Hydraulic Calculations Date: 07/29/03

Project: Neeta User input


Number: 1C02021.3 Calculated

Location: Storage Room


Zone: 1 SQFT/Head: 130
Hazard: Ord. Group I K-Factor: 5.6
Density: 0.15 GPM/SQFT. Head Q: 19.5 Q=k(P)^1/2
Area: 930 SQ.FT. Head P: 12.1
Hose: 0 GPM
Elevation: 10 Feet

Step 1: Estimate Sprinkler Flow

Q= (Density x Area)(1.15) + Hose


Q= 160.425

Step 2: Estimate Pressure Losses

Losses Thru System: PSI Refer to "Cameron Hydraulic" Ch. 3


Note: 1' = 0.433 PSI Sprinkler Flow: 160.425 GPM
Sprinklers: 12.13 Pipe Size Length Loss/100' Total Loss
Piping: 10.55 (See table --->) 6" 0.00
Elevation: 4.33 4" 0.00
Alarm Valve: 3" 420 5.8 24.36
Check Valve: 2-1/2" 0.00
Backflow: 5.00 Watts 709DCDA Total: 24.36 (feet)
Total: 32.00 10.55 (PSI)

Step 3: Plot Demand vs. Water Supply

Hydraulic Graph: Flow vs. Pressure


System Demand: 160.425 GPM GPM PSI
32.00 PSI Curve 1: City 0 0
0 0
Demand +10%: 176.47 GPM
35.20 PSI
HEAD
City Supply: Static Curve 2: Pump 0.00 From Pump Curve
Residual 0.00 From Pump Curve
Flow 0.00 From Pump Curve
Fire Pump: Flow 0 0.00 0.00 Rated Capacity
Feet 0 0.00 0.00 150% @ 65%

Hydraulic Graph
40
35
30
Pressure - PSI

25
20
15
10
5
0
0 20 40 60 80 100 120 140 160 180 200
Flow - GPM

Fire Pump City Supply


System Demand Demand +10%
Hydraulic Calculations Date: 07/29/03

Project: GladysHillman User input


Number: 04Y0038 Calculated

Location: Gymnasium
Zone: 1 SQFT/Head: 120
Hazard: Light Hazard K-Factor: 5.6
Density: 0.12 GPM/SQFT. Head Q: 14.4 Q=k(P)^1/2
Area: 1500 SQ.FT. Head P: 6.6
Hose: 100 GPM
Elevation: 47 Feet

Step 1: Estimate Sprinkler Flow

Q= (Density x Area)(1.15) + Hose


Q= 307

Step 2: Estimate Pressure Losses

Losses Thru System: PSI Refer to "Cameron Hydraulic" Ch. 3


Note: 1' = 0.433 PSI Sprinkler Flow: 207 GPM
Sprinklers: 6.61 Pipe Size Length Loss/100' Total Loss
Piping: 17.58 (See table --->) 6" 0.00
Elevation: 20.35 4" 700 5.8 40.60
Alarm Valve: 5.00 3" 0 0.00
Check Valve: 2-1/2" 0.00
Backflow: 5.00 Watts 709DCDA Total: 40.60 (feet)
Total: 54.54 17.58 (PSI)

Step 3: Plot Demand vs. Water Supply

Hydraulic Graph: Flow vs. Pressure


System Demand: 307 GPM GPM PSI
54.54 PSI Curve 1: City 0 48
905 45
Demand +10%: 337.70 GPM
60.00 PSI
HEAD
City Supply: 48 Static Curve 2: Pump 0.00 From Pump Curve
45 Residual 0.00 From Pump Curve
905 Flow 0.00 From Pump Curve
Fire Pump: 500 Flow 500 74.91 173.00 Rated Capacity
173.00 Feet 750 48.69 112.45 150% @ 65%

Hydraulic Graph
80
70
60
Pressure - PSI

50
40
30
20
10
0
0 100 200 300 400 500 600 700 800 900 1000
Flow - GPM

Fire Pump City Supply


System Demand Demand +10%