You are on page 1of 9

EXAMPLE PROJECT

Fire Hose System Reports

for

Jones & Wilson, Architects

1234 First Street NW


Harrisburg, PA

Prepared By:

YOUR NAME
ABC Engineering, Inc.
4567 2nd St.
Harrisburg, PA
555-555-9876
November 20, 2000
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 2

General Project Data Report (Inputs may have changed)

General Data
Project Title: EXAMPLE PROJECT Project File Name: Sample..fiw
Designed By: YOUR NAME Date: November 20, 2000
Code Reference: NFPA 13 Approving Agency: LOCAL JURISDICTION
Job number: 97594
Client Name: Jones & Wilson, Architects Phone: 555-555-1234
Address: 1234 First Street NW City, State Zip Code: Harrisburg, PA
Company Name: ABC Engineering, Inc. Representative: Mike Roberts
Company Address: 4567 2nd St. City And State: Harrisburg, PA
Phone: 555-555-9876
Job number: 97594
Building Name: Test Building Building Owner: Amalgamated, Inc.
Contact at Building: Jim Jones Phone at Building: 555-555-9876
Address Of Building: 1234 Main Street City, State Zip Code: Harrisburg, PA

Project Data
Description Of Hazard: Ordinary Group 1 Hose System Type: Wet
Design Area Of Water Application: 600 ft² Maximum Area Per Hose: 130 ft²
Default Hose K-Factor: 5.65 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 50.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Hose Specifications
Make: GLOBE Model: G
Size: 2.5 Temperature Rating: 160 F
NONE

Water Supply Test Data


Source Of Information: LOCAL FIRE MARSHAL
Test Hydrant ID: 3B Date Of Test: DECEMBER 15, 1992

Hydrant Elevation: 0 ft Static Pressure: 85.00 psi


Test Flow Rate: 202.00 gpm Test Residual Pressure: 77.00 psi
Calculated System Flow Rate: 141.08 gpm Calculated Inflow Residual Pressure: 20.44 psi
Available Residual Pressure At
80.88 psi
System Flow:

Calculation Project Data


Calculation Mode: Demand
HMD Minimum Residual Pressure: 7.00 psi Minimum Desired Flow Density: 0.00 gpm/ft²
Maximum Water Velocity: 20.00 ft/s Maximum Frictional Loss / 100 feet: 20.00 psi
Number Of Active Nodes: 10
Number Of Active Pipes: 10 Number Of Inactive Pipes: 0
Number Of Active Hoses: 6 Number Of Inactive Hoses: 0

C:\Users\Zicom\Documents\Elite Software\Fire 6 Projects\Sample..fiw Wednesday, April 20, 2022, 10:00 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 3

Fire Hose Input Data

Node Input Data (Inputs may have changed)


Hose KFactor Pressure Node Elev (ft) Fixed Flow
Area Group
Node Node Description (K) Estimate (psi) Branch Non- (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

Hose A 5.65 7.52 20.00 0.00


10
---- 0.000 0.0 ---- 0.0 0.00

Hose A 5.65 7.52 20.00 0.00


20
---- 0.000 0.0 ---- 0.0 0.00

Hose B 5.65 7.00 20.00 0.00


30
---- 0.000 0.0 ---- 0.0 0.00

Hose B 5.65 7.09 20.00 0.00


40
---- 0.000 0.0 ---- 0.0 0.00

Fixed B N/A 7.54 20.00 50.00


50
---- 0.000 0.0 ---- 0.0 0.00

No Discharge C N/A 7.58 20.00 0.00


60
---- 0.000 0.0 ---- 0.0 0.00

Hose C 5.65 7.14 20.00 0.00


70
---- 0.000 0.0 ---- 0.0 0.00

Hose C 5.65 7.04 20.00 0.00


80
---- 0.000 0.0 ---- 0.0 0.00

No Discharge C N/A 8.04 20.00 0.00


90
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 20.44 0.00 0.00


100
---- 0.000 0.0 ---- 0.0 0.00

C:\Users\Zicom\Documents\Elite Software\Fire 6 Projects\Sample..fiw Wednesday, April 20, 2022, 10:00 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 4

Fire Hose Input Data

Pipe Input Data (Inputs may have changed)


