Professional Documents
Culture Documents
for
PETROL STATION
Prepared By:
General Data
Project Title: PETROL STATION Project File Name: HC PETROL STATION..fiw
Designed By: ALFARID OFFICE DEPT MECH Date: 3/3/2021
Code Reference: SBC801 &NFPA 13&14 Approving Agency: CIVIL DEFANCE
Client Name: PETROL STATION Phone:
Address: DAMMAM 3RD INDUSTERIAL
City, State Zip Code:
CITY
Company Name: PETROL STATION Representative:
Company Address: DAMMAM 3RD INDUSTERIAL
City And State:
CITY
Phone:
Building Name: PETROL STATION Building Owner:
Contact at Building: Phone at Building:
Address Of Building: DAMMAM 3RD INDUSTERIAL
City, State Zip Code:
CITY
Project Data
Description Of Hazard: Ordinary 1 Hose System Type: Wet
Design Area Of Water Application: 1500 ft² Maximum Area Per Hose: 130 ft²
Default Hose K-Factor: 5.65 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 100.00 gpm Outside Hose Stream Allowance: 250.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm
Hose Specifications
Make: Model:
Size: 1/2" Temperature Rating: 155 F
Hose Summary
Hose System Type: Wet
Specified Area Of Application: 1499.95 ft²
Minimum Desired Density: 0.150 gpm/ft²
Application Average Density: 0.162 gpm/ft²
Application Average Area Per Hose: 1499.95 ft²
Hose Flow: 243.67 gpm
Average Hose Flow: 243.67 gpm
200
180
160
140
Pressure psi
120
107
100
80
60
40
20
0
1 2 3 4 5 6 7 8 9 10
Flowrate(x100) gpm