You are on page 1of 12

UNILEVER DRESSING AREA

Fire Sprinkler Reports

for

UNILEVER PH

Prepared By:

12/5/2020
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr UNILEVER DRESSING AREA
Hell Page 2

General Project Data Report

General Data
Project Title: DRESSING AREA ADRIAN
UNILEVER DRESSING AREA Project File Name:
OH2..fiw
Designed By: Date: 12/5/2020
Code Reference: NFPA 13 Approving Agency: AHJ
Client Name: UNILEVER PH Phone:
Address: City, State Zip Code:
Company Name: Representative:
Company Address: City And State:
Phone:
Building Name: UNILEVER DRESSING AREA Building Owner: UNILEVER PH
Contact at Building: Phone at Building:
Address Of Building: City, State Zip Code:

Project Data
Description Of Hazard: Ordinary 2 Sprinkler System Type: Wet
Design Area Of Water Application: 1500 ft² Maximum Area Per Sprinkler: 129 ft²
Default Sprinkler K-Factor: 5.60 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 250.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Sprinkler Specifications
Make: Model:
Size: Temperature Rating: 0 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID: Date Of Test:

Hydrant Elevation: 0 ft Static Pressure: 0.00 psi


Test Flow Rate: 0.00 gpm Test Residual Pressure: 0.00 psi
Calculated System Flow Rate: 377.77 gpm Calculated Inflow Residual Pressure: 101.24 psi

Calculation Project Data


Calculation Mode: Demand
HMD Minimum Residual Pressure: 10.00 psi Minimum Desired Flow Density: 0.20 gpm/ft²
Number Of Active Nodes: 18
Number Of Active Pipes: 17 Number Of Inactive Pipes: 0
Number Of Active Sprinklers: 12 Number Of Inactive Sprinklers: 0

C:\ ...\DRESSING AREA ADRIAN OH2.fiw Saturday, December 12, 2020, 10:45 PM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr UNILEVER DRESSING AREA
Hell Page 3

Fire Sprinkler Input Data

Node Input Data


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

No Discharge ---- N/A 101.24 0.00 0.00


1
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 100.15 0.00 0.00


2
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 90.36 22.00 0.00


3
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 55.01 22.00 0.00


4
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 45.87 23.00 0.00


5
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 37.28 23.00 0.00


6
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 24.87 23.00 0.00


7
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 22.25 23.00 0.00


8
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 53.12 22.00 0.00


9
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 46.78 23.00 0.00


10
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 38.03 23.00 0.00


11
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 25.38 23.00 0.00


12
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 22.71 23.00 0.00


13
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 52.62 22.00 0.00


14
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 43.84 23.00 0.00


15
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 35.61 23.00 0.00


16
---- 0.000 0.0 ---- 0.0 0.00

C:\ ...\DRESSING AREA ADRIAN OH2.fiw Saturday, December 12, 2020, 10:45 PM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr UNILEVER DRESSING AREA
Hell Page 4

Fire Sprinkler Input Data

Node Input Data (cont'd)


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)
Sprinkler ---- 5.60 23.73 23.00 0.00
17
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 21.23 23.00 0.00


18
---- 0.000 0.0 ---- 0.0 0.00

C:\ ...\DRESSING AREA ADRIAN OH2.fiw Saturday, December 12, 2020, 10:45 PM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr UNILEVER DRESSING AREA
Hell Page 5

Fire Sprinkler Input Data

Pipe Input Data


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inc
Node Node Group Data
(inch) (feet) (feet) (feet) h-psi)