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

10 20 SCHED 40 WET STEEL 2.500 1 10.00 0.00 10.00 120

10 60 SCHED 40 WET STEEL 2.500 1 E 25.00 6.00 31.00 120

20 50 SCHED 40 WET STEEL 2.500 1 E 15.00 6.00 21.00 120

30 40 SCHED 40 WET STEEL 1.500 2 10.00 0.00 10.00 120

40 50 SCHED 40 WET STEEL 1.500 2 T 5.00 8.00 13.00 120

50 90 SCHED 40 WET STEEL 2.500 1 15.00 0.00 15.00 120

60 70 SCHED 40 WET STEEL 1.500 2 T 5.00 8.00 13.00 120

60 90 SCHED 40 WET STEEL 2.500 1 ET 25.00 18.00 43.00 120

70 80 SCHED 40 WET STEEL 1.500 2 10.00 0.00 10.00 120

90 100 SCHED 40 WET STEEL 2.500 1 50.00 0.00 50.00 120

C:\Users\Zicom\Documents\Elite Software\Fire 6 Projects\Sample..fiw Wednesday, April 20, 2022, 10:00 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 5

Fire Hose Output Data

Overall Node Groupings Output Data (Inputs may have changed)


Pipe Segment Pipe Pipe Hose Flow Fixed Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

10 20 1 0.00 15.50 0.00 0.00 7.52 0.00055


10 60 1 0.00

20 10 1 0.00 15.50 0.00 0.00 7.52 0.00055


20 50 1 0.00

30 40 2 0.00 14.95 0.00 0.00 7.00 0.00000

40 30 2 0.00 15.05 0.00 0.00 7.09 -0.00007


40 50 2 0.00

50 20 1 0.00 0.00 50.00 0.00 7.54 0.00000


50 40 2 0.00
50 90 1 0.00

60 10 1 0.00 0.00 0.00 0.00 7.58


60 70 2 0.00
60 90 1 0.00

70 60 2 0.00 15.09 0.00 0.00 7.14 -0.00014


70 80 2 0.00

80 70 2 0.00 14.99 0.00 0.00 7.04 -0.00036

90 50 1 0.00 0.00 0.00 0.00 8.04


90 60 1 0.00
90 100 1 0.00

100 90 1 0.00 0.00 0.00 0.00 20.44

C:\Users\Zicom\Documents\Elite Software\Fire 6 Projects\Sample..fiw Wednesday, April 20, 2022, 10:00 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 6

Fire Hose Output Data

Overall Pipe Output Data (Inputs may have changed)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Hose/Fix Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

10 5.65 20.00 15.50 7.52 2.50 0.00 0.00009 10.00 0.001


20 5.65 20.00 15.50 7.52 2.469 3.82 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0.26 1 10.00 0.001

