a thermal comfort indoor environment,
Lin et al. (2005) investigated the air inlet positions on subjective experiments and verified CFD models were
design and performance of the displacement ventilation via introduced. Eight non-uniform ventilation methods were
CFD simulation, and the numerical results indicated that selected as the research cases, which included 2 inlet positions
Kong et al. / Building Simulation 3
and 5 outlet positions. The inlets were located mid-height 170.3 cm and 68.2 kg, respectively. Their body mass indexes
of 1.2 m (abbreviated as S-1.2) and lower level of 0.5 m (BMI) were all within the recommended range of 18.5 to
(abbreviated as S-0.5) on the front wall. Due to the positive 24.9. They were required not drinking alcohol or staying
thermal buoyancy, ceiling level of the inlet is not suitable up a day before the experiment. During the subjective
applied in the winter, for warm air hardly falls down to the experiments, the supply air temperature was maintained at
occupied zone (0.1–1.4 m); thus it is not discussed in this 27 °C, and the air change rate was kept at 7 ACH. The
study. As for the outlet positions, 2 outlets were located on indoor air temperature and velocity were monitored
the same wall with the inlets. One was at the level of 1.2 m throughout the whole procedure.
(abbreviated as SA-1.2), and the other was at the level of In the experiment, occupants were exposed to these
0.5 m (abbreviated as SA-0.5). 2 outlets were located on eight thermal environments in sequence. As shown in
the opposite wall compared with the inlets. One was at Figure 2, 48 occupants were divided into four groups and
1.2 m (abbreviated as OP-1.2), and the other was at 0.5 m each group contains 6 males and 6 females. Every research
(abbreviated as OP-0.5). The last one was on the ceiling thermal environment required four trials with all four
(abbreviated as CE). The corresponding locations of outlets groups of occupants. During the experiments, subjects were
and inlets under eight study cases are presented in Figure 1. asked to wear typical winter clothes with a thermal resistance
of 1.2 clo, and required to sit in the room with reading or
2.2 Subjective experiment writing. The activity level was around 1.0 met.
To collect the data of occupants’ response, a questionnaire
Subjective experiments are carried out in an experimental containing overall thermal sensation (OTS), local thermal
room which is located in Tianjin, a city in the cold area sensation (LTS) and draft sensation was distributed to
of China, and has the dimensions of 6 m (length) × 4 m the occupants. ASHRAE 7-point scale (−3 cold, −2 cool, −1
(width) × 3.5 m (height). This experimental room equipped slightly cool, 0 neutral, +1 slightly warm, +2 warm and +3
with multiple positions of air terminals. Every air terminal hot) was used to evaluate the occupants’ OTS and LTS
can be used as inlet or outlet. Different air distribution (forehead, check, neck, chest, arms, hands, legs and feet).
methods can be achieved via switching on or off of valves. A 4-point scale index (no draft, slightly draft, clearly draft
48 young students (24 males and 24 females) with an and strongly draft) was used to evaluate the draft sensation.
average age of 21 participated in the experiments. They After experiencing 30 min of trial, they were required to
were all non-smokers, and had no chronic and allergic finish the questionnaire.
skin diseases. They had lived in Tianjin for at least 3 years.
The average height and weight values of the students were 2.3 CFD simulation
Fig. 1 Schematic diagram of eight study cases Fig. 2 Layout of the indoor occupants for subjective experiment
4 Kong et al. / Building Simulation
provide the most realistic data, it is rather time-consuming. by cuboid of this dimension has been widely used in CFD
Meanwhile, due to the limitation of the number of simulations (Tian et al. 2011; Cheng and Lin 2015). Lamps
measuring points, it is impossible to know the velocity and are simplified as cuboid as well with dimensions of 0.9 m
temperature field at any random point of the room. After (length) × 0.2 m (width) × 0.1 m (thickness). The CFD
years of development of CFD technology, CFD simulations model is shown in Figure 3. As for the boundary conditions,
can detailed predict indoor airflows with high reliability the velocity–inlet and outflow boundary conditions are
(Haghshenaskashani et al. 2018; Yin et al. 2020). In addition, applied for the air inlets and air outlets, respectively. The
it is proven to be used in non-uniform thermal environment walls are defined to have constant temperature. As for the
assessment (Taghinia et al. 2015; Yan and Li 2020). Hence, heat sources, both of the occupants and lights are defined
CFD simulations are implemented in the same geometry as to have constant heat flux. The specific boundary conditions
the experimental room where subjective experiments are are listed in Table 1.
