1. Introduction ............................................................................................................. 1
1-1 System Requirements...................................................................................... 1
Basic requirements:
Pentium-Ⅲ 800M Hz, 256MB, HD500MB
Microsoft Windows 2000
Display 1024x768
Recommend requirement
Pentium-4 1.8G Hz, 512MB, HD2GB
Microsoft Windows XP
Display 1024x768
Step1:
Double click Setup.exe to execute the Setup program; refer to figure 2-1.
Figure 2-1
Step2:
If you agree this Software License Agreement, please click “ACCEPT” to continue
setup program. If not, please click “DO NOT ACCEPT” to stop the installation; refer to
figure 2-2.
Figure 2-2
Figure 2-3
Step4:
Chang the directory to you specified destination directory and then click button
to install this program; refer to figure 2-4.
Figure 2-4
Figure 2-5
Step6:
Program setup was completed successfully. Click “OK” button to exit this setup
program; refer to figure 2-6.
Figure 2-6
Figure 2-7
Step8:
Now you can start ESD-Link34 Monitoring Software.
Figure 3-1
Step2:
Please key in Serial number and Password, and then click Register button to register
this software; refer to figure 3-2. If the Serial number or Password wasn’t correct,
ESD-Link34 can’t be executed.
Caution:The password is the Administrator Login password.
Figure 3-2
Figure 3-3
Step4:
When all of the settings have completed, please select “Enter system” and then enter
ESD-Link34 main window; refer to figure 3-5. The functions of main window describe as
follows,
a. Communication Status:
Connected.
Disconnected.
b. Parameter Record Status:
When power parameters record function enable, icon will be showed. On the other
hand, icon will be hidden. When the parameter data is recording, icon will be
blanking.
c. Name:
The identification name of ESD34 that defined by user. Double click this Name to see
more detail information of ESD34.
d. Filter Name:
The identification name of ESD34 that under the Centralized Control Unit. Double
click this Name to see more detail information of ESD34.
e. Filtering:
When ESD34 turn on, this indicator is green . When ESD34 shut down, this indicator
is white .
f. Full Correcting:
When ESD34 operates under full load condition, this indicator is yellow . On the other
hand, this indicator is white .
g. Error :
When some possible external abnormal conditions or internal abnormal breakdown, the
APF should stop and this indicator is red . On the other hand, this indicator is white .
h. Phase/Wire:
Display the utility system is 3P3W or 3P4W.
Figure 3-5
When some of the settings were mistaken, select FunctionÆGo to Setting Page and
then come back Setting window.
Table 3-1 shows the function list of ESD-Link34. When the control panel of ESD34
is LCD panel, all functions are supported. The LED panel is without some of the functions.
Figure 3-6
Figure 3-7
b. Status:
1) Filtering:
When ESD34 turn on, this indicator is green.
2) Full Correcting:
When APF operates under full load condition, this indicator is yellow.
3) Error:
When some possible external abnormal conditions or internal abnormal
breakdown, the ESD34 should stop and this indicator is red.
4) Internal CAN BUS:
When the communication between ESD34 control board and LED/LCD
panel is normal, the indicator is green. If the communication is abnormal, the
indicator is red.
5) CPU1 Controller Ver.:
Display the CPU1 controller version.
6) CPU2 Controller Ver.:
Display the CPU2 controller version.
7) LCD Panel Program Ver.:
Display the LCD Panel controller version.
c. Control Button:
1) ON/OFF:
Only Administrator can click this button to control ESD34 to turn on or turn
off.
2) RESET:
Click this button to clear the error status.
g. Export: Export the parameter data in a CSV file which is Comma Separated Value
(CSV) file format.
b c
a
d
e
Figure 3-8
b c
d
a e
Figure 3-9
a. Update:Click Update button to download the event log data from ESD34.
b. Export:Click Export button to store the event log data in a CSV file which is the
Comma Separated Value (CSV) file format.
c. Count:Choose the download number of event logs.