30 5.65 20.00 14.95 7.00 1.50 0.00 0.00943 10.00 0.094


40 5.65 20.00 15.05 7.09 1.610 14.95 ----- 0.00 0.000
SCHED 40 WET STEEL 120 2.36 2 10.00 0.094

20 5.65 20.00 15.50 7.52 2.50 0.00 0.00074 15.00 0.016


50 0.00 20.00 50.00 7.54 2.469 11.68 E 6.00 0.000
SCHED 40 WET STEEL 120 0.78 1 21.00 0.016

40 5.65 20.00 15.05 7.09 1.50 0.00 0.03422 5.00 0.445


50 0.00 20.00 50.00 7.54 1.610 30.00 T 8.00 0.000
SCHED 40 WET STEEL 120 4.73 2 13.00 0.445

10 5.65 20.00 15.50 7.52 2.50 0.00 0.00189 25.00 0.059


60 0.00 20.00 0.00 7.58 2.469 19.32 E 6.00 0.000
SCHED 40 WET STEEL 120 1.29 1 31.00 0.059

60 0.00 20.00 0.00 7.58 1.50 0.00 0.03440 5.00 0.447


70 5.65 20.00 15.09 7.14 1.610 30.09 T 8.00 0.000
SCHED 40 WET STEEL 120 4.74 2 13.00 0.447

70 5.65 20.00 15.09 7.14 1.50 0.00 0.00948 10.00 0.095


80 5.65 20.00 14.99 7.04 1.610 14.99 ----- 0.00 0.000
SCHED 40 WET STEEL 120 2.36 2 10.00 0.095

50 0.00 20.00 50.00 7.54 2.50 0.00 0.03369 15.00 0.505


90 0.00 20.00 0.00 8.04 2.469 91.68 ----- 0.00 0.000
SCHED 40 WET STEEL 120 6.14 1 15.00 0.505

60 0.00 20.00 0.00 7.58 2.50 0.00 0.01073 25.00 0.462


90 0.00 20.00 0.00 8.04 2.469 49.40 ET 18.00 0.000
SCHED 40 WET STEEL 120 3.31 1 43.00 0.462

90 0.00 20.00 0.00 8.04 2.50 0.00 0.07479 50.00 3.740


100 0.00 0.00 0.00 20.44 2.469 141.08 ----- 0.00 8.660
SCHED 40 WET STEEL 120 9.45 1 50.00 12.400

C:\Users\Zicom\Documents\Elite Software\Fire 6 Projects\Sample..fiw Wednesday, April 20, 2022, 10:00 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 7

Fire Hose Output Data

Overall Hose Output Data (Inputs may have changed)


Flowing Node Residual Flowing Hose
Area Group Hose Flowing Area
Hose Node Elevation Pressure Density Discharge
Code KFactor (K) (ft²)
No. (feet) (psi) (gpm/ft²) (gpm)

10 A 5.65 20.00 7.52 130.00 0.119 15.50


20 A 5.65 20.00 7.52 130.00 0.119 15.50
Sub Totals For Group A 260.00 0.119 31.00

30 B 5.65 20.00 7.00 130.00 0.115 14.95


40 B 5.65 20.00 7.09 130.00 0.116 15.05
Sub Totals For Group B 260.00 0.115 30.00

70 C 5.65 20.00 7.14 130.00 0.116 15.09


80 C 5.65 20.00 7.04 130.00 0.115 14.99
Sub Totals For Group C 260.00 0.116 30.08

Totals For All Groups 780.00 0.117 91.08

C:\Users\Zicom\Documents\Elite Software\Fire 6 Projects\Sample..fiw Wednesday, April 20, 2022, 10:00 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 8

Fire Hose Output Summary (Inputs may have changed)

Hydraulically Most Demanding Hose Node


HMD Hose Node Number: 30
HMD Actual Residual Pressure: 7.00 psi
HMD Actual GPM: 14.95 gpm

Hose Summary
Hose System Type: Wet
Specified Area Of Application: 600.00 ft²
Minimum Desired Density: 0.000 gpm/ft²
Application Average Density: 0.152 gpm/ft²
Application Average Area Per Hose: 100.00 ft²
Hose Flow: 91.08 gpm
Average Hose Flow: 15.18 gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 0 - 0 ) 0.00 ft/sec
Maximum Velocity Pressure ( In Pipe 0 - 0 ) 0.00 psi

Allowable Maximum Nodal Pressure Imbalance: 0.0100 psi


Actual Maximum Nodal Pressure Imbalance: 0.0064 psi
Actual Average Nodal Pressure Imbalance: 0.0010 psi
Actual Maximum Nodal Flow Imbalance: 0.0006 gpm
Actual Average Nodal Flow Imbalance: 0.0002 gpm

Overall Network Summary


Number Of Unique Pipe Sections: 10
Number Of Flowing Hoses: 6

Pipe System Water Volume: 37.99 gal

Hose Flow: 91.08 gpm


Fixed Flow: 50.00 gpm

Minimum Required Residual Pressure At System Inflow


20.44 psi
Node:
Demand Flow At System Inflow Node: 141.08 gpm

C:\Users\Zicom\Documents\Elite Software\Fire 6 Projects\Sample..fiw Wednesday, April 20, 2022, 10:00 AM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr EXAMPLE PROJECT
Hell Page 9

Fire Hose Output Data (Inputs may have changed)

Hydraulic Supply/Demand Graph

100

90
85

80 77

70
Pressure psi

60

50

40

30

20

10

0
0
1 2 3 4 5 6 7 8 9 10
Flowrate(x100) gpm

Supply Curve Data


Static Pressure: 85 psi
Test Residual Pressure: 77 psi
Test Flow Rate: 202 gpm

Demand Curve Data


Calculated Residual Pressure: 20.44 psi
Calculated Flow Rate: 141.08 gpm
Excess Available Residual Pressure At Calculated Flow: 60.44 psi
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 8.66 psi

C:\Users\Zicom\Documents\Elite Software\Fire 6 Projects\Sample..fiw Wednesday, April 20, 2022, 10:00 AM