Professional Documents
Culture Documents
3RV10111HA15 Datasheet en
3RV10111HA15 Datasheet en
Ambient conditions
Installation altitude at height above sea level
● maximum 2 000 m
Ambient temperature
● during operation -20 ... +60 °C
● during storage -50 ... +80 °C
● during transport -50 ... +80 °C
Temperature compensation -20 ... +60 °C
Relative humidity during operation 10 ... 95 %
Main circuit
Number of poles for main current circuit 3
Adjustable pick-up value current of the current- 5.5 ... 8 A
dependent overload release
Operating voltage
● rated value 690 V
● at AC-3 rated value maximum 690 V
Operating frequency rated value 50 ... 60 Hz
Operating current rated value 8 A
Operating current
● at AC-3
— at 400 V rated value 8 A
Operating power
● at AC-3
— at 230 V rated value 1 500 W
— at 400 V rated value 3 000 W
— at 500 V rated value 4 000 W
— at 690 V rated value 5 500 W
Operating frequency
● at AC-3 maximum 15 1/h
Auxiliary circuit
UL/CSA ratings
Full-load current (FLA) for three-phase AC motor
● at 480 V rated value 8 A
● at 600 V rated value 8 A
Yielded mechanical performance [hp]
● for single-phase AC motor
Short-circuit protection
Product function Short circuit protection Yes
Design of the short-circuit trip magnetic
Design of the fuse link
● for short-circuit protection of the auxiliary switch fuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current
required Ik < 400 A)
Design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 240 V gL/gG 80 A
● at 400 V gL/gG 63 A
● at 500 V gL/gG 40 A
● at 690 V gL/gG 40 A
Connections/ Terminals
Product function
● removable terminal for auxiliary and control No
circuit
Type of electrical connection
● for main current circuit screw-type terminals
● for auxiliary and control current circuit screw-type terminals
Arrangement of electrical connectors for main current Top and bottom
circuit
Type of connectable conductor cross-sections
● for main contacts
— single or multi-stranded 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x (1 ... 4 mm²)
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Type of connectable conductor cross-sections
● for auxiliary contacts
— single or multi-stranded 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²)
Tightening torque
● for main contacts with screw-type terminals 0.8 ... 1.2 N·m
● for auxiliary contacts with screw-type terminals 0.8 ... 1.2 N·m
Certificates/ approvals
General Product Approval For use in hazardous locations
other Railway
Special Test Certi-
ficate
Further information
75
45 70
1 / L1 3 / L2 5 / L3
21 22 13 14
NC NO
45
90
2 / T1 4 / T2 6 / T3
3/L2
5/L3
13
21
-F
14
22
2/T1
4/T2
6/T3