performed. According to the relative research, RNG k-ε In aims to guarantee the accuracy of the model, the grid
model is better fitting turbulent airflows (Chen et al. 2013; independent test is carried out. Case S-0.5, SA-1.2 is used
Yang et al. 2021). Gebremedhin and Wu (2003) found the to conduct the test. In the test, three density levels of
RNG k-ε model is the most appropriate model to simulate hexahedral grids namely coarse, normal and fine are con-
the flow field of the ventilated space compared with the structed. The maximum sizes of X axis for coarse, normal
standard k-ε model, low-Reynolds number k-ε model and and fine are 0.5, 0.04, 0.03, respectively. The corresponding
Reynolds stress model. Hence, RNG k-ε model is applied grid numbers of coarse, normal and fine are 462076,
in this study. General governing equations for the RNG k-ε 2213693 and 4853184, respectively. The results show the
model are as follows: temperature and velocity field predicted by normal grid are
very close to those predicted by fine grid, whose difference
¶ ( ρk ) ¶ ( ρkui ) ¶ é ¶k ù
+ = ê αk μeff ú + Gk + ρε (1) is within 5%, while the difference between the coarse and
¶t ¶xi ¶x j êë ¶x j úû
fine grids is above 20%. Hence, the normal grid is good
¶ ( ρε ) ¶ ( ρεu ) ¶ é ¶ε ù εC1ε
*
ε2
+ = ê αε μeff ú+ Gk - ρC2ε
¶t ¶x i ¶x j êë ¶x j úû K k (2)
enough to obtain accurate results, thus is used in this study. at 7 ACH. Both the parameters were measured and collected
The grid is shown in Figure 4. throughout the experiment. As shown in Figure 5, a total
of 9 (L1–L9) measurement plumb lines were distributed
2.3.2 Model validation
in the room, and each plumb lines had six measuring
In this study, the CFD model is validated by objective points with different altitude (0.1 m, 0.6 m, 1.1 m, 1.4 m,
experiments, and the validated experiments are carried out 2.1 m and 2.8 m). The air temperature was measured by
in the room where the subjective experiments implemented. T-thermocouples, whose accuracy is ±0.1 °C in the range
The layout of the room is shown in Figure 5. Indoor of −200 to 260 °C. The air velocity was measured by Testo
heat resources are composed of six occupants and two 480 hot-line anemomter with an accuracy of ±0.05 m/s in
incandescent lamps. Each occupant is simplified as cuboid the range of 0–20 m/s. The error analysis was implemented in
with the dimensions of 0.4 m (length) × 0.25 m (width) × aims of identifying the uncertainty of the measurement.
1.2 m (height), with a constant heat flux of 90 W. Two Since the measurements of the air temperature and air
incandescent lamps are both located on the ceiling, and velocity are all directly measured variables, the error analysis
each lamp has the constant heat flux of 75 W. The primary method proposed by Kline and McClintock (1953) was
return air-conditioning system and variable air volume adopted. Assuming a variant R, which is a function of multiple
(VAV) air-handling unit are installed in the experimental independent variants X1, X2, ..., Xn, R can be expressed as R =
room. The air temperature and air velocity can be adjusted R (X1, X2, ..., Xn), the relative uncertainty can be calculated
through the control panel. To monitor the supply air by the following formula:
temperature and air velocity, the dry-bulb temperature
ΔR é n
= ê å i =1(ΔXi / Xi )2 ùú
1/2
sensor and air velocity sensor are installed. (3)
R ë û
During the experiments, the supply air temperature
was maintained at 27 °C, and the air change rate was kept The calculating results show the measurement accuracies
of the air temperature and air velocity are 0.08% and 0.25%,
respectively.
Case S-1.2, CE is used to do the validated experiments,
the overall average temperature data and velocity data are
compared to get access the accuracy of the local region.
