MEC-100 Interface System

Order number Test date


Generator serial number
Customer SAC JA S.A. Software Release 3.0.4
MEC-100 serial number EB 10564
Type Firmware Release 2.01

PARAMETER UNIT MIN MAX DATA

SYSTEM PARAMETERS
Generator Data
Rated Voltage V 480
Rated Current A 1407.00
Rated Power Factor 0.800
Rated Frequency Hz 60.00
Rated Excitation Current A 4.10
Rated Real Power kW 935.8
Rated Reactive Power kVAR 701.9
Rated Apparent Power kVA 1170
System Options
Voltage Sensing 3-Phase
PF/VAR PF
Aux. Analog Input Setting
Single operation No
Parallel operation No
SENSING
Generator VT
Primary Voltage V 100 22000 480
Secondary Voltage V 100 500 480
Line VT
Primary Voltage V 100 22000 480
Secondary Voltage V 100 500 480
Generator CT
Primary Current A 0 10000 1500
Secondary Current A 1 5 1
Adjustments
Generator VT Ratio % 95 105 100.0
Line VT Ratio % 95 105 100.0
Generator CT Ratio % 95 105 99.7
Phase Compensation Gradi -20 +20 5.0
Excitation Current Measurement Offset 120
SETPOINT
Generator Voltage Setpoint
Voltage % 70 130 100.0
Minimum % 70 100 80.0
Maximum % 100 130 100.0
Power Factor Setpoint
Power Factor - - - 0.95 CAPACITIVE
Leading PF - 0.5 1 0.95
Lagging PF - 0.5 1 0.95
Reactive Power Setpoint
Reactive Power % - - 10.00
Minimum % -50 0 -10.00
Maximum % 0 100 10.00
Excitation Current Setpoint
1/3
MEC-100 Interface System
Order number Test date
Generator serial number
Customer SAC JA S.A. Software Release 3.0.4
MEC-100 serial number EB 10564
Type Firmware Release 2.01

PARAMETER UNIT MIN MAX DATA


Excit. Current % - - 74.97
Minimum % 0 100 15.04
Maximum % 1 120 80.02
OTHER SETTINGS
Soft Start
Soft start time s 1 3600 15
Traverse rate
Voltage %/s 0.1 5 1.1
Power Factor .00/s 1 10 1
Reactive Power %/s 0.1 5 1.2
Voltage Matching
Minimum % 90 100 90
Maximum % 100 110 110
Droop Settings
Reactive Droop Compensation % 1 10 3.9
Voltage Setpoint Adjustment DISABLED
PID SETTINGS
Voltage Regulation Stability
Proportional Gain 500
Integral Gain 120
Derivative Gain 600
Derivative Adjustments
1° Derivative Item: Time 60
2° Derivative Item: Filter 20
PF/VAR Regulation Stability
Proportional Gain 125
Integral Gain 100
LIMITERS
Underfrequency Limiter ENABLED
Corner Frequency Hz 40 60 58.0
Zero Volt Frequency Hz 0 40 20.0
Short Circuit Limiter ENABLED
Limiting Options V 0 1000 0
Overexcitation Limiter ENABLED
Maximum Current A 0 25 4.0
Time Delay s 0 600 5
Max. Continuative Current A 0 15 2.7
Apply to Relay1 NO
Apply to Relay2 NO
Underexcitation Limiter ENABLED
Leading Power at PF=0 % 0 60 15
Apply to Relay1 NO
Apply to Relay2 NO
FIELD PROTECTIONS
Protection: Field Overcurrent ENABLED
Maximum Current A 0 15 5.0

2/3
MEC-100 Interface System
Order number Test date
Generator serial number
Customer SAC JA S.A. Software Release 3.0.4
MEC-100 serial number EB 10564
Type Firmware Release 2.01

PARAMETER UNIT MIN MAX DATA


Time Delay s 0 10 5
Apply to Relay1 NO
Apply to Relay2 NO
Protection: Field Overvoltage ENABLED
Voltage Threshold V 0 200 30
Time Delay s 0 300 5
Apply to Relay1 NO
Apply to Relay2 NO
GENERATOR PROTECTIONS
Protection: Generator Overcurrent ENABLED
Maximum Current % 0 120 110
Maximum Continuative Current % 0 110 104
Time Delay s 0 3600 10
Apply to Relay1 NO
Apply to Relay2 NO
Protection: Generator Overvoltage ENABLED
Voltage Threshold % 100 150 110
Time Delay s 0 300 10
Apply to Relay1 NO
Apply to Relay2 NO
Protection: Generator Undervoltage ENABLED
Voltage Threshold % 0 100 80
Time Delay s 0 300 10
Apply to Relay1 NO
Apply to Relay2 NO
Protection: Loss of Sensing ENABLED
Apply to Relay1 NO
Apply to Relay2 NO
FCR DISABLED
DIODE MONITORING DEVICE
Low Level
Maximum Ripple % 0 100 10
Delay s 0 100 60
Apply to Relay1 NO
Apply to Relay2 NO
High Level
Maximum Ripple % 0 100 50
Delay s 0 100 6
Apply to Relay1 NO
Apply to Relay2 NO
Alarm Options
Enable Monitoring DISABLED
Enable Shutdown DISABLED

3/3