Figure 3-11
A. Compensation Setting
Table 3-2. Compensation Setting Description
Option or Input
Item Function Description Default
Range
Harmonic To set the Harmonic Compensation is enabling or ENABLE
ENABLE
Compensation disabling. DISABLE
Power Factor To set the Power Factor Correction is enabling or ENABLE
ENABLE
Correction disabling. DISABLE
To set the priority of the compensation, either
Compensation Harmonic
Harmonic Compensation or Power Factor Harmonic
Priority PFC
Correction.
To set the reactive power compensation mode is
Dynamic
Reactive Power Target DPF or Fixed KVAR when Power Factor
Fixed
Dynamic
Correction is enabling.
: leading
Target DPF (cos ¢) To set the Target DPF cos¢1. 0.95
: lagging
0.7~1.0
: leading
: lagging
Fixed KVAR To set the Fixed KVAR. Please refer to 0
table 3-3 for input
range.
When 3 Phase load current load is unbalance and
Balance Utility is enabling ESD34 will compensate
ENABLE
Balance Utility the utility current to balance.
DISABLE
DISABLE
This function only for 3P4W application.
480V Model without this function.
0~6
ESD34 builds several control parameters for
Application Mode different type loads to obtain the best performance. Please refer to 5
table 3-4.
Figure 3-12
a. Order:
To show the harmonic order that want to compensate.
The maximum number of selected order is 12.
b. Active:
The function shows the harmonic orders which are compensated by ESD34. If the
resonance occurs between ESD34 and load, the filter will disable the harmonic order.
c. Reduction(%):
The function is setting harmonic reduction ratio. For example, when the load 5th
harmonic current is 10A and the reduction is set 80%, ESD34 only compensate 10A x
80%=8A 5th harmonic current.
d. High Order Compensation:
Global compensate from 32nd to 51st harmonic orders.
Figure 3-13
Figure 3-14
When user connects to Centralized Control Unit, it will show Figure 3-15 windows. It adds
ON/OFF and indicator function.
ON/OFF:
Turn on or turn off each ESD34. This button only available once Administrator log in.
Indicator:
This indicator will be green when ESD34 turn on. Otherwise it will be white.
When one of the units has abnormal conditions, this indicator will be red.
The Remote Control is set the function of input dry contact. The detail description refers to
Section 2-1-2(D) of “Enersine ESD34 Active Harmonic Filter User's Manual”.
Figure 3-16
Figure 3-17
ESD-Link34 User’s Manual 24
No. 192321852031001
Table 3-7 Event list
Item Event Item Event
1 POWER ON 2 Filtering
3 Full correcting 4 ERROR
5 MCCB Tripped 6 Fuse Blown
7 Input Power Abnormal 8 IGBT Fault
9 High Frequency Resonance 10 Over Peak Current
11 Over Current 12 Over Temperature(Power)
13 Fan Fault 14 Temp. Sensor Disconnected
15 DC Bus Error 16 DC Bus Under Voltage
17 DC Bus Over Voltage 18 External CTA Reversed
19 External CTB Reversed 20 External CTC Reversed
21 Parallel CTA Reversed 22 Parallel CTB Reversed
23 Parallel CTC Reversed 24 System Voltage Abnormal
25 System Under Voltage 26 System Over Voltage
27 Frequency Error 28 Phase Rotation Error
29 Control Board Error 30 Control Board EEPROM Error
31 Control Panel EEPROM Error 32 Power Supply Error
33 Current Cable Disconnected 34 CAN Bus Disconnected
35 Parallel Disconnected 36 Parallel ID Duplicated
37 Parallel Setting Error 38 Over Temperature(Control)
Figure 3-18
Figure 3-19
When the communication is disconnected, please check the communication cable between
the computer and ESD34 is connected properly and the communication card operates properly.
If the problem persists, please contact with local authorized service agent.
Figure 3-20
Figure 3-21
Figure 4-1
Figure 4-2
Figure 4-3