The data of measurement line L4 is also compared, and
the results are shown in Figure 6. There is an acceptable
agreement between the experiment and simulation data. But
due to the fluctuation of the outdoor parameters, a certain
difference occurred between the simulation and experiment
results. The mean deviations between the simulation and
experiment results for the total average temperature and
Fig. 4 Normal grid average air velocity are 8.8%, 11.3%, respectively. As for
line L4, the corresponding values are 6.8% and 6.6%,
respectively. The simulation results are in good agreement
with the experimental results. Therefore, the model is verified
to be used in the following discussion.
Fig. 6 (a) Temperature and velocity deviation between simulation and experiment on (a) the total average temperature and (b) the
measurement line L4
The turbulence intensity indicates the intensity of airflow EDT = (Tx - Tc ) - (v x - 1.1) (7)
fluctuations. It reveals the fluctuations of the air speed. The
higher fluctuation and higher air speed can cause the where Tx means the local air-stream dry-bulb temperature
sensation of draught (Koskela et al. 2001). Thus the turbulence (°C), Tc is the average room dry-bulb temperature (°C); vx
intensity is one of the main factors that affect the human is the local air-stream centerline speed (m/s). A thermal
thermal comfort (Cao et al. 2021). It is calculated as: comfort point has to satisfy the EDT within the range of
−1.2 K to 1.2 K, and with the air velocity below 0.8 m/s.
Vsd
Tu = ´100% (4) Normally, the better thermal comfort the ventilation
V
mode provides, the higher economic expenses it costs.
where Tu is the turbulence intensity, Vsd is the standard In order to investigate thermal comfort and energy con-
deviation, V is the average velocity. The turbulence intensity sumption of each ventilation method simultaneously, the
increases as the velocity decreases or the velocity fluctuation economic–comfort ratio proposed by Kong et al. (2020) is
increases. applied in this study. It is defined as the energy consumption
The ventilation effectiveness is applied to evaluating the to make one occupant reach thermal comfort. The formula
energy efficiency, which is defined as the below: is as below:
Et = ( Ts - Te ) / ( Ts - To ) (5) Q
η= (8)
Nc
where Et is the ventilation effectiveness, Ts is the supply air
temperature (°C), Te stands for the exhaust air temperature where η is the economic–comfort ratio, Q stands for the
(°C), To is the air temperature of the occupied zone (°C). total energy consumption, Nc is the number of the thermal
The energy efficiency increases with the increase of Et. comfort occupants.
The air diffusion performance index (ADPI) is applied The total energy consumption of the ventilation method
to evaluating the thermal comfort. It is defined as the ratio can be calculated as below:
of thermal comfort points to the total measured points in a
E t = Qe / Q (9)
space. The calculation formula is shown as follows (ASHRAE
2013):
where Et is the ventilation effectiveness, Qe stands for the
ADPI = N c / N ´ 100% (6) energy delivered in the ventilation (kWh), Q stands for the
total energy consumption (kWh).
where Nc stands for the thermal comfort points, N means While Nc can be expressed by ADPI, hence combining
the total measured points. Eqs. (5) and (8), the equation can be transferred to the
While the thermal comfort points are dominated by the following form:
effective draft temperature (EDT) and the air velocity of
the space. Lin (2011) proposed the following equation to Qe
evaluate the EDT for stratum ventilation, which is applied Q Et Q 1
η= = = e´ (10)
for all experimental cases: Nc ADPI ´ N N Et ´ ADPI
Kong et al. / Building Simulation 7
where, Qe/N is a constant number which is predominant by ventilation methods has a huge impact on indoor thermal
the characteristics of the building. While 1/(Et × ADPI) is comfort and thus needs to be analyzed. With the same supply
variable, use β stands for 1/(Et × ADPI), which is defined air temperature and velocity, the overall average temperature
as the ventilation correction factor. With the application provided by S-1.2 and S-0.5 is 20.3 °C and 20.2 °C, respectively,
of β, the combined effect of thermal comfort and energy which indicates that similar indoor thermal environment
consumption can be evaluated in different ventilation modes. can be achieved by both S-1.2 and S-0.5.