1 2 SCHED 40 WET STEEL 8.000 0 5ET 590.00 125.00 715.00 120

2 3 SCHED 40 WET STEEL 6.000 0 E 32.00 14.00 46.00 120

3 4 SCHED 40 WET STEEL 3.000 0 4ET 177.00 43.00 220.00 120

4 5 SCHED 40 WET STEEL 2.000 0 E3T 25.00 35.00 60.00 120

5 6 SCHED 40 WET STEEL 1.250 0 T 10.00 6.00 16.00 120

6 7 SCHED 40 WET STEEL 1.000 0 T 10.00 5.00 15.00 120

7 8 SCHED 40 WET STEEL 1.000 0 E 10.00 2.00 12.00 120

4 9 SCHED 40 WET STEEL 3.000 0 T 10.00 15.00 25.00 120

9 14 SCHED 40 WET STEEL 3.000 0 T 10.00 15.00 25.00 120

9 10 SCHED 40 WET STEEL 2.000 0 ET 25.00 15.00 40.00 120

10 11 SCHED 40 WET STEEL 1.250 0 T 10.00 6.00 16.00 120

11 12 SCHED 40 WET STEEL 1.000 0 T 10.00 5.00 15.00 120

12 13 SCHED 40 WET STEEL 1.000 0 E 10.00 2.00 12.00 120

14 15 SCHED 40 WET STEEL 2.000 0 E3T 25.00 35.00 60.00 120

15 16 SCHED 40 WET STEEL 1.250 0 T 10.00 6.00 16.00 120

16 17 SCHED 40 WET STEEL 1.000 0 T 10.00 5.00 15.00 120

17 18 SCHED 40 WET STEEL 1.000 0 E 10.00 2.00 12.00 120

C:\ ...\DRESSING AREA ADRIAN OH2.fiw Saturday, December 12, 2020, 10:45 PM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr UNILEVER DRESSING AREA
Hell Page 6

Fire Sprinkler Output Data

Overall Node Groupings Output Data


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

1 2 0 377.77 0.00 0.00 -377.77 101.24

2 1 0 -377.77 0.00 0.00 0.00 100.15 0.00000


2 3 0 377.77

3 2 0 -377.77 0.00 0.00 0.00 90.36 0.00000


3 4 0 377.77

4 3 0 -377.77 0.00 0.00 0.00 55.01 0.00000


4 5 0 126.46
4 9 0 251.31

5 4 0 -126.46 37.93 0.00 0.00 45.87 0.00000


5 6 0 88.54

6 5 0 -88.54 34.19 0.00 0.00 37.28 0.00000


6 7 0 54.34

7 6 0 -54.34 27.93 0.00 0.00 24.87 0.00000


7 8 0 26.42

8 7 0 -26.42 26.42 0.00 0.00 22.25 0.00000

9 4 0 -251.31 0.00 0.00 0.00 53.12 0.00000


9 14 0 123.57
9 10 0 127.73

10 9 0 -127.73 38.30 0.00 0.00 46.78 0.00000


10 11 0 89.43

11 10 0 -89.43 34.53 0.00 0.00 38.03 0.00000


11 12 0 54.90

12 11 0 -54.90 28.21 0.00 0.00 25.38 0.00000


12 13 0 26.69

13 12 0 -26.69 26.69 0.00 0.00 22.71 0.00000

14 9 0 -123.57 0.00 0.00 0.00 52.62 0.00000


14 15 0 123.57

15 14 0 -123.57 37.08 0.00 0.00 43.84 0.00000


15 16 0 86.50

16 15 0 -86.50 33.42 0.00 0.00 35.61 0.00000


16 17 0 53.08

17 16 0 -53.08 27.28 0.00 0.00 23.73 0.00000


17 18 0 25.80

C:\ ...\DRESSING AREA ADRIAN OH2.fiw Saturday, December 12, 2020, 10:45 PM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr UNILEVER DRESSING AREA
Hell Page 7

Fire Sprinkler Output Data

Overall Node Groupings Output Data (cont'd)


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)
18 17 0 -25.80 25.80 0.00 0.00 21.23 0.00000

C:\ ...\DRESSING AREA ADRIAN OH2.fiw Saturday, December 12, 2020, 10:45 PM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr UNILEVER DRESSING AREA
Hell Page 8

