Lately
Alor
follooihy We bor pin
PRELIMINARY
HEATING, VENTILATING AND AIR CONDITIONING
FUNDAMENTAL DESIGN REPORT
Design Criteria
is
Reference Criteria
BOCA Basic National Mechanical Code
BOCA Basic National Fire Prevention Code
BOCA National Energy Conservation Code
NFPA 211-84 Chimneys, Fire Places, Vents and Solid Fuel Burning
Appliances.
Guidelines of Construction and Equipment of Hospital and Medical
Facilities.
Latest issues of ASHRAE Handbooks, unless older issues are
referenced by state and/or local codes
Qutdoor design conditions for the Community Center and Residences
a. Summer: 89°F .0B, 73°F Wa
b. Winter: 10°F
¢. Source: ASHRAE 1989 Fundamentals Handbook, Chapter 24,
Weather Data, Columns of 2.5 Percent Values for
Cooling and 97.5 Percent Values for Heating for
New Brunswick, New Jersey
Outdoor design conditions for the Health Center
a. Summer: 92°F 0B, 74°F WB
b. Winter: — 69F
. Source: ASHRAE 1989 Fundamentals Handbook, Chapter 24,
Weather Data, Columns of 1 Percent Values for
Cooling and 99 Percent Values for Heating for
New Brunswick, New Jersey.
Qutdoor design condition for Cooling Tower selection
a. Summer: 78°F .WB,
b. Source: ASHRAE 1989 Fundamentals Handbook, Chapter 24,
Weather Data (July 1, 1978), 19F. Higher
than Column of 1 Percent for cooling for
New Brunswick, New JerseyIndoor design conditions
Space
Health Center
Patient Treatment
Areas
Health Center
Administrative and
Supportive Areas
Community Center
Administrative and
Supportive Areas
Dining Rooms
Library
Multipurpose
Room
Craft Shops
Swimming Pool
Locker Room
Exercise
kitchen
Laundry
Toilets
Apartments
Apartment,
Bathrooms,
Multistory
Apartment,
Corridors,
OB.
Summer
MAX
78
78
78
78
78
78
a0
80
78
86
No
No
78
No
80
NC
Cc
AC
RH
50
50
60
50
50
50
60
50
50
50
50
50
70
70
70
70
70
70
80
a0
75
70
68
70
70
80
70Spa Summer
0B MAK. RH
Mechanical and
Electrical Rooms No A/C 65 -
Ventilation
Space Minimum Air Changes of Minimum Total Air Changes
Outdoor Air per Hour per Hour Supplied to or
Supplied to Room Exhausted from Room
Patient Rm. - a
Patient Area
Corridor - 2
Examination &
Treatment. Am, = 6
Physical
Therapy - 6
Soiled
Workroom - 10
Clean
Workroom - 4
Patient Toilet
Room - 10
Patient
Bathroom - 10
Janitors"
Closet - 10
Linen Room - 10
Kitchen - 10
Warewash ing
Room - 10
Laundry - 10
Soiled Linen
Storage - 10Space Minimum Air Changes of Minimum Total Air Changes
Outdoor Air per Hour per Hour Supplied to or
Supplied to Room xhausted from Room
Corridors 5 cfm per person 0.02 cfm per sq. ft
Lockers 5 cfm per person 35 cfm per person
Public
Bathrooms - 75 cfm per water
closet or urinal
Nonpublic
Bathrooms - 50 cfm per water
closet
Parking
Garages - 1.5 cfm per sq. ft
Multipurpose
Room 5 cfm per person 35 cfm per person
Swimming pools &
Deck Areas 5 cfm per person 0.5 cfm per sq. ft
Barber and
Beauty Shops 5 cfm per person 35 cfm per person
Office Space 5 cfm per person 15 cfm per person
Source: Guidelines for Construction and Equipment of Hospitals
and Medical Facilities and the BOCA Basic National
Mechanical Code.