The room achieved thermal comfort with lower energy Figure 7 shows the temperature distribution of the
efficiency with the decrease of β. eight cases at Z = 2, and plane Z = 2 is marked in Figure 5.
It can be seen that the temperature fields of all cases
3 Results and discussions show significant space asymmetry, which is caused by the
temperature difference of the interior wall and outer wall,
resulting in lower indoor temperature and higher temperature
3.1 Simulation results
gradient near the outer wall region. For S-1.2 cases, high
3.1.1 Indoor air temperature field temperature appears in the upper zone, which indicates the
warm air would flow to the upper zone with the increase
The indoor temperature field created by eight non-uniform of supply distance due to the thermal buoyancy. Similar
S-0.5 and S-1.2 with the value of 1.17 and 1.14 respectively. 3.2 Subjective experimental results
It manifests that the outlet located on lower level of the
opposite wall can counteract the thermal buoyancy effect 3.2.1 Overall thermal sensation
better, therefore enhance the ventilation effectiveness. In
The thermal environment is considered acceptable for the
addition, there is another point worthy of attention. Both
occupants who vote the score of −1, 0 and +1. Figure 11
the maximum and the minimum values were appeared
shows the OTS of 48 occupants. It can be seen that the
when applying the outlet of CE. The corresponding
average OTS of all eight cases are within the acceptable
values for S-1.2 and S-0.5 are 1.17 and 0.92, respectively.
range. The standard deviation of S-0.5 cases and S-1.2 cases
The difference between these two reaches 0.25. This finding
are 0.22 and 0.58 respectively. It indicates that the indoor
implies that as long as the airflow path is long enough,
even with the effect of thermal buoyancy, the ventilation thermal environment served by S-0.5 has better uniformity.
efficiency is higher if the inlet is located on the lower level The large deviation occurs in S-1.2 cases, especially case S-1.2,
of the room. OP-0.5, where the OTS values of other cases are above 0,
while this case only reaches −0.32. It is due to that in this
3.1.4 ADPI ventilation mode, the air is forced to flow to the occupants
and return through the outlets, triggering an increasement
To evaluate the uniformity of the air temperature and
in indoor air speed, causing occupants’ uncomfortable
velocity distributions for universal thermal comfort in the
draught. For the cases, whose outlets are located higher
room, ADPI value is applied in this study. From Figure 10,
than inlets (S-1.2, OP-1.2; S-0.5, SA-1.2 and S-0.5, CE), the
it can be seen that the peak value of ADPI improved by
11.1% with the inlet position changes from S-0.5 to S-1.2. OTS values are more concentrated and closer to thermal
The average ADPI value of S-0.5 reaches 60.3% ranging neutrality. Among these cases, the smallest standard deviation
from 57.3% to 61.8%, while that of S-1.2 is only 49.35% of 0.50 in S-1.2, OP-1.2 is achieved, so the best uniformity
ranging from 48.0% to 50.7%. The former is 10.95% higher can be obtained in this airflow distribution.
than the latter. It demonstrates that S-1.2 significantly Since males and females have different physiological
performs better than S-0.5. However, under the premise of structures, there might be different thermal sensations about
the same position of inlet, ADPI only fluctuates within 5% the thermal environment. It is necessary to analyze the
with the changes of outlet positions, which demonstrates OTS of different genders, as shown in Figure 12. The result
that outlet positions act little impact on ADPI value. Even shows that there is noticeable difference between males and
so, it is still shows that higher average ADPI value is females. The average OTS value of males is 0.18, and the
obtained when applying OP-0.5 or CE. The corresponding average OTS value of females is −0.001, which is 0.181
ADPI values are 56.15% and 55.75% for S-1.2 and S-0.5, lower than that of males, indicating the thermal neutral
respectively. indoor environment for females requires higher indoor air
temperature. In addition, the OTS distribution of S-1.2 cases
between males and females is more concentrated while that
of S-0.5 cases varies greatly among different individuals.
Hence, it is considered that S-1.2 cases can create a more
uniform indoor environment for both males and females.