Fire Sprinkler Output Data

Overall Pipe Output Data


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

1 0.00 0.00 0.00 101.24 8.00 0.00 0.00153 590.00 1.092


2 0.00 0.00 0.00 100.15 7.981 377.77 5ET 125.00 0.000
SCHED 40 WET STEEL 120 2.42 0 715.00 1.092

2 0.00 0.00 0.00 100.15 6.00 0.00 0.00581 32.00 0.267


3 0.00 22.00 0.00 90.36 6.065 377.77 E 14.00 9.526
SCHED 40 WET STEEL 120 4.20 0 46.00 9.793

3 0.00 22.00 0.00 90.36 3.00 0.00 0.16066 177.00 35.344


4 0.00 22.00 0.00 55.01 3.068 377.77 4ET 43.00 0.000
SCHED 40 WET STEEL 120 16.39 0 220.00 35.344

4 0.00 22.00 0.00 55.01 2.00 37.93 0.14517 25.00 8.710


5 5.60 23.00 37.93 45.87 2.067 126.46 E3T 35.00 0.433
SCHED 40 WET STEEL 120 12.09 0 60.00 9.143

4 0.00 22.00 0.00 55.01 3.00 0.00 0.07557 10.00 1.889


9 0.00 22.00 0.00 53.12 3.068 251.31 T 15.00 0.000
SCHED 40 WET STEEL 120 10.91 0 25.00 1.889

5 5.60 23.00 37.93 45.87 1.25 34.19 0.53689 10.00 8.590


6 5.60 23.00 34.19 37.28 1.380 88.54 T 6.00 0.000
SCHED 40 WET STEEL 120 18.99 0 16.00 8.590

6 5.60 23.00 34.19 37.28 1.00 27.93 0.82746 10.00 12.412


7 5.60 23.00 27.93 24.87 1.049 54.34 T 5.00 0.000
SCHED 40 WET STEEL 120 20.17 0 15.00 12.412

7 5.60 23.00 27.93 24.87 1.00 26.42 0.21786 10.00 2.614


8 5.60 23.00 26.42 22.25 1.049 26.42 E 2.00 0.000
SCHED 40 WET STEEL 120 9.81 0 12.00 2.614

9 0.00 22.00 0.00 53.12 3.00 0.00 0.02032 10.00 0.508


14 0.00 22.00 0.00 52.62 3.068 123.57 T 15.00 0.000
SCHED 40 WET STEEL 120 5.36 0 25.00 0.508

9 0.00 22.00 0.00 53.12 2.00 38.30 0.14787 25.00 5.915


10 5.60 23.00 38.30 46.78 2.067 127.73 ET 15.00 0.433
SCHED 40 WET STEEL 120 12.21 0 40.00 6.348

10 5.60 23.00 38.30 46.78 1.25 34.53 0.54698 10.00 8.752


11 5.60 23.00 34.53 38.03 1.380 89.43 T 6.00 0.000
SCHED 40 WET STEEL 120 19.18 0 16.00 8.752

11 5.60 23.00 34.53 38.03 1.00 28.21 0.84318 10.00 12.648


12 5.60 23.00 28.21 25.38 1.049 54.90 T 5.00 0.000
SCHED 40 WET STEEL 120 20.38 0 15.00 12.648

C:\ ...\DRESSING AREA ADRIAN OH2.fiw Saturday, December 12, 2020, 10:45 PM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr UNILEVER DRESSING AREA
Hell Page 9

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

12 5.60 23.00 28.21 25.38 1.00 26.69 0.22202 10.00 2.664


13 5.60 23.00 26.69 22.71 1.049 26.69 E 2.00 0.000
SCHED 40 WET STEEL 120 9.91 0 12.00 2.664

14 0.00 22.00 0.00 52.62 2.00 37.08 0.13909 25.00 8.345


15 5.60 23.00 37.08 43.84 2.067 123.57 E3T 35.00 0.433
SCHED 40 WET STEEL 120 11.82 0 60.00 8.778

15 5.60 23.00 37.08 43.84 1.25 33.42 0.51423 10.00 8.228


16 5.60 23.00 33.42 35.61 1.380 86.50 T 6.00 0.000
SCHED 40 WET STEEL 120 18.55 0 16.00 8.228

16 5.60 23.00 33.42 35.61 1.00 27.28 0.79216 10.00 11.882


17 5.60 23.00 27.28 23.73 1.049 53.08 T 5.00 0.000
SCHED 40 WET STEEL 120 19.70 0 15.00 11.882

17 5.60 23.00 27.28 23.73 1.00 25.80 0.20853 10.00 2.502


18 5.60 23.00 25.80 21.23 1.049 25.80 E 2.00 0.000
SCHED 40 WET STEEL 120 9.58 0 12.00 2.502

C:\ ...\DRESSING AREA ADRIAN OH2.fiw Saturday, December 12, 2020, 10:45 PM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr UNILEVER DRESSING AREA
Hell Page 10