8. Heating Plant - Health and Community Center
1. Description
Three gas fired hot water boilers will provide heating hot water
for space heating and for heating of service water for the
Community and Health Center. The number and arrangements ofboilers will be such that, if one does not function or is taken
out of service, the remaining capacity will be adequate to provide
70% of the normal requirements of all systems and equipment
Secondary distribution system pumps will supply heating hot water
at different temperatures to various terminal heating equipment;
e.g. fan coil units, baseboard radiation, etc Secondary
distribution systems will consist of the following:
+ Health Center 4-pipe fan coil unit, reheat water, controlled
zone for the Conmunity and Health Center. Spare pumps wil)
be provided for all secondary distribution systems.
Primary heating water pumps will supply constant temperature hot
water produced by the boilers at 200°F. to all secondary
distribution systems and the service water heaters, Automatic
control valves will mix primary hot water with secondary
distribution system returns to provide secondary distribution
system supply water of the desired temperature. Each boiler will
have its own circulating pump. The boiler circulating pumps will
be located together with the boilers in the Community Center
Estimated Installed Capacity - 300 BHP.Chilled Water Plant - Health and Community Center
1
Description
Two chillers, each sized for 50% of the design load, will provide
chilled water for cooling of the Community and Health Center.- The
chilled water plant will be located in the Community Center
A primary-secondary pumping system will be provided. There will
be one chiller water pump per chiller and one system pump. These
pumps will supply chilled water to the air handling units in the
Community and Health Center, and to the 4-pipe fan coil units in
the Health Center. There will also be one spare chiller pump and
one spare system pump
Cooling towers located outside at grade will provide the chillers
with cool condenser water. The condenser water pumps, one per
chiller, will be located adjacent to the chillers. There will
also be one spare condenser water pump.
Two two-way valves in the condenser water return lines will divert,
water back to the chillers to permit cold weather startup of the
chillers. The cooling towers will, however, have to be draineddown for the cold weather season, because they will not be
"winterized" for year-round operation. The building operator will
decide when to start up and shut down the Chilled Water Plant.
Estimated Installed Capacity - 350 tons,
E. Air Conditioning System
1. General
Air conditioning systems will be designed to maintain the
conditions specified under "Design Criteria". The following
systems will be provided
2. Patient Rooms of the Health Center
Description: Each patient room will have a fan coil unit which
will heat and cool the room under the control of a room
thermostat. The fan coil units will have separate heating and
cooling coils which will be supplied with hot water for heating
and chilled water for cooling
Dedicated air handling units will supply all patient rooms with
the required amount of tempered and filtered outside air. The air
handling units will contain a hot water preheat coil and a chilledwater cooling coil, Energy recovery units will be installed
between the incoming filtered outside air and the filtered patient
bathroom exhaust system. Electric steam humidifiers will provide
humidification for the patient rooms through these units
3. Administrative and supportive areas of the Community and Health
Center.
Description: Areas of the Community and Health Centers will be
divided into multiple temperature control zones based on exposure
and/or usage. A variable air volume control box will supply each
zone with an amount of conditioned air varying directly with the
cooling load. When and where the cooling load is light, the
minimum required ventilation rate will be maintained and the
supply air reheated to prevent overcooling. Ahot water reheat
coil at the control box or hot water finned tube radiation at the
building perimeter will provide necessary reheating and heating,
A VAV air handling unit will supply all VAY control boxes with
conditioned air. The VAV air handling unit will contain a hot
water preheat coil and a chilled water cooling coil
Community Center DiningDescription: A constant volume air handling unit containing a chilled
water cooling coil and hot water reheat coil will condition the Dining
Room:
Hot water finned tube radiation at the perimeter will provide heating
in conjunction with the heating coil in the unit.
Community Center Kitchen
Description: A constant volume air handling unit containing a hot
water preheat coil, a chilled water cooling coil, and a hot water
reheat coil will condition the Kitchen. Depending upon make-up air
requirements due to exhaust, the unit may supply 100% outside air to
the Kitchen when it is occupied and in use, and change over to mostly
recirculated air when it is unoccupied and unused.
Community Center Multipurpose Room
Description: A constant volume air handling unit containing a hot
water preheat coil, a chilled water cooling coil and a hot water reheat
coil will condition the room, The unit may be shut down when the room
is unoccupied and unused. Hot water finned tube radiation at the
perimeter will provide heating to offset cold downdrafts.