Considering that all the eight ventilation modes belong 0.25 and 0.04 respectively. The result shows that the LTS
to non-uniform ventilation, the OTS may differ with the of S-0.5 is closer to thermal neutrality, indicating that the
distance between the occupants and inlets due to the thermal neutral temperature for lower part of the body is
unidentical local air temperature especially the air velocity. higher than that of the upper body. It also implies that for
Hence, as shown in Figure 13, it can be seen that the inlets installed on mid-height level of the room, there
average OTS value of the first row is lower than that of the should be a decrement in the supply air temperature to
second row on the whole, but the difference is quite limited. maintain a thermal neutrality indoor environment. It also
In most cases, the OTS of the first row is closer to thermal can be observed that the feet area is colder in S-1.2 cases
neutrality, while the occupants in the second row with compared to S-0.5 cases. The minimum value is as low as
smaller local wind speed feel warmer, which indicates −0.41 in S-1.2, CE, that is because the outlet is located
that the occupants tend to prefer some airflows in warm higher level leading to warm air hardly approaching to lower
environment. Moreover, in addition to S-0.5, SA-1.2, it can part of the body due to the thermal buoyancy, but the OTS
be seen that the OTS distribution in S-0.5 cases is relatively is yet close to thermal neutrality, indicating that the OTS is
scattered, and in S-0.5, CE, the OTS in the second row is less affected by the feet area.
lower than that of the first row conversely, indicating Figure 15 and Figure 16 show the LTS distribution of
thermal environment in S-0.5 cases is relatively uneven. different genders in eight cases. It can be seen that on the
whole, the LTS of females is generally lower than that of
3.2.2 Local thermal sensation
males, and females are more sensitive to warm and cold
Figure 14 provides the LTS distribution of 48 sedentary indoor environment, such as relatively warm of the chest
occupants. In the body segment where the airflow directly area in S-1.2, CE and S-0.5, OP-1.2, and relatively cold of
delivered, the upper part of the body (forehead, check, neck, leg and feet area in S-1.2, OP-0.5 and S-0.5, CE. It also can
chest, arms and hands) for S-1.2 and lower part of the body be observed that the LTS varies among different parts of
(legs and feet area) for S-0.5 have the average value of the body in S-1.2 cases, ranging from −0.77 to 0.67. The
Fig. 12 Overall thermal sensation of eight cases between males and females
Fig. 13 Overall thermal sensation of eight cases between the first and second rows
Kong et al. / Building Simulation 11
Fig. 17 Local thermal sensation of (a) the first row and (b) the
second row in S-1.2 cases
4 Comprehensive analysis
applied, outlets are better installed on the rear wall and Cao G, Awbi H, Yao R, et al. (2014). A review of the performance of
lower or at the same height compared to the inlets to different ventilation and airflow distribution systems in buildings.
reduce the effect of thermal buoyancy. Building and Environment, 73: 171–186.
(3) Inlet positions play a decisive role in ADPI values. The Cao S, Ming P, Zhao X (2021). Fuzzy comprehensive evaluation of
ADPI values of S-0.5 cases are 10% higher than that of human thermal comfort in simulating natural wind environment.
S-1.2 cases. It is concluded that good uniform indoor Building and Environment, 188: 107447.
Chen HJ, Moshfegh B, Cehlin M (2013). Investigation on the flow
environment is achieved when inlets located mid-level.
and thermal behavior of impinging jet ventilation systems in an
(4) Subjective experiments results show that LTS and OTS
office with different heat loads. Building and Environment, 59:
are more affected by the air inlets positions. The results
127–144.
suggest that the better inlets type is S-1.2, for indoor
Chen H, Chen W (2019). Potential impact of shifting coal to gas and
occupants feeling thermal neutrality. However, draft electricity for building sectors in 28 major northern cities of
sensation is influenced by both inlets and outlets China. Applied Energy, 236: 1049–1061.
positions. Although the S-1.2, OP-0.5 case has a better Cheng Y, Lin Z (2015). Technical feasibility of a stratum-ventilated
inlet type, it shows undesirable LTS and OTS performance room for multiple rows of occupants. Building and Environment,
and has the highest “clearly draft” feeling percentage 94: 580–592.