Fire Sprinkler Output Data

Overall Sprinkler Output Data


Flowing Sprinkler Residual Flowing Sprinkler
Area Group Sprinkler Flowing
Sprinkler Elevation Pressure Density Discharge
Code KFactor (K) Area (ft²)
Node No. (feet) (psi) (gpm/ft²) (gpm)

5 5.60 23.00 45.87 129.00 0.294 37.93


Sub Totals For Non-Group 129.00 0.294 37.93

6 5.60 23.00 37.28 129.00 0.265 34.19


Sub Totals For Non-Group 129.00 0.265 34.19

7 5.60 23.00 24.87 129.00 0.216 27.93


Sub Totals For Non-Group 129.00 0.216 27.93

8 5.60 23.00 22.25 129.00 0.205 26.42


Sub Totals For Non-Group 129.00 0.205 26.42

10 5.60 23.00 46.78 129.00 0.297 38.30


Sub Totals For Non-Group 129.00 0.297 38.30

11 5.60 23.00 38.03 129.00 0.268 34.53


Sub Totals For Non-Group 129.00 0.268 34.53

12 5.60 23.00 25.38 129.00 0.219 28.21


Sub Totals For Non-Group 129.00 0.219 28.21

13 5.60 23.00 22.71 129.00 0.207 26.69


Sub Totals For Non-Group 129.00 0.207 26.69

15 5.60 23.00 43.84 129.00 0.287 37.08


Sub Totals For Non-Group 129.00 0.287 37.08

16 5.60 23.00 35.61 129.00 0.259 33.42


Sub Totals For Non-Group 129.00 0.259 33.42

17 5.60 23.00 23.73 129.00 0.211 27.28


Sub Totals For Non-Group 129.00 0.211 27.28

18 5.60 23.00 21.23 129.00 0.200 25.80


Sub Totals For Non-Group 129.00 0.200 25.80

Totals For All Groups 1548.00 0.244 377.77

C:\ ...\DRESSING AREA ADRIAN OH2.fiw Saturday, December 12, 2020, 10:45 PM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr UNILEVER DRESSING AREA
Hell Page 11

Fire Sprinkler Output Summary

Hydraulically Most Demanding Sprinkler Node


HMD Sprinkler Node Number: 18
HMD Actual Residual Pressure: 21.23 psi
HMD Actual GPM: 25.80 gpm

Sprinkler Summary
Sprinkler System Type: Wet
Specified Area Of Application: 1500.00 ft²
Minimum Desired Density: 0.200 gpm/ft²
Application Average Density: 0.252 gpm/ft²
Application Average Area Per Sprinkler: 125.00 ft²
Sprinkler Flow: 377.77 gpm
Average Sprinkler Flow: 31.48 gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 11 - 12 ) 20.38 ft/sec
Maximum Velocity Pressure ( In Pipe 11 - 12 ) 2.80 psi

Allowable Maximum Nodal Pressure Imbalance: 0.0000 psi


Actual Maximum Nodal Pressure Imbalance: 0.0000 psi
Actual Average Nodal Pressure Imbalance: 0.0000 psi
Actual Maximum Nodal Flow Imbalance: 0.0000 gpm
Actual Average Nodal Flow Imbalance: 0.0000 gpm

Overall Network Summary


Number Of Unique Pipe Sections: 17
Number Of Flowing Sprinklers: 12

Pipe System Water Volume: 1675.07 gal

Sprinkler Flow: 377.77 gpm


Non-Sprinkler Flow: 0.00 gpm

Minimum Required Residual Pressure At System Inflow


101.24 psi
Node:
Demand Flow At System Inflow Node: 377.77 gpm

C:\ ...\DRESSING AREA ADRIAN OH2.fiw Saturday, December 12, 2020, 10:45 PM
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr UNILEVER DRESSING AREA
Hell Page 12

Fire Sprinkler Output Data

Hydraulic Supply/Demand Graph

200

180

160

140
Pressure psi

120

101
100

80

60

40

20

0
1 2 3 4 5 6 7 8 9 10
Flowrate(x100) gpm

Demand Curve Data


Calculated Residual Pressure: 101.24 psi
Calculated Flow Rate: 377.77 gpm
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 9.96 psi

C:\ ...\DRESSING AREA ADRIAN OH2.fiw Saturday, December 12, 2020, 10:45 PM