EPR POWER CABLE, SHIELDED, 5000/8000 VOLT, TYPE MV-105, SPEC 2-61-2

AEIC CS8 Ver. 8.0


Revised: 07/04/13

Copper
Conductor
Extruded
Conductor Shield EPR Semi-Conducting Copper Tape PVC or CPE
Insulation Insulation Shield Shield Jacket

105°C CONDUCTOR TEMPERATURE, WET OR DRY


Conductor Approximate
O.D. in Inches Approxi-
Nominal Ampacity** mate
Size AWG No. of O.D in Insulation Jacket Over 40°C Net Weight
or KCMIL Strands Inches in Mils in Mils Insulation Overall Ambient Lbs/Kft
SINGLE CONDUCTOR 5000 VOLT 133% or 8000 VOLT 100% INSULATION LEVEL, SHIELDED
6* 7 0.18 115 60 0.47 0.69 84 305
4* 7 0.23 115 60 0.52 0.74 110 375
2 7 0.27 115 60 0.56 0.78 145 470
1 19 0.30 115 60 0.59 0.81 175 540
1/0 19 0.34 115 60 0.63 0.85 200 625
2/0 19 0.38 115 60 0.67 0.89 225 730
3/0 19 0.42 115 80 0.71 0.98 270 895
4/0 19 0.48 115 80 0.77 1.03 305 1060
250 37 0.52 115 80 0.81 1.07 355 1200
350 37 0.62 115 80 0.91 1.17 430 1560
500 37 0.74 115 80 1.03 1.29 530 2085
750 61 0.91 115 80 1.20 1.46 665 2950
1000* 61 1.12 115 80 1.43 1.69 770 3860

SINGLE CONDUCTOR 8000 VOLT 133% INSULATION LEVEL, SHIELDED


6* 7 0.18 140 60 0.52 0.74 93 335
4* 7 0.23 140 60 0.57 0.79 120 410
2 7 0.27 140 60 0.61 0.83 165 505
1 19 0.30 140 60 0.64 0.86 190 575
1/0 19 0.34 140 60 0.68 0.90 215 665
2/0 19 0.38 140 80 0.72 0.98 255 805
3/0 19 0.42 140 80 0.76 1.03 290 940
4/0 19 0.48 140 80 0.82 1.08 330 1105
250 37 0.52 140 80 0.86 1.12 365 1250
350 37 0.62 140 80 0.96 1.22 440 1615
500 37 0.74 140 80 1.08 1.34 535 2145
750 61 0.91 140 80 1.25 1.51 655 3015
1000* 61 1.12 140 80 1.48 1.74 755 3935
Note: **Based on three single conductor cables in isolated conduit The above data is approximate and subject to normal manufacturing
in air per NEC. *Compressed conductors. tolerances.

STANDARDS AND RATINGS:


1. Listed by UL as Type MV-105 per Standard 1072.
2. Conforms to ICEA S-93-639/NEMA WC74 Shielded Power Cable 5 - 46KV.
3. Conforms to ICEA S-97-682 Utility Shielded Power Cables 5 - 46KV.
4. All sizes are listed by UL as Sunlight Resistant and sizes 1/0 AWG & larger are listed For CT Use.
5. Sizes 1/0AWG & larger are listed by UL for IEEE 1202 (must be 2/0AWG & larger for CPE jacketed).
6. Conforms to AEIC CS8.
AETNA INSULATED WIRE, LLC
1537 AIR RAIL AVENUE, VIRGINIA BEACH, VA 23455
TELEPHONE: (800) 423-6505 FAX: (757) 605-2094