of 15%. Therefore, outlets should be located higher to Cheng Y, Niu J, Du Z, et al. (2015). Investigation on the thermal
reduce the uncomfortable draft. comfort and energy efficiency of stratified air distribution
Since the results of thermal comfort and energy-saving systems. Energy for Sustainable Development, 28: 1–9.
are not unified, the economic–comfort ratio is thus Dong B, Yan D, Li Z, et al. (2018). Modeling occupancy and behavior
applied to access thermal comfort and energy efficiency for better building design and operation—A critical review.
simultaneously. The result demonstrates that in winter Building Simulation, 11: 899–921.
conditions, better thermal comfort and higher energy EIA (2019). International Energy Outlook 2019. The U.S. Energy
Information Administration.
efficiency can be achieved when the supply air temperature
Eom J, Clarke LE, Kim SH, et al. (2012). China’s building energy use:
is 27 °C and the air change per hour is 7 ACH, the inlet is
A long-term perspective based on a detailed assessment.
located at mid-height level of the front wall and the outlet
Richland, WA, USA: Pacific Northwest National Lab. (PNNL).
is located at the same height but the rear wall.
Fan Y, Ito K (2014). Optimization of indoor environmental quality
and ventilation load in office space by multilevel coupling of
Acknowledgements building energy simulation and computational fluid dynamics.
Building Simulation, 7: 649–659.
This work is supported by the National Natural Science Fong ML, Hanby V, Greenough R, et al. (2015). Acceptance of thermal
Foundation of China (No. 51978231), the Natural Science conditions and energy use of three ventilation strategies with six
Foundation of Hebei Province (No. E2019202452) and the exhaust configurations for the classroom. Building and Environment,
Hebei Province Funding Project for Returned Overseas 94: 606–619.
Chinese Scholars (No. C20190507). Gebremedhin KG, Wu BX (2003). Characterization of flow field in a
ventilated space and simulation of heat exchange between cows
References and their environment. Journal of Thermal Biology, 28: 301–319.
Haghshenaskashani S, Sajadi B, Cehlin M (2018). Multi-objective
Ahn H, Rim D, Lo LJ (2018). Ventilation and energy performance optimization of impinging jet ventilation systems: Taguchi-based
of partitioned indoor spaces under mixing and displacement CFD method. Building Simulation, 11: 1207–1214.
ventilation. Building Simulation, 11: 561–574. Huang X (2014). World Energy Development Report 2014. Beijing:
Ai Z, Hashimoto K, Melikov AK (2019). Airborne transmission Social Sciences Academic Press. (in Chinese)
between room occupants during short-term events: Measurement Kamaruzzaman S, Sabrani N (2011). The effect of indoor air quality
and evaluation. Indoor Air, 29: 563–576: (IAQ) towards occupants’ psychological performance in office
Almesri IF, Awbi HB (2011). Predictions of thermal comfort in buildings. Journal of Design+ Built, 4(1): 49–61.
stratified room environment. Building Simulation, 4: 169–180. Kline SJ, McClintock FA (1953). Describing uncertainties in single-
ASHRAE (2013). ASHRAE Handbook: Fundamentals-Chapter 18. sample experiments. Mechanical Engineering, 75: 3–8.
Nonresidantial cooling and heating load calculation. Atlanta, Kong X, Xi C, Li H, et al. (2019). A comparative experimental study
GA, USA: American Society of Heating, Refrigerating and on the performance of mixing ventilation and stratum ventilation
Air-Conditioning Engineers. for space heating. Building and Environment, 157: 34–46.
Awad AS, Calay RK, Badran OO, et al. (2008). An experimental study Kong X, Xi C, Li H, et al. (2020). Multi-parameter performance
of stratified flow in enclosures. Applied Thermal Engineering, 28: optimization for whole year operation of stratum ventilation in
2150–2158. offices. Applied Energy, 268: 114966.
Kong et al. / Building Simulation 15
Koskela H, Heikkinen J, Niemelä R, et al. (2001). Turbulence correction ventilated space with air recirculation. Building and Environment,
for thermal comfort calculation. Building and Environment, 36: 171: 106672.