Swimming PoolDescription: A constant volume air handling unit containing a hot
water preheat coil, a chilled water cooling coil and a hot water reheat
coil will condition the swinming pool. An energy recovery unit will be
installed between the incoming filtered outside air and the filtered
exhaust/relief from the pool. Hot water finned tube radiation at the
perimeter will provide heating in conjunction with the heating coil in
the unit.
Public Corridors of Multistory Apartment Blocks
Description: Constant volume air handling units containing gas or
electric heating and a direct-expansion (DX) cooling coil, will
condition the public corridors. The air handling unit will heat, cool
and ventilate the corridors. The air-cooled condensing unit for the DX
cooling coil will be located outside at grade. The decision to use
electric or gas heat will be made on the basis of economic analysis
Residential Apartments
Description: A residential electric heat pump or a gas fired furnace
containing a DC cooling coil will condition each apartment. The
air-cooled condensing unit will be located in the apartment exterior
wall or at grade. The decision to use electric heat pumps or gas Fired
furnaces will be made on the basis of economic analysis.F. Heating Systems
1. General
Heating systems will be designed to maintain the conditions
specified under "Design Criteria". The following systems will be
provided:
Systems Area Served
Fan Coil Units Patient Rooms
Unit Heaters Mechanical & Electrical Rooms
Cabinet Unit Heaters &
Convectors Building Entrances & Stairs
Radiation & Reheat Coils AN] Other Areas
Electric Radiant Ceiling
Panels Bathrooms
G. Heating & Ventilating SystemsH.
General
Heating and Ventilating systems will be designed to maintain the
conditions specified under "design Criteria". The following
systems will be provided.
Laundry
Description: A constant volume heating and ventilating unit with
a hot water heating coil will ventilate the Laundry spaces with up
to 100% outside air for heat removal. The unit-mounted heating
coil will provide heating as required.
Community Center Mechanical Room
Description: The units will provide 100% outside air for
combustion for the boilers at all times, The unit-mounted hot.
water heating coils will temper the air
Ventilating Systems
i
GeneralVentilating systems will be designed to maintain the conditions
specified under "Design Criteria". The following systems will be
provided.
2. Community Center Transformer Vault
Description: A two-speed exhaust fan will ventilate the
transformer vault with 100% filtered outside air for heat removal
I. Special Systems
1. Community Center Kitchen Range Exhaust Hood
Description: A make-up air unit will supply filtered, and
tempered outside air directly to the Kitchen range exhaust hoods
This make-up air will be approximately 50% of the hood exhaust air
quantity.
J. Energy Conservation
1. Air conditioning systems will operate on economizer cycles,
providing "free cooling" with outside air whenever possible
2. Variable air volume air conditioning systems will be employed to
minimize fan energy consumed and reheat energy requiredAir conditioning systems will be shut down during unoccupied
periods whenever possible. Upon startup, warmup or cooling
pulldown will be accomplished with no outside air.
Wherever possible, space heating temperatures will be reduced
during unoccupied periods
Kitchen range hood exhaust systems will employ as much tempered
ambient air as permissible.
Dual setpoint heating-cooling energy deadband room thermostats
will be used wherever applicable to reduce reheat energy consumed.
In order to improve part-load operation, the Central Cooling Plant
will be designed as a multiple chiller plant, which will enable
the operation of the chillers with their associated pumps to be
staged. .
Heating hot water temperatures for the controlled zones and fan
coil units will be reset with outside air temperatures to improve
controllability and reduce piping heat losses
Energy recovery units for the Health Center and Pool will preheat
and pre-cool the outside air being taken-in.Ke
10.
The supply air temperature of constant volume air conditioning
systems will be automatically reset up to minimize the use of
reheat energy.
Automatic Temperature Controls
‘The automatic temperature controls for the Community and Health
Center will be pneumatic. The pneumatic control systems will use
proportional (P) and proportional with reset (P1) controllers.
System chilled water flow and system primary heating water flows
will be measured and recorded to develop building operating data
for the present and future. An alarm system will be provided for
vital systems.
The automatic temperature controls for the Residences will be
electric.