247–255. Taghinia J, Rahman M, Siikonen T (2015). Simulation of indoor
Kuo J-Y, Chung K-C (1999). The effect of diffuser's location on airflow with RAST and SST-SAS models: A comparative study.
thermal comfort analysis with different air distribution strategies. Building Simulation, 8: 297–306.
Journal of Thermal Envelope and Building Science, 22: 208–229. Tahersima M, Tikalsky P (2018). Experimental and numerical study
Lau J, Chen Q (2007). Floor-supply displacement ventilation for on heating performance of the mass and thin concrete radiant
workshops. Building and Environment, 42: 1718–1730. floors with ground source systems. Construction and Building
Lee C, Fong K, Lin Z, et al. (2013). Year-round energy saving Materials, 178: 360–371.
potential of stratum ventilated classrooms with temperature and Tian L, Lin Z, Liu J, et al. (2011). The impact of temperature on mean
humidity control. HVAC&R Research, 19: 986–991. local air age and thermal comfort in a stratum ventilated office.
Li H, Xi C, Kong X, et al. (2020). A comparative experimental Building and Environment, 46: 501–510.
investigation on radiant floor heating system and stratum Tsinghua University Building Energy Research Center (2014). Annual
ventilation. Sustainable Cities and Society, 52: 101823. Report on China Building Energy Efficiency. Beijing: China
Lin Z, Chow TT, Tsang CF, et al. (2005). CFD study on effect of the Architecture & Building Press. (in Chinese)
air supply location on the performance of the displacement Wang D, Xu Y, Liu Y, et al. (2018). Experimental investigation of
ventilation system. Building and Environment, 40: 1051–1067. the effect of indoor air temperature on students’ learning
Lin Z (2011). Effective draft temperature for evaluating the performance performance under the summer conditions in China. Building
of stratum ventilation. Building and Environment, 46: 1843–1850. and Environment, 140: 140–152.
Lin Z, Lee CK, Fong S, et al. (2011). Comparison of annual energy Wilkinson D (1999). Poor housing and ill health: A summary of research
performances with different ventilation methods for cooling. evidence. Edinburgh: Scottish Office Central Research Unit.
Energy and Buildings, 43: 130–136. Yan S, Li X (2021). Comparison of space cooling/heating load under
Melikov AK, Cermak R, Majer M (2002). Personalized ventilation: non-uniform indoor environment with convective heat gain/loss
evaluation of different air terminal devices. Energy and Buildings, from envelope. Building Simulation, 14: 565–578.
34: 829–836. Yang B, Melikov AK, Kabanshi A, et al. (2019). A review of advanced
Norbäck D (2009). An update on sick building syndrome. Current air distribution methods - theory, practice, limitations and
Opinion in Allergy and Clinical Immunology, 9: 55–59. solutions. Energy and Buildings, 202: 109359.
Qiao R, Liu T (2020). Impact of building greening on building energy Yang X, Ye X, Zuo B, et al. (2021). Analysis of the factors influencing
consumption: A quantitative computational approach. Journal of the airflow behavior in an impinging jet ventilation room.
Cleaner Production, 246: 119020. Building Simulation, 14: 749–762.
Qin C, Lu W-Z (2021). Effects of ceiling exhaust location on thermal Yao T, Lin Z (2014). An experimental and numerical study on the
comfort and age of air in room under impinging jet supply effect of air terminal layout on the performance of stratum
scheme. Journal of Building Engineering, 35: 101966. ventilation. Building and Environment, 82: 75–86.
Sekhar C, Zheng L (2018). Study of an integrated personalized Yin H, Li L, Wu R, et al. (2021). A numerical study on the effect of
ventilation and local fan-induced active chilled beam air conditioning column layout on air distribution and performance of column
system in hot and humid climate. Building Simulation, 11: attachment ventilation. Building Simulation, 14: 1095–1108.
787–801. Zhang L, Xia J, Thorsen JE, et al. (2017). Method for achieving hydraulic
Shao X, Liang S, Li X, et al. (2020). Quantitative effects of supply air balance in typical Chinese building heating systems by managing
and contaminant sources on steady contaminant distribution in differential pressure and flow. Building Simulation, 10: 51–63.